Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹89.0 LAccepted-AOC NO 2 325 SOUTH STREET Z KULATHUR POST ANDIMADAM TALUK ARIYALUR DISTRICT | ARIYALUR | TAMIL NADU | L1 | Accepted-AOC 1st lowest | |
| 2 | L2₹93.5 L+₹2.7 L (2.98%)Rejected-AOC | L2 | Rejected-AOC 2nd lowest |
Tender Value
₹89 L
EMD Value
₹54,500
Closing Date
22 Feb 2024, 3:00 pmClosed
Superintending Engineer
Office of the Superintending Engineer, P.W.D., Buildings (C and M), Circle, Trichy-1
Provision of Internal and External Electrification to the New Government Industrial Training Institute at Kunnam in Perambalur Disrict. (Retender)
2024_PWD_426031_1
Tn.No.40SE/Dt.15.02.2024
Open Tender
Electrical Works
Lump-sum
180 days
Kunnam
Please refer Tender documents.
8 documents required · 8 mandatory
₹0
₹54,500
8 Mar 2024
16 Feb 2024
22 Feb 2024
16 Feb 2024
22 Feb 2024
16 Feb 2024
Amount
Wiring with 2 x1.5 sq.mm. (22/0.3) PVC insulated single core unsheathed copper conductor of 1100 V grade in suitable PVC rigid pipe Concealed in wall and ceiling with PVC accessories with Module GI switch box in flush with wall with 6A one way module switch with module front plate with continuous earth wire connection of 14 SWG TC wire and making good of the concealed portion with suitable colour for Concealed PVC Light point / fan point (for electronic regulator) (4points / Coil) Higher End ) (Work shop)
Wiring with 2 x1.5 sq.mm. (22/0.3) PVC insulated single core unsheathed copper conductor of 1100 V grade in suitable PVC rigid pipe Concealed in wall and ceiling with PVC accessories with Module GI switch box in flush with wall with 6A one way module switch with module front plate and making good of the concealed portion with suitable colour for Concealed PVC Light point / fan point (for electronic regulator) (5 points / Coil) Higher End )
Wiring with 2 x1.5 sq.mm. (22/0.3) PVC insulated single core unsheathed copper conductor of 1100 V grade in suitable PVC rigid pipe Concealed in wall and ceiling with PVC accessories with Module GI switch box in flush with wall with 6A one way module switch with module front plate with continuous earth wire connection of 14 SWG TC wire and making good of the concealed portion with suitable colour for Concealed PVC Light point / fan point (for electronic regulator) (6 points / Coil) Higher End
Wiring with 3 x1.5 sq.mm. (22/0.3) PVC insulated single core unsheathed copper conductor of 1100 V grade in suitable PVC rigid pipe Concealed in wall and ceiling with PVC accessories with Module GI switch box in flush with wall with 6A two way module switch with module front plate and making good of the concealed portion with suitable colour for Concealed PVC pipe Stair case Light point Higher End
Supply and fixing of single box type 4'20W LED fitting with LED complete with T.W. round block on wall or ceiling with PVC unsheathed copper leads from terminals to the fitting. (Make : Philips / Havells / Equivalent)
Supply and fixing of Twin box type 4'20W LED fitting with LED complete on suspension rod of 750 mm down rod with T.W. round block with PVC unsheathed copper leads from terminals to the fitting. (Make : Philips / Havells / Equivalent)
supply and fixing of 24W LED 2x2 square type Recessed fitting with LED (Higher end) on false Ceiling or on surface with suitable hanging support from ceiling with PVC unsheathed copper leads from terminals to the fitting.
supply and fixing of 18W LED square type Recessed fitting with LED (Higher end) on false Ceiling with suitable hanging support from ceiling with PVC unsheathed copper leads from terminals to the fitting
Supply and fixing of Battern Holder and 9W LED Bulb for BH point.
supply and fixing of 1200mm (48") sweep AC ceiling fan High speed complete with 2 module 100W fan step regulator (Higher end) with 300 mm down rod on the existing fan clamp.
supply and fixing of 1400mm (56") sweep AC ceiling fan High speed complete with 2 module 100W fan step regulator (Higher end) with 600mm down rod on the exisitng fan clamp
Supply and fixing of 300mm (12") sweep (light duty) AC exhaust fan complete with necessary wall opening and making good of the wall
Supply and fixing of louvers shutters arrangements for 300 mm (12") sweep (light duty) AC exhaust fan.
Supply and fixing of 375mm (15") sweep (light duty) AC exhaust fan complete with necessary wall opening and making of the wall
Supply and fixing of louvers shutters arrangements for 375mm (15") sweep light duty AC Exhaust fan
Supply and Fixing of buzzer suitable for 230Volts 50c/s single phase AC supply on suitable 1/2 module flush mounting box (GI) and 2 module white cover plate with frame (Plastic) with 6A Bell Push-1 Module with necessary connection. (Make: Legrend (MDS)/ Hager (L&T)/ equivalent).
Supply & Fixing of Gong Bell 12" size suitable for 250V 50 c/s single phase AC supply on suitable TW Board with push switch.
Supply and fixing of 1 no.6/16A two module socket , 1 no. 16A one module switch with module cover plate (plastic) on suitable module concealed Box (GI ) in flush with wall with connections. Higher
Supply and fixing of 3nos.6A two module 5 pin socket , 3 nos. 6A one module switch with module cover plate (plastic) on suitable module concealed Box (GI ) in flush with wall with connections. Higher End.
Supply and fixing of 2 no. 6A two module socket, 1no.6/16 A two module socket , 2 nos. 6A one module switch, 1 nos. 16A one module switch with module cover plate (plastic) on suitable module concealed Box (GI ) in flush with wall with connections. Higher End
Supply and fixing of 2 Nos. of 6A/16A combined socket 2 module with 16A 1way SP 1module switch with indicator in suitable 6 module surface mounting box (Plastic) on wall and 6 module white cover plate with frame (Plastic) (Higher End )
Supply and fixing of 2 way metal box enclosure with 6A to 32A DP MCB in flush with wall and making good of the concealed portion with earth connection.(Higher End) (for AC plug) [Like : Legrand /Hager/ L&T]
Supply and fixing of 12 way single pole and neutral MCB sheet steel enclosure distribution board with double door (metal) with 1 no. 32A DP MCB switch as incoming and 10 nos. 6A to 32A SP MCB as outgoing in flush with wall with earth connection only. Higher End
Supply and fixing of 7 segment 8 way 63A TPN MCB sheet steel distribution board (Higher end) with metal / acrylic door cover flush type /surface type fitted with busbars and neutral links with single / three phase MCB outgoings and seperate 4 way provision for accomodating one no. 4 pole incoming MCB / Isolator and another seperate 4 way provision for accomodating one no. 4 pole ELCB / RCD (totally 8 ways in one segment) (3x 6 ways in each segment) and seperate provision for MCB / Isolators ( totally 18 nos.) for sub incomers in 3 segments with lable holder and provison for taking up cable for size not less than 35 sq.mm. the following in flush with wall with earth connection only (Lighting/ Power)
Supply and fixing of 8 way Vertical Triple pole and neutral MCB sheet steel enclosure distribution board with double door (metal) with 1 no. 100 A 4P MCB Isolator as incoming and 8 nos. 32A 3P MCB, 3 nos. 6A to 32A SP MCB as outgoing in flush with wall with earth connection only. Higher End ( TP DB -Lighting)
Supply and fixing of 8 way Horizontal Triple pole and neutral MCB sheet steel enclosure distribution board with double door (metal) with 1 no. 63A 4P MCB Isolator as incoming and 24 nos. 6A to 32A SP MCB as outgoing in flush with wall with earth connection only. Higher End (For AC) GF-1; FF-1
Supply and fixing of HLF series Three phase type vertical type 8way 125A MCCB distribution board with metal door cover code IP 43 protection 1 No. 125A 4 pole MCCB 25KA as incoming and 6 Nos 32A TPMCB and 6 Nos 6A-32A SPMCB as outgoing on wall with cable entry boxes and necessary angle frame work with earth connection only. The MCCB DB and MCB should be with ISI mark (Like Legrand / Hager make). (For 32A TPNMCB-4 Nos)
Supply and fixing of HLF series Three phase type vertical type 8way 125A MCCB distribution board with metal door cover code IP 43 protection 125A 4 pole MCCB 25KA as incoming 1 Nos and 2 Nos 32A TPMCB and 18 Nos 6-32A SPMCB as outgoing on wall with cable entry boxes and necessary angle frame work with earth connection only. The MCCB DB and MCB should be with ISI mark (Like Legrand / Hager make) (For 20A TPNMCB - 6 Nos)
Supply and fixing of 32A FP pole MCB with suitable FP sheet steel enclosure box in flush with wall with suitable nacessary earth connection. (Legrand/Hager)
Supply and fixing of 63A FP pole MCB with suitable FP sheet steel Enclosure Box in flush with wall with suitable necessary earth connection (Legrand/Hager)
Supply and fixing of 125 A TPN sheet steel double break switch with HRC fuses on suitable angle Iron frame work with MS cable entry boxes and with earth connection only.
Supply, erection , testing and commissioning of pedestal type 400 A capacity dust and vermin proof panel board for LT CT metering made up of 16 SWG CRCA sheet of suitable dimensions comprising bus bar chamber, cut out fuse chamber, metering chamber confirming IE rules and as per TANGEDCO norms. The bus bars should be of 4 Nos. of 50mmx6mm copper flats for 3 phases and neutral and No. 8 SWG copper for double earth connection. The buses should be mounted on the SMC bus insulator with proper spacing and should be provided with heat shrinkable sleeves using RYB & Black colours.The bus bar chamber should be segregated from the adjacent chambers by providing 6mm thick hylem sheet. The cut out fuse chamber should be provided with 3 Nos. of 400 A HRC fuse links with fuse base with holders, test terminal block, earth link etc. The metering chamber should be provided with 400A/5A CTs, voltmeter, ammeter, frequency meter, powerfactor meter with suitable lugs, intrconnections and earth connection. The panel board should be provided with one coat of red oxide primer paint and two coats of Siemens grey approved by department officers along with danger board and the panel board should be erected on the suitable pedestal with suitable angle iron frame work and with necessary foundation, bolts & nuts etc.
Supply and fixing of 100 A Three phase 500V 4 Pole Change over Switch on suitable angle iron frame work with MS cable entry boxes with earth connection only.
Supply and run of 2 of 1.5 sq.mm. (22 / 0.3) PVC insulated SC unsheathed copper conductor of 1100V grade in rigid pipe concealed in wall and ceiling with continuous earth wire connnection of 14 SWG TC wire and making good of the concealed portion with suitable colourr (For 5A Plug and UPS wiring)
Supply and Run of 2 of 2.5 sq.mm. (36/0.3) PVC insulated SC unsheathed copper conductor of 1100 V grade in suitable PVC rigid pipe Concealed in wall and ceiling with continuous earth wire connection of 14 SWG TC wire and making good of the concealed portion with suitable colour ( For Computer Plug / 15A plug)
Supply and run of 2 of 4sqmm (56/0.3) PVC insulated SC unsheathed Cu.Conductor of 1100V Grade in suitable PVC rigid pipe concealed in wall and ceiling with continuous earth wire connection of 14SWG TC wire and making good of the concealed portion with suitable colour. (For 20A AC plug)
Supply and run of 2 of 4 sq.mm. (56 / 0.3) PVC insulated SC unsheathed copper conductor of 1100V grade in suitable heavy gauge MS conduit pipe concealed in wall and ceiling with continuous earth wire connection by 14 SWG TC wire and making good of the concealed portion wiith suitable colour (For 15A-2Nos in Lab)
Supply and run of 3 of 4 sq.mm. (56 / 0.3) PVC insulated SC unsheathed copper conductor of 1100V grade in suitable heavy gauge MS conduit pipe on wall and ceiling with continuous earth wire connection of 14 SWG TC wire with painting of suitable colour (For 32A FP Enclosure Box in Lab )
Supply and run of 4 of 6 sq.mm. (84 / 0.3) PVC insulated SC unsheathed copper conductor of 1100V grade in suitable PVC rigid pipe concealed in wall and ceiling with continuous earth wire connection by 14 SWG TC wire and making good of the concealed portion with suitable colour (For 7Segment 8W LDB i/c)
Supply and Run of 4 of 10 sq.mm. (140/0.3) PVC insulated SC unsheathed copper conductor of 1100 V grade in suitable PVC rigid pipe concealed in wall and ceiling with continuous earth wire connection of 14 SWG TC wire with painting of suitable colour (For VTPN DB for Lignting i/c)
Supply and clarnping of 3-1/2 x25 sq.mm. PVC LTUG armoured cable on post or on wall with MS clamps (For 63A FP Enclosure box)
Supply and fixing of brass cable gland for 3-1/2 x 25 sq.mm. PVC armoured LTUG cable with earth connection
Supply and providing cable end termination of 3-1/2 x 25 sq.mm. PVC LTUG aluminium armoured cable with necessary aluminium cable sockets by crimping etc with electrical connection complete
Supply and clamping of 3 ½ x 50 sq.mm PVC LTUG armoured LTUG cable on post or on wall with MS Clamps. (For 100A switch, )
Supply and fixing of brass cable gland for 3-1/2 x 50 sq.mm. PVC armoured LTUG cable with earth connection
Supply and providing cable end termination of 3-1/2 x 50 sq.mm. PVC LTUG aluminium armoured cable with necessary aluminium cable sockets by crimping etc with electrical connection complete
Supply and clamping of 3 ½ x 70 sq.mm PVC LTUG armoured LTUG cable on post or on wall with MS Clamps. (For TPDB in wOrk shop and DG i/c, o/g)
Supply and fixing of brass cable gland for 3-1/2 x 70 sq.mm. PVC armoured LTUG cable with earth connection
Supply and providing cable end termination of 3-1/2 x 70 sq.mm. PVC LTUG aluminium armoured cable with necessary aluminium cable sockets by crimping etc with electrical connection complete
Supply and laying of 3 1/2 x 120 sq mm PVC armoured LTUG cable in a trench to be excavated at a depth of 0.75 metre putting 0.15 mt. Laner of sand and covering the cable completely with bricks and sand and refilling the earth to make good (250 Panel i/c from 400A Panel o/g)
Supply and clamping of 3 ½ x 120 sqmm PVC LTUG armoured LTUG cable on post or on wall with MS clamps.
Supply and fixing of brass cable gland for 3 1/2 x 120 sqmm PVC armoured LTUG cable with earth connection .
Supply and providing cable end termination of 3 ½ x 120 qmm PVC LTUG Aluminium armoured cable with necessary aluminium cable sockets by crimping etc. with electrical connection complete.
Supply and laying of 3 1/2 x 185 sq mm PVC armoured LTUG cable in a trench to be excavated at a depth of 0.75 metre putting 0.15 mt. Laner of sand and covering the cable completely with bricks and sand and refilling the earth to make good (315A panel incoming from 400A o/g)
Supply and clamping of 3 ½ x 185 sqmm PVC LTUG armoured LTUG cable on post or on wall with MS clamps.
Supply and fixing of brass cable gland for 3 1/2 x 185 sqmm PVC armoured LTUG cable with earth connection .
Supply and providing cable end termination of 3 ½ x 185 sqmm PVC LTUG Aluminium armoured cable with necessary aluminium cable sockets by crimping etc. with electrical connection complete.
Supply and laying of 3 1/2 x 240 sq mm PVC armoured LTUG cable in a trench to be excavated at a depth of 0.75 metre putting 0.15 mt. Laner of sand and covering the cable completely with bricks and sand and refilling the earth to make good (for 400A Panel incoming & LTCT)
Supply and clamping of 3 ½ x 240 sqmm PVC LTUG armoured LTUG cable on post or on wall with MS clamps.
Supply and fixing of brass cable gland for 3 1/2 x 240 sqmm PVC armoured LTUG cable with earth connection .
Supply and providing cable end termination of 3 ½ x 240 sqmm PVC LTUG Aluminium armoured cable with necessary aluminium cable sockets by crimping etc. with electrical connection complete.
supply and fixing of 48W LED street light fitting with LED (Higher end) with 32mm dia. GI pipe (class B) with 1 no.32 mm GI bend complete on the existing post/ on wall with PVC unsheathed copper leads with MS clamps and with painting
Supply, Commissioning, testing and handing over of of 5 KVA Single Phase input to Single PhaseOutput True online Micro processor Controlled Double conversion type,True On line UPS system with Isolation transformer with 12V SMF batteries of required numbers with suitable battery Interlink cables for 2 Hours Back up Time, DC power should be minimum 30000W-Hour and with suitable MS powder coated Rack for Batteries complete with the following specifications.. Configuration: True On line double conversion UPS system with pulse width modulation (PWM) Technology using IGBT inverter. RECTIFIER: Full wave(shall fully meet the specified input power requirements ) INPUT: Three phase 320V -460V AC OUT PUT:230V AC± 1% on battery mode FREQUENCY: 47HZ - 53HZ SYSTEMDCVOLTAGE:Itmayvaryfrom240VDCto336VDCdependsonthemanufaturer,HoweverDC power should be minimum 30000Watts-Hour. INVERSIONTECHNOLOGY:Microprocessorcontrolled,pulsewidthmodulationwithInstantaneous sine Wave control using IGBT. INVERTEROUTPUT:(OutputGalvanicIsolationthroughDoublewindingIsolationTransformeratOutput of Inverter shall be part of UPS Design ) LOAD POWER FACTOR: 0.9 to unity REGULATION : for Balanced load ± 1% For 100% unbalanced load ± 2% FREQUENCY: 50Hz + 0.5% WAVE FORM : Pure sine wave TOTAL HARMONIC DISTORTION : < 3%
OVERLOADCAPACITY:InverseTimeCharacteristic125% for 10 minutes 150% for 1 minutes EFFICIENCY : 1. Converter – 95% 2. Inverter - 95% 3. Overall >90% ( full load) OperatingTemperature:0to45Degreescentigrade on full load CREAST FACTOR: 3 : 1 RELATIVEHumidity::95%at35DegreeCentigrade non- Condensing CHARGER: Built in solid state automatic float- cum boost charger with constant current, constant, voltage mode of charging along with current limiting features. Ripple in DC shall not exceed 2% when battery is disconnected.. PROTECTION( In built) i) output under Voltage ii) output over Voltage iii) ) output over load iv) output short circuit. v) HRC fuses /output/ battery vi) Battery low trip vii) battery charges current limit. INDICATIONS: i. Mains ON ii. Inverter ON iii. UPS ON battery iv. Load On UPS v. Battery LOW
METERING: i. Output AC Voltage ii.Output DC Voltage / Load details and Frequency By Pass: Manual Centigrade non- Condensing CHARGER: Built in solid state automatic float- cum boost charger with constant current,constant, voltage mode of charging along with current limiting features. Ripple in DC shall not exceed 2% when battery is disconnected. PROTECTION( In built) i) output under Voltage ii) output over Voltage iii) ) output over load iv) output short circuit. v) HRC fuses /output/ battery vi) Battery low trip vii) battery charges current limit. INDICATIONS: i. Mains ON ii. Inverter ON iii. UPS ON battery iv. Load On UPS v. Battery LOW METERING: i. Output AC Voltage ii.Output DC Voltage / Load details and Frequency By Pass: Manual Warranty:24MonthsfromDateofinstallationforthe UPS including battery. (Reputed make like numeric, consul)
Supply erection, testing, commissioning Off-line uninterrupted power supply OFFLINE (sinewave) with copper wound transformer of 2000VA with input supply of 230V, 50Hz AC supply with 150AH Tubular battery to work at full load capacity including transportation with following specification. 1.Input voltage: 230, 50Hz single phase AC Supply 2.Output voltage: 220V to 240V 50Hz AC Supply 3.Battery charging device of suitable rating 4.Circuit board of suitable capacity 5.Over load and short circuit protection 6.Visual Indication for ON/OFF/Trip/battery charging/mains failure/low battery etc., 7.Mode setting for By pass/Reset 8.12V 150AH battery - 2 Nos. 9.Trolly for heavy UPS & Battery (make: Exide/Microteck/Amron/Equivalent)
Earthing as per the ISI specification with an earth electrode of 2.10 metre Class 'B' GI pipe of dia not less than 40mm with copper earth plate of size 125mm x 50mm x 6mm with necessary funneling arrangements with necessary masonry work and with 38mm RCC cover slab for the brick masonry
Supply and run of 25mm x 3mm tinned copper flat with necessary clamps / supports on wall / floor / ground for earth connection.
supply and Run of 1 of No.8 SWG Hard drawn copper in suitable PVC rigid pipe on wall ceiling with painting of suitable colour.
Supply, Erection, testing and Commissioning of 2.0 TR (6000K cal / hr) ABS plastic split type Air conditioner confirming to IS 1391 [part 2] 1992 with Non CFL compressor operating on refrigerant suitable for wall mounting for operation on 230V, 50 HZ single phase AC supply with Three Star rating as per BEE Specification Three Star Rated and capable of performing the following functions. (A) Cooling (B) Dehumidifying (C) Air Circulating. (D) Filtering.The installation work for the above split type AC units includes the following. 1. Mounting / fixing indoor and outdoor units at their respective locations. 2. Laying refrigerent pipe line of 6mtrs. Length, both units after drilling hole / holes in the wall if required. Thickness of the copper tubing shall not be less than 0.7mm. 3. Installing the suction pipe with expanded polyurthelene foam 5mm thick tubing. 4. Laying 25mm dia flexible PVC drain pipe of 6mts. Length to drawn out the condensate water being formed in the indoor unit. 5. Leakage testing the entire gas unit. 6. Charging refrigerant gas in the unit. 7. Suitable electric wiring to be provided 3 core with 2.5 sqmm PVC insulated copper wire between indoor and outdoor units up to 4mtr. length and up to switch within the 3 mtrs. of location of indoor unit. (Make - Carrier / Voltas / Blue Star make only)
Supply, Erection, testing and Commissioning of 1.5 TR (4000K cal / hr) ABS plastic split type Air conditioner confirming to IS 1391 [part 2] 1992 with Non CFL compressor operating on refrigerant suitable for wall mounting for operation on 230V, 50 HZ single phase AC supply with Three Star rating as per BEE Specification Three Star Rated and capable of performing the following functions. (A) Cooling (B) Dehumidifying (C) Air Circulating. (D) Filtering.The installation work for the above split type AC units includes the following. 1. Mounting / fixing indoor and outdoor units at their respective locations. 2. Laying refrigerent pipe line of 6mtrs. Length, both units after drilling hole / holes in the wall if required. Thickness of the copper tubing shall not be less than 0.7mm. 3. Installing the suction pipe with expanded polyurthelene foam 5mm thick tubing. 4. Laying 25mm dia flexible PVC drain pipe of 6mts. Length to drawn out the condensate water being formed in the indoor unit. 5. Leakage testing the entire gas unit. 6. Charging refrigerant gas in the unit. 7. Suitable electric wiring to be provided 3 core with 2.5 sqmm PVC insulated copper wire between indoor and outdoor units up to 4mtr. length and up to switch within the 3 mtrs. of location of indoor unit. (Make - Carrier / Voltas / Blue Star make only)
Supply and Erection of 5 KVA electronic automatic Voltage stabilzer with input range of 170V-270V and output range of 200-240V with high / low cut off 3 minutes time delay relay with demonstration suitable for operation on 230V/50HZ single phase AC supply.(V-GUARD/syscom/equ).
Supply and Erection of 4 KVA electronic automatic Voltage stabilzer with input range of 170V-270V and output range of 200-240V with high / low cut off 3 minutes time delay relay with demonstration suitable for operation on 230V/50HZ single phase AC supply.(V-GUARD/syscom/equ).
Supply and fixing of MS stand for fixing outdoor unit
Supply, erection testing, commissioning and handing over of 1No,40 KVA diesel generator set 0.80 P.F, 3phase, 415v/420 Volts, 50c/s, 1500 RPM complete in all respects as detailed below A.Engine Air Cooled diesel engine suitable for generator application with a shaft out put of 56HP/41KW suitable at 1500 RPM under NTP conditions as per BSS 5414-ISO 10000. The engine shall comprise the following standard scope of supply: (Make Kirloskar/ Cummins/ Ashok Leyland/ Greaves/ Equivalent) A.Engine Air Cooled diesel engine suitable for generator applicationwith a shaft outputof56HP/41KWsuitableat1500RPMunderNTPconditionsasperBSS5414-ISO10000. The engine shall comprise the following standard scope of supply: (MakeKirloskar/ Cummins/ AshokLeyland/ Greaves/ Equivalent) 1) Dry type Air cleaner 2) Expansion bellow 3) Radiator, radiator fan and mounting 4) Air to air charge cooler 5) Exhaust gas turbo charger 6) Lube oil cooler and lube oil filter filter 7) Fuel filter (pre and micro) 8) In-line mono-block fuel injection pump with governor and fuel feed pump 9) Electronic governor 10) 12V / 24V battery charging alternator 11) 12V / 24V Volt electric starter motor 12) Engine test certificate 13) Residential Mufler 14) Fly wheel with starter ring. Engine instrument panel/mounted Engine control panel consisting of ON/OFF/START/KEY, lube oil pressure gauge, oil temperature gauge, high water temperature gauge and electronic hour meter and RPM indicator.
27)MCCB of 100A capacity with magnetic thermalover load release, instant start circuit trip and under voltage release switch. 28)Rectangular copperbusbars(1Noforeachphase,neutralandearthingterminal)ofadequatecapacitydulycolourcodedwithheadshrinkablePVC sleeves. 29) 1No mains voltage monitor 30)Hooter/Audioalarmforindicationsetfailstostart and for DG O/L 31) 1set timers 32) Audio and visual indication arrangements for a) Low lubricating oil pressure b) High water temperature c) Over speed 33) 1No Earth fault relay 34) Isolator to Isolate the neutral Note: 1.Thecontrolpanelshouldbecompletewithnecessaryfuses,cables,labels,otheraccessorieswith neutral isolation arrangements. 2.Theengineshouldtripforthefollowingconditions. a) Low lubricating oil pressure b) High water temperature c) Over speed 4) ACOUSTIC ENCLOSURE: Acoustic enclosure shall be powder coated and fabricated of 16SWG CRCA MS sheet. The silent canopy shall be nut bolt type construction. Critical processes of punching are done on CNC machine to maintain dimensional accuracy of hole within 0.1mm power coating done after seven-tank surface preparation process of sheet metal. Canopy panel and door shall have inside lining of FIRE-RETARDANT 64kg/m density mineral wool of 100mm thickness as acoustic material. Four hinged doors shall be provided to canopy.
The maximum permissble sound pressue level should be as per the norms prescribed by the Central Pollution Control Board / State Pollution Control Board/ Competent Authority concerened or shouble be 75 db(A) at 1 meter from the enclosure surface whichever is advantageous to the department. The emergency stop should be available on the enclosure panel. The enclosure provided shall be duly approved by the Engine Manufacturer of the Engine provided for Diesel Generator Sets mounted inside and should be to the satisfaction of inspection / testing authority concern. SURFACE TREATMENT – PAINTING The enclosure shall be suitably treated for degreasing, de-rusting and phospating. The canopies are passed through seven-tank treatment thoroughly. ADDITIONAL FEATURES OF CANOPIES Canopy fabricated on CNC machines with dimensional accuracy of 0.1mm so as to increase its durability. Special designed supporting rips/structures are used in canopies so as to give sturdiness and to reduce the vibrations of the DG sets if any. WORLD CLASS COOLING PACKAGE: Canopies shall have cooling package for which it can perform at 45 deg c/ambient temperature. No grounding required on the ground, only a level surface capable of with standing the DG weight. Lifting hooks shall be provided for the acoustic enclosure, which should be unloaded independently of the DG set. The Gen set frame shall also be provided with hooks for unloading. Temperature rise inside the canopy: Canopies shall be designed so as to maintain the temperature difference between ambient and air inlet at cleaner within the enclosure well with in 5-7 deg centigrade.
5) Base Frame Base frame should be fabricated in sheet metal. The base frame is rugged in construction and designed for mounting engine and brush less alternator closely coupled, with cross members mounted on AVM. The base frame shall have provision for mounting of acoustic enclosure on it. The supply of Gen set includes loading, unloading and transportation charges6) Fuel Tank 100 Ltrs. Removable Fuel tank shall be fabricated out of 14 SWG CRCA MS sheet and is part of base frame. It is duly painted and fitted with inlet an outlet connections and mechanical fuel gauge. Fuel tank can be easily removed for cleaning or any maintenance.. 7) Battery 12V 180 AH battery
ERECTION, TESTING AND COMMISSIONING Providing suitable concrete foundation with cement concrete 1:2:4 with sand cushion all around the foundation for erection of Diesel Generator set.
Supply and fixing of 65 mm dia. (2½") GI pipe (class B) of 6 metre length with 300mm x 300mm x 6mm MS base plate duly welded at the bottom with concreting with construction of masonary pedestal with suitable SMC box with door arrangement to house 6A SP MCB switch, 2/4 way connector on suitable hylem sheet and supply and fixing of 60W LED street light fitting with LED (Lower end) with 1 metre 32mm dia. GI pipe (class B) Complete with suitable MS clamps for LED steet light fitting and SMC box with PVC unsheathed copper leads from SMC box to fitting and with painting of suitable colour.
Supply and Laying of 4 x 10 sq.mm PVC Al armored LTUG cable in 32mm dia GI pipe(Class-B) in a tranch to be excavated at a depth of 0.75 mtrs and refilling the earth to make good.
Supply and Clamping of 4 x 10 sq.mm PVC Al armored LTUG cable in 32mm dia GI pipe(Class-B) in a tranch to be excavated at a depth of 0.75 mtrs and refilling the earth to make good.
Supply and fixing of brass cable gland for 4 x 10 sq.mm PVC armoured LTUG cable with earth connection.
Supply and providing cable end termination of 4 x 10 sq.mm PVC LTUG armoured Al cable with necessary aluminum cable sockets by crimping etc. with electrical connection complete.
Supply and fixing of 100W LED flood light fitting complete on MS angle with PVC unsheathed Copper leads from terminals to the fitting. (Make: Philips/ Havells/ Equ).
Supply and fixing of 40 mm dia GI pipe (Class 'B') of 0.5 Mts. Length with concreting and construction on existing Masonary pedestal with MS box of 30cm x 20cm x 10cm with angle iron frame work with door with lock and key arrangements and with supply and fixing of LED post top 40W LED fitting Bajaj Make [BGCTNP 40W WH/WW] made in Spun aluminium powder coated housing with higher ciency lighting & IP65 protection and necessary accessories with supply and fixing of 16A fuse unit (500V), 5A SP switch, inside the MS box and painting with suitable colour.
Supply and installation of unmanageable 24 port 10/100/1000 Mbps switches with 1G uplink and 24 port Jack Panel.Make:Cisco or Hp or Netgear or equivalent
Supply and installation of unmanageable 16 port 10/100/1000 Mbps switches with 1G uplink and 24 port Jack Panel.Make:Cisco or Hp or Netgear or equivalent
Supply,Installation and termination of Cat 6 UTP Patch cord of 1 metre. Make:DLink or ADC or Molex or Digilink or equivalent
Supply,Installation and termination of Cat 6 UTP Patch cord of 2 metre.Make:D Link or Molex or Digilink or equivalent
Supply,Installation and termination of RJ45 Cat-6 IO connector,Back box,face plate with surface mount.Make :Dlink or ADC or Molex or Digilink or Legrand or equivalent
Supply and installation of 4MP high resolution IR Bullet Camera with 1/3" Progressive scan CMO,HD video output,Day &Night IR Cut Filter,4MM (Angle of View 80degree)Lens,Low illumination,maximum 20fps,3D DNR & DWDR & BLC,IR range: up to 30m,Water and dust resistant (IP67)Make and Model:Hikvision or Dahua or equivalent
Supply and installation of 10 / 100/1000Mbps 08 Port Gigabyte PoE Switch with 8 × Gigabit PoE ports, 2 × Gigabit fiber optical ports.Make and Model:Netgear or Cisco or D link or equivalent
Supply and installation of 16Channel Network video Recorder Connectable to the third-party network camera,Support live view, storage, and playback of the connected camera with up to the resolution of 5 megapixels and 2 SATA hard disks can be connected.Make and Model:Hikvision or Dahua
Supply and installation of 4TB Hard Disc drive recording capacity NVR with USB 3.0 connectivity.Make and Model:Western /seagate/ Equivalent . SOR Part-P Item 38-b
Supply and installation of 32 inches Smart HD TV with 2 Nos of HDMI port with tilting Stand and 2 Nos of USB port with full HD resolution of 1920X1080 pixels.Make and Model:Sony/ Samsung/LG or equivalent
Supply and run of UTP Cat6 cable through existing pipe concealed in the wall/ceiling with necessary connection.Make : Finolex or Dlink or equivalent
Supply and laying of ISI approved 25 mm PVC rigid pipe concealed on wall and ceiling with painting of suitable colour.Make : Finolex or Dlink or equivalent
Supply and installation 4U MS Rack for housing Switches,Jack Panel with top and Bottom Cable Entry provision along with necessary power distribution unit,cable manager,fan and Lockable Toughened Glass D
Supply and installation 9U MS Rack for housing Switches,Jack Panel with top and Bottom Cable Entry provision along with necessary power distribution unit,cable manager,fan and Lockable Toughened Glass
Exhaust Piping with silencer :DG set should be offered completed with exhaust piping, ie, silence is mounted tnd connected by means of MS pipe through flexible pipe to the engine manifold. Entire exhaust piping inside the conopy (cold zone) is insulated by means of ceramic wool and aluminum glazing.
Providing fuel oil to run the set for 8 hours on load testing and commissioning using water rheostat or suitable leading element. First charging of oil to fll capacity and first charging of battery while handing over to dept.
Preparation of site plan, physical layout, electrical line schematic diagram in 10 sets getting drawing approval from CEIG preparation of completion report, rectification report and arranging CEIG inspection and obtaining safety certificate preparation of 1 set of approved drawing and a copy of safety certificate in a neat frame work to be fixed in generator room and payment of CEIG inspection fees.
Annai Electricals
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .