Karnataka Power Transmission Corporation Limited
Augmentation of 2 x 8 MVA, 66/11kV Transformers by 2 x 20 MVA, 66/11 kV Transformers at 66/11 KV K.Honnalagere sub-station in Maddur Taluk, Mandya district on Partial Turn Key (PTK) basis including supply of all matching materials/equipment (except 66/11kV Power Transformer, NIFES and 11kV switchgear) and erection & including civil works of all materials/equipment, testing and commissioning. CALL4 - Reserved for SC
306833
KPTCL/2025-26/SS/WORK_INDENT3515/CALL-2
Reserved
Sub-Station
KPTCL CEE Transmission Zone Office Mysuru
16 documents required · 16 mandatory
The Bidder should have carried out erection of atleast One(01) No. of 66kV voltage class or above voltage class Sub-Station/ Additional Transformer work OR atleast One(01) No. of 66kV voltage class or above voltage class Transformer Replacement/ Augmentation work on Total or Partial Turnkey Basis in the last 10 years preceding the date of bid submission and shall be completed and commissioned prior to the date of submission of the Bid OR The Bidder should have carried out erection of atleast Two (02) Nos of Agumentation/Replacement of 66kV or above voltage class Transformer works on Labour Contract Basis in the last 10 years preceding the date of bid submission and shall be completed and commissioned prior to the date of submission of the Bid OR Bidder who has executed Additional Transformer works or Replacement of Transformer works of private firms under the direct supervision of ESCOM/KPTCL officers are eligible to participate. Such Bidder should have carried out erection of not less than Two (02) Nos. of 66kV or above voltage class Additional Transformer Work on Total or Partial Turnkey Basis in the last 10 years preceding the date of bid submission and shall be completed and commissioned prior to the date of submission of the Bid
The Bidder shall be registered firm as Sole Proprietorship/Partnership/Pvt Ltd Company etc
For other than proprietorship, the Bidder shall furnish the registered partnership deed and Power of Attorney
valid Super grade Electrical Contractor License issued by the Government of Karnataka as on the date of opening of techno-commercial bid (refer 2.3 of ITT)
3.6: Tenderers who meet the above specified minimum qualifying criteria, will only be qualified, if their available tender capacity is more than the total tender value. The available tender capacity will be calculated as under:Assessed Available Tender Capacity: (AxNx5-B)Where A-Maximum value of works executed (KPTCL & Non-KPTCL) in any one year during the last five years (updated to FY 2024-2025) taking into account the completed as well as works in progress. N-Number of years prescribed for completion of the works for which tenders are invited.B-Value, at FY 2024-2025 price level of existing commitments (KPTCL & Non-KPTCL)and on-going works (KPTCL & Non-KPTCL) to be completed during the next 1(One)year.Note:(i)The statements showing the value of existing commitments and on-going works as well as the stipulated period of completion remaining for each of the works listed should be countersigned by the Employer in charge, not below the rank of an Executive Engineer or equivalent.(ii)A self-declaration is to be uploaded by the Tenderer stating that the information with regard to assessed available tender capacity (Works on Hand) furnished are correct.
Even though the Tenderers meet the above criteria, they are subject to be disqualified if they have:- Made misleading or false representations in the forms, statements and attachments submitted in proof of the qualification requirements and/or- Record of poor performance such as abandoning the works, not properly completing the contract, inordinate delays in completion, litigation history, or financial failures etc. and/or- Participated in the previous Tender for the same work and had quoted unreasonably high Tender prices and could not furnish rational justification.
Minimum Average Annual Turnover (MAAT) of the bidder for best one(01) year out of last preceding five financial years, shall not be less than Amount Put to Tender as per 3.2(a) of std tender documents(ITT).
Valid Caste Certificate in support of reserved tender participation
Valid Karnataka Residential Certificate
Bidder shall ensure that soft copies of Power of Attorney, Letter of Undertaking, No Deviation CERTIFICATE as revised in Annexure , Any other undertaking / agreement (if applicable) are to be uploaded besides submitting the Originals to the office of the Chief Engineer, Electy., Operation, KPTCL, Mysuru, after the last submission date as per 3.10(xviii) of ITT
Bidder shall ensure that soft copies of i. Letter of undertaking for Non performance ii. Letter of undertaking for Risk and Cost iii. Letter of undertaking for Litigation iv. Letter of undertaking to source the supply of equipment material from KPTCL approved Vendors only (if applicable) are uploaded besides submitting the Originals to the office of the Chief Engineer, Electy., Operation, KPTCL, Mysuru, after the last submission date as per 3.10(xviii) of ITT
i. Letter of undertaking to source the equipment/material for the work from the approved Vendors who meet the eligibility clauses regarding restrictions on procurement from a country which shares a land border with India (Annexure-XVI) ii. Letter of undertaking as per clause No.1.5 of Annexure-XVII iii. Letter of undertaking as per clause No.1.6 of Annexure-XVII (if applicable) are uploaded besides submitting the Originals to the office of the Chief Engineer, Electy., Operation, KPTCL, Mysuru, after the last submission date and on or before the date and time of opening of techno commercial bids.
ESI certificate
EPF Certificate
Shall upload valid GST Certificate and PAN copy
b) Liquid Assets and/or availability of credit facilities of not less than 30% of the Amount put to tender(Credit lines/ Letter of credit/ certificates from Banks for meeting the fund requirement etc.) (30% of APT)
₹1,560
₹62,200
15 Jun 2026
15 Jun 2026
1 Jul 2026
24 Jun 2026
22 Jun 2026
Augmentation of 2 x 8 MVA, 66/11kV Transformers by 2 x 20 MVA, 66/11 kV Transformers at 66/11 KV K.Honnalagere sub-station in Maddur Taluk, Mandya district on Partial Turn Key (PTK) basis
Current Transformer: Supply of 11 kV OUTDOOR Oil cooled CT of Ratio 1200-800/1-1-1 A, Acc. Class 0.2s as per technical Specifications.
(for Incomer 25 kA SWG)
PVC insulated Copper Control Cable with Lugs / Ferrules. 1.1 KV class
19 Core 2.5 Sq.mm.
4 Core 6.0 Sq.mm.
Supplying and erection of street lighting lattice type structure along with GI pipe for fixing of LED lamp (0.182 MT + 5% B&N)-8.5 mtr height(0.1911x7Nos)
Supply and fixing sheet Metal box made out of 18 SWG sheet metal with necessary holes forcable/ conduit entry as required with one coat (200mm x 200mm x 65mm)
PVC Insulated copper control cables : 1.1 kV PVC insulated copper control cable with glands/lugs/ferrules etc as per technical specification
Supplying and fixing of 6-32 A single pole MCB
Supply of LED Street light luminaire with pressure die cast aluminium housing body for optimal thermal dissipation. Lamp compartment comprising of anti glare clear diffuser with Injection moulded poly...
Augmentation of 2 x 8 MVA, 66/11kV Transformers by 2 x 20 MVA, 66/11 kV Transformers at 66/11 KV K.Honnalagere sub-station in Maddur Taluk, Mandya district on Partial Turn Key (PTK) basis
Erection of 20MVA, 66/11kV TRANSFORMER. (45MT) Power Transformers:
Testing and commissioning of Power Transformer
Erection of 11 kV OUTDOOR Oil cooled CT of Ratio 1200-800/1-1-1 A, Acc. Class 0.2s as per technical Specifications.
(for Incomer 25 kA SWG)
Testing and commissioning of Switchgear
Releasing and Re-erection of 11kV Class, 25kA, NCT of ratio 1200-800/1-1A for REFR Protection (of similar rating and ratio as that of Incomer of 11kV Switchgear) with terminal connector .
Releasing and Re-erection of 11kV Class, 25kA, NCT of ratio 1200-800/1-1A for REFR Protection (of similar rating and ratio as that of Incomer of 11kV Switchgear) with terminal connector .
Laying of 19 Core 2.5 Sq.mm.
Laying of 4 Core 6.0 Sq.mm.
Supplying, Laying and welding of M.S.Flats 50X6 mm, to be treated with sodium bentonite clay , applying ACB paint to welded portion and covering with earth. (1671+61.4+59.3+44.2+4.5=1841mtrs)
Supplying and Grounding of Equipment with G.I.Flat 50x6mm and connecting Equipment to the earth mat/ground pit. Each point of earthing with all formation works like bending, twisting, drilling of ho...
Supplying and Providing 25 mm dia M.S.Rod 1.05 m long earthmat spikes including heating, bending top 50mm overlap flattening and making spike edge at the ground level and welding the rod with ground ...
Grounding of equipments by providing cast iron pipe of 100mm ID 13mm thickness, 2.75mtrs long with 2 part clamp out of G.I.Flat 50x6 mm continuously welded around the pipe using cast iron welding elec...
Supplying and fixing of 450mm dia x 450mm height 1.5" to 2" hume pipe collars for earth pits.
Erection of street lighting lattice type structure along with GI pipe for fixing of LED lamp (0.182 MT + 5% B&N)-8.5 mtr height
PVC Insulated copper control cables : 1.1 kV PVC insulated copper control cable with glands/lugs/ferrules etc as per technical specification
Dismantling of 2x8 MVA, 66/11 KV, Transformer and parts like Radiator, Bushings, Draining of oil from transformer etc., as per the direction of site Engineer (2*21.5 MT=43MT)
Moving of Transformer from the plinth to the loading point as per direction of site Engineer.
21.5 Mt x 50mtrs x 2no=2150
Released 11kv class CTs of Ratio 800-400/1-1-1A (Outdoor oil cooled)
Augmentation of 2 x 8 MVA, 66/11kV Transformers by 2 x 20 MVA, 66/11 kV Transformers at 66/11 KV K.Honnalagere sub-station in Maddur Taluk, Mandya district on Partial Turn Key (PTK) basis
Earth work in surface excavation by mechanical means for lowering & leveling the ground for all works other than foundation in all kinds of soils & upto depthnot exceeding 300mm as per drawing and tec...
Earth excatvation for pipeline trenches in all kinds of soils by mechanical means as per drawing and technical specification, including setting out, construction of shoring, strutting, barricading, ca...
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations and other similar works etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by r...
Providing and laying in position Cement Concrete for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes...
Providing and laying in position Cement Concrete for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS C...
Providing Size Stone masonry with hard stone in foundation & plinth with Cement mortar 1:6 (1 cement : 6 coarse sand)
Providing and constructing load bearing wall with Solid Concrete blocks of size 400x200x200mm having block density more than 1800kg/m3 and minimum compressive strength of 4.00 N/mm2 conforming to IS 2...
Providing 20 mm cement plaster of mix :1:6 (1 cement: 6 fine sand) to brick/stone masonry including rounding off corners wherever required smooth rendering, providing and removing scaffolding, includi...
Finishing walls with Acrylic Smooth exterior paint of required shade :New work (Two coat applied @ 1.67 ltr/10 m² over and including priming coat of exterior primer applied @ 2.20 kg/10 m²) with pai...
Providing Flush / Ruled/ Struck or weathered pointing Pointing on brick work or brick flooring with cement mortar 1:3 (1 cement : 3 fine sand) after raking joints to depth nicely lining, including cos...
Supplying PVC ringtite pipes conforming to IS 4985:2000 with latest amendments and conveying to worksite, rolling and lowering into trenches, laying true to line and level and perfect linking at joint...
Providing and fixing Structural Steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of appro...
Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50 mm including strengthening with 2 mm dia wire or nuts, bolts and washers as required complete as per the direct...
Fencing with G.I. barbed wire Angle iron post placed at required distance embedded in cement concrete blocks, every 15th post, last but one end post and corner post shall be strutted on both sides and...
Jelly Spreading (20-25 mm) : Supplying and providing jelly in the station yard of uniform thickness of 100 mm including the cost of materials, labour charges, required tools and plants etc., complete....
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
Tender document kw3R K Honnalgere.pdf
Tender Document • 1.57 MB
Volume II A B.zip
Technical Information / Worksheet • 19.19 MB
credit facility certificate-FORMAT toUL.pdf
Commercial Information / Worksheet • 0.05 MB
Work on Hand details format.doc
Techno-Commercial Worksheet • 0.06 MB
NIT-Mys Tz-Khonnalagere 2x20MVA.pdf