| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.3 LAccepted-AOC GROUND FLOOR TRACTOR MARKET KAITHAL ROAD ASSANDH KARNAL HARYANA 132039 | KARNAL | HARYANA | 132039 | L1 | Accepted-AOC L1 | |
| 2 | L2₹11.5 L+₹1.7 L (16.9%)Rejected-Finance | L2 | Rejected-Finance Other than L1 | |
| 3 | L3₹11.8 L+₹1.9 L (19.6%)Rejected-Finance CHANDPURA TIKAMGARH DIST TIKAMGARH MP | TIKAMGARH | TIKAMGARH | MADHYA PRADESH | L3 | Rejected-Finance Other than L1 |
Tender Value
₹16.4 L
EMD Value
₹32,700
Closing Date
7 Feb 2022, 6:00 pmClosed
GE (AF) Bhisiana
Military Engineer Services, Garrison Engineer (AF), Bhisiana, Bathinda-151201
Maint/Repair/Replacement of External Water Supply Distribution and Fire Hydrant System alongwith connected ITems at AF Stn Bhisiana
2022_MES_500675_1
GE/BHI-64/2021-22
Open Tender
Miscellaneous Works
Item Rate
180 days
GE (AF) Bhisiana
Please Refer Tender Documents
8 documents required · 8 mandatory
₹500
GE (AF) Bhisiana
₹32,700
Yes
12 May 2022
10 Jan 2022
9 Feb 2022
10 Jan 2022
7 Feb 2022
24 Jan 2022
11 Jan 2022 - 18 Jan 2022
Amount
Taking down U/S and supply and fix single channel four pipe Laser Aspiration detection unit . The unit should be UL and VDS approved complete with display of all alaram dual filter on board 20000 event log memory woth RS 232 port . The device should support minimum 100 m pipe for each channel and sesnivity of 1%/m All as specified and directed by Engr-in-Charge.
Taking down unserviceable and S&F repeater panel having display system of existing make and model suitable to incorporate in existing system having LOOP: fire red Lamp ON, Open Amber Lamp ON, Short Amber Lamp ON, Isolate Amber Lamp ON Monitor Mains ON 230VDC, Earth Line fault, BAT, low , BAT Discharge, CPU RUN-Processor working Controls: Lamp Test-Healthiness of lamp, Silence -tomute sounders Evacuate-evacuate the building, Re set - Torestore system. Contractor shall visit each repeater panel prior quoting the rate to know the current status of respective Panel No claim on whatsoever account shall be entertained during current of work, complete all as directed by Engr-in-Charge of existing make Agni.
Taking down unserviceable and S&F of ECO sensor for CO monitoring suitable to existing make and model to incorporate in existing system. Contractor shall visit each sensor prior quoting the rate to know the current status of respective sensor mechanism No claim on whatsoever account shall be entertained during current of work all as directed by Engr-in-Charge.
Comprehensive maintenance of Microprocessor based panel 1 loop analogue addressble type fire alaram control panel with 80 character CD diaplay with battery backup of 1½ hours access 500 events histrocial logging having loop Free red lamp on, Open Amber lamp ON, Short - Amber lamp On , Isolate - Amber Lamp On, Control : Lamp test-LED Healthy, Sielence - TO stop alarm, Evacuate - fire alarm ON, Reset-to Restore system, Monitor : mains ON-230 VAC, BAT ON-system at BAT, System ON -24 VDC, Xharger ON 27.3 VDC, Fire sounser ON, Silence - MUTE/ACK, Earth - Line Fault , BAT LOW -Bat Below 22 V . Note : The ccontractor will be responsible to replace all spare parts minior/major required to serviceabe of panle, Nothing will be paid to extra during contract period, If he fail to rectify with 24 Hrs Recovery @ 1000 per day wiil be made in RAR/Final Bill.
Taking out unserviceable and S&F power supply units comprising of battery backup for 1½ hours charging units, MCB DB and necessary MCB-power supply unit should have capacity to operate on 230 volt AC main input and provide 24 to 30 volts DC output for powering up. The unit shall also supports battery backup in case of AC main failure and should have built in charging circuit to batttery suitable to existing make and model suitable to incorporate in existing system. Contractor shall visit each supply unit prior quoting the rate to know the current status of respective supply unit mechanism. No claim on whatsoever account shall be entertained during current of work all as directed by Engr-in-Charge.
Taking down unserviceable and S&F of analoge addressable photo electric smoke detector with mounting based LED, address switch to programme the detector from 01-99 with BASE complete as required programme the detector rom 01-99 with BASE complete as required the contractor shall visit each photo electric smoke detector unit prior quoting the rate to know the current status of respective photo electric smoke detector mechanism. No claim on whatsoever account shall be entertained during current of work all as directed by Engr-in-Charge.
Taking down unserviceable and S&F of addressable hooter with strobe for alaram annunciation along with all required accessories (Weathr proof all as specified and as directed by Engr-in-charge existing make and model suitable to incorporate in existing system. The contractor shall visit each photo hooter unit prior quoting the rate to know the current status of respective hooter mechanism. No claim on whatsoever account shall be entertained during current of work complete all as directed by Engr-in-Charge.
Taking down unserviceable and S&F addressable manual call point complete as per OEM specification (weather proof). The item should be suitable to incorporate in existing system, complete all as directed by Engr-in-Charge. Note : The contractor shall advised to check make and model before quoting of tender and examine each photo hooter unit prior quoting the rate to know the current status of respective hooter mechanism. No claim on whatsoever account shall be entertained during current of work.
Taking down unserviceable and S&F response indicator the item should be suitable to incorporate in existing system, complete all as directed by Engr-in-Charge. Note : The contractor swill be check make and model before quoting of tender he contractor shall visit each photo hooter unit prior quoting the rate to know the current status of respective hooter mechanism. No claim on whatsoever account shall be entertained during current of work.
Takng down unserviceable and S&F addressable control module for Hooter complete as required as per OEM specification and suitable to existing make and model suitable to incorporate in existing system, complete all as directed by Engr-in-Charge. Note : The contractor will be check make and model before quoting of tender. The contractor shall visit each photo hooter unit prior quoting the rate to know the current status of respective hooter mechanism. No claim on whatsoever account shall be entertained during current of work.
Taking down unserviceable of aspiration system address switch to programme the monitor modules from 01-09 complete as per OEM specification suitable existing make and model suitable to incorporate in existing system, complete all as directed by Engr-in-Charge. Note : The contractor will be check make and model before quoting of tender. The contractor shall visit each photo hooter unit prior quoting the rate to know the current status of respective hooter mechanism. No claim on whatsoever account shall be entertained during current of work.
Taking down unserviceable and S&F cable copper 03 core x 1 sqmm for power-24 AWG stranded (7x32) tinned coppper conductor in suitable PVC conduit existing make Havells/Polycab/KEI and model suitable to incorporate in existing system. Note : The contractor shall check make and model before quoting of tender.
Taking down unserviceable and S&F cable copper 02 core x 1.5 sqmm twisted pair shielded cable for FAP connectivity-24 SWG stranded (7x32) tinned copper conductor in suitable PVC conduit existing make Havells/Polycab/KEI and model suitable to incorporate in existing system. Note : The contractor will be check make and model before quoting of tender.
Repacemet of Motor shaft of item No 10 abvoe. The contractor shall visit each photo hooter unit prior quoting the rate to know the current status of respective hooter mechanism. No claim on whatsoever account shall be entertained during current of work all as specified and directed by Engr-in-Charge.
Taking down electric motor 40 HP, 415 volt, 03 Phase coupled to pump after disconnecting the electrical connection, and earth connections from its foundation and transportation to work shop, checking the serviceability of ball bearing on both side of motor, greasing of bearing up to free rotation of shaft of motor complete, greasing on reassemblying the motor to reinstallation on foundation, reconnecting back the cable and earth connections etc complete in all respect and starting the pump all as directed. The contractor shall visit each photo hooter unit prior quoting the rate to know the current status of respective hooter mechanism. No claim on whatsoever account shall be entertained during current of work all as specified and directed by Engr-in-Charge.
Replacement of ball bearing of above motor bearing of existing make and model with providing of high grade grease, suitable to incorporate in existing system. Note : The contractor will be check make and model before quoting of tender.
Repacemet of Motor shaft of above item No. 15 here in before.
Taking down jockey fire hydrant motor coupled with jockey pump fire hydrant motor 70 mtr head horizantal mounted split case two stage centrifugal pump electric induction motor 10 HP to 15 HP, 3 phase, 415 volt, 50 Hz coupled to pump after disconnecting the electrical connection, and earth connections from its foundation and transportation to work shop, checking the serviceability of ball bearing both side of motor, greasing of bearing up to free rotation of shaft of motor complete, greasing on reassemblying the motor to reinstallation on foundation, reconnecting back the cable and earth connections etc complete in all respect and starting the motor all as directed by Engr-in-Charge.
Replacement of ball bearing of above motor bearing of existing make and model with providing of high grade grease suitable to incorporate in existing system. The contractor shall visit each photo hooter unit prior quoting the rate to know the current status of respective hooter mechanism. No claim on whatsoever account shall be entertained during current of work all as specified and directed by Engr-in-Charge.
Replacement of motor shaft of 10 -15 HP Motor of item No 18 here in before.
M&L for opening of submersible motor coupled with submersible pump non dog type with horizontal/verticle mounted submersible pump electric induction motor 10 HP, 415 volt 03 phase coupled to pump after disconnecting the electrical connection, and earth connections from its foundation and transportation to work shop, checking the serviceability of ball bearing both side of motor, greasing of bearing up to free rotation of shaft of motor complete, greasing on reassemblying the motor to reinstallation on foundation, reconnecting back the cable and earth connections etc complete in all respect and starting the pump all as directed.
Replacement of ball bearing of above motor bearing of existing make and model with providing of high grade grease suitable to incorporate in existing system. Note : The contractor will be check make and model before quoting of tender.
Replacemet of Motor shaft of item No 21 here in above.
M&L for opening of submersible motor coupled with submersible pump non dog type with horizantal/ verticle mounted submersible pump electric induction motor 15 to 20 HP, 415 volt, 03 phase coupled to pump after disconnecting the electrical connection, and earth connections from its foundation and transportation to work shop, checking the serviceability of ball bearing both side of motor, greasing of bearing up to free rotation of shaft of motor complete, greasing on reassemblying the motor to reinstallation on foundation, reconnecting back the cable and earth connections etc complete in all respect and starting the pump all as directed.
Replacement of ball bearing of above motor bearing of existing make and model with providing of high grade grease suitable to incorporate in existing system. Note : The contractor shall check make and model before quoting of tender.
Replacemet of Motor shaft of item No 24 here in abvoe.
M&L for opening of submersible motor coupled with submersible pump with horizantal/verticle mounted submersible pump electric induction motor up to 05 HP, 415 volt, 3 phase coupled to pump after disconnecting the electrical connection, and earth connections from its foundation and transportation to work shop, checking the serviceability of ball bearing both side of motor, greasing of bearing up to free rotation of shaft of motor complete, greasing on reassemblying the motor to reinstallation on foundation, reconnecting back the cable and earth connections etc complete in all respect and starting the pump all as directed.
Replacement of ball bearing of above motor bearing of existing make and model with providing of high grade grease suitable to incorporate in existing system. Note : The contractor will be check make and model before quoting of tender.
Repacemet of motor shaft of item No 27 here in above.
M&L for opening jockey fire hydrant pump horizantal mounted centrifugal pump having discharge 180 LPM LPM at 70 mtr head pressure not less than 7.0 kg/cm2 suitable for fire fighting and conforming to IS 12469-1988 coupled with totally enclosed drip proof squrrel cage energy efficent induction motor 10 to 12.5 HP, make Kirloskar Compton from motor coupling after opening of suction and deliverry pipe along with sluice valve/ butterfly valve connections opening the pump set for repair/overhauling & proper alignment of shaft etc including replacing the items with new items given vide item below, reassemblying the pumpset greasing connecting, testing and commissioning complete including necessary Lathe works in OEM Workshop in prenesenc eof Rep of GE Bhisiana all as specified. Note (i) The contractor shall be visit the pump before quoting of tender. (ii) Spare part will be measured and paid separately under following item No 31.
Supply only following items for Ser Item No. 30 above:-
Supply only pump shaft sleeve made out of gun metal.
Supply only key for main shaft/impeller.
Supply only check nut for pump set shaft.
Supply only motor pump coupling complete with nut, bolts etc.
Supply only water seal.
Supply only rubber tyre coupling complete make Fenner/Unique/Unimac.
Supply only pump set bearing housing.
Supply only pump Shaft.
Supply ball/roller bearing complete.
Couping guard.
Shaft Bush.
Bronze impeller.
Note : All the items/parts mentioned against 31 here-in-before shall be suitable/compatible for the type and make of pumping set as mentioned against item No 30 above. Cost of fixing of items is deemed to be included in the unit rate of item above.
M&L for opening pump set split case centrifugal type coupled to electric motor of capacity 40 HP, make Kirloskar Compton from motor coupling after dismntling the suction and delivery pipe connections opening the pump set for repair/overhauling and proper alignment of shaft etc including replacing the items with new items given vide item No. 33 below, reassemblying the pump set greasing connecting, testing and commissioning complete including necessary Lathe works all as specified.
Supply only spare parts for pump set for fixing against item No 32 as follows:-
Supply only pump shaft sleeve made out of gun metal.
Supply only key for main shaft/impeller.
Supply only check nut for pump set shaft.
Supply only stuffing box bush.
Supply only motor pump coupling complete with nut, bolts etc.
Supply only water seal.
Supply only stuffing box packing.
Supply only rubber tyre coupling complete make Fenner/Unique/Unimac.
Supply only pump set bearing housing.
Supply only pump Shaft.
Supply ball/roller bearing complete.
Supply only Air relase valve.
Supply only Bronze impeller.
Note: All the items/parts mentioned against 33.01 to 33.13 here-in-before shall be suitable/compatible for the type and make of pumping set as mentioned against item No 32 above. Cost of fixing of items is deemed to be included in the unit rate of item above.
Dismantling Submersible pump set 15-20 HP 3 phase 415 V from UG sump/open well/ Borewell after isolating the electric and earth lead connections, suction and delivery pipes etc opening the pump set, replacing the unserviceable parts with new items given vide item No 35 given below and reassemblying the pump set and reinstalling on foundation frame connecting, testing and commissioning complete all as specified. The contractor shall visit each photo hooter unit prior quoting the rate to know the current status of respective hooter mechanism. No claim on whatsoever account shall be entertained during current of work all as specified and directed by Engr-in-Charge.
Supply only spare parts for pump set of capacity 15-20 HP for item No. 34 above as follows:-
Supply only pump shaft sleeve made out of gun metal.
Supply only key for main shaft.
Supply only check nut.
Supply only Bronze impeller.
Supply only water seal.
Supply only pump shaft any type borewell / horizantal/vericle submersible pump.
Supply only ball bearing complete.
Supply only Bush.
Dismantling Submersible pump set/ centrifugal type up to 5 HP, 3 phase 415 V from foundation base plate after isolating the electric and earth lead connections, suction and delivery pipes etc opening the pump set, motor rotor and stator etc for repair/overhauling and warnishing and baking the stator winding to enhance the insulation level including replacing the unserviceable parts with new items given vide item No 37. below and reassemblying the pumpset and reinstalling on foundation frame connecting, testing and commissioning complete all as specifiedV for fire SWT Pump.
Supply only spare parts for pump set of capacity up to 5 HP for above item No. 36. as follows:-
Supply only pump shaft sleeve made out of gun metal.
Supply only key for main shaft.
Supply only check nut.
Supply only bronze iron impeller.
Supply only water seal.
Supply only ball bearing complete.
M&L for opening diesel driven horizantal mounted centrifugal pump having discharge 2850 LPM at 70 mtr head Bronze impelller suitable for fire fighting and conforming to IS 12469-1988 coupled with totally diesel driven engine any make/model in from motor coupling after opening of suction and deliverry pipe alon with sluice valve/ butterfly valve connections opening the pump set for repair/overhauling and proper alignment of shaft etc including replacing the items with new items given vide item No. 39 below, reassemblying the pumpset greasing connecting, testing and commissioning complete including necessary Lathe works in OEM Workshop in prenesenc of Rep of GE Bhisiana all as specified. Note : (i) The contractor shall be visit the pump before quoting of tender. (ii) Spare part will be measured and paid seprately.
Supply only following items for above item No. 38. as follows:-
Supply only pump shaft sleeve made out of gun metal.
Supply only key for main shaft/impeller.
Supply only check nut for pump set shaft.
Supply only motor pump coupling complete with nut, bolts etc.
Supply only water seal.
Supply only rubber tyre coupling complete make Fenner/Unique/Unimac.
Supply only pump set bearing housing.
Supply only pump Shaft.
Supply ball/roller bearing complete.
Couping guard.
Bronze impeller.
Bush Brass.
Note : All the items/parts mentioned against 39.01 to 39.12 here-in-before shall be suitable/compatible for the type and make of pumping set as mentioned against item No 38 above. Cost of fixing of items is deemed to be included in the unit rate of item above.
M&L for Rewinding of pump motor 415 Volt 3 phase after disconnecting electric cable and eath lead, suction and delivery pipes, shifting to Bhatinda work shop, dismantling the motor assembly and removing the burnt out copper winding of stator and cleaning the stator slots and core assembly, rewinding to stator with suitable gauge super enamelled copper wire with insulating papers and insulation cloths, varnishing the winding and baking heating for achieving the required insulation resistance, re-assembling the motor and testing complete, incl transporting back to site and fixing motor to its original place, reconnecting electric cable and earth leads etc testing and commissioning complete in all respect all as specified and as directed by Engr-in-Charge for the following capacity: -
Up to 5 HP.
Taking out unserviceable basket type simple strainer of CS/CI body with stainless strainer element 40 mesh matching flange including nut & Bolts, gaskets suitable for flow 136 Cum/Hr at pressure of drop not more than 0.2 kg /cm2 at 50% chocked condition, body hydroest at 16.0 kg /cm2 for suction for fire fighting of size 150 mm bore.
Taking out unserviceable and S&F 'Y' type strainer of CS/CI body with ss strainer element 40 mesh matching flange nut bolt, gasket etc suitable for flow of 136 Cum/Hr at pressure of drop not more than 0.2 kg/cm 2 at 50% chocked condition, body hdrotest at 16 kg/cm2 for suction suitable for fire fighting of size 50 mm with suitable material complete all as directed.
M&L for cleaning of strainer all type and any size including dismantling and cleaning using Fernox DS-3 cleaner chemical or OEM recommendation and refixing of the same all as specified and as directed by Engr-in-Charge.
Taking down unservicjeable and S&F pressure gauge / indicatior 8" dial 0-21 kg rating including electrical connection with cut off setting etc suitable for fire fighting with suitable material complete all as specified and as directed.
Taking down unserviceable and supply and fix pressure switch -21 kgs rating 150 mm dial complete with isolation cock and syphone tube etc suitable for fighting with suitable material all as specified and directed by Engr-in-Charge.
Takaing out unserviceable and S&F fire hydrant landing valve double headed type with pick tube suitable for dischare of 900 LPM at a pressure of 7kg/cm2 complete suitable for fire fighting with suitable material all as directed by Engr-in-Charge.
Taking down unserviceable S&F fire hydrant stand post end flanged 1.5 mtr height with one end bend to 90 degree suitable for double fire hydrant valves including 1 No. CI duck foot bend 80 mm double end flanged and 1 No 80 mm 63mm reducer and 1 No 80 mm dia CI butterfly valve complete all as specified and as directed by Engr-in-Charge.
M&L for painting of fire hydrant stand post end flanged 1.5 mtr height with one end bend to 90 degree suitable for double fire hydrant valves including 1 No. CI duck foot bend 80 mm double end flanged and 1 No 80 mm 63mm reducer and 1 No 80 mm dia CI butterfly valve complete after removing all dust, dirt etc and clean the surface thoroughly with two coats of synthetic enamel paint including writing the complete all as specified and directed.
Taking down unserviceable and S&F in replacement weather proof cabinet of size 900x600x450mm made out of MS sheet 16 gauge having central opening and 4mm thick glass doors (2 Nos) suitably marked on the outside with Letters 'FIRE HOSE' cabinet with necessary locking arrangement including all fasterns etc and shutter shall be powder coated with signal red colour, shutter with frame fabricated all as specified and directed. The hose cabinet will be fixed PCC Platform near the Fire Hydrant and cost of PCC platform and fixing is deemed to be included in quoted cost.
Taking down unserviceable and M&L for replacement of RRL hose ISI marked with both coupling dia 63mm in 15mtr length of existing Make: life Guard/ OMEX.
Taking down unserviceable and M&L for replacement of RRL hose ISI marked with both male and female coupling dia 63mm in 30mtr length of existing Make: Life Guard or OMEX.
Taking down unserviceable and S&F in replacement 19mm dia rubber braided hose of 36 mtr length with gate valve of same size made of Brass material and shut of nozzle with working pressure of 12 bar in existing Hose reel drum of dia 565mm die cast manual swinging type as complete.
Taking out the existing pump and motor from the base plate of capacity 40 HP including disconnecting the existing electrical connection, suction and delivery line including earth work and dismantling/Demolition /breaking the existing RCC /PCC foundation and make NEW foundation same size as existing or as per OEM Recommendation Providing new RCC foundation same size as existing, base plate made from 6 mm thick iron plate/ angel suitable size as existing pump frame, iron angles frame, anti vibration pad, nut bolts washer for holding to pump with motor and again re-fixing, testing, installation, commissioning of the 40 HP Pump set with motor with "0" vibration of pump set, pipe line foundation as per manufacture design, including necessery electrical connection and water connection in let out let testing complete as existing and as directed by Eng-In-Charge. Note : The cost shall be making new foundation using included Iron Rod, RCC work, PCC work and making disturbed surface as same as existing. The cost shall also included removing, demolition material obtaining from old structure and deposited 50 mtr away from pump house. The contractor will check the site and will take measurement of existing foundation i.e Length, width, height, nut, bolt size, base frame etc. before quoting of tender and take measurement of existing pump with motor foundation.
Taking down unserviceable and supply and fix RYB indicator.
Taking down unserviceable and supply and fix voltmeter as per sample, Digital type.
Taking down unserviceable and supply and fix Amp meter as per, Digital type.
Taking down unserviceable and supply and fix over laod relay as per existing capacity.
Taking out unserviceable and supply and fix Auxillary contactor 2 NO-2 NC as per sample.
Taking out unserviceable and supply and fix on delay timer as per sample.
Taking out unserviceable and supply and fix push button start/stop as per sample.
Taking out unserviceable and supply and fix red indication as per sample.
Taking out unserviceable and supply and fix yellow indication as per sample.
Taking out unserviceable and supply and fix green indication as per sample.
Taking down unserviceable and supply and fix 4 sqmm copper wire for internal wiring.
Taking down unserviceable and supply and fix lugs as per sample.
Taking down unserviceable and supply and fix add on 2 NO - 02 NC as per sample.
Taking down unserviceable and supply and fix spreader link kit as per sample.
Taking out unservicable and S&F MCCB 4 pole 200 Amp, breaking capacity 35 Ka, 415 volts, 50 Hz including necessary incoming and out going electric connection with suitable size of copper lugs etc.
Taking out unservicable and S&F MCCB 4 pole 200 Amp, breaking capacity 50 Ka, 415 volts, 50 Hz including necessary incoming and out going electric connection with suitable size of copper lugs etc.
Taking out unservicable and S&F MCCB 4 pole 63 Amp, breaking capacity 50 Ka, 415 volts, 50 Hz including necessary incoming and out going electric connection with suitable size of copper lugs etc.
S&F Motor protection relay MPR 300 of exising make of L&T/as approved Make.
Taking down unserviceable and S&F fully automatic Star delta startor up to 15 H.P. in sheet metal enclosure with 415 voltage 3 Phase with overload relay range (Amp range 9-22) with single phase preventer. Make C&S BE3-spssdx254321x or L&T.
Taking out unserviceable and S&F power contactor 3 pole 415 V AC type MNX 50, Make : L&T Cat No . ST19001 or equivalent in Siemens, C&S.
Taking out unserviceable and S&F electronic timer type ET 100 with time range 0 to 60 seconds, 360 Volt Make : L&T Cat No SE92003 or equivalent in Siemens, C&S.
Taking out unserviceable and S&F cast iron fittings like bends, tee, tail pieces collars etc, spigot, socketed and flanged ends type etc confirming IS up to 150mm bore pipes all as directed by Engineer in charge. Note : Lead Joints will be measured and paid seperately.
Taking down unserviceable and S&F electrically operated water pressure soleniod switch to operate at pressure rangeof 2.5 to 7.5 kg/cm2 complete all as directed by Engr-in-Charge.
Repair/overhauling of Diesel Driven Pump of Capacity 62-73 BHP installated at Tech Area and M&L for Periodical Maintenance and servicing of 62 BHP Diesel engine, battery with electrolite solution, terminals posts, repair of wiring in control panel using copper wire complete and and replacing contactor, timer, MCCB, indicator lamp keeping Diesel engine set fully operationable condition all as directed. (a) Dismantling and removing nuts & bolts electric connections, water connections for the following repairs/overhauling :- (i) Dismantling/opening of complete cylindr head assembly rocker arms assembly piston head assembly sleeves by removing nuts & bolts for repairs complete. (ii) Servicing Washing of complete engine parts with kerosene oil. (iii) Reassembling of complete engine by tightening of nuts and bolts with replacement of the following engine part given in Ser Item No. 70. and testing on full load for 8 hours :- Diesel Engine of Capacity 62-73 BHP (In Tech Area). Note: (i) The quoted rates shall deem to include cost of sufficent/ required man power employed for the maintanance purpose, T&P used and other petty items such as cotton waste, kerosene oil, nuts, bolts and washerss etc complete including labour cost for fixing spares etc. (ii) During maintanance, any spares required to be replaced shall be paid under respective items here under. Fixing charges of same are deemed to be included in quoted rate for maintenance of Diesel engine. If spares are not included here under, then department will provide the same free of cost for fixing. (iii) The contractor shall be liable to provide adequate number of mechanics if required during the maintenance/break down without any extra cost to government for smooth functioning of Diesel Engine. (iv) Contractor shall visit each Diesel engine prior Diesel engine quoting the rate to know the current status of respective Diesel engine. No claim on whatsoever account shall be entertained during current of work.
Supply only following materials/spares for maintanance of Diesel Engine of various capacities 62-73 BHP. To be changed if required at the time of maintanance of Diesel Engine, labour cost deemed included in Item No 69 above:-
Piston complete.
Sleeve.
Valve Seat.
Guide Valve.
Injector.
Gasket Set.
Pump repair complete.
Fuel Filter.
Lubrication oil filter.
Air Filter.
Ring Set.
Conneting Rod Bearing.
Cylinder Head.
CR Brush.
Main Bearing.
Timing Seal.
Complete Packing Kit.
Water Ring Kit.
Nozzle Pump Set.
Repair/overhauling of Diesel Driven Pump of Capacity 43-52 BHP installated at Tech Area and M&L for Periodical Maintenance and servicing of 62 BHP Diesel engine, battery with electrolite solution, terminals posts, repair of wiring in control panel using copper wire complete and replacing contactor, timer, MCCB, indicator lamp keeping Diesel engine set fully operationable condition all as directed. (a) Dismantling and removing nuts and bolts electric connections, water connections for the following repairs/overhauling :- (i) Dismantling/opening of complete cylindr head assembly rocker arms assembly piston head assembly sleeves by removing nuts & bolts for repairs complete. (ii) Servicing washing of complete engine parts with kerosene oil. (iii) Re-assembling of complete engine by tightening of nuts and bolts with replacement of the following engine part given at Ser No. 72 and testing on full load for 8 hours :- Diesel Engine of Capacity 43-52 BHP (at Tech Area) Note : (i) The quoted rates shall deem to include cost of sufficent/ required man power employed for the maintanance purpose, T&P used and other petty items such as cotton waste, kerosene oil, nuts, bolts and washerss etc complete including labour cost for fixing spares etc. (ii) During maintanance, any spares required to be replaced shall be paid under respective items hereunder. Fixing charges of same are deemed to be included in quoted rate for maintenance of Diesel engine. If spares are not included here under, then department will provide the same free of cost for fixing. (iii) The contractor shall be liable to provide adequate number of mechanics if required during the maintenance/break down without any extra cost to government for smooth functioning of Diesel engine. (iv) Contractor shall visit each Diesel engine prior Diesel engine quoting the rate to know the current status of respective Diesel engine. No claim on whatsoever account shall be entertained during current of work.
Supply only following materials/spares for maintanance of Diesel Engine of various capacities 43-52 BHP. To be changed if required at the time of maintanance of Diesel Engine, labour cost deemed included in Item No. 71 here in above:-
Piston complete.
Sleeve.
Valve Seat.
Guide Valve.
Injector.
Gasket Set.
Pump repair complete.
Fuel Filter with 'O' Ring.
Lubrication oil filter.
Air Filter.
Ring Set.
Conneting Rod Bearing.
Cylinder Head.
CR Brush.
Main Bearing.
Timing Seal.
Complete Packing Kit.
Water Ring Kit.
Nozzle Pump Set.
Supply only Lubricant oil 20 W 40W Make :- Castrol, Premix ,K-Cool.
Supply only distilled water in supplier's packing.
Supply only battery terminals for DG Set Battery.
Supply only flexiable fuel pipe of suitable size with banzo washers.
Supply and install 120 AH, 24 V Maintanance free battery. Make:- Exide, Amaco/As approved.
M&L for replacement of radiator cap with rubber gasket complete all as specefied and directed.
M&L for descaling and servicing the radiator of Diesel engine 62-73 BHP Cap internally and externally by using chemicals, including soldering the copper tubes and tank etc for arresting leakage complete all as specified and directed.
M&L for descaling and servicing the radiator of Diesel engine 43-52 BHP Cap internally and externally by using chemicals, including soldering the copper tubes and tank etc for arresting leakage complete all as specified and directed.
M&L for repairing the self Dynamo 12 Volts after removing from diesel engine set of any capacity and transporting to an authorised sevice centre complete all as specified and directed.
Supply and replacing Lub oil pressure guage 0 to 10 kg / sq cm complete all as specified and directed.
Supply and replacing Water outlet and inlet hose pipe from radiator to Engine and back from Engine to radiator complete all as specified and directed.
Supply and replacing Lub oil pipe complete all as specified and directed.
Supply and replacing Anti vibration rubber pad for radiator complete all as specified and directed.
Supply and fix in replacement fuel pipe, fuel filter to FIP wire braided complete all as specified and directed.
Supply and fix in replacement Low oil pressure switch 12 V, 1.7 Kg/sq cm complete all as specified and directed.
S&F in replacement of battery lead of copper conductor PVC insulated multi strand 1.25 Mtr long (two Nos) duly fixed with terminals and lugs complete all as directed.
Repairing the self starter after removing from the Diesel Engine set of capacity 73/62 BHP and transporting to an authorised sevice centre complete all as specified and directed.
Taking out unserviceable and S&F siren electric motor operated 35 KM range continious normal operation for at least 50 minut with sound level 65 db fixed on building roof all as specified and directed.
M&L for prepration of old painted surface of 35 to 60 HP Centrifugal Pump and motor by scratching /rubbing down the old paint by wire brush or emery paper and applying two coat of synthetic enamelecd paint etc. complete all as specified and directed .
M&L for prepration of old painted surface of 10 to 20 HP Centrifugal Pump and motor by scratching /rubbing down the old paint by wire brush or emery paper and applying two coat of synthetic enamelecd paint etc. complete all as specified and directed .
M&L for prepration of old painted surface of MS class C pipe of 150 mm dia by scratching /rubbing down the old paint by wire brush or emery paper and applying two coat of RED synthetic enamelecd paint and one coat of red oxide on surface of pipe up 20 mtr of length etc. complete all as specified and directed.
M&L for prepration of old painted surface of MS class C pipe of 100 mm dia by scratching /rubbing down the old paint by wire brush or emery paper and applying two coat of synthetic enamelecd paint and one coat of red oxide on surface of pipe up top 20 mtr of length etc. complete all as specified and directed.
S&F in replacement Female/Male Coupling with Blank Caps/Plugs of 63 mm of working pressure 10.5 kg/cm2 of Gun metal/Brass complete.
S&F in replacement Flanged & shore connection of 63 mm outlet of material Gun metal/S.S with nuts, bolts washer etc. complete.
S&F of glass of fire hydrant boxes of size 60x60 mm incl rubber gasket/seal complete all as specified and directed by Engr-in-Charge.
S&F in replacement Gun metal Air Release Valve 25/20 mm on wet riser, with shut off Forge Brass ball valve complete.
M&L for prepration of old painted surface of Fire Hose Cabinet of any size by scratching /rubbing down the old paint by wire brush or emery paper and applying two coat RED Paint and two coat of Red oxide Paint (weather proof and rust resistant) etc. complete all as specified and directed.
S&F in replacement Single Phase Preventor (VSP 3), 415 VAC, 50 Hz complete as per existing sample Sr No.-7W0609 of existing Make- Minilec/ As approved by GE.
S&F in replacement Contactor 150A, 415 VAC, 50 Hz complete as per existing make HPL/ As approved by GE.
S&F 25 Sqmm Copper Condutor Single core for connecting LT Panel to Motor (copper lugs and nut and bolts included in the quoted rate) all as specified and directed by Engr-in-Charge.
Taking out unserviceable and S&F Fire Hose Box made of 18 gauge MS Sheet 1800mmx600mmx250 mm with double door with 4 mm thick glasses and door frame made of 16 gauge MS sheet paint fire red oxide and brilliant white inside complate all as specified and all as directed by Engr-in-Charge.
Taking out unservicable cable of size 2.5 and Supply and fix 3 core 2.5 sqmm cable PVC insulated and sheathed sumersible type with stranded copper conductor.
Taking down unserviceable and S&F gland packing into the pump and sluice valve of any capcity and size all as specified and as directed.
Taking out unserviceable and M&L for gland flange suitable for 10 to 40HP monoblock pump set incl replacement of gland packing all as directed.
Supply and fill pump set bearing Grease/Lubicant oil suitbale for existing pump in various motor/pump.
Taking out unserviceable battery cell and S&F New battery cell 12 V 7 AH , Charging voltage ; Stand by 13.5 V Cyclic : 14.7V. Make Amaron/Exide.
M&L for opening air blower set twin lobe type of capacity 140 m3/hr with head of 0.65 mmwc make kirloskar rpm 1367 , blower & motor coupling after isolating the electric and earth lead connections opening the pump set for repair/overhauling & proper alignment of shaft etc including replacing the items with new items given below, reassemblying the pumpset greasing connecting, testing and commissioning complete including necessary Lath works all as specified at Filter plant at AF Stn Bhisiana. Note : Major Spares Parts will be measured & paid seperatly as supply only items.
Supply only spare parts for Air blower:-
Supply Only Blower Bearing of Existing size.
Supply Only Blower V Belt of Existing size.
Supply Only Blower Pulley of Existing.
Supply Only Blower Oil Seal & Packing.
Supply Only Blower Sucton Fiilter.
Supply and fill Blower Oil No. 90 Servo/Shell.
Taking down electric motor 5 kw 415 volt 3 phase coupled to compressor/ air blower after disconnecting the electrical connection, and earth connections from its foundation and transportation to work shop, checking the serviceability of ball bearing gboth side of motor, greasing of bearing up to free rotation of shaft of motor complete, greasing on reassemblying the motor to reinstallation on foundation, reconnecting back the cable and earth connections etc complete in all respect and starting the pump all as directed.
Taking down unserviceable and S&F NRV Tikki (Leather JEEP) suitable for 150mm bore NRV minimum thickness of rubber/leather 08 mm thickness all as specified and directed.
Taking out unserviceable and S&F cooling fan blade for motor fan plastic body capacity upto 40 HP, complete all as directed by Engineer-in-Charge.
Note No. 01: The contractor should attend the complaint and rectify the defect within 02 days (Maximum) receiving the complaints by phone call, letter or by Message by rep of GE/User failing to rectify the defect/replaceing the itemes given in relevant shedule, the penality will be recovered to Rs. @ 700 per day per complaint of above all CA items from the RAR/Final bill.
Note No. 02 : The cost shall be included for Pump mechanic and Electrician for attending daily complaint. The Contractor shall arrange 01 Pump mechanic and 01 Electrician with required Tool & Equipments for attending of complaint day to day on daily basis. They will be report to AGE E/M office on every day at 0800 Hrs to 1600 Hrs. If they absent on attending of complaint a recovey will be panalised @ Rs. 1,000/- per day and recovey will be made on RAR/Final bills.
Note No. 03 : All above mentioned items will be executed in different location/ pump house/ E/M installation / Fire Hydrant/ Technical area will be executed on daily complaint basis in different location / bldg or as directed by Engr-In-Charge. The contractor could not ask at few site for execution of all CA quantities. He will be bound to attend complaint as per user requirement or directed by Enge-In-Charge.
Note No. 04 : The cost shall be included checking/serviceability and finding the fault such as checking the supply of electricity, finding fault in cable, starter, diesel engine, pump, motor , all type of panel , hooter, smoke detector, sensor, all type of valve, fire hydrant unit, Hose box, etc in all CA Items/ quantity nothing will be paid to extra or sepearate .
classic estate developers
POOJA CONSTRUCTION COMPANY
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .