Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.0 CrAccepted-AOC KTA ROAD LAMBA LINE JUNGLIGHAT PO PORT BLAIR 744103 | PORT BLAIR | SOUTH ANDAMANS | ANDAMAN AND NICOBAR ISLANDS | 744103 | ₹2.0 Cr | L1 | Accepted-AOC LOWEST BIDDER |
| 2 | L2₹2.0 Cr+₹4.5 L (2.25%)Rejected-AOC D NO 37 8 1 MANCHUKONDA GARDENS INDUSTRIAL ESTATE VISAKHAPATNAM 530007 | VISAKHAPATANAM | ANDHRA PRADESH | 530007 | ₹2.0 Cr+₹4.5 L (2.25%) | L2 | Rejected-AOC NOT BEING LOWEST |
| 3 | L3₹2.3 Cr+₹34.7 L (17.5%)Rejected-AOC 660 POLICE LINE AREA HISAR HARYANA 125001 | HISAR | HARYANA | 125001 | ₹2.3 Cr+₹34.7 L (17.5%) | L3 | Rejected-AOC NOT BEING LOWEST |
| 4 | L4₹2.4 Cr+₹37.8 L (19.1%)Rejected-AOC 2ND FLOOR 9 EZRA STREET KOLKATA WEST BENGAL 700001 | KOLKATA | KOLKATA | WEST BENGAL | 700001 | ₹2.4 Cr+₹37.8 L (19.1%) | L4 | Rejected-AOC NOT BEING LOWEST |
| 5 | L5₹2.8 Cr+₹78.1 L (39.5%)Rejected-AOC 308 HERITAGE PLAZA OPP GURUKUL DRIVEIN ROAD AHMEDABAD GUJARAT 380052 | AHMADABAD | GUJARAT | 380052 | ₹2.8 Cr+₹78.1 L (39.5%) | L5 | Rejected-AOC NOT BEING LOWEST |
Tender Value
₹2.3 Cr
EMD Value
₹3.1 L
Closing Date
26 Jul 2022, 6:00 pmClosed
Chief Engineer Chennai Zone
HQ Chief Engineer Chennai Zone, Island Grounds, Chennai - 600 009
PROVISION OF DESALINATION PLANTS AND CONNECTED ITEMS AT CHENNAI UNDER GE CHENNAI
2022_MES_527925_1
82940/E8
Open Tender
Civil Works - Water Works
Item Rate
365 days
Chennai
As per NIT
8 documents required · 8 mandatory
₹2,000
GE Chennai, Chennai
₹3.1 L
Yes
26 Aug 2022
2 Jun 2022
28 Jul 2022
2 Jun 2022
26 Jul 2022
4 Jul 2022
3 Jun 2022 - 15 Jun 2022
Amount
BUILDING WORK :
Design and construction of plant room buildings (03 Nos) having plinth area of 30.36sqm and 3.65m internal clear height each in single storey with permanent specification in RCC framed structure with fly ash brick masonry including ATT, WPT by APP membrane, kota stone flooring, etc., (excluding internal electric supply) all as specified in tender documents, located at three different areas as listed below:- (a) One Plant Room at PGOE Area (b) One Plant Room at IGOE Area (c) One Plant Room at Camp-I Area
DESALINATION PLANTS AND CONNECTED WORKS :
Notes for Item 2.00, 3.00 & 4.00 :- (i) The plant shall be designed suitable for indoor installation. However, Multi-grade Filter, Activated Carbon Filter and Iron Removal Filter (as applicable) shall be designed and installed outside the plant room building all as directed. (ii) The equipments of plant are to be skid mounted. Rate quoted shall be deemed to be inclusive of all fitments and necessary foundation/ civil works at site. (iii) The necessary filter media, Chemicals are to be filled as per OEM specifications and rates are to deemed to be included in the quoted rates. (iv) The system shall have auto start/ stop based on water level in the supply tank. (v) The system shall have inbuilt protection to high pressure pump by way of low/ high pressure switch. (vi) After successful commissioning of the plant, the treated water shall achieve the following quality parameters:- (a) pH : 7.0 to 7.5 (b) Total Dissolved Solids : Less than 250ppm (c) Hardness : Less than 100 ppm (d) Turbidity : NIL (e) Bacteria/Oil & Grease : NIL
Supply, installation, testing & commissioning of Desalination Plant (with RO Process) of capacity 5000LPH & 50 KLD capacity alongwith necessary pipelines, fittings and control valves including all other accessories to make the plant fully functional complete all as per latest engineering practices and the plant subsystems shall be having the following specifications :- Make of the Plant : Ion Exchange/ Thermax/ any other makes approved by E-in-C's Branch with prior experience of installing minimum 4000LPH capacity RO plant.
Sl Item 2.00 Contd… (A) Raw water Transfer Pump : [Qty : 2 Nos] (1W+1S) Raw Water Horizontal monoblock non-submersible type pump set shall be of Pump Capacity 10 Cum/ hour @ 30mtrs Head, 3 phase 50Hz, 400-415Volts with necessary unions, flanges, foundations, bolts, etc., complete with head conditions and it shall be complete with Mechanical seal, CI with bronze impeller, SS Shaft, other accessories, etc., including valves and instrumentation such as Suction Valve-2Nos, Discharge Valve-2Nos, Non Return Valve-2Nos, Pressure Gauge-1 No, Base frame-2Nos, Rotameter-1 No (Range-20,000L/Hr) of suitable sizes complete. Make : Kirloskar/ Grundfos/ KSB/ Wilo/ Lubi/ as per OEM recommendation & as approved by GE.
Sl Item 2.00 Contd… (B) Hypo Dosing System : [Qty : 1 No] NAOCL dosing system shall be with Electronic diaphragm type metering with digital display alongwith accessories having the following specification and parameters : (a) Pump Capacity : 4LPH @ 4kg/cm2 (b) Stroke : 200 SPM (Strokes per min) (c) Pump (MOC) : PP (Poly Propylene) (d) Chemical to be dosed : NAOCL (e) Solution Tank of HDPE & Cap : 150 ltrs (1 No) Make : Ion Exchange/ Milton Roy/ Grundfos/ Minimax/ LMI/ as per OEM recommendation & as approved by GE.
(C) Multi Grade Filter : [Qty : 1 No] The Multi Grade Filter shall comply the following specification and parameters :- (a) Material of Construction : Mild Steel, shell & Dish - IS:2062 Grade B (b) Internal Protection : Epoxy Painted - Food Grade, 60-80 DFT (Dry Film Thickness) (c) External Protection : Red oxide with Enamel finished paint
Sl Item 2.00 (C) Contd… (d) Diameter (Min) : 1000mm (e) Height On Straight (Min) : 1875mm (f) Design Flow Rate : 10m3/hr (g) Operating Pressure(Min) : 2Kg/cm (h) Design Pressure : 3.5kg/cm2 (j) Testing pressure : 5.25kg/cm2 (k) Filtering Media : Quartz sand-mixture, Fine Silex, Coarse Silex and Pebbles mixture (l) Type of valve : Individual - Butterfly Valves (m) Frontal MS Pipe work : 80mm or suitable size, Code : IS-1239 Medium duty; Flange : BS-10 Table D
(n) Media Qty : 1213 kg (Min) (p) Media Depth : 915mm (Min) (p) Pressure Gauge : 2 Nos (q) Sample water valve : 2 Nos (r) Air release pipe work : MS (s) Foundation bolts & Nuts : As per OEM Make : ION Exchange/ Pentair/ Astral/ Thermax/ as per OEM recommendation & as approved by GE. Note : Design details of the Pressure filter plant with schematic diagram of pipe connections, position of butterfly valves including all accessories, centrifugal pumps, etc,. mentioned above in detailed specification which are part of filter plant shall be submitted to GE for approval before manufacturing.
Sl Item 2.00 Contd… (D) Activated Carbon Filter : [Qty : 1 No] The Activated Carbon Filter shall comply the following specification and parameters :- (a) Material of Construction : Mild Steel, shell & Dish- IS:2062, Grade B (b) Internal Protection : Epoxy Painted - Food Grade, 60-80 DFT (Dry Film Thickness) (c) External Protection : Red oxide with Enamel finished paint (d) Diameter : 1000mm (Min) (e) Height On Straight : 1875mm (Min) (f) Design Flow Rate : 10 m3/hr (g) Operating Pressure : 2.0 Kg/cm2 (Min) (h) Design Pressure : 3.5 Kg/cm2, (j) Testing pressure : 5.25 kg/cm2 (k) Filtering Media : Quartz sand-mixture, Fine Silex, Coarse Silex and Pebbles mixture
Sl Item 2.00 (D) Contd…. (l) Type of valve : Individual Butterfly Valves (m) Frontal MS Pipe work : 80mm or suitable size, Code : IS-1239 Medium duty; Flange : BS10 Table D (n) Carbon Qty : 440 kgs (Min) (p) Carbon media Depth : 1000mm (Min) (p) Pressure Gauge : 2 Nos, (q) Sample valve : 2 Nos (r) Air release pipe work : MS (s) Foundation bolts & Nuts : As per OEM Make : ION Exchange/ Pentair/ Astralpool/ Thermax/ Gopani/ Pratham/ as per OEM recommendation & as approved by GE. Note : Design details of the Activated Carbon filter plant with schematic diagram of pipe connections, position of butterfly valves,etc., including all accessories mentioned above in detailed specification which are part of filter plant shall be submitted to GE for approval before manufacturing.
Sl Item 2.00 Contd…. (E) SMBS (Sodium Meta Bi Sulphate) Dosing System [Qty : 1 No] The SMBS dosing system (to remove excess chlorine if any based on inlet water condition) shall be with Electronic diaphragm type metering with digital display having the following specification and parameters :- (a) Pump Capacity : 6 LPH @ 4 kg/cm2 (b) Stroke : 350 SPM (c) Pump MOC : PP (d) Chemical to be dosed : SMBS (e) Solution HDPE Tank & Cap : 150 Ltrs (1 No) Make : Ion Exchange/ Milton Roy/ Grundfos/ Minimax/ LMI/ as per OEM recommendation & as approved by GE.
(F) Iron Removal filter : [Qty : 1 No] The Iron Removal Filter shall comply the following specification and parameters :- (a) Material of Construction : Mild Steel - shell & Dish - IS:2062, Grade B (b) Internal Protection : Epoxy Painted - Food Grade 60-80 DFT (Dry Film Thickness) (c) External Protection : Red oxide with Enamel finished paint
Sl Item 2.00 (F) Contd…. (d) Diameter : 800mm (Min) (e) Height On Straight : 1875mm (Min) (f) Design Flow Rate : 10 m3/hr (g) Operating Pressure : 2.0 Kg/cm2 (Min) (h) Operating Pressure : 3.5 Kg/cm2 (Max) (j) Filtering Media : Iron Specific Resin (k) Type of valve : Individual Butterfly Valves (l) Frontal MS Pipe work : 50mm, Code : IS-1239 Medium duty; Flange : BS10 Table D (m) Resin Qty : 375 ltrs (Min) (n) Media Depth : 750mm (Min) (p) Pressure Gauge : 2 Nos Make : ION Exchange/ Pentair/ Astralpool/ Thermax/ Waaree/ Baumer/ Gluck India/ as per OEM recommendation & as approved by GE. Note : Design details of the Iron Removal filter plant with schematic diagram of pipe connections, position of valves including all accessories, etc., in above detailed specification. which are part of filter plant shall be submitted to GE for approval before manufacturing.
Sl Item 2.00 Contd…. (G) Antiscalent Dosing System [Qty : 1 No] The Antiscalent Dosing System (to perform removal of scaling in RO membrane based on inlet water conditions) shall be with Electronic Diaphragm type metering with digital display having the following specification and parameters:- (a) Pump Capacity : 6 LPH @ 4 kg/cm2 (b) Stroke : 350 SPM (c) Pump MOC : PP (d) Chemical to be dosed : Antiscalent (e) Solution HDPE Tank & Cap : 150 Ltrs (1 No) Make : Ion Exchange/ Milton Roy/ Grundfos/ Minimax/ LMI/ as per OEM recommendation & as approved by GE.
Sl Item 2.00 Contd…. (H) Acid Dosing System [Qty : 1 No] The dosing system shall be with Electronic metering pump with digital display having following specification and parameters :- (a) Pump Capacity : 6 LPH @ 4 kg/cm2 (b) Stroke : 350 SPM (c) Pump MOC : PP (d) Chemical to be dosed : Acid (e) Solution HDPE Tank & Cap : 150 Ltrs (1 No) Make : Ion Exchange/ Milton Roy/ Grundfos/ Minimax/ LMI/ as per OEM recommendation & as approved by GE.
Sl Item 2.00 Contd…. (J) RO System [Qty : 1 No] The RO system (skid mounted ) with backword and forward wash provision shall comply the following specification and parameters :- (a) Feed flow rate : 10 m3/hr (b) Permeate flow rate : 5 m3/hr (c) Recovery : 50-60% (d) Salt Rejection : 90-95% (e) Type RO Membrane : TFC (Thin film Composite) -Brackish water membrane (f) Qty of Membrane : 08 Nos (Min) (g) Std Size (dia & length): 8"x40" Make of Membrane : Hydramem/ DuPont/ Suez/ Hydranutics/ KOCH/ Pentair/ Inge/ as per OEM recommendation & as approved by GE. (h) Pressure vessel (of composite material) : 2 Nos (of 4 element long Each), (Make of Pressure Vessel : Ion Exchange/ Advanced Composite/ Pentair/ Pure Aqua/ as per OEM recommendation & as approved by GE.
Sl Item 2.00 (J) Contd…. (j) Skid : Stainless Steel of suitable size (k) Micron Cartridge Filter : 1 No (To be installed before RO membrane) (l) High Pressure pump : (12 - 15 Bar) Make of High Pressure Pump : Grundfos - CRN, Model : SS316 or equivalent in Ebara/ Wilo/ Kirloskar/Xylem/ as per OEM recommendation & as approved by GE. (m) High pressure switch, low pressure switch, Auto flush timer : As per OEM (n) Product & reject Rota Flow Meters : As per OEM (p) Wet panel with indication lamps : As per OEM
Sl Item 2.00 Contd…. (K) ORP (Oxidential Reduction Potential) Transmitter [Qty : 1 No] ORP transmitter/ Controller (to sense excess free chlorine in feed water and stop water supply to RO system) shall be provided with an IP-54 Panel Mounted Enclosure with 4-20 mA output, 24Volts DC operated complete. Model : 4000 R (PS/041) of Ion Exchange or equivalent in Forbes Marshall/ E&H/ as per OEM recommendation & as approved by GE. Sensor for ORP Transmitter : Glass Body Double Junction ORP Sensor, Threaded cap (Red), 5 mtrs cable and pp flow assembly for raw water, treated water alongwith suitable ORP Dump valve (Auto Butterfly Valves) Make & Model : F 142 E (PS/451) of Iron exchange or equivalent in Forbes Marshall/ E&H/ as per OEM recommendation & as approved by GE.
Sl Item 2.00 Contd…. (L) pH Correction Dosing System for Permeate Water [Qty : 1 No] The pH Correction Dosing System shall be with Electronic Diaphargm type metering with digital display having following specification and parameters:- (a) Pump Capacity : 6 LPH @ 4 kg/cm2 (b) Stroke : 350 SPM (c) Pump MOC : PP (d) Chemical to be dosed : pH Correction dosing chemical (e) Solution HDPE Tank & Cap : 150 Ltrs (1 No) Make : Ion Exchange/ Milton Roy/ Grundfos/ Minimax/ LMI/ as per OEM recommendation & as approved by GE.
Sl Item 2.00 Contd…. (M) Chemical Cleaning System [Qty : 1 No] The Chemical Cleaning System (for removal of any chocking/fouling in the membrane) shall comply with the following specification and parameters :- (a) Pump Capacity : 9 m3/hr Make : Kirloskar/ Grundfos/ KSB/ Wilo/ Lubi/ Ebara (b) Pump MOC : SS-316 (c) CIP Tank (MOC): LLDPE/ HDPE (d) Capacity : One No, 500 Ltrs (e) Micron Cartridge Filter : PP, 5 Micron (f) Type : Trolley Mounted (g) Piping : Combination of rigid PVC & Flexible Hose of suitable size System Make : Model CS40 of Ion Exchange or equivalent in Thermax/ Suez/ as per OEM recommendation & as approved by GE.
Sl Item 2.00 Contd…. (N) Spare Dosing Pumps [Qty : 2 Nos] The Spare Dosing Pumps shall comply with the following specification & parameters :- (a) Pump Capacities : 4 and 6 LPH @ 4 kg/cm2 (b) Stroke : 350 SPM (c) Type : Electronic Diaphragm type metering with digital display (d) Pump MOC : PP Make : Ion Exchange /Milton Roy/ Grundfos/ Minimax/ LMI
(P) pH Indicator in RO Permeate Line[Qty : 1No] (a) The pH indicator shall be with field mounted enclosure without Temp compensation, 220Volts AC operated. Model : FM (W) (PS/065) of Ion Exchange or equivalent in Forbes Marshall/ E&H/ as per OEM recommendation & as approved by GE. (b) The pH Sensor shall be Glass gel, Double Junction, Threaded cap (Blue) with 5 mtrs cable For Raw/ Treated Water, Deionised/ low condensed Water. Model : F0042 of Ion Exchange or equivalent in Forbes Marshall/ E&H/ as per OEM recommendation & as approved by GE.
Sl Item 2.00 Contd…. (Q) Supply, Installation and Commissioning inter unit piping of UPVC SCH-40/ SS-304/ PVC of required lengths with necessary flanges, bolts, nuts, neoprene gaskets, wherever necessary with necessary control valves, non return valves, etc., complete all as specified and as directed. Notes : (a) High pressure pipeline shall be of material SS-304. (b) Low pressure pipeline shall be of material UPVC SCH-40. (c) Drain pipe shall be of material PVC. (d) Cost of the same is deemed to be included in the quoted rates.
Sl Item 2.00 (R) Contd…. (a) Level switch for Raw water tank and treated water tank Qty : 3 Nos (b) Inter unit cabling for all equipments with necessary armoured/ unarmoured cables with necessary termination lugs, glands, etc., complete. (c) Making earthing connections with GI strips and GI wire of electrical equipments for electrical safety shall be done as per relevant IS. Cost of such extra GI strips/ wire is deemed to be included in quoted rates. Make of Switch Gear Items : L&T/ Schneider/ Siemens/ as per OEM recommendation & as approved by GE. Make of Cables : Polycab/ Finolex Note : The item for earthing and earth strip upto test point are considered and measured separately under relevant item of this BOQ.
Supply, installation, testing & commissioning of Desalination Plant (with RO Process) of capacity 8000LPH & 100 KLD capacity alongwith necessary pipelines, fittings and control valves including all other accessories to make the plant fully functional complete all as per latest engineering practices and the plant subsystems shall be having the following specifications :- Make of the Plant :- Ion Exchange/ Thermax/ any other make approved by E-in-C's Branch with prior experience of installing minimum 4000LPH capacity RO plant.
Sl Item 3.00 Contd… (A) Raw water Transfer Pump : [Qty : 2 Nos] (1W+1S) Raw Water Horizontal monoblock non-submersible type pump set shall be of Pump Capacity 16 Cum/ hour @ 30mtrs Head, 3 phase 50Hz, 400-415Volts with necessary unions, flanges, foundations, bolts, etc., complete with head conditions and it shall be complete with Mechanical seal, CI with bronze impeller, SS Shaft, other accessories, etc., including valves and instrumentation such as Suction Valve-2Nos, Discharge Valve-2Nos, Non Return Valve-2Nos, Pressure Gauge-1 No, Base frame-2Nos, Rotameter-1 No (Range-30,000L/Hr) of suitable sizes complete. Make : Kirloskar/ Grundfos/ KSB/ Wilo/ Lubi/ as per OEM recommendation & as approved by GE.
Sl Item 3.00 Contd… (B) Hypo Dosing System : [Qty : 1 No] NAOCL dosing system shall be with Electronic diaphragm type metering with digital display alongwith accessories having the following specification and parameters : (a) Pump Capacity : 4 LPH @ 4 kg/cm2 (b) Stroke : 200 SPM (c) Pump (MOC ) : PP (Poly Propylene) (d) Chemical to be dosed : NAOCL (e) Solution Tank of HDPE & Cap : 150 ltrs (1 No) Make : Ion Exchange/ Milton Roy/ Grundfos/ Minimax/ LMI/ as per OEM recommendation & as approved by GE.
Sl Item 3.00 Contd… (C) Multi Grade Filter : [Qty : 1 No] The Multi Grade Filter shall comply the following specification and parameters :- (a) Material of Construction : Mild Steel, shell & Dish - IS:2062 Grade B (b) Internal Protection : Epoxy Painted - Food Grade, 60-80 DFT (Dry Film Thickness) (c) External Protection : Red oxide with Enamel finished paint (d) Diameter : 1200mm (Min) (e) Height On Straight : 1875mm (Min) (f) Design Flow Rate : 20 m3/hr (g) Operating Pressure : 2.0 Kg/cm (Min) (h) Design Pressure : 3.5 kg/cm2, (j) Testing pressure : 5.25 kg/cm2 (k) Filtering Media : Quartz sand-mixture, Fine Silex, Coarse Silex and Pebbles mixture
Sl item 3.00 (C) Contd... (l) Type of valve : Individual - Butterfly Valves (m) Frontal MS Pipe work : 80mm or suitable size, Code : IS-1239 Medium duty; Flange : BS-10 Table D (n) Media Qty : 1213 kg Minimum (p) Media Depth : 915mm Minimum (q) Pressure Gauge : 2 Nos, (r) Sample water valve : 2 Nos (s) Air release pipe work : MS (t) Foundation bolts & Nuts : As per OEM Make : ION Exchange/ Pentair/ Astral/ Thermax/ as per OEM recommendation & as approved by GE. Note : Design details of the Pressure filter plant with schematic diagram of pipe connections, position of butterfly valves including all accessories, centrifugal pumps, etc,. mentioned above in detailed specification which are part of filter plant shall be submitted to GE for approval before manufacturing.
Sl Item 3.00 Contd… (D) Activated Carbon Filter : [Qty : 1 No] The Activated Carbon Filter shall comply the following specification and parameters :- (a) Material of Construction : Mild Steel, shell & Dish- IS:2062, Grade B (b) Internal Protection : Epoxy Painted - Food Grade, 60-80 DFT (Dry Film Thickness) (c) External Protection : Red oxide with Enamel finished paint (d) Diameter : 1200mm (Min) (e) Height On Straight : 1875mm (Min) (f) Design Flow Rate : 20 m3/hr (g) Operating Pressure : 2.0 Kg/cm2 (Min) (h) Design Pressure : 3.5 Kg/cm2, (j) Testing pressure : 5.25 kg/cm2 (k) Filtering Media : Quartz sand-mixture, Fine Silex, Coarse Silex and Pebbles mixture
Sl Item 3.00 (D) Contd…. (l) Type of valve : Individual Butterfly Valves (m) Frontal MS Pipe work : 80mm or suitable size, Code : IS-1239 Medium duty; Flange : BS10 Table D (n) Carbon Qty : 620 kgs (Min) (p) Carbon media Depth : 1000mm (Min) (p) Pressure Gauge : 2 Nos (q) Sample valve : 2 Nos (r) Air release pipe work : MS (s) Foundation bolts & Nuts : As per OEM Make : ION Exchange/ Pentair/ Astralpool/ Thermax/ Gopani/ Pratham/ as per OEM recommendation & as approved by GE. Note : Design details of the Activated Carbon filter plant with schematic diagram of pipe connections, position of butterfly valves,etc., including all accessories mentioned above in detailed specification which are part of filter plant shall be submitted to GE for approval before manufacturing.
Sl Item 3.00 Contd…. (E) SMBS (Sodium Meta Bi Sulphate) Dosing System [Qty : 1 No] The SMBS dosing system (to remove excess chlorine if any based on inlet water condition) shall be with Electronic diaphragm type metering with digital display having the following specification and parameters :- (a) Pump Capacity : 11 LPH @ 4 kg/cm2 (b) Stroke : 350 SPM (c) Pump MOC : PP (d) Chemical to be dosed : SMBS (e) Solution HDPE Tank & Cap : 150 Ltrs (1 No) Make : Ion Exchange/ Milton Roy/ Grundfos/ Minimax/ LMI/ as per OEM recommendation & as approved by GE.
(F) Iron Removal filter : [Qty : 1 No] The Iron Removal Filter shall comply the following specification and parameters :- (a) Material of Construction : Mild Steel - shell & Dish - IS:2062, Grade B (b) Internal Protection : Epoxy Painted - Food Grade 60-80 DFT (Dry Film Thickness) (c) External Protection : Red oxide with Enamel finished paint
Sl Item 3.00 (F) Contd…. (d) Diameter : 1200mm (Min) (e) Height On Straight : 1875mm (Min) (f) Design Flow Rate : 24 m3/hr (g) Operating Pressure : 2.0 Kg/cm2 (Min) (h) Operating Pressure : 3.5 Kg/cm2 (Max) (j) Filtering Media : Iron Specific Resin (k) Type of valve : Individual Butterfly Valves
(l) Frontal MS Pipe work : 50mm, Code : IS:1239, Medium duty; Flange : BS10 Table D (m) Resin Qty : 845 ltrs (Min) (n) Media Depth : 750mm (Min) (p) Pressure Gauge : 2 Nos Make : ION Exchange/ Pentair / Astralpool/ Thermax/ Waaree/ Baumer/ Gluck India/ as per OEM recommendation & as approved by GE. Note : Design details of the Iron Removal filter plant with schematic diagram of pipe connections, position of valves including all accessories, etc., in above detailed specification. which are part of filter plant shall be submitted to GE for approval before manufacturing.
Sl Item 3.00 Contd…. (G) Antiscalent Dosing System [Qty : 1 No] The Antiscalent Dosing System (to perform removal of scaling in RO membrane based on inlet water conditions) shall be with Electronic Diaphragm type metering with digital display having the following specification and parameters:- (a) Pump Capacity : 6 LPH @ 4 kg/cm2, (b) Stroke : 350 SPM (c) Pump MOC : PP (d) Chemical to be dosed : Antiscalent (e) Solution HDPE Tank & Cap : 150 Ltrs (1 No) Make : Ion Exchange/ Milton Roy/ Grundfos/ Minimax/ LMI/ as per OEM recommendation & as approved by GE.
(H) RO System [Qty : 1 No] The RO system (skid mounted ) with backword and forward wash provision shall comply the following specification and parameters :- (a) Feed flow rate : 16 m3/hr (b) Permeate flow rate : 8 m3/hr (c) Recovery : 50-60% (d) Salt Rejection : 90-95% (e) Type RO Membrane : TFC (Thin film Composite) -Brackish water membrane
Sl Item 3.00 (H) Contd…. (H) RO System [Qty : 1 No] (f) Qty of Membrane : 08 Nos (Min) (g) Std Size : 8"x40" (dia & length) Make of Membrane : Hydramem/ DuPont/ Suez/ Hydranutics/ KOCH/ Pentair/ Inge/ as per OEM recommendation & as approved by GE. (h) Pressure vessel (of composite material) : 2 Nos (of 4 element long Each) Make of Pressure Vessel : Ion Exchange/ Advanced Composite/ Pentair/ Pure Aqua/ as per OEM recommendation & as approved by GE. (j) Skid : Stainless Steel of suitable size (k) Micron Cartridge Filter : 1 No (To be installed before RO membrane) (l) High Pressure pump : 12 - 15 Bar Make of High Pressure Pump : Grundfos - CRN, Model : SS316 or equivalent in Ebara/ Kirloskar/ Wilo/ Xylem/ as per OEM recommendation & as approved by GE. (m) High pressure switch, low pressure switch, Auto flush timer : As per OEM (n) Product & reject Rota Flow Meters : As per OEM (p) Wet panel with indication lamps : As per OEM
Sl Item 3.00 Contd…. (J) ORP (Oxidential Reduction Potential) Transmitter [Qty : 1 No] ORP transmitter/ Controller (to sense excess free chlorine in feed water and stop water supply to RO system) shall be provided with an IP-54 Panel Mounted Enclosure with 4-20 mA output, 24Volts DC operated complete. Model : 4000 R (PS/041) of Ion Exchange or equivalent in Forbes Marshall/ E&H/ as per OEM recommendation & as approved by GE. Sensor for ORP Transmitter : Glass Body Double Junction ORP Sensor, Threaded cap (Red), 5 mtrs cable and pp flow assembly for raw water, treated water alongwith suitable ORP Dump valve (Auto Butterfly Valves) Make & Model : F 142 E (PS/451) of Iron exchange or equivalent in Forbes Marshall/ E&H/ as per OEM recommendation & as approved by GE.
Sl Item 3.00 Contd…. (K) pH Correction Dosing System for Permeate Water [Qty : 1 No] The pH Correction Dosing System shall be with Electronic Diaphragm type metering with digital display having following specification and parameters:- (a) Pump Capacity : 6 LPH @ 4 kg/cm2 (b) Stroke : 350 SPM (c) Pump MOC : PP (d) Chemical to be dosed : pH Correction dosing chemical (e) Solution HDPE Tank & Cap : 150 Ltrs (1 No) Make : Ion Exchange/ Milton Roy/ Grundfos/ Minimax/ LMI/ as per OEM recommendation & as approved by GE.
Sl Item 3.00 Contd…. (L) Chemical Cleaning System (CIP) [Qty : 1 No] The Chemical Cleaning System (for removal of any chocking/fouling in the membrane) shall comply with the following specification and parameters :- (a) Pump Capacity : 9 m3/hr Make : Kirloskar/ Grundfos/ KSB/ Wilo/ Lubi/ Ebara (b) Pump MOC : SS-316 (c) CIP Tank (MOC) : LLDPE/ HDPE (d) Capacity : One No., 500 Ltrs (e) Micron Cartridge Filter : PP, 5 Micron (f) Type : Trolley Mounted (g) Piping : Combination of rigid PVC & Flexible Hose of suitable size System Make : Model CS40 of Ion Exchange or equivalent in Thermax/ Suez/ as per OEM recommendation & as approved by GE.
Sl Item 3.00 Contd…. (M) Spare Dosing Pumps [Qty : 2 Nos] The Spare Dosing Pumps shall comply with the following specification & parameters :- (a) Pump Capacities : 6 LPH and 11 LPH @ 4 kg/cm2 (b) Stroke : 350 SPM (c) Type : Electronic Diaphragm type metering with digital display; (d) Pump MOC : PP Make : Ion Exchange /Milton Roy/ Grundfos/ Minimax/ LMI/ as per OEM recommendation & as approved by GE.
(N) pH Indicator in RO Permeate Line [Qty :1No] (a) The pH indicator shall be with field mounted enclosure without Temp compensation, 220Volts AC operated. Model : FM (W) (PS/065) of Ion Exchange or equivalent in Forbes Marshall/ E&H/ as per OEM recommendation & as approved by GE. (b) The pH Sensor shall be Glass gel, Double Junction, Threaded cap (Blue) with 5 mtrs cable For Raw/ Treated Water, Deionised/ low condensed Water. Model : F0042 of Ion Exchange or equivalent in Forbes Marshall/ E&H/ as per OEM recommendation & as approved by GE.
Sl Item 3.00 Contd…. (P) Supply, Installation and Commissioning inter unit piping of UPVC SCH-40/ SS-304/ PVC of required lengths with necessary flanges, bolts, nuts, neoprene gaskets, wherever necessary with necessary control valves, non return valves, etc., complete all as specified and as directed. Notes : (a) High pressure pipeline shall be of material SS-304. (b) Low pressure pipeline shall be of material UPVC SCH-40. (c) Drain pipe shall be of material PVC. (d) Cost of the same is deemed to be included in the quoted rates.
Sl Item 3.00 (Q) Contd…. (a) Level switch for Raw water tank, treated water tank Qty : 3 Nos (b) Inter unit cabling for all equipments with necessary armoured/ unarmoured cables with necessary termination lugs, glands, etc., complete. (c) Making earthing connections with GI strips and GI wire of electrical equipments for electrical safety shall be done as per relevant IS. Cost of such extra GI strips/ wire is deemed to be included in quoted rates. Make of Switch Gear Items : L&T/ Schneider/ Siemens/ as per OEM recommendation & as approved by GE. Make of Cables : Polycab/ Finolex Note : The item for earthing and earth strip upto test point are considered and measured separately under relevant item of this BOQ.
Supply, installation, testing & commissioning of Desalination plant (with RO Process) of capacity 12000LPH & 150 KLD capacity alongwith necessary pipelines, fittings and control valves including all other accessories to make the plant fully functional complete all as per latest engineering practices and the plant subsystems shall be having the following specifications :- Make of the Plant :- Ion Exchange/ Thermax/ any other make approved by E-in-C's Branch with prior experience of installing minimum 4000LPH capacity RO plant
Sl Item 4.00 Contd… (A) Raw water Transfer Pump : [Qty : 2 Nos] (1W+1S) Raw Water Horizontal monoblock non-submersible type pump set shall be of Pump Capacity 24 Cum/ hour @ 30mtrs Head, 3 phase 50Hz, 400-415Volts with necessary unions, flanges, foundations, bolts, etc., complete with head conditions and it shall be complete with Mechanical seal, CI with bronze impeller, SS Shaft, other accessories, etc., including valves and instrumentation such as Suction Valve-2Nos, Discharge Valve-2Nos, Non Return Valve-2Nos, Pressure Gauge-1 No, Base frame-2Nos, Rotameter-1 No (Range-40,000L/Hr) of suitable sizes complete. Make : Kirloskar/ Grundfos/ KSB/ Wilo/ Lubi/ as per OEM recommendation & as approved by GE.
Sl Item 4.00 Contd… (B) Hypo Dosing System : [Qty : 1 No] NAOCL dosing system shall be with Electronic diaphragm type metering with digital display alongwith accessories having the following specification and parameters :- (a) Pump Capacity : 6 LPH @ 4 kg/cm2 (b) Stroke : 350 SPM (c) Pump (MOC) : PP (Poly Propylene) (d) Chemical to be dosed : NAOCL (e) Solution Tank of HDPE & Cap : 150 ltrs (1 N0) Make : Ion Exchange/ Milton Roy/ Grundfos/ Minimax/ LMI/ as per OEM recommendation & as approved by GE.
Sl Item 4.00 Contd… (C) Multi Grade Filter : [Qty : 1 No] The Multi Grade Filter shall comply the following specification and parameters :- (a) Material of Construction : Mild Steel, shell & Dish - IS:2062 Grade B (b) Internal Protection : Epoxy Painted - Food Grade, 60-80 DFT (Dry Film Thickness) (c) External Protection : Red oxide with Enamel finished paint (d) Diameter : 1400mm (Min) (e) Height On Straight : 1875mm (Min) (f) Design Flow Rate : 24 m3/hr (g) Operating Pressure : 2.0 Kg/cm (Min) (h) Design Pressure : 3.5 kg/cm2 (j) Testing pressure : 5.25 kg/cm2 (k) Filtering Media : Quartz sand-mixture, Fine Silex, Coarse Silex and Pebbles mixture
Sl item 4.00 (C) Contd... (l) Type of valve : Individual - Butterfly Valves (m) Frontal MS Pipe work : 100mm or suitable size, Code : IS-1239 Medium duty; Flange : BS-10 Table D (n) Media Qty : 2146 kg (Min) (p) Media Depth : 915mm (Min) (q) Pressure Gauge : 2 Nos, (r) Sample water valve : 2 Nos, (s) Air release pipe work : MS, (t) Foundation bolts & Nuts : As per OEM Make : ION Exchange/ Pentair/ Astral/ Thermax/ as per OEM recommendation & as approved by GE. Note : Design details of the Pressure filter plant with schematic diagram of pipe connections, position of butterfly valves including all accessories, centrifugal pumps, etc,. mentioned above in detailed specification which are part of filter plant shall be submitted to GE for approval before manufacturing.
Sl Item 4.00 Contd… (D) Activated Carbon Filter : [Qty : 1 No] The Activated Carbon Filter shall comply the following specification and parameters :- (a) Material of Construction : Mild Steel, shell & Dish- IS:2062, Grade B (b) Internal Protection : Epoxy Painted - Food Grade, 60-80 DFT (Dry Film Thickness) (c) External Protection : Red oxide with Enamel finished paint (d) Diameter : 1600mm (Min) (e) Height On Straight : 1875mm (Min) (f) Design Flow Rate : 24 m3/hr (g) Operating Pressure : 2.0 Kg/cm2 (Min) (h) Design Pressure : 3.5 Kg/cm2, (j) Testing pressure : 5.25 kg/cm2 (k) Filtering Media : Quartz sand-mixture, Fine Silex, Coarse Silex and Pebbles mixture
Sl Item 4.00 (D) Contd…. (l) Type of valve : Individual Butterfly Valves (m) Frontal MS Pipe work : 100mm or suitable size, Code : IS-1239 Medium duty; Flange : BS10 Table D (n) Carbon Qty : 1100 kgs (Min) (p) Carbon media Depth : 1000mm (Min) (p) Pressure Gauge : 2 Nos, (q) Sample valve : 2 Nos (r) Air release pipe work : MS (s) Foundation bolts & Nuts : As per OEM Make : ION Exchange/ Pentair/ Astralpool / Thermax/ Gopani/ Pratham/ as per OEM recommendation & as approved by GE. Note : Design details of the Activated Carbon filter plant with schematic diagram of pipe connections, position of butterfly valves,etc., including all accessories mentioned above in detailed specification which are part of filter plant shall be submitted to GE for approval before manufacturing.
Sl Item 4.00 Contd…. (E) SMBS (Sodium Meta Bi Sulphate) Dosing System [Qty : 1 No] The SMBS dosing system (to remove excess chlorine if any based on inlet water condition) shall be with Electronic diaphragm type metering with digital display having the following specification and parameters :- (a) Pump Capacity : 11 LPH @ 4 kg/cm2 (b) Stroke : 350 SPM (c) Pump MOC : PP (d) Chemical to be dosed : SMBS (e) Solution HDPE Tank & Cap : 150 Ltrs (1No) Make : Ion Exchange/ Milton Roy/ Grundfos/ Minimax/ LMI/ as per OEM recommendation & as approved by GE.
Sl Item 4.00 Contd…. (F) Antiscalent Dosing System [Qty : 1 No] The Antiscalent Dosing System (to perform removal of scaling in RO membrane based on inlet water conditions) shall be with Electronic Diaphragm type metering with digital display having the following specifications and parameters :- (a) Pump Capacity : 6 LPH @ 4 kg/cm2 (b) Stroke : 350 SPM (c) Pump MOC : PP (d) Chemical to be dosed : Antiscalent (e) Solution HDPE Tank & Cap : 150 Ltrs (1No) Make : Ion Exchange/ Milton Roy/ Grundfos/ Minimax/ LMI/ as per OEM recommendation & as approved by GE.
Sl Item 4.00 Contd…. (G) RO System [Qty : 1 No] The RO system (skid mounted ) with backword and forward wash provision shall comply the following specification and parameters :- (a) Feed flow rate : 24 m3/hr (b) Permeate flow rate : 12 m3/hr (c) Recovery : 50-60% (d) Salt Rejection : 90-95% (e) Type RO Membrane : TFC (Thin film Composite) -Brackish water membrane (f) Qty of Membrane : 08 Nos (Min) (g) Std Size (dia & length) : 8"x40" Make of Membrane : Hydramem/ DuPont/ Suez/ Hydranutics/ KOCH/ Pentair/ Inge/ as per OEM recommendation & as approved by GE. (h) Pressure vessel (of composite material) : 2 Nos (of 4 element long Each), Make of Pressure Vessel : Ion Exchange/ Advanced Composite/ Pentair/ Pure Aqua/ as per OEM recommendation & as approved by GE. (j) Skid : Stainless Steel of suitable size
Sl Item 4.00 (G) Contd…. (k) Micron Cartridge Filter : 1 No (To be installed before RO membrane) (l) High Pressure pump : 12 - 15 Bar Make of High Pressure Pump : Grundfos - CRN, Model : SS316 or equivalent in Ebara/ Wilo/ Kirloskar/Xylem/ as per OEM recommendation & as approved by GE. (m) High pressure switch, low pressure switch, Auto flush timer : As per OEM (n) Product & reject Rota Flow Meters : As per OEM (p) Wet panel with indication lamps : As per OEM
Sl Item 4.00 Contd…. (H) ORP (Oxidential Reduction Potential) Transmitter [Qty : 1 No] ORP transmitter/ Controller (to sense excess free chlorine in feed water and stop water supply to RO system) shall be provided with an IP-54 Panel Mounted Enclosure with 4-20 mA output, 24Volts DC operated complete. Model : 4000 R (PS/041) of Ion Exchange or equivalent in Forbes Marshall/ E&H/ as per OEM recommendation & as approved by GE. Sensor for ORP Transmitter : Glass Body Double Junction ORP Sensor, Threaded cap (Red), 5 mtrs cable and pp flow assembly for raw water, treated water alongwith suitable ORP Dump valve (Auto Butterfly Valves) Make & Model : F 142 E (PS/451) of Iron exchange or equivalent in Forbes Marshall/ E&H/ as per OEM recommendation & as approved by GE.
Sl Item 4.00 Contd…. (J) pH Correction Dosing System for Permeate Water [Qty : 1 No] The pH Correction Dosing System shall be with Electronic Diaphragm type metering with digital display having following specification and parameters:- (a) Pump Capacity : 11 LPH @ 4 kg/cm2 (b) Stroke : 350 SPM (c) Pump MOC : PP (d) Chemical to be dosed : pH Correction dosing chemical (e) Solution HDPE Tank & Cap : 150 Ltrs (1No) Make : Ion Exchange/ Milton Roy/ Grundfos/ Minimax/ LMI/ as per OEM recommendation & as approved by GE.
Sl Item 4.00 Contd…. (K) Chemical Cleaning System (CIP) [Qty : 1 No] The Chemical Cleaning System (for removal of any chocking/fouling in the membrane) shall comply with the following specification and parameters :- (a) Pump Capacity : 9 m3/hr Make : Kirloskar/ Grundfos/ KSB/ Wilo/ Lubi/ Ebara/ as per OEM recommendation & as approved by GE. (b) Pump MOC : SS-316 (c) CIP Tank (MOC) : LLDPE/ HDPE (d) Capacity : One No., 500 Ltrs (e) Micron Cartridge Filter : PP, 5Micron (f) Type : Trolley Mounted (g) Piping : Combination of rigid PVC & Flexible Hose of suitable size System Make : Model CS40 of Ion Exchange or equivalent in Thermax/ Suez/ as per OEM recommendation & as approved by GE.
Sl Item 4.00 Contd…. (L) Spare Dosing Pumps [Qty : 2 Nos] The Spare Dosing Pumps shall comply with the following specification & parameters :- (a) Pump Capacities : 6 LPH and 11 LPH @ 4 kg/cm2 (b) Stroke : 350 SPM (c) Type : Electronic Diaphragm type metering with digital display (d) Pump MOC : PP Make : Ion Exchange /Milton Roy/ Grundfos/ Minimax/ LMI/ as per OEM recommendation & as approved by GE.
(M) pH Indicator in RO Permeate Line [Qty : 1 No] (a) The pH indicator shall be with field mounted enclosure without Temp compensation, 220Volts AC operated. Model : FM (W) (PS/065) of Ion Exchange or equivalent in Forbes Marshall/ E&H/ as per OEM recommendation & as approved by GE. (b) The pH Sensor shall be Glass gel, Double Junction, Threaded cap (Blue) with 5 mtrs cable For Raw/ Treated Water, Deionised/ low condensed Water. Model : F0042 of Ion Exchange or equivalent in Forbes Marshall/ E&H/ as per OEM recommendation & as approved by GE.
Sl Item 4.00 Contd…. (N) Supply, Installation and Commissioning inter unit piping of UPVC SCH-40/ SS-304/ PVC of required lengths with necessary flanges, bolts, nuts, neoprene gaskets, wherever necessary with necessary control valves, non return valves, etc., complete all as specified and as directed. Notes : (a) High pressure pipeline shall be of material SS-304. (b) Low pressure pipeline shall be of material UPVC SCH-40. (c) Drain pipe shall be of material PVC. (d) Cost of the same is deemed to be included in the quoted rates.
Sl Item 4.00 (P) Contd…. Make of Cables : Polycab/ Finolex (a) Level switch for Raw water tank, treated water tank [Qty : 3 Nos] (b) Inter unit cabling for all equipments with necessary armoured/ unarmoured cables with necessary termination lugs, glands, etc., complete. (c) Making earthing connections with GI strips and GI wire of electrical equipments for electrical safety shall be done as per relevant IS. Cost of such extra GI strips/ wire is deemed to be included in quoted rates. Note : The item for earthing and earth strip upto test point are considered and measured separately under relevant item of this BOQ.
Excavation in trenches n.exc.1.5m in width and 1.5m in depth and getting out in soft/ loose soil complete all as specified and as directed.
Returning filling in including spreading, levelling, watering and well ramming in layers n.exc.25cm thick complete all as specified and as directed.
Removing excavated material/ soil to a distance n.exc.50m and depositing where directed at a level n.exc. 1.5m above the starting point complete all as specified and directed.
Supply and lay river sand as cushioning to cables including spreading and levelling in cable trenches all as specified and directed (Punned thickness only shall be measured and paid).
Supply and laying well burnt bricks sub class 'B' in trenches for protection of UG cable all as specified and directed by Engr-in-Charges.
Supply and lay pipe galvanized, Medium grade including fittings of 40mm dia complete all as specified and as directed.
Supply and lay pipe galvanized Medium grade including fittings of 50mm dia complete all as specified and as directed.
Supply and lay pipe galvanized Medium grade including fittings of 80mm dia complete all as specified and as directed.
Supply, laying and testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100Volts grade with stranded aluminium conductor of size 50 sqmm 3.5 core complete all as specified and as directed.
S&F MCCB adjustable thermal & magnetic setting 415Volts, 4 pole, 50Hz of capacity 125Amps 16KA complete all as specified and directed by Engr-in charge.
S&F enclosure box wall mounted suitable for MCCB of capacity 125Amps 25KA complete all as specified and directed by Engr-in charge.
Material and labour for point wiring complete all as specified with 1100Volts grade 1.5 Sqmm PVC insulated FRLS unsheathed cable with multistranded Copper conductor conforming to IS:694:1990 with ISI marking in and including non metallic PVC rigid conduit medium grade of size 19mm dia with all accessories concealed in wall / ceiling including continuous earth wire 1.5 Sqmm PVC insulated FRLS unsheathed 1100Volts multistranded Copper conductor connected to common earth and earth dolly including modular metal flush boxes concealed in walls and modular white plate covers for mounting of modular switches/ sockets/ fan regulators, etc., complete all as specified for the following:
(a) One light/ fan point controlled by one switch.
(b) One three pin switch socket 5/6 Amps outlet on independent board.
(c) One three pin switch socket 5/6 amps outlet on same board.
All as per item No 16 here-in-before but with cable 4 sqmm multi stranded copper FRLS wire, 1100Volts grade, unsheathed for one 3 pin socket out let 15Amps on independent board including continuous earth wire PVC insulated 4 sqmm Copper stranded conductor FRLS, 1100Volts grade, connecting to common earth and earth dolly complete all as specified.
Supply and fix Modular switch 1 way 6A with indicator, 1-module all as specified and directed.
Supply and fix Modular switch 1 way 16A with indicator, 1-module all as specified and directed.
Supply and fix Modular socket, 6A - 2/3 pin combined 2-module all as specified and as directed.
Supply and fix Modular socket, 6/16A - 2/3 pin combined 2-module all as specified and as directed.
Supply and fix modular type Electronic fan regulator 120Watts, Single Phase 230Volts (2 modules) stepped and flush type and connecting up complete all as specified and as directed.
Supply and fix Ceiling rose, 3 phase/PVC/ polycarbonate, isolated body complete all as specified.
Supply and fix Sheet metal enclosure MCB DB, SPN 8 ways, 240Volts, double door all as specified.
Supply and fixing 240Volts, 10 KA 'B' curve Miniature Circuit Breaker (MCB) of single poles and current carrying capacity 5 to 32Amps in the MCB DB Complete with connection testing and commissioning complete all as specified and as directed.
Supply and fixing 240Volts, 10KA 'C' curve miniature circuit breaker (MCB) of SPN and current carrying capacity 5 to 32Amps in the DB complete with connection testing and commissioning complete all as specified and as directed.
Supply and fixing ceiling fans complete with blades, down rods and accessories, 230Volts, 1200mm sweep, minimum air delivery 210CFM with service value 6.00 BEE, five star rated with brushless direct current motor (BLDC) complete all as specified and as directed.
Supply and fix exhaust fan, steel body AC single phase, 230Volts of size 300mm sweep with blades, frame and louvers complete all as specified and as directed.
Supply and fix LED lights fitting 1x20Watts, 220Volts, AC decorative box type with driver, holder including LED tube light connecting up with three core flexible Copper conductor cable of suitable size from ceiling rose complete all as specified and as directed.
Supply and fixing LED street/security light fitting 35Watts 230Volts AC outdoor type with high pressure die cast Aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and as directed. Note:- The rate quoted shall include the cost of necessary fixing brackets and clamps, electrical connection, etc., all as specified and as directed.
Earthing complete with Galavanised steel earth plate electrode of size 600x600x6mm buried directly in the ground vertically to depth not less than 3.0m below the ground level with the top edge of earth plate, depth not less than 2.25m below the ground level connected to GI earth strip of 32x6mm size by means of bolts, nuts and washers protected by GI tubing light grade 40mm dia upto test point 20mm dia watering pipe with funnel & wire mesh, PCC pit in PCC 1:2:4 using 20mm stone aggregate, 40mm thick RCC cover slab 1:2:4 type B-1 using 20mm graded stone aggregates complete all as specified and shown in Electrical Plate No.3 of SSR Part-I including earth work in any type of soil, removing of surplus sil and providing charcoal dust & salt layers all around the earth plate upto 15cm as required including testing all as specified and as directed. Note : The rate is deemed to be inclusive of the cost of earth work, excavation on any type soil and removal of surplus soil to a distance of 50m, PCC 1:2:4 type B1 for earth pit cover, CTD bars, earth lead protection, GI pipe medium grade of suitable size from earth plate electrode to main switch, GI strip length up to 7.50m, lugs, etc,.)
All as per Item No.31.00 above but GI earth strip of size 25x4mm connected to machanery/ equipments installed at plant room bldg all as specified including testing on completion complete all as specified and as directed.
KRISHNA ENGINEARING
VERMA BROTHERS
surendra infrastructure pvt ltd
Solar Sewage Basic Infrastructure Pvt Ltd
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .