GE SHILLONG
GE SHILLONG SHILLONG DIVISION PIN 793002
SPL REPAIR FOR REPLACEMENT OF BER DG SET AT CANTT AREA UNDER GE SHILLONG AND PROVN OF 01 X DG SET 15 KVA CAPACITY WITH WIRING AN ALL ACCESSORIES AND 02 X WATER PRESSURE PUMP IN BLDG NO T 67 UNDER HQ 101 AREA UNDER GE SHILLONG
2023_MES_584463_1
GE/SHL/TOKEN-87 OF 2022-23
Open Tender
Civil Works
Item Rate
270 days
GE SHILLONG
ALL AS PER TENDER DOCUMENTS
7 documents required · 7 mandatory
₹500
Yes
GE SHILLONG
₹82,000
Yes
30 Jun 2023
6 Mar 2023
11 Apr 2023
6 Mar 2023
10 Apr 2023
13 Mar 2023
Amount
Supply and installation, testing, commissiong Erection of silent Diesel Engine driven generating set 415 volts, 3 phase 4 wire, engine as per BS-5514/IS 10002 and Alternator as per IS: 13364 complete with relay panel and switch gears for automatic starting on main failure, control panel having meter and sound proof canopy as per CPCB norms and foundation etc. of capacity 10 KVA with following details:-Make- Ashok Leyland ,DG Set Model :AL2CDG1 / Mahindra
ENGINE DETAILS :Engine Rating :10 KVA, Engine Rated HP:21. Stroke:4, No. of Cylinders-2, RPM-1500,Cyl. Configuration - Vertical Inline, Direction of Rotation-Counter Clockwise viewed from flywheel end, Method of aspiration- Naturally aspirated, Method of cooling-Coolant cooled, Type of Governor-Mechanical ,Class of Governor- A1, Bore X Stroke-104 X 113mm, Displacement-1.915ltrs,Compression ratio-17.5±0.5:1,Lube oil capacity-6 ltrs, Coolant capacity-10 ltrs,Starting system-12V Electric Start, Overload capacity-10% for 1hr. in every 12hrs. running, Continuous duty, Safety control-Low lube oil pressure, High coolant Temp., Standards-ISO 3046,BS 5514, Fuel Tank 75 ltrs shall be supplied and to be mounted inside thee canopy, Battery 12 V, 90 Ah make Exide with battery lead, anti vibration mounting pads ( fitted inside the canopy, Residential silencer (fitted on top of canopy), first fill of lube oil and coolant Lub oil change period- 600 Hrs or 12 Month which is earlier, Acoustic Enclosure shall be made of specially procured 16 SWG CRCA Sheet and structural sheet metal base frame and comply with CPCB norms with features , the most compact, six sided close, modular construction and detachable, meet CPCB/ MOEF norms, sound level <75 DbA at one meter distance under free field conditions as per norms. Easy accessibility around the DG set, which ensures optimum serviceability, special power coated enclosure, weather proof, corrosion resistant, environment friendly, specially designed lifting hooks, use of high quality hardware ensures longer life of enclosure, provision for emergency stop faculty Dimension with - 1750X900X1220mm (LXWXH), DG Set Weight-676Kgs (Approx).
ALTERNATOR :- Rating : 10KVA , 8KW, Type : Brushless, Excitation : Self excited, self regulated (AVR), Enclosure : SPDP, Enclosure protection : IP-23, Rating : Continuous, Rated current : 10KVA: 14Amps, Rated Voltage : 415V, No. of Phases : 3Ph., 4 wire system,Frequency : 50Hz, Power factor : 0.8pf. Class of Insulation : H, Voltage Regulation : ±1%, Overload capacity : 10% for 1hr. for every 12hrs. running., standards : IS 4722/BS 5000 Make-- LeroySomer/ Crompton Greaves
Supply and installation, testing, commission Erection of silent Diesel Engine driven generating set 415 volts, 3 phase 4 wire, engine as per BS-5514/IS 10002 including emission control device and Alternator as per IS: 13364 complete with relay panel and switch gears for automatic starting on main failure, control panel having meter and sound proof canopy as per CPCB norms and foundation etc. of capacity 62.5 KVA with following details:-Make- Ashok Leyland ,DG Set Model :AL4CTIDG5 / Mahindra
ENGINE DETAILS :Engine Rating :62.5KVA, Engine Rated HP:79. Stroke:4, No. of Cylinders-4, RPM-1500,Cyl. Configuration - Vertical Inline, Direction of Rotation-Counter Clockwise viewed from flywheel end, Method of aspiration- Naturally aspirated, Method of cooling-Coolant cooled, Type of Governor-Electronic , Class of Governor- A0,Bore X Stroke-104 X 113mm, Displacement-3.84 ltrs,Compression ratio-16.5±0.5:1,Lube oil capacity-8.5 ltrs, Coolant capacity-13.5 ltrs Starting system-12V Electric Start, Overload capacity-10% for 1hr. in every 12hrs. running,Continuous duty, Safety control-Low lube oil pressure, High coolant Temp., Standards-ISO 3046,BS 5514, Fuel Tank 140 ltrs shall be supplied and to be mounted inside thee canopy, Battery 12 V, 90 Ah make Exide with battery lead, anti vibration mounting pads ( fitted inside the canopy, Residential silencer (fitted on top of canopy), first fill of lube oil and coolant Lub oil change period- 600 Hrs or 12 Month which is earlier, Acoustic Enclosure shall be made of specially procured 16 SWG CRCA Sheet and structural sheet metal base frame and comply with CPCB norms with features , the most compact, six sided close, modular construction and detachable, meet CPCB/ MOEF norms, sound level <75 DbA at one meter distance under free field conditions as per norms. Easy accessibility around the DG set, which ensures optimum serviceability, special power coated enclosure, weather proof, corrosion resistant, environment friendly, specially designed lifting hooks, use of high quality hardware ensures longer life of enclosure, provision for emergency stop facitty Dimension with - 2800X1200X1400mm (LXWXH), DG Set Weight-1350Kgs (Approx).
ALTERNATOR :- Rating : 62.5KVA , 50KW, Type : Brushless, Excitation : Self excited, self regulated (AVR), Enclosure : SPDP, Enclosure protection : IP-23, Rating : Continuous, Rated current : 62.5KVA: 87Amps, Rated Voltage : 415V, No. of Phases : 3Ph., 4 wire system, Frequency : 50Hz, Power factor : 0.8pf. Class of Insulation : H, Voltage Regulation : ±1%, Overload capacity : 10% for 1hr. for every 12hrs. running., standards : IS 4722/BS 5000 Make-- LeroySomer/ Crompton Greaves
Supply and installation, testing, commission Erection of silent Diesel Engine driven generating set 415 volts, 3 phase 4 wire, engine as per BS-5514/IS 10002 including emission control device and Alternator as per IS: 13364 complete with relay panel and switch gears for automatic starting on main failure, control panel having meter and sound proof canopy as per CPCB norms and foundation etc. of capacity 140 KVA with following details:-Make- Ashok Leyland ,DG Set Model :AL6DTIDG4 / Mahindra
ENGINE DETAILS :Engine Rating :140KVA, Engine Rated HP:197.13. Stroke:4, No. of Cylinders-6, RPM-1500,Cyl. Configuration - Vertical Inline, Direction of Rotation-Counter Clockwise viewed from flywheel end, Method of aspiration- Naturally aspirated, Method of cooling-Coolant cooled, Type of Governor-Electronic , Class of Governor- A0, Bore X Stroke-104 X 113mm, Displacement-5.76 ltrs,Compression ratio-17.5±0.5:1,Lube oil capacity-17.5 ltrs, Coolant capacity-25 ltrs Starting system-12V Electric Start, Overload capacity-10% for 1hr. in every 12hrs. running, Continuous duty, Safety control-Low lube oil pressure, High coolant Temp., Standards-ISO 3046,BS 5514, Fuel Tank 175 ltrs shall be supplied and to be mounted inside thee canopy, Battery 12 V, 105 Ah make Exide with battery lead, anti vibration mounting pads ( fitted inside the canopy, Residential silencer (fitted on top of canopy), first fill of lube oil and coolant Lub oil change period- 600 Hrs or 12 Month which is earlier, Acoustic Enclosure shall be made of specially procured 16 SWG CRCA Sheet and structural sheet metal base frame and comply with CPCB norms with features , the most compact, six sided close, modular construction and detachable, meet CPCB/ MOEF norms, sound level <75 DbA at one meter distance under free field conditions as per norms. Easy accessibility around the DG set, which ensures optimum serviceability, special power coated enclosure, weather proof, corrosion resistant, environment friendly, specially designed lifting hooks, use of high quality hardware ensures longer life of enclosure, provision for emergency stop facitty Dimension with - 3900X1350X1700mm (LXWXH), DG Set Weight-2188 Kgs (Approx).
ALTERNATOR :- Rating : 140 KVA , 112 KW, Type : Brushless, Excitation : Self excited, self regulated (AVR), Enclosure : SPDP, Enclosure protection : IP-23, Rating : Continuous, Rated current : 140KVA: 194.7Amps, Rated Voltage : 415V, No. of Phases : 3Ph., 4 wire system, Frequency : 50Hz, Power factor : 0.8pf. Class of Insulation : H, Voltage Regulation : ±1%, Overload capacity : 10% for 1hr. for every 12hrs. running., standards : IS 4722/BS 5000 Make-- LeroySomer/ Crompton Greaves
AMF CONTROL PANEL (AUTO) : (Note : AMF Suitable for Item no 1 ,2 and 3 each DG set.) The AMF control panel shall be made 16 SWG CRCA sheet, floor mounted, indoor type, dust and vermin proof and powder coated and suitable for 415 V 3 Phase 50 Hz system. The panel will be external type and shall consist of the following components Engine display features: Low lube oil pressure, high water temp, over speed, low fuel level, RPM no, of hours Run, batter voltage. Safeties : LLOP HWT, LFL, Over Speed Alternator display features: Ampere, voltage, frequency, power factor, kw , kwh, kvar Safeties: over current , over / under voltage, over under Frequency, short circuit , Current Transformer of suitable ratio, 2 Nos 4 Pole suitably rated , MCCB with power contactor of AC 1 Duty with No+ NC contacts for mains & DG, indicating lamps for DG ON (RYB) / Load on DG / Main on RYB/ load on Mains, MCB for control of suitable rating, battery charger with auto trickle and boost charging facility, current transformer of suitable rating Note: All Engine and Alternator display parameters and safety shutdown features will be shown in above AMF controller only.
Disconnecting old BER DG set by shutting down electric supply , uploading of DG set for Shufting of Old BER DG set From B Camp, MH power house respectively and MH Pump house to AGE E/M store yard GE Shillong complete all as directed by Engr-in-charge at site.
Supply, lay in trenches, floors ,fix on wall/pole, passing through pipes etc.,LT UG cable , 1100 volts grade, XLPE insulated , with multistranded aluminum conductors, armored with galvanized steel wire or tape ,gland, lugs etc , of size 70 Sq.mm 3.5 core , confirming to IS specifications complete all as specied and directed by Engr-in-charge at site.
All as per item no 5 above but cable of size 16 Sq.mm 4 core complete all as specied and directed by Engr-in-charge at site.
Material and labour for earthling complete with galvanized steel earth plate electrode 60 Cm X 60 Cm X 6 mm buried directly in ground vertically to a depth notless than 2.25 mtr deep below ground level with top edge of earth plate at a depth not less than 1.5 m below normal ground level connected to galvanized earth strip 32×6mm by means of bolts, check nuts and washers ,galvanized steel and protected by GI pipe 40 mm bore light grade & connected to main switch board or main control board as directed and including concrete pit in PCC (1:3:6) type C1, precast RCC (1:2:4) type B1 cover slab 30 cm X 30 cmX 5 cm with 10mm dia TMT bars 8 cm C/c both ways and one handle for lifting made out of 8 mm dia TMT bar, funnel, wire mesh, 20mm bore galvanized iron pipe (medium grade) for watering, charcoal or coke and salt in alternative layers, necessary excavation and earth work in any type of soil and including necessary testing complete all as shown in Electrical Plate No 3 of SSR part -I.
Supply and installation of pressure (Booster) pump of capacity 1 HP single phase 240 Volt, Pipe size 25 x 25mm dia outlet and inlet, head 15-32mtr including all cutting and fitting all as specified and direted by Engr-in-charge
Material and labour for sub main wiring with two single core 4.0 sqmm FRLSH, ISI marked PVC insulated multi stranded, unsheathed copper conductor cable and one single core unsheathed FRLSH , ISI marked, PVC insulated multistranded copper conductor cable of size 4.0 sqmm green colour as earth lead including PVC casing capping of suitable size complete all as specified and directed, including taking down unservicable one.(Note: two run of 4.0 sqmm cable , one run of earth wire of 4.0 sqmm and one run of PVC casing capping shall be measured as one length).
Supply and fix switch piano (ISI marked) Single pole 240 volts, 15 Amps all as specified and directed. Make- Havells/anchor/ Legrand.
Supply and fix socket outlet (ISI marked), 2/3 pin and 15 Amps, 240 volts, complete all as specified and directed. Make- Havells/anchor/ Legrand.
Supply,install, testing and commissioning of Silent Diesel engine driven generating set 415 Volts 3 phase 4 wire engine as per BS 5514/ IS 10002 including Emission control device as per PPCB Norms and alternator as per IS : 13364 complete with relay panel for automatic starting on mains failure, control panel having meters, sound proof canopy and foundation etc for capacity 15 KVA as per ISO - 3046/BS 5514 conforming to the detailed specification as under. make- Kirloskar Model No- KEC-T82.5-II or Greaves Power or Equivalent a) Engine : The Diesel Enginewith AMF Panell shall be radiator water cooled, 15 KVA or 12 KW at 1500 RPM, Cylinder- 2 Nos. Starting stopping : Electrical start with 12 V DC 1 x 88 AH, 12 V Exide / Prestolite Low Maintenance Battery,Electronic governer , The fuel tank provided shall be suitably mounted on the base frame fabricated out of 16 SWG MS sheets and capacity to run the genset for 8 to 12 hours continuously on full load. Fuel tank shall have Drain plug, Hand hole for cleaning, vent breather, fuel suction and return connections, fuel level indicator fuel filling neck with cap etc as per the standards. The engine and alteranator shall be directly coupled to ensure perfect alignment. The engine and alternator shall be mounted on a common base frame with AVM pads all as per manufracturer CUMMINS / KIRLOSKAR / GREAVES POWER.
(b) Alternator : Rating 15 KVA or 12 KW at 1500 RPM 415 V Phase to Phase and 240 Volt Phase to Neutral, 50 Hz 3 Phase 4 wire system , solid state Voltage Regulator,(+/-) 1 voltage regulation, alternato Screen protected / drip proof, self ventilating, self excited, self regulated, brushless, contineous duy protention IP 21 as per IS 13364 developing 20 KVA at 0.8 PF. It shall have provision for 10% overload for one hour on every 12 hours, The alternator shall confirm to IS : 13364/BS5000 Make : KIRLOSKAR / CROMPTON/ POWER GREAVES. (C) Controls/Protection : (i) Low LOP fault indication (ii) Indication for Water Temparature, (iii) High Colant Temparature fault Indication, (iv) Failure to start fault indication (v) Battery Volage monitoring, (vi) Low Battery Indication, (vii) Fuel level Indication, (viii) Engine RPM meter, (ix) Engine run hours meter, (x) Voltage for all three Phases, (xi) Amper meter for measuring current in all three phase. (xii) Frequency meter indication, (xiii) Protection for Over/Under Voltage (xiv) Protection for Over/Under Voltage (xv) Electronic tamper proof KWH meter 3 phase, 4 wire system with suitable ratio CTs. (xvi) Oveload protection (xvii)Suitable capacity of Battery charger shall be provided in the control panel to charge the batteries when mains supply in availbale. When the Gen set is running the battery will be charged from the charging alternato. Make : KIRLOSKAR/ CROMPTON/GREAVES POWER.
(d) Acoustic enclosure : (i) Shall be maticulously designed CNC Turret punch press and hydraulic press brake manufractured body out of corrossion resistant cold rolled steel 16 SWG CRCA / MS sheet duly surface trated phosphated and finally powder coated constructed from folded sections to ensure regidness and aesthatic in looks. Canopy panel and doors shall have High density/ fire retradent / non igniting and noise reduction type Foam or Resin bonded Rock wool of suitable density properly covered with fibre cloth / tissue and perforated fixed to absorb noise. The average sound levell when measure in greenfiled (ISO 8525 Part 10) at 1 meter distance from all four sides is less than 75 dB (A) average as per CPCB Norms The average stablised hot air temperature rise with i the canopy near suction air filter to be maintained 7 degree centigrade over and above the ambient temperature Four higned doors shall be provided to canopy one door shall have glass window for control panel. The exhaust gasses shall be taken out through a suitable flexible pipe to prevent any back pressure on the engine. Provision shall be made on the canopy for connectig the output cable terminatiion should be provided. (ii) The eshaust system and noise suppressor shall be provided with thermal insulation, to prevent excess heat radiation on the Engine and safe for operator. (iii) Absorbtion type non residential silencer insulated from inside with glass wool shall be provided to suppress exhaust noise from the Engine. (iv) A suitably designed draught ventilation system is to be incorporated. make:- Kirloskar green /Jackson /Powerwool (e) DG power Control Panel : (i) Shall be outdoor type sheet steel type cubicle type control panel ,floor standing, dust and vermin proof under normal conditions complete with all internal wiring & will house the following:- (a) AC voltmeter (b) AC ammeter (c) vibrating reed Frequency meter (d) Indicating Lamps for SET ON & LOAD ON (e)MCCB for short circuit & Overload Protection (f) Aluminium Bus bars of adequate rating (g) Provision for bottom entry & Exit of power cabling (g)set of current transformer (h) set of control fuses
Excavation in trenches not exc 1.5 m wde and 1.5 m deep for taking out/laying of UG cable/GI pipe of any dismeter in hard/dense soil and getting out complete all as specified and directed
Returning and filling including spreading levelling watering and well ramming in layers not exc 25 cm thick hard/dense soil complete all as specified and directed
Removing excavated material at a distance n exc 50m and deposited where directed at a level not exc 1.5 above the starting point for soft/lose soil complete all as specified and directed
M & L for sand filing in treances for providing sand cushion for protection of UG cable complete all as specified and directed.
Supply and laying of fly ash bricks locally available of size 230x110x70 mm alying perpendicular of UG cable complete all as specified and directed.
Supply and fix ON LOAD change over switch 415 V in sheet Metal enclosures 4 Pole of capacity 63 Amps Make-LT Cat-CO10630OSOO or Havells Or Legrand
Supply, laying connecting and testing XLPE insulated, PVC sheathed, armoured LT electric power UG cable (heavy duty) with stranded aluminium conductor, 1100 Volts grade, cross sectional area 50 Sqmm, 3.5 core laid through duct/ pipe / in trench etc. including cable glands & lugs complete all as specified and directed.
MONA GENERATOR SEVICES PVT. LTD.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .