Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹28.9 LAccepted-AOC | ₹28.9 L Quoted ₹25.5 L | L1 | Accepted-AOC LOWEST TENDERER |
| 2 | L2₹25.6 LRejected-AOC | ₹25.6 L | L2 | Rejected-AOC SECOND LOWEST TENDERER |
| Sl No | Description | Qty | Unit | KARTHIKEYAN ELECTRICALS L1 | SASTHA ELECTRICALS L2 |
|---|---|---|---|---|---|
| 1.00ELECTRICALWORK | |||||
| 1.01 | Wiring Wiring with 2x1.5 sq.mm. PVC insulated unsheathed FRLS SC copper conductor of 1100V grade insuitable PVC rigid pipe on wall and ceiling with PVC accessories with TW switch box with 5A FT switch inflush with wall covered with hylum sheet of 3mm thick with painting of suitable colour for open PVC light / fan point (for electronic regulator) (5points per coil) etc., complete complying with standard specification and as directed by the departmental officer. | 45 | POINTS | 1,641 ₹73,845 | 1,700 ₹76,500 |
| 1.02 | Supply and Run of 2 of 2.5 sq.mm. PVC insulated SC unsheathed FRLS copper conductor of 1100 V grade in suitable PVC rigid Pipe on wall and ceiling with continuous earth wire connection of 2.5 sq.mm copper wire with painting of suitable colour etc., complete complying with standard specification and as directed by the departmental officer. | 150 | RM | 203 ₹30,450 | 210 ₹31,500 |
| 1.03 | Supply and laying of 2x16 Sq.mm sized PVC armoured LTUG cable in a trench to be excavated at a depth of 0.75 Mtr Putting 0.15mt layer of sand and covering the three sides of the cable with bricks and refilling the earth to make good etc., complete complying with standard specification and as directed by the departmental officer. | 245 | RM | 457 ₹1.1 L | 460 ₹1.1 L |
| 1.04 | Supply and clamping of 2x16 sq.mm PVC LTUG armoured ALU cable on post or on wall with MS clamps etc., complete complying with standard specification and as directed by the departmental officer. | 44 | RM | 333 ₹14,652 | 340 ₹14,960 |
| 1.05 | Supply and fixing of brass cable gland for 2x16 sqmm PVC armoured LTUG cable with earth connection etc., complete complying with standard specification and as directed by the departmental officer. | 8 | EACH | 344 ₹2,752 | 350 ₹2,800 |
| 1.06 | Supply and fixing of 8 way single pole and neutral MCB sheet steel enclosure Distribution board 1No 32 Amps DB MCB as incoming and 6 Nos 6 Amps to 32 Amps SPMCB outgoing in flush with wall and making good of the concealed portion with earth connection only. The MCB DB and MCB's should be with ISI mark (Like Standard make) etc., complete complying with standard specification and as directed by the departmental officer. | 4 | EACH | 3,340 ₹13,360 | 3,400 ₹13,600 |
| 1.07 | Supply and fixing of 5A 3 pin and 2 pin combined flush type wall socket with 5A flush type switch on suitable TW box with hylem sheet etc., complete complying with standard specification and as directed by the departmental officer. | 9 | EACH | 584 ₹5,256 | 600 ₹5,400 |
| 1.08 | Supply and fixing of 5A/15A 3 pin combined flush type wall socket with 15A flush type switch on suitable TW box with hylem sheet etc., complete complying with standard specification and as directed by the departmental officer. | 4 | EACH | 652 ₹2,608 | 662 ₹2,648 |
| 1.09 | Supply and fixingof 3Nos.5A(3pinand2pin) combined flus htype wall socket with control switches concealed in
suitable TW box covered with hylem sheet in flush with wall with earth connection (for computer plug socket) etc., complete complying with standard specification and as directed by the departmental officer
. | 5 | EACH | 650 ₹3,250 | 655 ₹3,275 |
Tender Value
Refer Docs
EMD Value
₹24,560
Closing Date
12 Feb 2026, 2:00 pmClosed
MANAGING DIRECTOR
Head Office, Koyambedu, Chennai-107
Providing Electrical Installation to the work of Semi Covered shed campus for Paddy Storage along with basic amenities of 9000 MT Capacity (3 Nos of 3000MT) at Kovilammapatty Village in Palani Taluk in Dindigul District
2026_TCSC_649398_1
48/CE/DB/DOE/063150/2025
Open Tender
Electrical Works
90 days
KOVILAMMAPATTY
Please refer Tender documents.
6 documents required · 6 mandatory
₹0
₹24,560
11 Mar 2026
31 Jan 2026
13 Feb 2026
31 Jan 2026
12 Feb 2026
31 Jan 2026
ELECTRICALWORK
Wiring Wiring with 2x1.5 sq.mm. PVC insulated unsheathed FRLS SC copper conductor of 1100V grade insuitable PVC rigid pipe on wall and ceiling with PVC accessories with TW switch box with 5A FT switch inflush with wall covered with hylum sheet of 3mm thick with painting of suitable colour for open PVC light / fan point (for electronic regulator) (5points per coil) etc., complete complying with standard specification and as directed by the departmental officer.
Supply and Run of 2 of 2.5 sq.mm. PVC insulated SC unsheathed FRLS copper conductor of 1100 V grade in suitable PVC rigid Pipe on wall and ceiling with continuous earth wire connection of 2.5 sq.mm copper wire with painting of suitable colour etc., complete complying with standard specification and as directed by the departmental officer.
Supply and laying of 2x16 Sq.mm sized PVC armoured LTUG cable in a trench to be excavated at a depth of 0.75 Mtr Putting 0.15mt layer of sand and covering the three sides of the cable with bricks and refilling the earth to make good etc., complete complying with standard specification and as directed by the departmental officer.
Supply and clamping of 2x16 sq.mm PVC LTUG armoured ALU cable on post or on wall with MS clamps etc., complete complying with standard specification and as directed by the departmental officer.
Supply and fixing of brass cable gland for 2x16 sqmm PVC armoured LTUG cable with earth connection etc., complete complying with standard specification and as directed by the departmental officer.
Supply and fixing of 8 way single pole and neutral MCB sheet steel enclosure Distribution board 1No 32 Amps DB MCB as incoming and 6 Nos 6 Amps to 32 Amps SPMCB outgoing in flush with wall and making good of the concealed portion with earth connection only. The MCB DB and MCB's should be with ISI mark (Like Standard make) etc., complete complying with standard specification and as directed by the departmental officer.
Supply and fixing of 5A 3 pin and 2 pin combined flush type wall socket with 5A flush type switch on suitable TW box with hylem sheet etc., complete complying with standard specification and as directed by the departmental officer.
Supply and fixing of 5A/15A 3 pin combined flush type wall socket with 15A flush type switch on suitable TW box with hylem sheet etc., complete complying with standard specification and as directed by the departmental officer.
Supply and fixingof 3Nos.5A(3pinand2pin) combined flus htype wall socket with control switches concealed in suitable TW box covered with hylem sheet in flush with wall with earth connection (for computer plug socket) etc., complete complying with standard specification and as directed by the departmental officer .
Supply and fixingof 25A Flush type Wall Socket 25A DPMCB completeset for AC Plug in flush with wall with earth connection (For AC Plug) etc., complete complying with standard specification and as directed by the departmental officer.
Supply and run of 3core of 2.5 sqmm FLEXIBLE COPPER CABLE of 1100V Grade with suitable connection from 20Amps DP Box to Godown inside Switch box etc complete (ISI make) etc., complete complying with standard specification and as directed by the departmental officer.
Supply and fixing of single box type 4'36W fluorescent fitting complete with electronic ballast with TW round blocks on wall or ceiling with flu tube with PVC unsheathed FRLS Copper leads from terminals to the fitting etc., complete complying with standard specification and as directed by the departmental officer.
Supply and fixing of 60W LED street light fitting with LED (Lower end) with 32mm dia. GI pipe (class B) with 1 no.32 mm dia GI bend complete on the existing post/ on wall with PVC unsheathed FRLS copper leads with MS clamps and with painting etc., complete complying with standard specification and as directed by the departmental officer .
Supply and fixing of 1200mm sweep (48") AC ceiling fan complete with stepped electronic 300W regulator with 1 metre down rod on the existing clamp etc., complete complying with standard specification and as directed by the departmental officer.
Supply and fixing of 300mm (12") sweep (light duty) AC exhaust fan complete with necessary wall opening and making good of the wall etc., complete complying with standard specification and as directed by the departmental officer.
Supply of Power supply-Extension box,consist of 3 Nos. 5Amps (3 Pin and 2 Pin) socket with control switches,one Indicator in suitable TW Box covered with Hylem sheet, with 15Meter of 3core- 1.5Sq.mm copper wire of flat flexible cable wire and 5A-3pin top.The extension box with all inner-connections, flat cable wire connections with 3pin top also.The cost includes all materials cost,incidental charges,transportation charges and the materials of ISI make and as directed at site.(power supply provision for Weigh-Machine & bag-closing machine inside godown usage) etc., complete complying with standard specification and as directed by the departmental officer.
Supply and fixng of TNEB meter board suitable for 3 phase 63A service connection made up of suitable angle iron frame work of size 2feet x 1-1/2feet using angle iron of size1-1/2"x1-1/2"x1/4"rigidly fixed on wall covered with hylem sheet of size 2 feet x1/2 feet of 6mm thick ness with necessary bolts and nut s supports and supply and fixing of 3Nos. 63A fuse units(500V),1No.neutral link, copper earth flat of size1"x1/4"with interconnection of EB meter to fuse units by 16Sq.mm PVC insulated copper wire with 1No 63Amp 30MAFour Pole RCD/RCCB (Lower End)with suitable necessary connection with earth connection etc., complete complying with standard specification and as directed by the departmental officer.
Supply and run of 6 of 4sq.mm. PVC insulated SC unsheathed FRLS copper conductor of 1100V grade insuitable heavy gauge MS conduitpipe on wall and ceiling with continuous earth wire connection of 4sq.mm copper wire with painting of suitable colour etc., complete complying with standard specification and as directed by the departmental officer.
Supply and fixing of Panel with Fabrication, power coating ,and 25 x 3mm copper bus bar for phase, neutral and 25 x 3 mm copper flat for earthing , complete inter connection with 25 x 3mm copper flat , and VAF Meter wiring. (Main Panel board line with Control panel board) Material details. 1. 63A ON LOAD CHANGE OVER SWITCH = 1Set. 2.32A SDF SWITCH+ FUSE LINK = 3 Nos 3.16 A SDF SWITCH+ FUSE LINK = 3 Nos 4.VAF METER =1 No 5. INTICATION LAMB = 3 Nos
Earthing as per the ISI specification with an earth electrode of 2.10 metre Class 'B' GI pipe of dia not less than 40mm with copper earth plate of size 125mm x 50mm x 6mm with necessary funneling arrangements with necessary masonry work and with 38mm RCC cover slab for the brick masonry etc., complete complying with standard specification and as directed by the departmental officer.
Supply and Run of 1 of No.8 SWG GI wire in suitable PVC rigid pipe on wall / floor / ground for earth connection etc., complete complying with standard specification and as directed by the departmental officer.
Supply and laying in suitable size HDPE pipe in a trench dia for road crossing protect of UG cable including all incisdental charges etc., complete complying with standard specification and as directed by the departmental officer.
Supply and fixing of 60W LED ALL IN SOLAR STREET LIGHT, Lumens 100lm/watt, In build Charge Controller, PIR Motion Sensor,12.8V 25 - 24AH Lifepo4 Battery,60wp Module MonoPerc Pannel ,Led chip, LUMENS 4000, WORKING TIME : 1NIGHT, charging time:6 hours,IP -65,WARRANTY 3 years.1 METRE( 50X50X6) MM Angle 3Nos, and sutable size of MS pipe light fitting With supporting rod Clamp and installation ISI make etc., complete complying with standard specification and as directed by the departmental officer
Supply, Fabrication, Commissioning and Testing of 50 Watts -LED-Solar-Off Grid - Street Light with Gi- Post .The cost includes material cost, transportation cost, masonry work cost, any escalation in GST-cost as arises, Fabrication charges for Street light Post, Electrical wiring with material cost and labour cost as required at site. The Solar PV panels and LED light fittings to be ISI make and to be satisfy to TEDA norms as directed by the departmental officers. Solar PV Module 12 Volt- 90 Watts - Mono- crystalline. The modules are designed to withstand highly corrosive atmosphere and heavy wind loads and of certified standards. Temperature of Operation should be of 10 to 50 degree Celsius with Thermal Management System for ambient temperature in lower & higher rated value. The controller to be MPPT.(ISI Make) Battery-Lithium Ferro Phosphate make and designed for tropical conditions and have a long life. Minimum Voltage - 12.8V, 42 AH capacity ( ISI make) LED Light- White Light Emitting Diode (W-LED) (ISI Make) 12 Watt, W-LED luminary, dispersed beam, soothing to eyes with the use of proper optics and diffuser.LED Chip is of compliance to IES: LM-80 (Approved Method for Measuring Lumen Maintenance of LED Light Sources and LED lumen depreciation time to L70). Test report to be submitted before installation and to be get approval from Departmental Officers. The Color Temperature to be between 5500 K to 6500 K. The Die cast Aluminium IP66 enclosure provides excellent Protection against water entry, dust and humidity. Street light Post:- GI- Class-B (ISI norms) Pole height 6.5 m above the ground level. The G.I post must with 300mm x 300mm x 6mm MS base plate duly welded at the bottom and with concreting and construction on masonry pedestal.
Please Enable Macros to View BoQ information
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_778547.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.31 MB
BOQ_778547.xls
BOQ • 0.29 MB
Download all tender documents and submit your bid