| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.9 CrAccepted-AOC 1 225 5 6 SADAR BAZAR DELHI CANTT 110010 | NEW DELHI | DELHI | 110010 | ₹8.9 Cr | L1 | Accepted-AOC being lowest Tender |
| 2 | L2₹9.6 Cr+₹67.6 L (7.61%)Rejected-Finance | ₹9.6 Cr+₹67.6 L (7.61%) | L2 | Rejected-Finance OTHER THAN LOWEST |
| 3 | L3₹9.6 Cr+₹72.2 L (8.12%)Rejected-Finance STREET NO 11 SECTOR NO 04 TILAK NAGAR SAGAR ROAD BIKANER RAJASTHAN 334001 | BIKANER | RAJASTHAN | 334001 | ₹9.6 Cr+₹72.2 L (8.12%) | L3 | Rejected-Finance OTHER THAN LOWEST |
| 4 | L4₹9.9 Cr+₹99.6 L (11.2%)Rejected-Finance | ₹9.9 Cr+₹99.6 L (11.2%) | L4 | Rejected-Finance OTHER THAN LOWEST |
| 5 | L5₹10.1 Cr+₹1.2 Cr (13.3%)Rejected-Finance | ₹10.1 Cr+₹1.2 Cr (13.3%) | L5 | Rejected-Finance OTHER THAN LOWEST |
Tender Value
Refer Docs
EMD Value
₹7.4 L
Closing Date
17 Jul 2021, 6:00 pmClosed
CHIEF ENGINEER DELHI ZONE
HQ CE DELHI ZONE DELHI CANTT-10
AUGMENTATION OF EXISTING HT NETWORK WITH UPGRADATION OF HT BREAKERS AND PANELS AT DELHI CANTT UNDER GE (U) ELECTRIC SUPPLY DELHI CANTT-10
2021_MES_450995_1
CA NO CEDZ/14 of 2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
DELHI CANTT
MES contractor enlisted in MES under class S cat b ii having deposited Standing Security of Rs 11.00 lakh with department. Contractors not enlisted in MES should meet the MES enlistment criteria corresponding to appropriate class and category.
9 documents required · 9 mandatory
₹3,000
GE (U) Electric Supply
₹7.4 L
Yes
2 Aug 2021
12 Jun 2021
19 Jul 2021
12 Jun 2021
17 Jul 2021
10 Jul 2021
Amount
Supply, Installalation and testing of water cooled Diesel Engine driven Prime duty Generating Set of net capacity after all derating factors net of not less than 62.5 KVA/50 KWe ,50Hz 415 volt 3 phase, 4 wire,0.8 lagg, 84 hp minimum Required Power for Rated kVA (hp) along with AMF system with Acoustic Enclosure exhaust critical grade silencer in line , as per the noise emmission standards liad down by MoEF / CPCB Norms complete all as specified and directed
A) Engine comprising of the following: Rugged engine natural liquid cooled (EG Compleat 50:50) with radiator as secondary media with world class OEM such as Cummins/Perkins/Kohler/Greaves/Ashok Leyland Engines for powered diesel generator set along with these specifications of Advanced in-cylinder technology turbo charged , air cooled aspriated to meet latest emission norms without any after-treatment device. Class defining technology engine is designed to meet stringent exhaust emission tests as per revised MoEF norms, thus offering environment friendly powe Compact in size with optimum power to weight ratio, 4 cylinder, In-line 4 stroke, radiator cooled engine Well designed air handling system with Dry type, heavy duty, replaceable paper element aircleaner with restriction indicator, Air to air aftercooling, Optimised turbocharger for increased altitude capabilities, Best in class fuel economy with Inline fuel pump with A1 class mechanical governing, Spin on fuel filter, Standard integral set-mounted radiator system, designedand tested for 50°C ambient temperature,Full flow spin on lube oil filte,First fill of lube oil and coolant, Electrical starter motor with soft start engagement feature, Battery charging alternator,1 x 12 V DC battery/Alternator
b) Alternator PMG type comprising of the following: Stamford UC/jyothi/crompton alternator frames from Technologies Brushless type, Screen protected, Revolving field, Self excited alternator conforming to IS/IEC 60034-13 Phase reconnectable winding with 12 terminals brought out for connection Dedicated winding specially designed for 1 phase and 3 phase operation Better motor starting capability Best in class efficiency Compact design with sealed bearings for longer life and lesser maintenance Impregnation on all wound components for better mechanical strength with Alternator of IP 23, Voltage regulation (Max.)±1%, Class of Insulation H Class, Winding Pitch 2/3,Stator Winding Double layer lap Rotor Dynamically Balanced, Waveform distortion/ Total Harmonic Distortion No load < 1.5 %, Non distorting balanced linear load < 5 %,Maximum Unbalanced Load across phases# less than or equal to 25%, Telephonic Harmonic factor < 2% alternator capacity output shall not be less than 62.5 KVA / 50KWe ,50Hz 415 volt 3 phase, 4 wire,0.8 lagg. 87 Amp / phase
Control Panel comprising of the following: c) AMF / Control panel is manufactured with 14/16 gauge CRCA sheet and is powder coated for weather-proof and long lasting finish.The control panel consists of the following parts of makes as per OEM recomendation: microprocessor based generator set monitoring and control system. along with AMF Functionality is inbuilt and this control includes an intuitive operator interface that allows for complete generator set control as well as system metering, fault annunciation, configuration, and diagnostics, Copper bus bars with suitable capacity with incoming/outgoing terminals, Indicating lamps for ‘Load ON’ and ‘Set Running’,Instrument fuses / MCBs duly wired and ferruled, Circuit breakers of suitable rating with overload and shortcircuit protections. with motorised change overs /on load power contactors with copper busbars, cables and protective acessories with load / bypass arrangements
Critical grade silencer Critical grade silencer suitably optimized to meet stringentnoise emission standards laid down by MoEF / CPCBalong with MS supporting structures .along with thermal Insulation on horizontal pipe with Mineral Wool/ Asbestos Rope 50mm Thick wire mesh and 26 gauge aluminium cladding (12")
d) Controller should be compatable to the following specifications: (i)AMF Functionality controllers of Makes from the OEM : Deep Sea/ Cummins/ Wood Ward/ Com Amp (II) Intuitive operator interface which includes LED backlit128X64 pixel graphic display with tactile feel soft-switches.Indications - Generator set, Utility Status Lamp. (iii)Remote start-stop with Engine Metering: Oil pressure, Engine temperature, Startingbattery voltage, Engine running hours (iv)AC Alternator Metering: L-L Voltage and L-N Voltage,Current (phase and total), kVA (phase and total) andFrequency. kwh, Total & per phase (kw & kVA), PF, UtilityVoltage and Freq. (v)Engine Protection: Low lube oil pressure, High/Low coolanttemperature, Battery Over/Under/Weak Volts, Fail to Crank/Start, Sensor failure, Cranking lockout, Low fuel level. (vi)AC Alternator Protection: Over/Under Voltage, Over/UnderFrequency, Loss of AC sensing. Overspeed, Over Current. (vii)Data Logging: Engine hours, Control hours and upto 5 recent fault codes (viii)Configurable glow plug control, Cycle Cranking (ix)12/24 Volt DC operation,Sleep mode,Modbus interface (RS485 RTU),InPower compatible (PC based service tool),Certifications - meets the requirement of relevant ISO, EN,Mil Std. and CE standards (e)Maintenance due alarm based on Engine Run Time and duedate,Exercisor scheduler (f) Remote HMI, Digital electronic governor with temperture compensation and smooth starting, digital AVR for shunt of PMG excitor with Torque monitoring
(e) All pipe line connections, valves etc.required for the lube oils, fuel and cooling system
(f) Battery & Battery charger of rated capacity as per the alternator/ Engine compatability
(g) Mounting Arrangement shall be of the following: (i) Engine and alternator are mounted on a common MSfabricated base frame with AVM pads. (ii) Base frame with integral fuel tank is provided with drainplug, air vent, inlet and outlet connection, level indicator andprovision for cleaning
(h) Fuel Tank of capacity 150 ltrs capacity along with Fuel pipe MS c class 25mm ID with bends , flanges , valves, tees and bends.
(I) Critical grade silencer with MS pipe as designed by the OEM horizontal Exhaust pipe complete with bends and flanges of adeeaquate length not less than 10 Mtr.along with thermal Insulation on horizontal pipe with Mineral Wool/ Asbestos Rope 50mm Thick wire mesh and 26 gauge aluminium cladding (12")
(j) Controll / service cables shall be of 4cx 2.5 sqmm, 24 c x 2.5 sqmm , 2 c x 2.5 sqmm, and 8c x 0.75 sqmm shielded control cables ,pvc insulated copper armoured, controll panel for auxilaries with starters for pumps,heaters etc
(k) RCC foundation with necessary earth work ,PCC 1:4:8 type D-2 (40mm graded stone aggregate) as in foundation, filling and mass concrete / RCC M-30 (20 mm graded aggregate) as in foundations, Plinth beam along with necessary form work / TMT bars of 10mm dia and over cut to length bend to shape required including cranking, bending, spirally for hooping for columns, hooking ends and bidning with and including MS wire (annealed) not less than 0.9mm dia securing with clips / 10 mm thick plastering on fair faces of brick work or concrete surface in CM (1:6),even and smooth without using extra cement / Sand filling in layers around the foundation including watering and consolidation as per OEM dimensions
(l) Acoustic Enclosure shall comprise of the following (i) Specially designed to meet stringent MoEF/ CPCB norms of75 dBA @ 1mtr at 75% load under free field conditions (ii) The Acoustic Enclosure as per CPCB Norms is made of CRCA sheets in Munselgreen shade and a structural/ sheet metal base frame painted in black. or any other standard colour as specified by the OEM (iii) High quality noise absorbant and fire-retardant gradeacoustic insulation material (P.U. Foam) complying to IS8183 designed to have optimum serviceability (iv) Air inlet louvers specially designed to operate at rated load, Made on special purpose CNC machines for consistency inquality and workmanship (v) 11 tank pretreatment process and UV resistant powdercoating of all parts to withstand extreme environment, Use of special hardware for longer life, Flush styling - no projections, Fluid drains for lube oil and fuel,Fuel filling arrangement inside the enclosure
Supply, Installalation and testing of water cooled Diesel Engine driven Prime duty Generating Set of net capacity after all derating factors net of not less than 125 KVA /100 KWe ,50Hz 415 volt 3 phase, 4 wire,0.8 lagg , 159 hp minimum Required Power for Rated kVA (hp) along with AMF system with Acoustic Enclosure exhaust silencer Hospital Grade in line, as per the noise emmission standards liad down by MoEF / CPCB Norms complete all as specified and directed
A) Engine comprising of the following: Rugged engine natural liquid cooled (EG Compleat 50:50) with radiator as secondary media with world class OEM such as Cummins/Perkins/Kohler/Greaves/Ashok Leyland Engines for powered diesel generator set along with these specifications of Advanced in-cylinder technology turbo charged , air cooled aspriated to meet latest emission norms without any after-treatment device. Class defining technology engine is designed to meet stringent exhaust emission tests as per revised MoEF norms, thus offering environment friendly powe Compact in size with optimum power to weight ratio, 6 cylinder, In-line 4 stroke, radiator cooled engine Well designed air handling system with Dry type, heavy duty, replaceable paper element aircleaner with restriction indicator, Air to air aftercooling, Optimised turbocharger for increased altitude capabilities, Best in class fuel economy with Inline fuel pump with A1 class mechanical governing, Spin on fuel filter, Standard integral set-mounted radiator system, designedand tested for 50°C ambient temperature,Full flow spin on lube oil filte,First fill of lube oil and coolant, Electrical starter motor with soft start engagement feature, Battery charging alternator,1 x 12 V DC battery/Alternator
b) AlternatorPMG type comprising of the following: Stamford UC/jyothi/crompton alternator frames from Technologies Brushless type, Screen protected, Revolving field, Self excited alternator conforming to IS/IEC 60034-13 Phase reconnectable winding with 12 terminals brought out for connection Dedicated winding specially designed for 1 phase and 3 phase operation Better motor starting capability Best in class efficiency Compact design with sealed bearings for longer life andlesser maintenance Impregnation on all wound components for bettermechanical strength Voltage regulation (Max.)±1%,Class of Insulation H Class, Winding Pitch 2/3, Stator Winding Double layer lap Rotor Dynamically Balanced,Waveform distortion/ Total Harmonic Distortion No load < 1.5 %, Non distorting balanced linear load < 5 %,Maximum Unbalanced Load across phases# less than or equal to 25%, Telephonic Harmonic factor < 2% alternator capacity net output shall not be less than 125 KVA /100 KWe ,50Hz 415 volt 3 phase, 4 wire,0.8 lagg. 124 Amp / phase
Control Panel comprising of the following: c) AMF / Control panel is manufactured with 14/16 gauge CRCA sheet and is powder coated for weather-proof and long lasting finish.The control panel consists of the following parts of makes as per OEM recomendation: microprocessor based generator set monitoring and control system. AMF Functionality is inbuilt and this control includes an intuitive operator interface that allows for complete generator set control as well as system metering, fault annunciation, configuration, and diagnostics, Copper bus bars with suitable capacity with incoming/outgoing terminals, Indicating lamps for ‘Load ON’ and ‘Set Running’,Instrument fuses / MCBs duly wired and ferruled, Circuit breakers of suitable rating with overload and shortcircuit protections.along with motorised change overs /on load power contactors with copper busbars, cables and protective acessories with load / bypass arrangements
Hospital Grade silencer silencer with Rain Cap suitably optimized to meet stringentnoise emission standards laid down by MoEF / CPCBalong with MS supporting structures .along with thermal Insulation on horizontal pipe with Mineral Wool/ Asbestos Rope 50mm Thick wire mesh and 26 gaugealuminium cladding (12")
d) Controller should be compatable to the following specifications: (i)AMF Functionality controllers of Makes from the OEM : Deep Sea/ Cummins/ Wood Ward/ Com Amp (II)Intuitive operator interface which includes LED backlit128X64 pixel graphic display with tactile feel soft-switches.Indications - Generator set, Utility Status Lamp. (iii)Remote start-stop with Engine Metering: Oil pressure, Engine temperature, Startingbattery voltage, Engine running hours (iv)AC Alternator Metering: L-L Voltage and L-N Voltage,Current (phase and total), kVA (phase and total) andFrequency. kwh, Total & per phase (kw & kVA), PF, UtilityVoltage and Freq. (v)Engine Protection: Low lube oil pressure, High/Low coolanttemperature, Battery Over/Under/Weak Volts, Fail to Crank/Start, Sensor failure, Cranking lockout, Low fuel level.
(vi)AC Alternator Protection: Over/Under Voltage, Over/UnderFrequency, Loss of AC sensing. Overspeed, Over Current. (vii)Data Logging: Engine hours, Control hours and upto 5 recent fault codes (viii)Configurable glow plug control, Cycle Cranking (ix)12/24 Volt DC operation,Sleep mode,Modbus interface (RS485 RTU),InPower compatible (PC based service tool),Certifications - meets the requirement of relevant ISO, EN,Mil Std. and CE standards (e)Maintenance due alarm based on Engine Run Time and duedate,Exercisor scheduler (f) Remote HMI, Digital electronic governor with temperture compensation and smooth starting, digital AVR for shunt of PMG excitor with Torque monitoring
(e) All pipe line connections, valves etc.required for the lube oils, fuel and cooling system
(f) Battery & Battery charger of rated capacity as per the alternator/ Engine compatability
(g) Mounting Arrangement shall be of the following: (i) Engine and alternator are mounted on a common MSfabricated base frame with AVM pads. (ii) Base frame with integral fuel tank is provided with drainplug, air vent, inlet and outlet connection, level indicator andprovision for cleaning
(h) Fuel Tank of capacity 290 Ltrs capacity along with Fuel pipe MS c class 25mm ID with bends , flanges , valves, tees and bends.
(I) Hospital grade silencer with MS pipe as designed by the OEM horizontal Exhaust pipe complete with bends and flanges of adeeaquate length not less than 10 Mtr.along with thermal Insulation on horizontal pipe with Mineral Wool/ Asbestos Rope 50mm Thick wire mesh and 26 gaugealuminium cladding (12")
(j) Controll / service cables shall be of 4cx 2.5 sqmm, 24 c x 2.5 sqmm , 2 c x 2.5 sqmm, and 8c x 0.75 sqmm shielded control cables ,pvc insulated copper armoured, controll panel for auxilaries with starters for pumps,heaters etc
(k) RCC foundation with necessary earth work ,PCC 1:4:8 type D-2 (40mm graded stone aggregate) as in foundation, filling and mass concrete / RCC M-30 (20 mm graded aggregate) as in foundations, Plinth beam along with necessary form work / TMT bars of 10mm dia and over cut to length bend to shape required including cranking, bending, spirally for hooping for columns, hooking ends and bidning with and including MS wire (annealed) not less than 0.9mm dia securing with clips / 10 mm thick plastering on fair faces of brick work or concrete surface in CM (1:6),even and smooth without using extra cement / Sand filling in layers around the foundation including watering and consolidation as per OEM dimensions
(l) Acoustic Enclosure shall comprise of the following (i)Specially designed to meet stringent MoEF/ CPCB norms of75 dBA @ 1mtr at 75% load under free field conditions (ii)The Acoustic Enclosure as per CPCB Norms is made of CRCA sheets in Munselgreen shade and a structural/ sheet metal base frame painted in black. or any other standard colour as specified by the OEM (iii)High quality noise absorbant and fire-retardant gradeacoustic insulation material (P.U. Foam) complying to IS8183 designed to have optimum serviceability (iv)Air inlet louvers specially designed to operate at rated load, Made on special purpose CNC machines for consistency inquality and workmanship (v)11 tank pretreatment process and UV resistant powdercoating of all parts to withstand extreme environment, Use of special hardware for longer life, Flush styling - no projections, Fluid drains for lube oil and fuel,Fuel filling arrangement inside the enclosure
Supply, Installalation and testing of water cooled Diesel Engine driven Prime duty Generating Set of net capacity after all derating factors net of not less than 200 KVA /160 KWe ,50Hz 415 volt 3 phase, 4 wire,0.8 lagg , 256 bhp minimum Required Power for Rated kVA (bhp)along with AMF system with Acoustic Enclosure as per CPCB Norms, exhaust silencer-Hospital Grade in line complete all as specified and directed
A) Engine comprising of the following: Rugged engine natural liquid cooled (EG Compleat 50:50) with radiator as secondary media with world class OEM such as Cummins/Perkins/Kohler/Greaves/Ashok Leyland Engines for powered diesel generator set Advanced in-cylinder technology turbo charged , air cooled aspriated to meet latest emission norms without any after-treatment device. Class defining technology engine is designed to meet stringent exhaust emission tests as per revised MoEF norms, thus offering environment friendly powe Compact in size with optimum power to weight ratio, 6 cylinder, In-line 4 stroke, radiator cooled engine Well designed air handling system with Dry type, heavy duty, replaceable paper element aircleaner with restriction indicator, Air to air aftercooling,Optimised turbocharger for increased altitudecapabilities, Best in class fuel economy with Inline fuel pump with A1 class mechanical governing, Spin on fuel filter, Standard integral set-mounted radiator system, designedand tested for 50°C ambient temperature,Full flow spin on lube oil filte,First fill of lube oil and coolant, Electrical starter motor with soft start engagement feature, Battery charging alternator,1 x 12 V DC battery/Alternator
b) Alternator PMG type comprising of the following: Stamford UC/jyothi/crompton alternator frames from Technologies Brushless type, Screen protected, Revolving field, Self excited alternator conforming to IS/IEC 60034-13 Phase reconnectable winding with 12 terminals brought out for connection Dedicated winding specially designed for 1 phase and 3 phase operationBetter motor starting capability Best in class efficiency Compact design with sealed bearings for longer life andlesser maintenance Impregnation on all wound components for better mechanical strength aternator with IP 23,Voltage regulation (Max.)±1%, Class of Insulation H Class, Winding Pitch 2/3, Stator Winding Double layer lap Rotor Dynamically Balanced,Waveform distortion/ Total Harmonic Distortion No load < 1.5 %, Non distorting balanced linear load < 5 %,Maximum Unbalanced Load across phases# less than or equal to 25%, Telephonic Harmonic factor < 2% alternator capcity out put shall not be less than 200 KVA ,50Hz 415 volt 3 phase, 4 wire,0.8 lagg. 278Amp / phase
Control Panel comprising of the following: c) AMF / Control panel is manufactured with 14/16 gauge CRCA sheet and is powder coated for weather-proof and long lasting finish.The control panel consists of the following parts of makes as per OEM recomendation: microprocessor based generator set monitoring and control system. AMF Functionality is inbuilt and this control includes an intuitive operator interface that allows for complete generator set control as well as system metering, fault annunciation, configuration, and diagnostics, Copper bus bars with suitable capacity with incoming/outgoing terminals, Indicating lamps for ‘Load ON’ and ‘Set Running’,Instrument fuses / MCBs duly wired and ferruled, Circuit breakers of suitable rating with overload and shortcircuit protections. along with motorised change overs /on load power contactors with copper busbars, cables and protective acessories with load / bypass arrangements
Hospital grade silencer silencer suitably optimized to meet stringentnoise emission standards laid down by MoEF / CPCBalong with MS supporting structures .along with thermal Insulation on horizontal pipe with Mineral Wool/ Asbestos Rope 50mm Thick wire mesh and 26 gaugealuminium cladding (12")
d) Controller should be compatable to the following specifications: (i) AMF Functionality controllers of Makes from the OEM : Deep Sea/ Cummins/ Wood Ward/ Com Amp (II)Intuitive operator interface which includes LED backlit display with tactile feel soft-switches.Indications - Generator set, Utility Status Lamp. (iii)Remote start-stop with Engine Metering: Oil pressure, Engine temperature, Startingbattery voltage, Engine running hours (iv)AC Alternator Metering: L-L Voltage and L-N Voltage,Current (phase and total), kVA (phase and total) andFrequency. kwh, Total & per phase (kw & kVA), PF, UtilityVoltage and Freq. (v)Engine Protection: Low lube oil pressure, High/Low coolanttemperature, Battery Over/Under/Weak Volts, Fail to Crank/Start, Sensor failure, Cranking lockout, Low fuel level. (vi)AC Alternator Protection: Over/Under Voltage, Over/UnderFrequency, Loss of AC sensing. Overspeed, Over Current.
(vii)Data Logging: Engine hours, Control hours and upto 5 recent fault codes (viii)Configurable glow plug control, Cycle Cranking (ix)12/24 Volt DC operation,Sleep mode,Modbus interface (RS485 RTU),InPower compatible (PC based service tool),Certifications - meets the requirement of relevant ISO, EN,Mil Std. and CE standards (e)Maintenance due alarm based on Engine Run Time and duedate,Exercisor scheduler (f) Remote HMI, Digital electronic governor with temperture compensation and smooth starting, digital AVR for shunt of PMG excitor with Torque monitoring, Digital electronic governor with temperture compensation and smooth starting, digital AVR for shunt of PMG excitor with Torque monitoring
(e) All pipe line connections, valves etc.required for the lube oils, fuel and cooling system
(f) Battery & Battery charger of rated capacity as per the alternator/ Engine compatability
(g) Mounting Arrangement shall be of the following: (i) Engine and alternator are mounted on a common MSfabricated base frame with AVM pads. (ii) Base frame with integral fuel tank is provided with drainplug, air vent, inlet and outlet connection, level indicator andprovision for cleaning
(h) Fuel Tank of capacity 350 Ltrs capacity along with Fuel pipe MS c class 25mm ID with bends , flanges , valves, tees and bends.
(I) Residnetial type silencer with MS pipe as designed by the OEM horizontal Exhaust pipe complete with bends and flanges of adeeaquate length not less than 10 Mtr.along with thermal Insulation on horizontal pipe with Mineral Wool/ Asbestos Rope 50mm Thick wire mesh and 26 gaugealuminium cladding (12")
(j) Controll / service cables shall be of 4cx 2.5 sqmm, 24 c x 2.5 sqmm , 2 c x 2.5 sqmm, and 8c x 0.75 sqmm shielded control cables ,pvc insulated copper armoured, controll panel for auxilaries with starters for pumps,heaters etc
(k) RCC foundation with necessary earth work ,PCC 1:4:8 type D-2 (40mm graded stone aggregate) as in foundation, filling and mass concrete / RCC M-30 (20 mm graded aggregate) as in foundations, Plinth beam along with necessary form work / TMT bars of 10mm dia and over cut to length bend to shape required including cranking, bending, spirally for hooping for columns, hooking ends and bidning with and including MS wire (annealed) not less than 0.9mm dia securing with clips / 10 mm thick plastering on fair faces of brick work or concrete surface in CM (1:6),even and smooth without using extra cement / Sand filling in layers around the foundation including watering and consolidation as per OEM dimensions
(l) Acoustic Enclosure shall comprise of the following (i)Specially designed to meet stringent MoEF/ CPCB norms of75 dBA @ 1mtr at 75% load under free field conditions (ii)The Acoustic Enclosure as per CPCB Norms is made of CRCA sheets in Munselgreen shade and a structural/ sheet metal base frame painted in black. or any other standard colour as specified by the OEM (iii)High quality noise absorbant and fire-retardant gradeacoustic insulation material (P.U. Foam) complying to IS8183 designed to have optimum serviceability (iv)Air inlet louvers specially designed to operate at rated load, Made on special purpose CNC machines for consistency inquality and workmanship (v)11 tank pretreatment process and UV resistant powdercoating of all parts to withstand extreme environment, Use of special hardware for longer life, Flush styling - no projections, Fluid drains for lube oil and fuel,Fuel filling arrangement inside the enclosure
Supply, Installalation and testing of water cooled Diesel Engine driven Prime duty Generating Set of capacity after all derating factors net of not less than 225 KVA/ 180 KWe ,50Hz 415 volt 3 phase, 4 wire,0.8 lagg, 280bhp minimum Required Power for Rated kVA (bhp) along with AMF system with Acoustic Enclosure as per CPCB Norms, exhaust silencer-Hospital Grade in line complete all as specified and directed
A) Engine comprising of the following: Rugged engine natural liquid cooled (EG Compleat 50:50) with radiator as secondary media with world class OEM such as Cummins/Perkins/Kohler/Greaves/Ashok Leyland Engines for powered diesel generator set Advanced in-cylinder technology turbo charged , air cooled aspriated to meet latest emission norms without any after-treatment device. Class defining technology engine is designed to meet stringent exhaust emission tests as per revised MoEF norms, thus offering environment friendly powe Compact in size with optimum power to weight ratio, 6 cylinder, In-line 4 stroke, radiator cooled engine Well designed air handling system with Dry type, heavy duty, replaceable paper element aircleaner with restriction indicator, Air to air aftercooling,Optimised turbocharger for increased altitudecapabilities, Best in class fuel economy with Inline fuel pump with A1 class mechanical governing, Spin on fuel filter, Standard integral set-mounted radiator system, designedand tested for 50°C ambient temperature,Full flow spin on lube oil filte,First fill of lube oil and coolant, Electrical starter motor with soft start engagement feature, Battery charging alternator,1 x 12 V DC battery/Alternator
b) AlternatorPMG type comprising of the following: Stamford UC/jyothi/crompton alternator frames from Cummins Generator TechnologiesbBrushless type, Screen protected, Revolving field, Self excited alternator conforming to IS/IEC 60034-13 Phase reconnectable winding with 12 terminals brought out for connection Dedicated winding specially designed for 1 phase / 3 pahse operation Better motor starting capability Best in class efficiency Compact design with sealed bearings for longer life andlesser maintenance Impregnation on all wound components for better mechanical strength, alternator of IP 23, Voltage regulation (Max.)±1%,Class of Insulation H Class, Winding Pitch 2/3,Stator Winding Double layer lap Rotor Dynamically Balanced,Waveform distortion/ Total Harmonic Distortion No load < 1.5 %, Non distorting balanced linear load < 5 %,Maximum Unbalanced Load across phases# less than or equal to 25%, Telephonic Harmonic factor < 2% alternator capcity out put shall not be less than 200 KVA /180KWe ,50Hz 415 volt 3 phase, 4 wire,0.8 lagg. 313Amp / phase
Control Panel comprising of the following: c) AMF / Control panel is manufactured with 14/16 gauge CRCA sheet and is powder coated for weather-proof and long lasting finish.The control panel consists of the following parts of makes as per OEM recomendation: microprocessor based generator set monitoring and control system. AMF Functionality is inbuilt and this control includes an intuitive operator interface that allows for complete generator set control as well as system metering, fault annunciation, configuration, and diagnostics, Copper bus bars with suitable capacity with incoming/outgoing terminals, Indicating lamps for ‘Load ON’ and ‘Set Running’,Instrument fuses / MCBs duly wired and ferruled, Circuit breakers of suitable rating with overload and shortcircuit protections. with motorised change overs /on load power contactors with copper busbars, cables and protective acessories with load / bypass arrangements
Hospital grade silencer silencer suitably optimized to meet stringentnoise emission standards laid down by MoEF / CPCBalong with MS supporting structures .along with thermal Insulation on horizontal pipe with Mineral Wool/ Asbestos Rope 50mm Thick wire mesh and 26 gaugealuminium cladding (12")
d) Controller should be compatable to the following specifications: (i) AMF Functionality controllers of Makes from the OEM : Deep Sea/ Cummins/ Wood Ward/ Com Amp (II)Intuitive operator interface which includes LED backlit display with tactile feel soft-switches.Indications - Generator set, Utility Status Lamp. (iii)Remote start-stop with Engine Metering: Oil pressure, Engine temperature, Startingbattery voltage, Engine running hours (iv)AC Alternator Metering: L-L Voltage and L-N Voltage,Current (phase and total), kVA (phase and total) andFrequency. kwh, Total & per phase (kw & kVA), PF, UtilityVoltage and Freq. (v)Engine Protection: Low lube oil pressure, High/Low coolanttemperature, Battery Over/Under/Weak Volts, Fail to Crank/Start, Sensor failure, Cranking lockout, Low fuel level. (vi)AC Alternator Protection: Over/Under Voltage, Over/UnderFrequency, Loss of AC sensing. Overspeed, Over Current. (vii)Data Logging: Engine hours, Control hours and upto 5 recent fault codes (viii)Configurable glow plug control, Cycle Cranking (ix)12/24 Volt DC operation,Sleep mode,Modbus interface (RS485 RTU),InPower compatible (PC based service tool),Certifications - meets the requirement of relevant ISO, EN,Mil Std. and CE standards (e)Maintenance due alarm based on Engine Run Time and duedate,Exercisor scheduler (f) Remote HMI, Digital electronic governor with temperture compensation and smooth starting, digital AVR for shunt of PMG excitor with Torque monitoring, Digital electronic governor with temperture compensation and smooth starting, digital AVR for shunt of PMG excitor with Torque monitoring
(e) All pipe line connections, valves etc.required for the lube oils, fuel and cooling system
(f) Battery & Battery charger of rated capacity as per the alternator/ Engine compatability
(g) Mounting Arrangement shall be of the following: (i) Engine and alternator are mounted on a common MSfabricated base frame with AVM pads. (ii) Base frame with integral fuel tank is provided with drainplug, air vent, inlet and outlet connection, level indicator andprovision for cleaning
(h) Fuel Tank of capacity 350 Ltrs capacity along with Fuel pipe MS c class 25mm ID with bends , flanges , valves, tees and bends.
(I) Hospital Grade silencer with MS pipe as designed by the OEM horizontal Exhaust pipe complete with bends and flanges of adeeaquate length not less than 10 Mtr.along with thermal Insulation on horizontal pipe with Mineral Wool/ Asbestos Rope 50mm Thick wire mesh and 26 gaugealuminium cladding (12")
(j) Controll / service cables shall be of 4cx 2.5 sqmm, 24 c x 2.5 sqmm , 2 c x 2.5 sqmm, and 8c x 0.75 sqmm shielded control cables ,pvc insulated copper armoured, controll panel for auxilaries with starters for pumps,heaters etc
(k) RCC foundation with necessary earth work ,PCC 1:4:8 type D-2 (40mm graded stone aggregate) as in foundation, filling and mass concrete / RCC M-30 (20 mm graded aggregate) as in foundations, Plinth beam along with necessary form work / TMT bars of 10mm dia and over cut to length bend to shape required including cranking, bending, spirally for hooping for columns, hooking ends and bidning with and including MS wire (annealed) not less than 0.9mm dia securing with clips / 10 mm thick plastering on fair faces of brick work or concrete surface in CM (1:6),even and smooth without using extra cement / Sand filling in layers around the foundation including watering and consolidation as per OEM dimensions
(l) Acoustic Enclosure shall comprise of the following (i)Specially designed to meet stringent MoEF/ CPCB norms of75 dBA @ 1mtr at 75% load under free field conditions (ii)The Acoustic Enclosure as per CPCB Norms is made of CRCA sheets in Munselgreen shade and a structural/ sheet metal base frame painted in black. or any other standard colour as specified by the OEM (iii)High quality noise absorbant and fire-retardant gradeacoustic insulation material (P.U. Foam) complying to IS8183 designed to have optimum serviceability (iv)Air inlet louvers specially designed to operate at rated load, Made on special purpose CNC machines for consistency inquality and workmanship (v)11 tank pretreatment process and UV resistant powdercoating of all parts to withstand extreme environment, Use of special hardware for longer life, Flush styling - no projections, Fluid drains for lube oil and fuel,Fuel filling arrangement inside the enclosure
Note for Item No. 01 to 04 (i) Rate quoted shall include the necessary T&P , RCC foundation , structural works required to support the acessoriess of Dg set such asAMF panels, controll cables, Radiators / cooling tower, Exhaust mufflers and water circualtion system / cooling System (ii) rate quoted includes the cost of All fuel ( high speed diesel) , lubes and collant required to carry out the no load and full load test of not less than 24 hrs as diercted by the accepting officer (iii) Rate quoted includes the cost of B check for the DG set such as replacement of lube oil, oil/ fuel filters /belts, O rings consumeables after the test run of the DG set during the warrenty period frist 250 hrs/ 1 st year which ever is earlier after the date of commissioning
Material and labour for complete removal of the BER DG set from the foundation complete with out damaging the installation and the equipment isolating all the cables, fuel tank and pipe lines complete and shifting the retrived DG set with in the permises of the Delhi cantt to MT yard under GE (U) E/s delhi cantt complete all as specified and directed
Earthing complete with copper strip of size 20 x 3 mm thick earth plate electrode 600 x 600 x 3.15mm thick, buried directly into ground vertically not less than 2.25 Mtr below the ground level with top edge of the earth plate to a depth not less than 1.5 Mtr below the ground level, connected to a copper strip 20 x 3 mm including GI protection pipe 15mm bore light grade connected from electrode up to test point including necessary earth work, PCC/RCC chamber cover 50mm thick in RCC 1:2:4 type B1 with 8mm TMT bars 15 cm c/c both ways, funnel arrangement etc as per electrical plate No 5 of SSR part I complete all as specified and directed Note : Rate shall be deemed to be inclusive of necessary excavation and earth work in any type of soil, removal of surplus soil to a distance not exceeding 50m, RCC cover slab and PCC chamber etc.
M & L for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc.Ditto, but 20 x 3 mm copper strip complete all as specified and directed
Material and labour for complete removal of the BER OCB/VCB from the foundation/ electrical cables bus bars complete with out damaging the installation and the equipment isolating all the cables, complete and shifting the retrived Breakers with in the permises of the Delhi cantt to Store yard under GE (U) E/s delhi cantt complete all as specified and directed
Supplying, installing, testing and commissioning of Indoor arc flash protected Draw-Out with roll on floor type Vacuum Circuit Breaker Panel , rated for 11kV, 800 Amp, 26.3kA/3-sec, comprising of 02 No. Incomer, and 04 Nos. Outgoing VCB Panels at chitral line substation under AGE(U) I and Top mounted Bus PTs /Line PTs on panel for each bus section, confirming to IEC 62271-200, Internal Arc Classified IAC AFLR – 26.3kA for 1sec, Accessibility Class LSC2B-PM Class, comprising of 800 Amp, continuous rated Copper insulated busbars and droppers in all bus / breaker/ adaptor and and cable chambers, The busbars to be covered with insulating material, The earthing busbar is made of electrolytic copper and it runs longitudinally throughout the switchgear Encapsulated feeder connections IS3427 and IS12729. with 02nos. . Rack-In-Rack-Out Handles, structure made from AluZinc/GI/powder coated CRCA sheets to prevent corrosion and rusting.The complete panel incl. HT and LT chamber with FRLS wiring and acessories shall be manufactured by approved OEM at its own mancufacturing in house facility, and same will be verified via stage/final inspection. system house integrator / channel partner products arenot accepted complete all as specified and directed Note: These HT pannels shall be clubbed with the existing / fixed with the existing VCB and Bus Copupler
(A) 02 x Incomer Panel, each comprising of :-
(i) 11kV, 800 Amp, 26.3kA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100 with roll on floor type Vacuum Circuit Breaker having 03 Nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24VDC).
(ii) Current Transformers 11kV, 400/200/5A Core1: Class 5P10, 5VA, Core2: Class 0.5, 5VA, Remote HMI, Digital electronic governor with temperture coCore3: Class PS-X - Set of 03 No per breaker
(iii) Potential Transformers, Draw-out type for easy maintenance, 11kV/rt3:110V/rt3, 50VA, Cl.0.5 with associated gun-type HRC fuses and MCBs for HT/LT isolation - complete set per breaker
(iv) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT+05PT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) Directional over-current or earth-fault in any of the three phases, (b) Synchronism and Energizing Check before breaker closing to prevent un-syncronized mixing of supplies (c) circuit-breaker-failure alarm, (d) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (e) Integrted arc flash protection with current and light sensing The relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Line-Voltage, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), AC Supply Fail, PT Fuse failure relay, Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with power & frequency measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(v) Metering Equipment including:- (a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port.
(vi) LED Indications :- (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) R-Y-B, (c) DC Available LED with push-button (d) AC Supply Fail (e) Trip Circuit Healthy
(vii) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip (c) Trip Circuit Failure, (d) Inter-Tripping Fault, (e) Synchro-Check. (f) PT Fuse Failure The Annunciator will be complete with required Acknowledge/Test buttons as required
(viii) Control Equipment incl. :- (a) 01 x TNC Switch, (b) 01 x Local/Remote Switch, (c) 01 x Emergency Trip Push Button, (d) MCBs for AC (e) MCBs for DC (f) Heater Switch with Thermostat - 01no. (g) 3-pin socket with ON/OFF switch - 01no. (h) LED Lamp with ON/OFF switch - 01no.
(ix) Flush mounted Auxillary Protection Relays incl:- (a) Trip Circuit Supervision Relay, (b) Master trip Relay, (c) PT Fuse failure relay. (d) DC Supervision Scheme
(x) Suitable Disconnecting Link type terminal arrangement shall be provided for interfacing PS-Class CTs installed in the panel for achieving the required protection.
(B) 04 x Outgoing Panel, each comprising of :- (i) 11kV, 630Amp, 26.3KA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100. Vacuum Circuit Breaker having 03nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24VDC).
(ii) Current Transformers 11kV, 150-75/5A, for 2 breakers and 100-50/5A for 2 breakers Core1: Class 5P10, 10VA, Core2: Class 0.5, 10VA - Set of 03 Nos.each/ breaker
(iii) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) over-current or earth-fault in any of the three phases, (b) circuit-breaker-failure alarm, (c) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (d) Integrted arc flash protection with current and light sensing. (e )Transformer protection (Marshalling Box and Buchhloz relay). The relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with current measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(iv) Metering Equipment including:- (a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port.
(v) LED Indications - (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) Trip Circuit Healthy
(vi) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip (c) Trip Circuit Failure, (d) Inter-Tripping Fault, The Annunciator will be complete with required Acknowledge/Test buttons as required
(vii) Control Equipment incl. (a) 01 x TNC Switch, (b) 01 x Emergency Trip Push Button, (c) 01 x Local/Remote Switch, (d) MCBs for AC/DC isolation (e) Heater Switch with Thermostat - 01no. (f) 3-pin socket with ON/OFF switch - 01no. (g) LEDLamp with ON/OFF switch - 01no.
(viii) Flush mounted Auxillary Protection Relays incl. (a) Trip Circuit Supervision Relay, (b) Master trip Relay,
(ix) Transformer protection each comprising of :- (a) Oil Temperature high. (b) Winding Temperature high. (c ) Tank oil level low. (d) OLTC oil level low. (e) Buchhloz relay trip or sudden gas and sudden oil pressure relay trip. (f) Pressure relief.
Supplying, installing, testing and commissioning of Indoor arc flash protected Draw-Out with roll on floor type Vacuum Circuit Breaker Panel , rated for 11kV, 800 Amp, 26.3kA/3-sec, both side extendable type coupled with existing VCB panel with suitable size of bus bar/blank complete as Outgoing VCB Panels -01No at Chitral line substation under AGE(U) E/S- I and Top mounted Bus PTs /Line PTs on panel for each bus section, confirming to IEC 62271-200, Internal Arc Classified IAC AFLR – 26.3kA for 1sec, Accessibility Class LSC2B-PM Class, comprising of 800 Amp, continuous rated Copper insulated busbars and droppers in all bus / breaker/ adaptor and and cable chambers, The busbars to be covered with insulating material, The earthing busbar is made of electrolytic copper and it runs longitudinally throughout the switchgear Encapsulated feeder connections IS3427 and IS12729. with 02nos. . Rack-In-Rack-Out Handles, structure made from AluZinc/GI/powder coated CRCA sheets to prevent corrosion and rusting. The complete panel incl. HT and LT chamber with FRLS wiring and acessories shall be manufactured by approved OEM at its own mancufacturing in house facility, and same will be verified via stage/final inspection. system house integrator / channel partner products arenot accepted complete all as specified and directed Note: These HT pannels shall be clubbed with the existing / fixed with the existing VCB and Bus Extension
(A) (i) 11kV, 630Amp, 26.3KA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100. Vacuum Circuit Breaker having 03nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24VDC).
(ii) Current Transformers 11kV, 400-200/5A, Core1: Class 5P10, 5VA, Core2: Class 0.5, 5VA - Set of 03 Nos.
(iii) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) over-current or earth-fault in any of the three phases, (b) circuit-breaker-failure alarm, (c) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (d) Integrted arc flash protection with current and light sensing The relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with current measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(iv) Metering Equipment including:- (a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port.
(v) LED Indications - (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) Trip Circuit Healthy
(vi) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip (c) Trip Circuit Failure, (d) Inter-Tripping Fault, The Annunciator will be complete with required Acknowledge/Test buttons as required
(b) All Multi-function-meters shall be connected in a ModBus loop terminating into 01 No. ModBus-to-TCP/IP converter to be provided for sending data to SCADA console via networking switch.
(viii) Control Equipment incl. (a) 01 x TNC Switch, (b) 01 x Emergency Trip Push Button, (c) 01 x Local/Remote Switch, (d) MCBs for AC/DC isolation (e) Heater Switch with Thermostat - 01no. (f) 3-pin socket with ON/OFF switch - 01no. (g) LED Lamp with ON/OFF switch - 01no.
(ix) Flush mounted Auxillary Protection Relays incl. (a) Trip Circuit Supervision Relay, (b) Master trip Relay,
(x) Suitable Disconnecting Link type terminal arrangement shall be provided for interfacing PS-Class CTs installed in the panel with existing VCB panel relay suituated in the 11 KV CRP for achieving the required protection.
Supplying, installing, testing and commissioning of Indoor arc flash protected Draw-Out with roll on floor type Vacuum Circuit Breaker Panel , rated for 11kV, 800 Amp, 26.3kA/3-sec, both side extendable type with suitable size of bus bar/blank complete as Outgoing VCB Panels-01 no at IR /CVD substation under AGE(U) E/S- I and Top mounted Bus PTs /Line PTs on panel for each bus section, confirming to IEC 62271-200, Internal Arc Classified IAC AFLR – 26.3kA for 1sec, Accessibility Class LSC2B-PM Class, comprising of 800 Amp, continuous rated Copper insulated busbars and droppers in all bus / breaker/ adaptor and and cable chambers, The busbars to be covered with insulating material, The earthing busbar is made of electrolytic copper and it runs longitudinally throughout the switchgear Encapsulated feeder connections IS3427 and IS12729. with 02nos. . Rack-In-Rack-Out Handles, structure made from AluZinc/GI/powder coated CRCA sheets to prevent corrosion and rusting. The complete panel incl. HT and LT chamber with FRLS wiring and acessories shall be manufactured by approved OEM at its own mancufacturing in house facility, and same will be verified via stage/final inspection. system house integrator / channel partner products arenot accepted complete all as specified and directed
(A) (i) 11kV, 630Amp, 26.3KA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100. Vacuum Circuit Breaker having 03nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24VDC).
(ii) Current Transformers 11kV, 100-50/5A, Core1: Class 5P10, 5VA, Core2: Class 0.5, 5VA - Set of 03 Nos.
(iii) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) over-current or earth-fault in any of the three phases, (b) circuit-breaker-failure alarm, (c) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (d) Integrted arc flash protection with current and light sensing The relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with current measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(iv) Metering Equipment including:- (a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port.
(v) LED Indications - (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) Trip Circuit Healthy
(vi) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip (c) Trip Circuit Failure, (d) Inter-Tripping Fault, The Annunciator will be complete with required Acknowledge/Test buttons as required
(b) All Multi-function-meters shall be connected in a ModBus loop terminating into 01 No. ModBus-to-TCP/IP converter to be provided for sending data to SCADA console via networking switch.
(viii) Control Equipment incl. (a) 01 x TNC Switch, (b) 01 x Emergency Trip Push Button, (c) 01 x Local/Remote Switch, (d) MCBs for AC/DC isolation (e) Heater Switch with Thermostat - 01no. (f) 3-pin socket with ON/OFF switch - 01no. (g) LED Lamp with ON/OFF switch - 01no.
(ix) Flush mounted Auxillary Protection Relays incl. (a) Trip Circuit Supervision Relay, (b) Master trip Relay,
(x) Suitable Disconnecting Link type terminal arrangement shall be provided for interfacing PS-Class CTs installed in the panel with existing VCB panel relay suituated in the 11 KV CRP for achieving the required protection.
Supplying, installing, testing and commissioning of Indoor arc flash protected Draw-Out with roll on floor type Vacuum Circuit Breaker Panel , rated for 11kV, 800 Amp, 26.3kA/3-sec, comprising of 03 No. Incomer, 02 No. Bus Coupler and 26 Nos. Outgoing VCB Panels for COD power house undre AGE(U)E/S-I and Top mounted Bus PTs /Line PTs on panel for each bus section, confirming to IEC 62271-200, Internal Arc Classified IAC AFLR – 26.3kA for 1sec, Accessibility Class LSC2B-PM Class, comprising of 800 Amp, continuous rated Copper insulated busbars and droppers in all bus / breaker/ adaptor and and cable chambers, The busbars to be covered with insulating material, The earthing busbar is made of electrolytic copper and it runs longitudinally throughout the switchgear Encapsulated feeder connections IS3427 and IS12729. with 02nos. . Rack-In-Rack-Out Handles, structure made from AluZinc/GI/powder coated CRCA sheets to prevent corrosion and rusting complete all as specified and directed The complete panel incl. HT and LT chamber with FRLS wiring and acessories shall be manufactured by approved OEM at its own mancufacturing in house facility, and same will be verified via stage/final inspection. system house integrator / channel partner products arenot accepted .
(A) 03 x Incomer Panel, each comprising of :-
(i) 11kV, 800 Amp, 26.3kA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100 with roll on floor type Vacuum Circuit Breaker having 03 Nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24V DC).
(ii) Current Transformers 11kV,400-200/5A, Core1: Class 5P10, 5VA, Core2: Class 0.5, 5VA, Core3: Class PS-X - Set of 03 Nos per breaker
(iii) Potential Transformers, Draw-out type for easy maintenance, 11kV/rt3:110V/rt3, 50VA, Cl.0.5 with associated gun-type HRC fuses and MCBs for HT/LT isolation - complete set per breaker
(iv) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT+05PT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) Directional over-current or earth-fault in any of the three phases, (b) Synchronism and Energizing Check before breaker closing to prevent un-syncronized mixing of supplies (c) circuit-breaker-failure alarm, (d) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (e) Integrted arc flash protection with current and light sensing The relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Line-Voltage, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), AC Supply Fail, PT Fuse failure relay, Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with power & frequency measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(v) Metering Equipment including:- (a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port.
(vi) LED Indications :- (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) R-Y-B, (c) DC Available LED with push-button (d) AC Supply Fail (e) Trip Circuit Healthy
(vii) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip (c) Trip Circuit Failure, (d) Inter-Tripping Fault, (e) Synchro-Check. (f) PT Fuse Failure The Annunciator will be complete with required Acknowledge/Test buttons as required
(viii) Control Equipment incl. :- (a) 01 x TNC Switch, (b) 01 x Local/Remote Switch, (c) 01 x Emergency Trip Push Button, (d) MCBs for AC (e) MCBs for DC (f) Heater Switch with Thermostat - 01no. (g) 3-pin socket with ON/OFF switch - 01no. (h) LED Lamp with ON/OFF switch - 01no.
(ix) Flush mounted Auxillary Protection Relays incl:- (a) Trip Circuit Supervision Relay, (b) Master trip Relay, (c) PT Fuse failure relay. (d) DC Supervision Scheme
(x) Suitable Disconnecting Link type terminal arrangement shall be provided for interfacing PS-Class CTs installed in the panel for achieving the required protection.
(B) 02 x Bus Coupler Panel, each comprising of :- (i) 11kV, 800 Amp, 26.3KA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100 with roll on floor type Vacuum Circuit Breaker having 03nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24V DC).
(ii) Current Transformers 11kV, 400-200/5A Core1: Class 5P10, 5VA, Core2: Class 0.5, 5VA, Core3: Class PS-X - Set of 03 Nos per breaker
(iii) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04PT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) Synchronism and Energizing Check before bus-coupler closing to prevent un-syncronized mixing of supplies (b) circuit-breaker-failure alarm. (c) circuit-breaker-failures and interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. The relay shall be fully integrated with the feeder, internally capturing feeder statuses incl. various status, Bus-Voltage and display the same locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with power & frequency measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(iv) LED Indications - (a) Breaker ON/OFF/TRIP/Spring-Charged (b) Trip Circuit Healthy
(v) Control Equipment incl. :- (a) 01 x TNC Switch, (b) 01 x Local/Remote Switch, (c) 01 x Emergency Trip Push Button, (d) MCBs for AC (e) MCBs for DC (f) Heater Switch with Thermostat - 01 No. (g) 3-pin socket with ON/OFF switch - 01 No. (h) LED Lamp with ON/OFF switch - 01 No.
(vi) Flush mounted Auxillary Protection Relays incl. (a) Trip Circuit Supervision Relay, (b) Master trip Relay,
(vii) 08-Window Annunciator with Hooter to indicate following alarms :- (a) Trip Circuit Failure, (b) Inter-Tripping Fault, (c) Synchro-Check. (d) PT Fuse Failure The Annunciator will be complete with required Acknowledge/Test buttons as required
(C) 26 x Outgoing Panel, each comprising of :- (i) 11kV, 630Amp, 26.3KA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100. Vacuum Circuit Breaker having 03nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24V DC).
(ii) Current Transformers 11kV, 300-150/5A for 1 out going , 250-125/5A for 2 outgoinhg, and 200-100/5A, for 23 outgoing Core1: Class 5P10, 10VA, Core2: Class 0.5, 10VA - Set of 03 Nos. Per breaker
(iii) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) over-current or earth-fault in any of the three phases, (b) circuit-breaker-failure alarm, (c) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (d) Integrted arc flash protection with current and light sensing.
(e )Transformer protection (Marshalling Box and Buchhloz relay). The relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with current measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(iv) Metering Equipment including:- (a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port.
(v) LED Indications - (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) Trip Circuit Healthy
(vi) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip (c) Trip Circuit Failure, (d) Inter-Tripping Fault, The Annunciator will be complete with required Acknowledge/Test buttons as required
(vii) Control Equipment incl. (a) 01 x TNC Switch, (b) 01 x Emergency Trip Push Button, (c) 01 x Local/Remote Switch, (d) MCBs for AC/DC isolation (e) Heater Switch with Thermostat - 01no. (f) 3-pin socket with ON/OFF switch - 01no. (g) LEDLamp with ON/OFF switch - 01no.
(viii) Flush mounted Auxillary Protection Relays incl. (a) Trip Circuit Supervision Relay, (b) Master trip Relay,
(ix) Transformer protection each comprising of :- (a) Oil Temperature high. (b) Winding Temperature high. (c ) Tank oil level low. (d) OLTC oil level low. (e) Buchhloz relay trip or sudden gas and sudden oil pressure relay trip. (f) Pressure relief.
Supplying, installing, testing and commissioning of Indoor arc flash protected Draw-Out with roll on floor type Vacuum Circuit Breaker Panel , rated for 11kV, 800 Amp, 26.3kA/3-sec, comprising of 01 No. Incomer, and 03 Nos. Outgoing VCB Panels for EDP substation house undre AGE(U)E/S-I and Top mounted Bus PTs /Line PTs on panel for each bus section, confirming to IEC 62271-200, Internal Arc Classified IAC AFLR – 26.3kA for 1sec, Accessibility Class LSC2B-PM Class, comprising of 800 Amp, continuous rated Copper insulated busbars and droppers in all bus / breaker/ adaptor and and cable chambers, The busbars to be covered with insulating material, The earthing busbar is made of electrolytic copper and it runs longitudinally throughout the switchgear Encapsulated feeder connections IS3427 and IS12729. with 02nos. . Rack-In-Rack-Out Handles, structure made from AluZinc/GI/powder coated CRCA sheets to prevent corrosion and rusting. The complete panel incl. HT and LT chamber with FRLS wiring and acessories shall be manufactured by approved OEM at its own mancufacturing in house facility, and same will be verified via stage/final inspection. system house integrator / channel partner products arenot accepted complete all as specified and directed
(A) 01 x Incomer Panel, each comprising of :-
(i) 11kV, 800 Amp, 26.3kA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100 with roll on floor type Vacuum Circuit Breaker having 03 Nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24V DC).
(ii) Current Transformers 11kV,200-100/5A, Core1: Class 5P10, 5VA, Core2: Class 0.5, 5VA, Core3: Class PS-X - Set of 03 Nos per breaker
(iii) Potential Transformers, Draw-out type for easy maintenance, 11kV/rt3:110V/rt3, 50VA, Cl.0.5 with associated gun-type HRC fuses and MCBs for HT/LT isolation - complete set per breaker
(iv) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT+05PT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) Directional over-current or earth-fault in any of the three phases, (b) Synchronism and Energizing Check before breaker closing to prevent un-syncronized mixing of supplies (c) circuit-breaker-failure alarm, (d) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (e) Integrted arc flash protection with current and light sensing
The relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Line-Voltage, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), AC Supply Fail, PT Fuse failure relay, Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with power & frequency measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(v) Metering Equipment including:- (a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port.
(vi) LED Indications :- (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) R-Y-B, (c) DC Available LED with push-button (d) AC Supply Fail (e) Trip Circuit Healthy
(vii) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip (c) Trip Circuit Failure, (d) Inter-Tripping Fault, (e) Synchro-Check. (f) PT Fuse Failure The Annunciator will be complete with required Acknowledge/Test buttons as required
(viii) Control Equipment incl. :- (a) 01 x TNC Switch, (b) 01 x Local/Remote Switch, (c) 01 x Emergency Trip Push Button, (d) MCBs for AC (e) MCBs for DC (f) Heater Switch with Thermostat - 01no. (g) 3-pin socket with ON/OFF switch - 01no. (h) LED Lamp with ON/OFF switch - 01no.
(ix) Flush mounted Auxillary Protection Relays incl:- (a) Trip Circuit Supervision Relay, (b) Master trip Relay, (c) PT Fuse failure relay. (d) DC Supervision Scheme
(x) Suitable Disconnecting Link type terminal arrangement shall be provided for interfacing PS-Class CTs installed in the panel for achieving the required protection.
(B) 03 x Outgoing Panel, each comprising of :- (i) 11kV, 630Amp, 26.3KA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100. Vacuum Circuit Breaker having 03nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24V DC).
(ii) Current Transformers 11kV,50-25/5A for 3 out going , Core1: Class 5P10, 10VA, Core2: Class 0.5, 10VA - Set of 03 Nos. Per breaker
(iii) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) over-current or earth-fault in any of the three phases, (b) circuit-breaker-failure alarm, (c) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (d) Integrted arc flash protection with current and light sensing. (e )Transformer protection (Marshalling Box and Buchhloz relay). The relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with current measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(iv) Metering Equipment including:- (a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port.
(v) LED Indications - (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) Trip Circuit Healthy
(vi) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip (c) Trip Circuit Failure, (d) Inter-Tripping Fault, The Annunciator will be complete with required Acknowledge/Test buttons as required
(vii) Control Equipment incl. (a) 01 x TNC Switch, (b) 01 x Emergency Trip Push Button, (c) 01 x Local/Remote Switch, (d) MCBs for AC/DC isolation (e) Heater Switch with Thermostat - 01no. (f) 3-pin socket with ON/OFF switch - 01no. (g) LEDLamp with ON/OFF switch - 01no.
(viii) Flush mounted Auxillary Protection Relays incl. (a) Trip Circuit Supervision Relay, (b) Master trip Relay,
(ix) Transformer protection each comprising of :- (a) Oil Temperature high. (b) Winding Temperature high. (c ) Tank oil level low. (d) OLTC oil level low. (e) Buchhloz relay trip or sudden gas and sudden oil pressure relay trip. (f) Pressure relief.
Supplying, installing, testing and commissioning of Indoor arc flash protected Draw-Out with roll on floor type Vacuum Circuit Breaker Panel , rated for 11kV, 800 Amp, 26.3kA/3-sec, comprising of 1 No. Incomer, and 02 Nos. Outgoing VCB Panels for COD substation No 1 under AGE(U)E/S-I and Top mounted Bus PTs /Line PTs on panel for each bus section, confirming to IEC 62271-200, Internal Arc Classified IAC AFLR – 26.3kA for 1sec, Accessibility Class LSC2B-PM Class, comprising of 800 Amp, continuous rated Copper insulated busbars and droppers in all bus / breaker/ adaptor and and cable chambers, The busbars to be covered with insulating material, The earthing busbar is made of electrolytic copper and it runs longitudinally throughout the switchgear Encapsulated feeder connections IS3427 and IS12729. with 02nos. . Rack-In-Rack-Out Handles, structure made from AluZinc/GI/powder coated CRCA sheets to prevent corrosion and rusting. The complete panel incl. HT and LT chamber with FRLS wiring and acessories shall be manufactured by approved OEM at its own mancufacturing in house facility, and same will be verified via stage/final inspection. system house integrator / channel partner products arenot accepted complete all as specified and directed
(A) 01 x Incomer Panel, each comprising of :-
(i) 11kV, 800 Amp, 26.3kA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100 with roll on floor type Vacuum Circuit Breaker having 03 Nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24V DC).
(ii) Current Transformers 11kV,200-100/5A, Core1: Class 5P10, 5VA, Core2: Class 0.5, 5VA, Core3: Class PS-X - Set of 03 Nos per breaker
(iii) Potential Transformers, Draw-out type for easy maintenance, 11kV/rt3:110V/rt3, 50VA, Cl.0.5 with associated gun-type HRC fuses and MCBs for HT/LT isolation - complete set per breaker
(iv) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT+05PT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) Directional over-current or earth-fault in any of the three phases, (b) Synchronism and Energizing Check before breaker closing to prevent un-syncronized mixing of supplies (c) circuit-breaker-failure alarm, (d) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (e) Integrted arc flash protection with current and light sensing The relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Line-Voltage, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), AC Supply Fail, PT Fuse failure relay, Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with power & frequency measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(v) Metering Equipment including:- (a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port.
(vi) LED Indications :- (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) R-Y-B, (c) DC Available LED with push-button (d) AC Supply Fail (e) Trip Circuit Healthy
(vii) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip (c) Trip Circuit Failure, (d) Inter-Tripping Fault, (e) Synchro-Check. (f) PT Fuse Failure The Annunciator will be complete with required Acknowledge/Test buttons as required
(viii) Control Equipment incl. :- (a) 01 x TNC Switch, (b) 01 x Local/Remote Switch, (c) 01 x Emergency Trip Push Button, (d) MCBs for AC (e) MCBs for DC (f) Heater Switch with Thermostat - 01no. (g) 3-pin socket with ON/OFF switch - 01no. (h) LED Lamp with ON/OFF switch - 01no.
(ix) Flush mounted Auxillary Protection Relays incl:- (a) Trip Circuit Supervision Relay, (b) Master trip Relay, (c) PT Fuse failure relay. (d) DC Supervision Scheme
(x) Suitable Disconnecting Link type terminal arrangement shall be provided for interfacing PS-Class CTs installed in the panel for achieving the required protection.
(B) 02 x Outgoing Panel, each comprising of :- (i) 11kV, 630Amp, 26.3KA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100. Vacuum Circuit Breaker having 03nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24V DC).
(ii) Current Transformers 11kV,150-75/5A, for 01 out going and 50-25/5A for 1out going , Core1: Class 5P10, 10VA, Core2: Class 0.5, 10VA - Set of 03 Nos. Per breaker
(iii) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) over-current or earth-fault in any of the three phases, (b) circuit-breaker-failure alarm,
(c) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (d) Integrted arc flash protection with current and light sensing. (e )Transformer protection (Marshalling Box and Buchhloz relay). The relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with current measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(iv) Metering Equipment including:- (a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port.
(v) LED Indications - (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) Trip Circuit Healthy
(vi) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip (c) Trip Circuit Failure, (d) Inter-Tripping Fault, The Annunciator will be complete with required Acknowledge/Test buttons as required
(vii) Control Equipment incl. (a) 01 x TNC Switch, (b) 01 x Emergency Trip Push Button, (c) 01 x Local/Remote Switch, (d) MCBs for AC/DC isolation (e) Heater Switch with Thermostat - 01no. (f) 3-pin socket with ON/OFF switch - 01no. (g) LEDLamp with ON/OFF switch - 01no.
(viii) Flush mounted Auxillary Protection Relays incl. (a) Trip Circuit Supervision Relay, (b) Master trip Relay,
(ix) Transformer protection each comprising of :- (a) Oil Temperature high. (b) Winding Temperature high. (c ) Tank oil level low. (d) OLTC oil level low. (e) Buchhloz relay trip or sudden gas and sudden oil pressure relay trip. (f) Pressure relief.
Supplying, installing, testing and commissioning of Indoor arc flash protected Draw-Out with roll on floor type Vacuum Circuit Breaker Panel , rated for 11kV, 800 Amp, 26.3kA/3-sec, comprising of 01 No. Incomer, 01 No. Bus Coupler and 05 Nos. Outgoing VCB Panels for Hazipeer Sub station under AGE(U)E/S-I and Top mounted Bus PTs /Line PTs on panel for each bus section, confirming to IEC 62271-200, Internal Arc Classified IAC AFLR – 26.3kA for 1sec, Accessibility Class LSC2B-PM Class, comprising of 800 Amp, continuous rated Copper insulated busbars and droppers in all bus / breaker/ adaptor and and cable chambers, The busbars to be covered with insulating material, The earthing busbar is made of electrolytic copper and it runs longitudinally throughout the switchgear Encapsulated feeder connections IS3427 and IS12729. with 02nos. . Rack-In-Rack-Out Handles, structure made from AluZinc/GI/powder coated CRCA sheets to prevent corrosion and rusting. The complete panel incl. HT and LT chamber with FRLS wiring and acessories shall be manufactured by approved OEM at its own mancufacturing in house facility, and same will be verified via stage/final inspection. system house integrator / channel partner products arenot accepted complete all as specified and directed
(A) 01 x Incomer Panel, each comprising of :-
(i) 11kV, 800 Amp, 26.3kA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100 with roll on floor type Vacuum Circuit Breaker having 03 Nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24V DC).
(ii) Current Transformers 11kV,300-150/5A, Core1: Class 5P10, 5VA, Core2: Class 0.5, 5VA, Core3: Class PS-X - Set of 03 Nos per breaker
(iii) Potential Transformers, Draw-out type for easy maintenance, 11kV/rt3:110V/rt3, 50VA, Cl.0.5 with associated gun-type HRC fuses and MCBs for HT/LT isolation - complete set per breaker
(iv) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT+05PT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) Directional over-current or earth-fault in any of the three phases, (b) Synchronism and Energizing Check before breaker closing to prevent un-syncronized mixing of supplies (c) circuit-breaker-failure alarm, (d) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (e) Integrted arc flash protection with current and light sensing
The relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Line-Voltage, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), AC Supply Fail, PT Fuse failure relay, Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with power & frequency measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(v) Metering Equipment including:- (a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port.
(vi) LED Indications :- (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) R-Y-B, (c) DC Available LED with push-button (d) AC Supply Fail (e) Trip Circuit Healthy
(vii) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip (c) Trip Circuit Failure, (d) Inter-Tripping Fault, (e) Synchro-Check. (f) PT Fuse Failure The Annunciator will be complete with required Acknowledge/Test buttons as required
(viii) Control Equipment incl. :- (a) 01 x TNC Switch, (b) 01 x Local/Remote Switch, (c) 01 x Emergency Trip Push Button, (d) MCBs for AC (e) MCBs for DC (f) Heater Switch with Thermostat - 01no. (g) 3-pin socket with ON/OFF switch - 01no. (h) LED Lamp with ON/OFF switch - 01no.
(ix) Flush mounted Auxillary Protection Relays incl:- (a) Trip Circuit Supervision Relay, (b) Master trip Relay, (c) PT Fuse failure relay. (d) DC Supervision Scheme
(x) Suitable Disconnecting Link type terminal arrangement shall be provided for interfacing PS-Class CTs installed in the panel for achieving the required protection.
(B) 01 x Bus Coupler Panel, each comprising of :- (i) 11kV, 800 Amp, 26.3KA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100 with roll on floor type Vacuum Circuit Breaker having 03nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24V DC).
(ii) Current Transformers 11kV, 300-150/5A Core1: Class 5P10, 5VA, Core2: Class 0.5, 5VA, Core3: Class PS-X - Set of 03 Nos per breaker
(iii) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04PT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) Synchronism and Energizing Check before bus-coupler closing to prevent un-syncronized mixing of supplies (b) circuit-breaker-failure alarm. (c) circuit-breaker-failures and interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. The relay shall be fully integrated with the feeder, internally capturing feeder statuses incl. various status, Bus-Voltage and display the same locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with power & frequency measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(iv) LED Indications - (a) Breaker ON/OFF/TRIP/Spring-Charged (b) Trip Circuit Healthy
(v) Control Equipment incl. :- (a) 01 x TNC Switch, (b) 01 x Local/Remote Switch, (c) 01 x Emergency Trip Push Button, (d) MCBs for AC (e) MCBs for DC (f) Heater Switch with Thermostat - 01 No. (g) 3-pin socket with ON/OFF switch - 01 No. (h) LED Lamp with ON/OFF switch - 01 No.
(vi) Flush mounted Auxillary Protection Relays incl. (a) Trip Circuit Supervision Relay, (b) Master trip Relay,
(vii) 08-Window Annunciator with Hooter to indicate following alarms :- (a) Trip Circuit Failure, (b) Inter-Tripping Fault, (c) Synchro-Check. (d) PT Fuse Failure The Annunciator will be complete with required Acknowledge/Test buttons as required
(C) 05 x Outgoing Panel, each comprising of :- (i) 11kV, 630Amp, 26.3KA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100. Vacuum Circuit Breaker having 03nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24V DC).
(ii) Current Transformers 11kV, 200-100/5A, for 02 outgoing and 100-50/5A for 03 outgoing Core1: Class 5P10, 10VA, Core2: Class 0.5, 10VA - Set of 03 Nos. Per breaker
(iii) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) over-current or earth-fault in any of the three phases, (b) circuit-breaker-failure alarm, (c) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (d) Integrted arc flash protection with current and light sensing.
(e )Transformer protection (Marshalling Box and Buchhloz relay). The relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with current measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(iv) Metering Equipment including:- (a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port.
(v) LED Indications - (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) Trip Circuit Healthy
(vi) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip (c) Trip Circuit Failure, (d) Inter-Tripping Fault, The Annunciator will be complete with required Acknowledge/Test buttons as required
(vii) Control Equipment incl. (a) 01 x TNC Switch, (b) 01 x Emergency Trip Push Button, (c) 01 x Local/Remote Switch, (d) MCBs for AC/DC isolation (e) Heater Switch with Thermostat - 01no. (f) 3-pin socket with ON/OFF switch - 01no. (g) LEDLamp with ON/OFF switch - 01no.
(viii) Flush mounted Auxillary Protection Relays incl. (a) Trip Circuit Supervision Relay, (b) Master trip Relay,
(ix) Transformer protection each comprising of :- (a) Oil Temperature high. (b) Winding Temperature high. (c ) Tank oil level low. (d) OLTC oil level low. (e) Buchhloz relay trip or sudden gas and sudden oil pressure relay trip. (f) Pressure relief.
Supplying, installing, testing and commissioning of Indoor arc flash protected Draw-Out with roll on floor type Vacuum Circuit Breaker Panel , rated for 11kV, 800 Amp, 26.3kA/3-sec, comprising of 01 No. Incomer, and 04 Nos. Outgoing VCB Panels for 2 GarhwalSub station under AGE(U)E/S-I and Top mounted Bus PTs /Line PTs on panel for each bus section, confirming to IEC 62271-200, Internal Arc Classified IAC AFLR – 26.3kA for 1sec, Accessibility Class LSC2B-PM Class, comprising of 800 Amp, continuous rated Copper insulated busbars and droppers in all bus / breaker/ adaptor and and cable chambers, The busbars to be covered with insulating material, The earthing busbar is made of electrolytic copper and it runs longitudinally throughout the switchgear Encapsulated feeder connections IS3427 and IS12729. with 02nos. . Rack-In-Rack-Out Handles, structure made from AluZinc/GI/powder coated CRCA sheets to prevent corrosion and rusting. The complete panel incl. HT and LT chamber with FRLS wiring and acessories shall be manufactured by approved OEM at its own mancufacturing in house facility, and same will be verified via stage/final inspection. system house integrator / channel partner products arenot accepted complete all as specified and directed
(A) 01 x Incomer Panel, each comprising of :-
(i) 11kV, 800 Amp, 26.3kA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100 with roll on floor type Vacuum Circuit Breaker having 03 Nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24V DC).
(ii) Current Transformers 11kV,200-100/5A, Core1: Class 5P10, 5VA, Core2: Class 0.5, 5VA, Core3: Class PS-X - Set of 03 Nos per breaker
(iii) Potential Transformers, Draw-out type for easy maintenance, 11kV/rt3:110V/rt3, 50VA, Cl.0.5 with associated gun-type HRC fuses and MCBs for HT/LT isolation - complete set per breaker
(iv) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT+05PT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) Directional over-current or earth-fault in any of the three phases, (b) Synchronism and Energizing Check before breaker closing to prevent un-syncronized mixing of supplies (c) circuit-breaker-failure alarm, (d) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (e) Integrted arc flash protection with current and light sensing The relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Line-Voltage, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), AC Supply Fail, PT Fuse failure relay, Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with power & frequency measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(v) Metering Equipment including:- (a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port.
(vi) LED Indications :- (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) R-Y-B, (c) DC Available LED with push-button (d) AC Supply Fail (e) Trip Circuit Healthy
(vii) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip (c) Trip Circuit Failure, (d) Inter-Tripping Fault, (e) Synchro-Check. (f) PT Fuse Failure The Annunciator will be complete with required Acknowledge/Test buttons as required
(viii) Control Equipment incl. :- (a) 01 x TNC Switch, (b) 01 x Local/Remote Switch, (c) 01 x Emergency Trip Push Button, (d) MCBs for AC (e) MCBs for DC (f) Heater Switch with Thermostat - 01no. (g) 3-pin socket with ON/OFF switch - 01no. (h) LED Lamp with ON/OFF switch - 01no.
(ix) Flush mounted Auxillary Protection Relays incl:- (a) Trip Circuit Supervision Relay, (b) Master trip Relay, (c) PT Fuse failure relay. (d) DC Supervision Scheme
(x) Suitable Disconnecting Link type terminal arrangement shall be provided for interfacing PS-Class CTs installed in the panel for achieving the required protection.
(B) 04 x Outgoing Panel, each comprising of :- (i) 11kV, 630Amp, 26.3KA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100. Vacuum Circuit Breaker having 03nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24V DC).
(ii) Current Transformers 11kV, 100-50/5A, for 04 outgoing Core1: Class 5P10, 10VA, Core2: Class 0.5, 10VA - Set of 03 Nos. Per breaker
(iii) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) over-current or earth-fault in any of the three phases, (b) circuit-breaker-failure alarm, (c) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol.
(d) Integrted arc flash protection with current and light sensing. (e )Transformer protection (Marshalling Box and Buchhloz relay). The relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with current measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(iv) Metering Equipment including:- (a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port.
(v) LED Indications - (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) Trip Circuit Healthy
(vi) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip (c) Trip Circuit Failure, (d) Inter-Tripping Fault, The Annunciator will be complete with required Acknowledge/Test buttons as required
(vii) Control Equipment incl. (a) 01 x TNC Switch, (b) 01 x Emergency Trip Push Button, (c) 01 x Local/Remote Switch, (d) MCBs for AC/DC isolation (e) Heater Switch with Thermostat - 01no. (f) 3-pin socket with ON/OFF switch - 01no. (g) LEDLamp with ON/OFF switch - 01no.
(viii) Flush mounted Auxillary Protection Relays incl. (a) Trip Circuit Supervision Relay, (b) Master trip Relay,
(ix) Transformer protection each comprising of :- (a) Oil Temperature high. (b) Winding Temperature high. (c) Tank oil level low. (d) OLTC oil level low. (e) Buchhloz relay trip or sudden gas and sudden oil pressure relay trip. (f) Pressure relief.
Supplying, installing, testing and commissioning of Indoor arc flash protected Draw-Out with roll on floor type Vacuum Circuit Breaker Panel , rated for 11kV, 800 Amp, 26.3kA/3-sec, comprising of 03 No. Incomer, 02 No. Bus Coupler and 07 Nos. Outgoing VCB Panels for Main Yard / Link House Sub station under AGE(U)E/S-II and Top mounted Bus PTs /Line PTs on panel for each bus section, confirming to IEC 62271-200, Internal Arc Classified IAC AFLR – 26.3kA for 1sec, Accessibility Class LSC2B-PM Class, comprising of 800 Amp, continuous rated Copper insulated busbars and droppers in all bus / breaker/ adaptor and and cable chambers, The busbars to be covered with insulating material, The earthing busbar is made of electrolytic copper and it runs longitudinally throughout the switchgear Encapsulated feeder connections IS3427 and IS12729. with 02nos. . Rack-In-Rack-Out Handles, structure made from AluZinc/GI/powder coated CRCA sheets to prevent corrosion and rusting. The complete panel incl. HT and LT chamber with FRLS wiring and acessories shall be manufactured by approved OEM at its own mancufacturing in house facility, and same will be verified via stage/final inspection. system house integrator / channel partner products arenot accepted complete all as specified and directed
(A) 03 x Incomer Panel, each comprising of :-
(i) 11kV, 800 Amp, 26.3kA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100 with roll on floor type Vacuum Circuit Breaker having 03 Nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24V DC).
(ii) Current Transformers 11kV,300-150/5A, Core1: Class 5P10, 5VA, Core2: Class 0.5, 5VA, Core3: Class PS-X - Set of 03 Nos per breaker
(iii) Potential Transformers, Draw-out type for easy maintenance, 11kV/rt3:110V/rt3, 50VA, Cl.0.5 with associated gun-type HRC fuses and MCBs for HT/LT isolation - complete set per breaker
(iv) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT+05PT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) Directional over-current or earth-fault in any of the three phases, (b) Synchronism and Energizing Check before breaker closing to prevent un-syncronized mixing of supplies (c) circuit-breaker-failure alarm
, (d) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (e) Integrted arc flash protection with current and light sensing The relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Line-Voltage, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), AC Supply Fail, PT Fuse failure relay, Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with power & frequency measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(v) Metering Equipment including:- (a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port.
(vi) LED Indications :- (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) R-Y-B, (c) DC Available LED with push-button (d) AC Supply Fail (e) Trip Circuit Healthy
(vii) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip (c) Trip Circuit Failure, (d) Inter-Tripping Fault, (e) Synchro-Check. (f) PT Fuse Failure The Annunciator will be complete with required Acknowledge/Test buttons as required
(viii) Control Equipment incl. :- (a) 01 x TNC Switch, (b) 01 x Local/Remote Switch, (c) 01 x Emergency Trip Push Button, (d) MCBs for AC (e) MCBs for DC (f) Heater Switch with Thermostat - 01no. (g) 3-pin socket with ON/OFF switch - 01no. (h) LED Lamp with ON/OFF switch - 01no.
(ix) Flush mounted Auxillary Protection Relays incl:- (a) Trip Circuit Supervision Relay, (b) Master trip Relay, (c) PT Fuse failure relay. (d) DC Supervision Scheme
(x) Suitable Disconnecting Link type terminal arrangement shall be provided for interfacing PS-Class CTs installed in the panel for achieving the required protection.
(B) 02 x Bus Coupler Panel, each comprising of :- (i) 11kV, 800 Amp, 26.3KA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100 with roll on floor type Vacuum Circuit Breaker having 03nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24V DC).
(ii) Current Transformers 11kV,300-150/5A Core1: Class 5P10, 5VA, Core2: Class 0.5, 5VA, Core3: Class PS-X - Set of 03 Nos per breaker
(iii) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04PT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) Synchronism and Energizing Check before bus-coupler closing to prevent un-syncronized mixing of supplies (b) circuit-breaker-failure alarm. (c) circuit-breaker-failures and interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. The relay shall be fully integrated with the feeder, internally capturing feeder statuses incl. various status, Bus-Voltage and display the same locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with power & frequency measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(iv) LED Indications - (a) Breaker ON/OFF/TRIP/Spring-Charged (b) Trip Circuit Healthy
(v) Control Equipment incl. :- (a) 01 x TNC Switch, (b) 01 x Local/Remote Switch, (c) 01 x Emergency Trip Push Button, (d) MCBs for AC (e) MCBs for DC (f) Heater Switch with Thermostat - 01 No. (g) 3-pin socket with ON/OFF switch - 01 No. (h) LED Lamp with ON/OFF switch - 01 No.
(vi) Flush mounted Auxillary Protection Relays incl. (a) Trip Circuit Supervision Relay, (b) Master trip Relay,
(vii) 08-Window Annunciator with Hooter to indicate following alarms :- (a) Trip Circuit Failure, (b) Inter-Tripping Fault, (c) Synchro-Check. (d) PT Fuse Failure The Annunciator will be complete with required Acknowledge/Test buttons as required
(C) 07 x Outgoing Panel, each comprising of :- (i) 11kV, 630Amp, 26.3KA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100. Vacuum Circuit Breaker having 03nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24V DC).
(ii) Current Transformers 11kV, 150-75/5A, for 03 outgoing and 50-25/5A for 04 no outgoing Core1: Class 5P10, 10VA, Core2: Class 0.5, 10VA - Set of 03 Nos. Per breaker
(iii) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) over-current or earth-fault in any of the three phases, (b) circuit-breaker-failure alarm, (c) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (d) Integrted arc flash protection with current and light sensing. (e )Transformer protection (Marshalling Box and Buchhloz relay). The relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with current measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(iv) Metering Equipment including:- (a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port.
(v) LED Indications - (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) Trip Circuit Healthy
(vi) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip (c) Trip Circuit Failure, (d) Inter-Tripping Fault, The Annunciator will be complete with required Acknowledge/Test buttons as required
(vii) Control Equipment incl. (a) 01 x TNC Switch, (b) 01 x Emergency Trip Push Button, (c) 01 x Local/Remote Switch, (d) MCBs for AC/DC isolation (e) Heater Switch with Thermostat - 01no. (f) 3-pin socket with ON/OFF switch - 01no. (g) LEDLamp with ON/OFF switch - 01no.
(viii) Flush mounted Auxillary Protection Relays incl. (a) Trip Circuit Supervision Relay, (b) Master trip Relay,
(ix) Transformer protection each comprising of :- (a) Oil Temperature high. (b) Winding Temperature high. (c ) Tank oil level low. (d) OLTC oil level low. (e) Buchhloz relay trip or sudden gas and sudden oil pressure relay trip. (f) Pressure relief.
Supplying, installing, testing and commissioning of Indoor arc flash protected Draw-Out with roll on floor type Vacuum Circuit Breaker Panel , rated for 11kV, 800 Amp, 26.3kA/3-sec, comprising of 02 No. Incomer, 01 No. Bus Coupler and 06 Nos. Outgoing VCB Panels for Church Road Sub station under AGE(U)E/S-II and Top mounted Bus PTs /Line PTs on panel for each bus section, confirming to IEC 62271-200, Internal Arc Classified IAC AFLR – 26.3kA for 1sec, Accessibility Class LSC2B-PM Class, comprising of 800 Amp, continuous rated Copper insulated busbars and droppers in all bus / breaker/ adaptor and and cable chambers, The busbars to be covered with insulating material, The earthing busbar is made of electrolytic copper and it runs longitudinally throughout the switchgear Encapsulated feeder connections IS3427 and IS12729. with 02nos. . Rack-In-Rack-Out Handles, structure made from AluZinc/GI/powder coated CRCA sheets to prevent corrosion and rusting. The complete panel incl. HT and LT chamber with FRLS wiring and acessories shall be manufactured by approved OEM at its own mancufacturing in house facility, and same will be verified via stage/final inspection. system house integrator / channel partner products arenot accepted complete all as specified and directed
(A) 02 x Incomer Panel, each comprising of :-
(i) 11kV, 800 Amp, 26.3kA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100 with roll on floor type Vacuum Circuit Breaker having 03 Nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24V DC).
(ii) Current Transformers 11kV,300-150/5A, Core1: Class 5P10, 5VA, Core2: Class 0.5, 5VA, Core3: Class PS-X - Set of 03 Nos per breaker
(iii) Potential Transformers, Draw-out type for easy maintenance, 11kV/rt3:110V/rt3, 50VA, Cl.0.5 with associated gun-type HRC fuses and MCBs for HT/LT isolation - complete set per breaker
(iv) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT+05PT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) Directional over-current or earth-fault in any of the three phases, (b) Synchronism and Energizing Check before breaker closing to prevent un-syncronized mixing of supplies (c) circuit-breaker-failure alarm, (d) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (e) Integrted arc flash protection with current and light sensing The relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Line-Voltage, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), AC Supply Fail, PT Fuse failure relay, Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with power & frequency measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(v) Metering Equipment including:- (a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port.
(vi) LED Indications :- (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) R-Y-B, (c) DC Available LED with push-button (d) AC Supply Fail (e) Trip Circuit Healthy
(vii) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip (c) Trip Circuit Failure, (d) Inter-Tripping Fault, (e) Synchro-Check. (f) PT Fuse Failure The Annunciator will be complete with required Acknowledge/Test buttons as required
(viii) Control Equipment incl. :- (a) 01 x TNC Switch, (b) 01 x Local/Remote Switch, (c) 01 x Emergency Trip Push Button, (d) MCBs for AC (e) MCBs for DC (f) Heater Switch with Thermostat - 01no. (g) 3-pin socket with ON/OFF switch - 01no. (h) LED Lamp with ON/OFF switch - 01no.
(ix) Flush mounted Auxillary Protection Relays incl:- (a) Trip Circuit Supervision Relay, (b) Master trip Relay, (c) PT Fuse failure relay. (d) DC Supervision Scheme
(x) Suitable Disconnecting Link type terminal arrangement shall be provided for interfacing PS-Class CTs installed in the panel for achieving the required protection.
(B) 01 x Bus Coupler Panel, each comprising of :- (i) 11kV, 800 Amp, 26.3KA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100 with roll on floor type Vacuum Circuit Breaker having 03nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24V DC).
(ii) Current Transformers 11kV,300-150/5A Core1: Class 5P10, 5VA, Core2: Class 0.5, 5VA, Core3: Class PS-X - Set of 03 Nos per breaker
(iii) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04PT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) Synchronism and Energizing Check before bus-coupler closing to prevent un-syncronized mixing of supplies (b) circuit-breaker-failure alarm. (c) circuit-breaker-failures and interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. The relay shall be fully integrated with the feeder, internally capturing feeder statuses incl. various status, Bus-Voltage and display the same locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with power & frequency measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(iv) LED Indications - (a) Breaker ON/OFF/TRIP/Spring-Charged (b) Trip Circuit Healthy
(v) Control Equipment incl. :- (a) 01 x TNC Switch, (b) 01 x Local/Remote Switch, (c) 01 x Emergency Trip Push Button, (d) MCBs for AC (e) MCBs for DC (f) Heater Switch with Thermostat - 01 No. (g) 3-pin socket with ON/OFF switch - 01 No. (h) LED Lamp with ON/OFF switch - 01 No.
(vi) Flush mounted Auxillary Protection Relays incl. (a) Trip Circuit Supervision Relay, (b) Master trip Relay,
(vii) 08-Window Annunciator with Hooter to indicate following alarms :- (a) Trip Circuit Failure, (b) Inter-Tripping Fault, (c) Synchro-Check. (d) PT Fuse Failure The Annunciator will be complete with required Acknowledge/Test buttons as required
(C) 06 x Outgoing Panel, each comprising of :- (i) 11kV, 630Amp, 26.3KA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100. Vacuum Circuit Breaker having 03nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24V DC).
(ii) Current Transformers 11kV, 150-75/5A, for 02 outgoing and 50-25/5A for 04 no outgoing Core1: Class 5P10, 10VA, Core2: Class 0.5, 10VA - Set of 03 Nos. Per breaker
(iii) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) over-current or earth-fault in any of the three phases, (b) circuit-breaker-failure alarm, (c) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (d) Integrted arc flash protection with current and light sensing.
(e )Tranformer protection (Marshalling Box and Buchhloz relay). The relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with current measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(iv) Metering Equipment including:- (a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port.
(v) LED Indications - (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) Trip Circuit Healthy
(vi) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip (c) Trip Circuit Failure, (d) Inter-Tripping Fault, The Annunciator will be complete with required Acknowledge/Test buttons as required
(vii) Control Equipment incl. (a) 01 x TNC Switch, (b) 01 x Emergency Trip Push Button, (c) 01 x Local/Remote Switch, (d) MCBs for AC/DC isolation (e) Heater Switch with Thermostat - 01no. (f) 3-pin socket with ON/OFF switch - 01no. (g) LEDLamp with ON/OFF switch - 01no.
(viii) Flush mounted Auxillary Protection Relays incl. (a) Trip Circuit Supervision Relay, (b) Master trip Relay,
(ix) Transformer protection each comprising of :- (a) Oil Temperature high. (b) Winding Temperature high. (c ) Tank oil level low. (d) OLTC oil level low. (e) Buchhloz relay trip or sudden gas and sudden oil pressure relay trip. (f) Pressure relief.
Supplying, installing, testing and commissioning of Indoor arc flash protected Draw-Out with roll on floor type Vacuum Circuit Breaker Panel , rated for 11kV, 800 Amp, 26.3kA/3-sec, comprising of 02 No. Incomer, 01 No. Bus Coupler and 09 Nos. Outgoing VCB Panels for Cassel Road Sub station under AGE(U)E/S-II and Top mounted Bus PTs /Line PTs on panel for each bus section, confirming to IEC 62271-200, Internal Arc Classified IAC AFLR – 26.3kA for 1sec, Accessibility Class LSC2B-PM Class, comprising of 800 Amp, continuous rated Copper insulated busbars and droppers in all bus / breaker/ adaptor and and cable chambers, The busbars to be covered with insulating material, The earthing busbar is made of electrolytic copper and it runs longitudinally throughout the switchgear Encapsulated feeder connections IS3427 and IS12729. with 02nos. . Rack-In-Rack-Out Handles, structure made from AluZinc/GI/powder coated CRCA sheets to prevent corrosion and rusting. The complete panel incl. HT and LT chamber with FRLS wiring and acessories shall be manufactured by approved OEM at its own mancufacturing in house facility, and same will be verified via stage/final inspection. system house integrator / channel partner products arenot accepted complete all as specified and directed
(A) 02 x Incomer Panel, each comprising of :-
(i) 11kV, 800 Amp, 26.3kA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100 with roll on floor type Vacuum Circuit Breaker having 03 Nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24V DC).
(ii) Current Transformers 11kV,300-150/5A, Core1: Class 5P10, 5VA, Core2: Class 0.5, 5VA, Core3: Class PS-X - Set of 03 Nos per breaker
(iii) Potential Transformers, Draw-out type for easy maintenance, 11kV/rt3:110V/rt3, 50VA, Cl.0.5 with associated gun-type HRC fuses and MCBs for HT/LT isolation - complete set per breaker
(iv) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT+05PT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) Directional over-current or earth-fault in any of the three phases, (b) Synchronism and Energizing Check before breaker closing to prevent un-syncronized mixing of supplies (c) circuit-breaker-failure alarm,
(d) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (e) Integrted arc flash protection with current and light sensing The relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Line-Voltage, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), AC Supply Fail, PT Fuse failure relay, Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with power & frequency measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(v) Metering Equipment including:- (a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port.
(vi) LED Indications :- (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) R-Y-B, (c) DC Available LED with push-button (d) AC Supply Fail (e) Trip Circuit Healthy
(vii) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip (c) Trip Circuit Failure, (d) Inter-Tripping Fault, (e) Synchro-Check. (f) PT Fuse Failure The Annunciator will be complete with required Acknowledge/Test buttons as required
(viii) Control Equipment incl. :- (a) 01 x TNC Switch, (b) 01 x Local/Remote Switch, (c) 01 x Emergency Trip Push Button, (d) MCBs for AC (e) MCBs for DC (f) Heater Switch with Thermostat - 01no. (g) 3-pin socket with ON/OFF switch - 01no. (h) LED Lamp with ON/OFF switch - 01no.
(ix) Flush mounted Auxillary Protection Relays incl:- (a) Trip Circuit Supervision Relay, (b) Master trip Relay, (c) PT Fuse failure relay. (d) DC Supervision Scheme
(x) Suitable Disconnecting Link type terminal arrangement shall be provided for interfacing PS-Class CTs installed in the panel for achieving the required protection.
(B) 01 x Bus Coupler Panel, each comprising of :- (i) 11kV, 800 Amp, 26.3KA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100 with roll on floor type Vacuum Circuit Breaker having 03nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24V DC).
(ii) Current Transformers 11kV,300-150/5A Core1: Class 5P10, 5VA, Core2: Class 0.5, 5VA, Core3: Class PS-X - Set of 03 Nos per breaker
(iii) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04PT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) Synchronism and Energizing Check before bus-coupler closing to prevent un-syncronized mixing of supplies (b) circuit-breaker-failure alarm. (c) circuit-breaker-failures and interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. The relay shall be fully integrated with the feeder, internally capturing feeder statuses incl. various status, Bus-Voltage and display the same locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with power & frequency measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(iv) LED Indications - (a) Breaker ON/OFF/TRIP/Spring-Charged (b) Trip Circuit Healthy
(v) Control Equipment incl. :- (a) 01 x TNC Switch, (b) 01 x Local/Remote Switch, (c) 01 x Emergency Trip Push Button, (d) MCBs for AC (e) MCBs for DC (f) Heater Switch with Thermostat - 01 No. (g) 3-pin socket with ON/OFF switch - 01 No. (h) LED Lamp with ON/OFF switch - 01 No.
(vi) Flush mounted Auxillary Protection Relays incl. (a) Trip Circuit Supervision Relay, (b) Master trip Relay,
(vii) 08-Window Annunciator with Hooter to indicate following alarms :- (a) Trip Circuit Failure, (b) Inter-Tripping Fault, (c) Synchro-Check. (d) PT Fuse Failure The Annunciator will be complete with required Acknowledge/Test buttons as required
(C) 09 x Outgoing Panel, each comprising of :- (i) 11kV, 630Amp, 26.3KA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100. Vacuum Circuit Breaker having 03nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24V DC).
(ii) Current Transformers 11kV, 200-100/5A, for 04 outgoing ,100-50/5A, for 02 outgoing and 50-25/5A for 03 no outgoing Core1: Class 5P10, 10VA, Core2: Class 0.5, 10VA - Set of 03 Nos. Per breaker
(iii) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) over-current or earth-fault in any of the three phases, (b) circuit-breaker-failure alarm, (c) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (d) Integrted arc flash protection with current and light sensing. (e )Transformer protection (Marshalling Box and Buchhloz relay).
The relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with current measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(iv) Metering Equipment including:- (a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port.
(v) LED Indications - (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) Trip Circuit Healthy
(vi) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip (c) Trip Circuit Failure, (d) Inter-Tripping Fault, The Annunciator will be complete with required Acknowledge/Test buttons as required
(vii) Control Equipment incl. (a) 01 x TNC Switch, (b) 01 x Emergency Trip Push Button, (c) 01 x Local/Remote Switch, (d) MCBs for AC/DC isolation (e) Heater Switch with Thermostat - 01no. (f) 3-pin socket with ON/OFF switch - 01no. (g) LEDLamp with ON/OFF switch - 01no.
(viii) Flush mounted Auxillary Protection Relays incl. (a) Trip Circuit Supervision Relay, (b) Master trip Relay,
(ix) Transformer protection each comprising of :- (a) Oil Temperature high. (b) Winding Temperature high. (c ) Tank oil level low. (d) OLTC oil level low. (e) Buchhloz relay trip or sudden gas and sudden oil pressure relay trip. (f) Pressure relief.
Supplying, installing, testing and commissioning of Indoor arc flash protected Draw-Out with roll on floor type Vacuum Circuit Breaker Panel , rated for 11kV, 800 Amp, 26.3kA/3-sec, comprising of 01 No. Incomer, and 04 Nos. Outgoing VCB Panels at Parade Ground substation under AGE(U) II and Top mounted Bus PTs /Line PTs on panel for each bus section, confirming to IEC 62271-200, Internal Arc Classified IAC AFLR – 26.3kA for 1sec, Accessibility Class LSC2B-PM Class, comprising of 800 Amp, continuous rated Copper insulated busbars and droppers in all bus / breaker/ adaptor and cable chambers, Encapsulated feeder connections IS3427 and IS1272902 nos. Rack-In-Rack-Out Handles, structure made from AluZinc/GI/powder coated CRCA sheets to prevent corrosion and rusting.The complete panel incl. HT and LT chamber with FRLS wiring and acessories shall be manufactured by approved OEM at its own mancufacturing in house facility, and same will be verified via stage/final inspection. system house integrator / channel partner products arenot accepted complete all as specified and directed
(A) 01 x Incomer Panel, each comprising of :-
(i) 11kV, 800 Amp, 26.3kA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100 with roll on floor type Vacuum Circuit Breaker having 03 Nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24VDC).
(ii) Current Transformers 11kV, 300-150/5A Core1: Class 5P10, 5VA, Core2: Class 0.5, 5VA, Remote HMI, Digital electronic governor with temperture coCore3: Class PS-X - Set of 03 No per breaker
(iii) Potential Transformers, Draw-out type for easy maintenance, 11kV/rt3:110V/rt3, 50VA, Cl.0.5 with associated gun-type HRC fuses and MCBs for HT/LT isolation - complete set per breaker
(iv) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT+05PT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) Directional over-current or earth-fault in any of the three phases, (b) Synchronism and Energizing Check before breaker closing to prevent un-syncronized mixing of supplies (c) circuit-breaker-failure alarm, (d) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (e) Integrted arc flash protection with current and light sensing The relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Line-Voltage, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), AC Supply Fail, PT Fuse failure relay, Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with power & frequency measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(v) Metering Equipment including:- (a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port.
(vi) LED Indications :- (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) R-Y-B, (c) DC Available LED with push-button (d) AC Supply Fail (e) Trip Circuit Healthy
(vii) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip (c) Trip Circuit Failure, (d) Inter-Tripping Fault, (e) Synchro-Check. (f) PT Fuse Failure The Annunciator will be complete with required Acknowledge/Test buttons as required
(viii) Control Equipment incl. :- (a) 01 x TNC Switch, (b) 01 x Local/Remote Switch, (c) 01 x Emergency Trip Push Button, (d) MCBs for AC
(e) MCBs for DC (f) Heater Switch with Thermostat - 01no. (g) 3-pin socket with ON/OFF switch - 01no. (h) LED Lamp with ON/OFF switch - 01no.
(ix) Flush mounted Auxillary Protection Relays incl:- (a) Trip Circuit Supervision Relay, (b) Master trip Relay, (c) PT Fuse failure relay. (d) DC Supervision Scheme
(x) Suitable Disconnecting Link type terminal arrangement shall be provided for interfacing PS-Class CTs installed in the panel for achieving the required protection.
(B) 04 x Outgoing Panel, each comprising of :- (i) 11kV, 630Amp, 26.3KA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100. Vacuum Circuit Breaker having 03nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24VDC).
(ii) Current Transformers 11kV, 200-100/5A, for 1 breakers and 50-25/5A for 3 breakers Core1: Class 5P10, 10VA, Core2: Class 0.5, 10VA - Set of 03 Nos.each/ breaker
(iii) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) over-current or earth-fault in any of the three phases, (b) circuit-breaker-failure alarm,
(c) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (d) Integrted arc flash protection with current and light sensing. (e )Transformer protection (Marshalling Box and Buchhloz relay). The relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with current measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(iv) Metering Equipment including:- (a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port.
(v) LED Indications - (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) Trip Circuit Healthy
(vi) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip (c) Trip Circuit Failure, (d) Inter-Tripping Fault, The Annunciator will be complete with required Acknowledge/Test buttons as required
(vii) Control Equipment incl. (a) 01 x TNC Switch, (b) 01 x Emergency Trip Push Button, (c) 01 x Local/Remote Switch, (d) MCBs for AC/DC isolation (e) Heater Switch with Thermostat - 01no. (f) 3-pin socket with ON/OFF switch - 01no. (g) LEDLamp with ON/OFF switch - 01no.
(viii) Flush mounted Auxillary Protection Relays incl. (a) Trip Circuit Supervision Relay, (b) Master trip Relay,
(ix) Transformer protection each comprising of :- (a) Oil Temperature high. (b) Winding Temperature high. (c) Tank oil level low. (d) OLTC oil level low. (e) Buchhloz relay trip or sudden gas and sudden oil pressure relay trip. (f) Pressure relief.
Supplying, installing, testing and commissioning of Indoor arc flash protected Draw-Out with roll on floor type Vacuum Circuit Breaker Panel , rated for 11kV, 800 Amp, 26.3kA/3-sec, comprising of 01 No. Incomer, 01 No. Bus Coupler and 04 Nos. Outgoing VCB Panels for Main Shankar VIhar (LH wing) Sub station under AGE(U)E/S-III and Top mounted Bus PTs /Line PTs on panel for each bus section, confirming to IEC 62271-200, Internal Arc Classified IAC AFLR – 26.3kA for 1sec, Accessibility Class LSC2B-PM Class, comprising of 800 Amp, continuous rated Copper insulated busbars and droppers in all bus / breaker/ adaptor and and cable chambers, The busbars to be covered with insulating material, The earthing busbar is made of electrolytic copper and it runs longitudinally throughout the switchgear Encapsulated feeder connections IS3427 and IS12729. with 02nos. . Rack-In-Rack-Out Handles, structure made from AluZinc/GI/powder coated CRCA sheets to prevent corrosion and rusting. The complete panel incl. HT and LT chamber with FRLS wiring and acessories shall be manufactured by approved OEM at its own mancufacturing in house facility, and same will be verified via stage/final inspection. system house integrator / channel partner products arenot accepted .complete all as specified and directed Note: These HT pannels shall be clubbed in between with the existing / fixed with the existing VCB and Bus Copupler
(A) 01 x Incomer Panel, each comprising of :-
(i) 11kV, 800 Amp, 26.3kA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100 with roll on floor type Vacuum Circuit Breaker having 03 Nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24V DC).
(ii) Current Transformers 11kV,400-200/5A, Core1: Class 5P10, 5VA, Core2: Class 0.5, 5VA, Core3: Class PS-X - Set of 03 Nos per breaker
(iii) Potential Transformers, Draw-out type for easy maintenance, 11kV/rt3:110V/rt3, 50VA, Cl.0.5 with associated gun-type HRC fuses and MCBs for HT/LT isolation - complete set per breaker
(iv) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT+05PT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) Directional over-current or earth-fault in any of the three phases, (b) Synchronism and Energizing Check before breaker closing to prevent un-syncronized mixing of supplies (c) circuit-breaker-failure alarm, (d) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (e) Integrted arc flash protection with current and light sensing
The relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Line-Voltage, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), AC Supply Fail, PT Fuse failure relay, Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with power & frequency measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(v) Metering Equipment including:- (a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port.
(vi) LED Indications :- (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) R-Y-B, (c) DC Available LED with push-button (d) AC Supply Fail (e) Trip Circuit Healthy
(vii) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip (c) Trip Circuit Failure, (d) Inter-Tripping Fault, (e) Synchro-Check. (f) PT Fuse Failure The Annunciator will be complete with required Acknowledge/Test buttons as required
(viii) Control Equipment incl. :- (a) 01 x TNC Switch, (b) 01 x Local/Remote Switch, (c) 01 x Emergency Trip Push Button, (d) MCBs for AC (e) MCBs for DC (f) Heater Switch with Thermostat - 01no. (g) 3-pin socket with ON/OFF switch - 01no. (h) LED Lamp with ON/OFF switch - 01no.
(ix) Flush mounted Auxillary Protection Relays incl:- (a) Trip Circuit Supervision Relay, (b) Master trip Relay, (c) PT Fuse failure relay. (d) DC Supervision Scheme
(x) Suitable Disconnecting Link type terminal arrangement shall be provided for interfacing PS-Class CTs installed in the panel for achieving the required protection.
(B) 01 x Bus Coupler Panel, each comprising of :- (i) 11kV, 800 Amp, 26.3KA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100 with roll on floor type Vacuum Circuit Breaker having 03nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24V DC).
(ii) Current Transformers 11kV,400-200/5A Core1: Class 5P10, 5VA, Core2: Class 0.5, 5VA, Core3: Class PS-X - Set of 03 Nos per breaker
(iii) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04PT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) Synchronism and Energizing Check before bus-coupler closing to prevent un-syncronized mixing of supplies (b) circuit-breaker-failure alarm. (c) circuit-breaker-failures and interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. The relay shall be fully integrated with the feeder, internally capturing feeder statuses incl. various status, Bus-Voltage and display the same locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with power & frequency measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(iv) LED Indications - (a) Breaker ON/OFF/TRIP/Spring-Charged (b) Trip Circuit Healthy
(v) Control Equipment incl. :- (a) 01 x TNC Switch, (b) 01 x Local/Remote Switch, (c) 01 x Emergency Trip Push Button, (d) MCBs for AC (e) MCBs for DC (f) Heater Switch with Thermostat - 01 No. (g) 3-pin socket with ON/OFF switch - 01 No. (h) LED Lamp with ON/OFF switch - 01 No.
(vi) Flush mounted Auxillary Protection Relays incl. (a) Trip Circuit Supervision Relay, (b) Master trip Relay,
(vii) 08-Window Annunciator with Hooter to indicate following alarms :- (a) Trip Circuit Failure, (b) Inter-Tripping Fault, (c) Synchro-Check. (d) PT Fuse Failure The Annunciator will be complete with required Acknowledge/Test buttons as required
(C) 04 x Outgoing Panel, each comprising of :- (i) 11kV, 630Amp, 26.3KA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100. Vacuum Circuit Breaker having 03nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24V DC).
(ii) Current Transformers 11kV, 150-75/5A, for 02 outgoing and 200-100/5A for 02 no outgoing Core1: Class 5P10, 10VA, Core2: Class 0.5, 10VA - Set of 03 Nos. Per breaker
(iii) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) over-current or earth-fault in any of the three phases, (b) circuit-breaker-failure alarm, (c) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (d) Integrted arc flash protection with current and light sensing. (e )Transformer protection (Marshalling Box and Buchhloz relay).
The relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with current measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(iv) Metering Equipment including:- (a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port.
(v) LED Indications - (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) Trip Circuit Healthy
(vi) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip (c) Trip Circuit Failure, (d) Inter-Tripping Fault, The Annunciator will be complete with required Acknowledge/Test buttons as required
(vii) Control Equipment incl. (a) 01 x TNC Switch, (b) 01 x Emergency Trip Push Button, (c) 01 x Local/Remote Switch, (d) MCBs for AC/DC isolation (e) Heater Switch with Thermostat - 01no. (f) 3-pin socket with ON/OFF switch - 01no. (g) LEDLamp with ON/OFF switch - 01no.
(viii) Flush mounted Auxillary Protection Relays incl. (a) Trip Circuit Supervision Relay, (b) Master trip Relay,
(ix) Transformer protection each comprising of :- (a) Oil Temperature high. (b) Winding Temperature high. (c ) Tank oil level low. (d) OLTC oil level low. (e) Buchhloz relay trip or sudden gas and sudden oil pressure relay trip. (f) Pressure relief.
Supplying, installing, testing and commissioning of Indoor arc flash protected Draw-Out with roll on floor type Vacuum Circuit Breaker Panel , rated for 11kV, 800 Amp, 26.3kA/3-sec, comprising of 01 No. Incomer, and 04Nos. Outgoing VCB Panels for Main Shankar VIhar (RH wing) Sub station under AGE(U)E/S-III and Top mounted Bus PTs /Line PTs on panel for each bus section, confirming to IEC 62271-200, Internal Arc Classified IAC AFLR – 26.3kA for 1sec, Accessibility Class LSC2B-PM Class, comprising of 800 Amp, continuous rated Copper insulated busbars and droppers in all bus / breaker/ adaptor and and cable chambers, The busbars to be covered with insulating material, The earthing busbar is made of electrolytic copper and it runs longitudinally throughout the switchgear Encapsulated feeder connections IS3427 and IS12729. with 02nos. . Rack-In-Rack-Out Handles, structure made from AluZinc/GI/powder coated CRCA sheets to prevent corrosion and rusting. The complete panel incl. HT and LT chamber with FRLS wiring and acessories shall be manufactured by approved OEM at its own mancufacturing in house facility, and same will be verified via stage/final inspection. system house integrator / channel partner products arenot accepted complete all as specified and directed Note: These HT pannels shall be clubbed in between with the existing / fixed with the existing VCB and Bus Copupler
(A) 01 x Incomer Panel, each comprising of :-
(i) 11kV, 800 Amp, 26.3kA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100 with roll on floor type Vacuum Circuit Breaker having 03 Nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24V DC).
(ii) Current Transformers 11kV,400-200/5A, Core1: Class 5P10, 5VA, Core2: Class 0.5, 5VA, Core3: Class PS-X - Set of 03 Nos per breaker
(iii) Potential Transformers, Draw-out type for easy maintenance, 11kV/rt3:110V/rt3, 50VA, Cl.0.5 with associated gun-type HRC fuses and MCBs for HT/LT isolation - complete set per breaker
(iv) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT+05PT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) Directional over-current or earth-fault in any of the three phases, (b) Synchronism and Energizing Check before breaker closing to prevent un-syncronized mixing of supplies (c) circuit-breaker-failure alarm, (d) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (e) Integrted arc flash protection with current and light sensing The relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Line-Voltage, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), AC Supply Fail, PT Fuse failure relay, Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with power & frequency measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(v) Metering Equipment including:- (a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port.
(vi) LED Indications :- (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) R-Y-B, (c) DC Available LED with push-button (d) AC Supply Fail (e) Trip Circuit Healthy
(vii) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip (c) Trip Circuit Failure, (d) Inter-Tripping Fault, (e) Synchro-Check. (f) PT Fuse Failure The Annunciator will be complete with required Acknowledge/Test buttons as required
(viii) Control Equipment incl. :- (a) 01 x TNC Switch, (b) 01 x Local/Remote Switch, (c) 01 x Emergency Trip Push Button, (d) MCBs for AC (e) MCBs for DC (f) Heater Switch with Thermostat - 01no. (g) 3-pin socket with ON/OFF switch - 01no. (h) LED Lamp with ON/OFF switch - 01no.
(ix) Flush mounted Auxillary Protection Relays incl:- (a) Trip Circuit Supervision Relay, (b) Master trip Relay, (c) PT Fuse failure relay. (d) DC Supervision Scheme
(x) Suitable Disconnecting Link type terminal arrangement shall be provided for interfacing PS-Class CTs installed in the panel for achieving the required protection.
(B) 04 x Outgoing Panel, each comprising of :- (i) 11kV, 630Amp, 26.3KA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100. Vacuum Circuit Breaker having 03nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24V DC).
(ii) Current Transformers 11kV, 150-75/5A, for 02 outgoing and 200-100/5A for 02 no outgoing Core1: Class 5P10, 10VA, Core2: Class 0.5, 10VA - Set of 03 Nos. Per breaker
(iii) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) over-current or earth-fault in any of the three phases, (b) circuit-breaker-failure alarm, (c) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (d) Integrted arc flash protection with current and light sensing. (e )Transformer protection (Marshalling Box and Buchhloz relay). The relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with current measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(iv) Metering Equipment including:- (a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port.
(v) LED Indications - (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) Trip Circuit Healthy
(vi) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip (c) Trip Circuit Failure, (d) Inter-Tripping Fault, The Annunciator will be complete with required Acknowledge/Test buttons as required
(vii) Control Equipment incl. (a) 01 x TNC Switch, (b) 01 x Emergency Trip Push Button, (c) 01 x Local/Remote Switch, (d) MCBs for AC/DC isolation (e) Heater Switch with Thermostat - 01no. (f) 3-pin socket with ON/OFF switch - 01no. (g) LEDLamp with ON/OFF switch - 01no.
(viii) Flush mounted Auxillary Protection Relays incl. (a) Trip Circuit Supervision Relay, (b) Master trip Relay,
(ix) Transformer protection each comprising of :- (a) Oil Temperature high. (b) Winding Temperature high. (c ) Tank oil level low. (d) OLTC oil level low. (e) Buchhloz relay trip or sudden gas and sudden oil pressure relay trip. (f) Pressure relief.
Supplying, installing, testing and commissioning of Indoor arc flash protected Draw-Out with roll on floor type Vacuum Circuit Breaker Panel , rated for 11kV, 800 Amp, 26.3kA/3-sec, comprising of 02 No. Incomer, 01 No. Bus Coupler and 04Nos. Outgoing VCB Panels for VRC-III Sub station under AGE(U)E/S-III and Top mounted Bus PTs /Line PTs on panel for each bus section, confirming to IEC 62271-200, Internal Arc Classified IAC AFLR – 26.3kA for 1sec, Accessibility Class LSC2B-PM Class, comprising of 800 Amp, continuous rated Copper insulated busbars and droppers in all bus / breaker/ adaptor and and cable chambers, The busbars to be covered with insulating material, The earthing busbar is made of electrolytic copper and it runs longitudinally throughout the switchgear Encapsulated feeder connections IS3427 and IS12729. with 02nos. . Rack-In-Rack-Out Handles, structure made from AluZinc/GI/powder coated CRCA sheets to prevent corrosion and rusting. The complete panel incl. HT and LT chamber with FRLS wiring and acessories shall be manufactured by approved OEM at its own mancufacturing in house facility, and same will be verified via stage/final inspection. system house integrator / channel partner products are not accepted complete all as specified and directed
(A) 02 x Incomer Panel, each comprising of :-
(i) 11kV, 800 Amp, 26.3kA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100 with roll on floor type Vacuum Circuit Breaker having 03 Nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24V DC).
(ii) Current Transformers 11kV,300-150/5A, Core1: Class 5P10, 5VA, Core2: Class 0.5, 5VA, Core3: Class PS-X - Set of 03 Nos per breaker
(iii) Potential Transformers, Draw-out type for easy maintenance, 11kV/rt3:110V/rt3, 50VA, Cl.0.5 with associated gun-type HRC fuses and MCBs for HT/LT isolation - complete set per breaker
(iv) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT+05PT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) Directional over-current or earth-fault in any of the three phases, (b) Synchronism and Energizing Check before breaker closing to prevent un-syncronized mixing of supplies (c) circuit-breaker-failure alarm,
(d) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (e) Integrted arc flash protection with current and light sensing The relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Line-Voltage, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), AC Supply Fail, PT Fuse failure relay, Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with power & frequency measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(v) Metering Equipment including:- (a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port.
(vi) LED Indications :- (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) R-Y-B, (c) DC Available LED with push-button (d) AC Supply Fail (e) Trip Circuit Healthy
(vii) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip (c) Trip Circuit Failure, (d) Inter-Tripping Fault, (e) Synchro-Check. (f) PT Fuse Failure The Annunciator will be complete with required Acknowledge/Test buttons as required
(viii) Control Equipment incl. :- (a) 01 x TNC Switch, (b) 01 x Local/Remote Switch, (c) 01 x Emergency Trip Push Button, (d) MCBs for AC (e) MCBs for DC (f) Heater Switch with Thermostat - 01no. (g) 3-pin socket with ON/OFF switch - 01no. (h) LED Lamp with ON/OFF switch - 01no.
(ix) Flush mounted Auxillary Protection Relays incl:- (a) Trip Circuit Supervision Relay, (b) Master trip Relay, (c) PT Fuse failure relay. (d) DC Supervision Scheme
(x) Suitable Disconnecting Link type terminal arrangement shall be provided for interfacing PS-Class CTs installed in the panel for achieving the required protection.
(B) 01 x Bus Coupler Panel, each comprising of :- (i) 11kV, 800 Amp, 26.3KA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100 with roll on floor type Vacuum Circuit Breaker having 03nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24V DC).
(ii) Current Transformers 11kV,300-150/5A Core1: Class 5P10, 5VA, Core2: Class 0.5, 5VA, Core3: Class PS-X - Set of 03 Nos per breaker
(iii) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04PT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) Synchronism and Energizing Check before bus-coupler closing to prevent un-syncronized mixing of supplies (b) circuit-breaker-failure alarm. (c) circuit-breaker-failures and interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. The relay shall be fully integrated with the feeder, internally capturing feeder statuses incl. various status, Bus-Voltage and display the same locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with power & frequency measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(iv) LED Indications - (a) Breaker ON/OFF/TRIP/Spring-Charged (b) Trip Circuit Healthy
(v) Control Equipment incl. :- (a) 01 x TNC Switch, (b) 01 x Local/Remote Switch, (c) 01 x Emergency Trip Push Button, (d) MCBs for AC (e) MCBs for DC (f) Heater Switch with Thermostat - 01 No. (g) 3-pin socket with ON/OFF switch - 01 No. (h) LED Lamp with ON/OFF switch - 01 No.
(vi) Flush mounted Auxillary Protection Relays incl. (a) Trip Circuit Supervision Relay, (b) Master trip Relay,
(vii) 08-Window Annunciator with Hooter to indicate following alarms :- (a) Trip Circuit Failure, (b) Inter-Tripping Fault, (c) Synchro-Check. (d) PT Fuse Failure The Annunciator will be complete with required Acknowledge/Test buttons as required
(C) 04 x Outgoing Panel, each comprising of :- (i) 11kV, 630Amp, 26.3KA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100. Vacuum Circuit Breaker having 03nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24V DC).
(ii) Current Transformers 11kV, 150-75/5A, for 01 outgoing and 100-50/5A for 03 no outgoing Core1: Class 5P10, 10VA, Core2: Class 0.5, 10VA - Set of 03 Nos. Per breaker
(iii) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) over-current or earth-fault in any of the three phases, (b) circuit-breaker-failure alarm, (c) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (d) Integrted arc flash protection with current and light sensing. (e )Transformer protection (Marshalling Box and Buchhloz relay). The relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with current measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(iv) Metering Equipment including:- (a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port.
(v) LED Indications - (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) Trip Circuit Healthy
(vi) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip (c) Trip Circuit Failure, (d) Inter-Tripping Fault, The Annunciator will be complete with required Acknowledge/Test buttons as required
(vii) Control Equipment incl. (a) 01 x TNC Switch, (b) 01 x Emergency Trip Push Button, (c) 01 x Local/Remote Switch, (d) MCBs for AC/DC isolation (e) Heater Switch with Thermostat - 01no. (f) 3-pin socket with ON/OFF switch - 01no. (g) LEDLamp with ON/OFF switch - 01no.
(viii) Flush mounted Auxillary Protection Relays incl. (a) Trip Circuit Supervision Relay, (b) Master trip Relay,
(ix) Transformer protection each comprising of :- (a) Oil Temperature high. (b) Winding Temperature high. (c ) Tank oil level low. (d) OLTC oil level low. (e) Buchhloz relay trip or sudden gas and sudden oil pressure relay trip. (f) Pressure relief.
Supplying, installing, testing and commissioning of Indoor arc flash protected Draw-Out with roll on floor type Vacuum Circuit Breaker Panel , rated for 11kV, 800 Amp, 26.3kA/3-sec, comprising of 02 No. Incomer, 01 No. Bus Coupler and 04Nos. Outgoing VCB Panels for OTM-II Sub station under AGE(U)E/S-III and Top mounted Bus PTs /Line PTs on panel for each bus section, confirming to IEC 62271-200, Internal Arc Classified IAC AFLR – 26.3kA for 1sec, Accessibility Class LSC2B-PM Class, comprising of 800 Amp, continuous rated Copper insulated busbars and droppers in all bus / breaker/ adaptor and and cable chambers, The busbars to be covered with insulating material, The earthing busbar is made of electrolytic copper and it runs longitudinally throughout the switchgear Encapsulated feeder connections IS3427 and IS12729. with 02nos. . Rack-In-Rack-Out Handles, structure made from AluZinc/GI/powder coated CRCA sheets to prevent corrosion and rusting. The complete panel incl. HT and LT chamber with FRLS wiring and acessories shall be manufactured by approved OEM at its own mancufacturing in house facility, and same will be verified via stage/final inspection. system house integrator / channel partner products arenot accepted complete all as specified and directed
(A) 02 x Incomer Panel, each comprising of :-
(i) 11kV, 800 Amp, 26.3kA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100 with roll on floor type Vacuum Circuit Breaker having 03 Nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24V DC).
(ii) Current Transformers 11kV, 200-100/5A, Core1: Class 5P10, 5VA, Core2: Class 0.5, 5VA, Core3: Class PS-X - Set of 03 Nos per breaker
(iii) Potential Transformers, Draw-out type for easy maintenance, 11kV/rt3:110V/rt3, 50VA, Cl.0.5 with associated gun-type HRC fuses and MCBs for HT/LT isolation - complete set per breaker
(iv) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT+05PT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) Directional over-current or earth-fault in any of the three phases, (b) Synchronism and Energizing Check before breaker closing to prevent un-syncronized mixing of supplies (c) circuit-breaker-failure alarm, (d) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (e) Integrted arc flash protection with current and light sensing The relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Line-Voltage, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), AC Supply Fail, PT Fuse failure relay, Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with power & frequency measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(v) Metering Equipment including:- (a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port.
(vi) LED Indications :- (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) R-Y-B, (c) DC Available LED with push-button (d) AC Supply Fail (e) Trip Circuit Healthy
(vii) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip (c) Trip Circuit Failure, (d) Inter-Tripping Fault, (e) Synchro-Check. (f) PT Fuse Failure The Annunciator will be complete with required Acknowledge/Test buttons as required
(viii) Control Equipment incl. :- (a) 01 x TNC Switch, (b) 01 x Local/Remote Switch, (c) 01 x Emergency Trip Push Button, (d) MCBs for AC (e) MCBs for DC (f) Heater Switch with Thermostat - 01no. (g) 3-pin socket with ON/OFF switch - 01no. (h) LED Lamp with ON/OFF switch - 01no.
(ix) Flush mounted Auxillary Protection Relays incl:- (a) Trip Circuit Supervision Relay, (b) Master trip Relay, (c) PT Fuse failure relay. (d) DC Supervision Scheme
(x) Suitable Disconnecting Link type terminal arrangement shall be provided for interfacing PS-Class CTs installed in the panel for achieving the required protection.
(B) 01 x Bus Coupler Panel, each comprising of :- (i) 11kV, 800 Amp, 26.3KA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100 with roll on floor type Vacuum Circuit Breaker having 03nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24V DC).
(ii) Current Transformers 11kV,200-100/5A Core1: Class 5P10, 5VA, Core2: Class 0.5, 5VA, Core3: Class PS-X - Set of 03 Nos per breaker
(iii) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04PT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) Synchronism and Energizing Check before bus-coupler closing to prevent un-syncronized mixing of supplies (b) circuit-breaker-failure alarm.
(c) circuit-breaker-failures and interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. The relay shall be fully integrated with the feeder, internally capturing feeder statuses incl. various status, Bus-Voltage and display the same locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with power & frequency measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(iv) LED Indications - (a) Breaker ON/OFF/TRIP/Spring-Charged (b) Trip Circuit Healthy
(v) Control Equipment incl. :- (a) 01 x TNC Switch, (b) 01 x Local/Remote Switch, (c) 01 x Emergency Trip Push Button, (d) MCBs for AC (e) MCBs for DC (f) Heater Switch with Thermostat - 01 No. (g) 3-pin socket with ON/OFF switch - 01 No. (h) LED Lamp with ON/OFF switch - 01 No.
(vi) Flush mounted Auxillary Protection Relays incl. (a) Trip Circuit Supervision Relay, (b) Master trip Relay,
(vii) 08-Window Annunciator with Hooter to indicate following alarms :- (a) Trip Circuit Failure, (b) Inter-Tripping Fault, (c) Synchro-Check. (d) PT Fuse Failure The Annunciator will be complete with required Acknowledge/Test buttons as required
(C) 04 x Outgoing Panel, each comprising of :- (i) 11kV, 630Amp, 26.3KA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100. Vacuum Circuit Breaker having 03nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24V DC).
(ii) Current Transformers 11kV, 150-75/5A, for 02 outgoing and 50-25/5A for 02 no outgoing Core1: Class 5P10, 10VA, Core2: Class 0.5, 10VA - Set of 03 Nos. Per breaker
(iii) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) over-current or earth-fault in any of the three phases, (b) circuit-breaker-failure alarm, (c) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (d) Integrted arc flash protection with current and light sensing. (e )Transformer protection (Marshalling Box and Buchhloz relay).
The relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with current measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(iv) Metering Equipment including:- (a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port.
(v) LED Indications - (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) Trip Circuit Healthy
(vi) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip (c) Trip Circuit Failure, (d) Inter-Tripping Fault, The Annunciator will be complete with required Acknowledge/Test buttons as required
(vii) Control Equipment incl. (a) 01 x TNC Switch, (b) 01 x Emergency Trip Push Button, (c) 01 x Local/Remote Switch, (d) MCBs for AC/DC isolation (e) Heater Switch with Thermostat - 01no. (f) 3-pin socket with ON/OFF switch - 01no. (g) LEDLamp with ON/OFF switch - 01no.
(viii) Flush mounted Auxillary Protection Relays incl. (a) Trip Circuit Supervision Relay, (b) Master trip Relay,
(ix) Transformer protection each comprising of :- (a) Oil Temperature high. (b) Winding Temperature high. (c ) Tank oil level low. (d) OLTC oil level low. (e) Buchhloz relay trip or sudden gas and sudden oil pressure relay trip. (f) Pressure relief.
Supplying, installing, testing and commissioning of Indoor arc flash protected Draw-Out with roll on floor type Vacuum Circuit Breaker Panel , rated for 11kV, 800 Amp, 26.3kA/3-sec, both side extendable type with suitable size of bus bar/blank complete as Outgoing VCB Panels-02 Nos at CAMS substation under AGE(U) E/S- III and Top mounted Bus PTs /Line PTs on panel for each bus section, confirming to IEC 62271-200, Internal Arc Classified IAC AFLR – 26.3kA for 1sec, Accessibility Class LSC2B-PM Class, comprising of 800 Amp, continuous rated Copper insulated busbars and droppers in all bus / breaker/ adaptor and and cable chambers, The busbars to be covered with insulating material, The earthing busbar is made of electrolytic copper and it runs longitudinally throughout the switchgear Encapsulated feeder connections IS3427 and IS12729. with 02nos. . Rack-In-Rack-Out Handles, structure made from AluZinc/GI/powder coated CRCA sheets to prevent corrosion and rusting. The complete panel incl. HT and LT chamber with FRLS wiring and acessories shall be manufactured by approved OEM at its own mancufacturing in house facility, and same will be verified via stage/final inspection. system house integrator / channel partner products arenot accepted complete all as specified and directed Note: These HT pannels shall be clubbed in with the existing / fixed with the existing VCB and Bus Copupler
(A) (i) 11kV, 630Amp, 26.3KA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100. Vacuum Circuit Breaker having 03nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24VDC).
(ii) Current Transformers 11kV, 100-50/5A, Core1: Class 5P10, 5VA, Core2: Class 0.5, 5VA - Set of 03 Nos.
(iii) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) over-current or earth-fault in any of the three phases, (b) circuit-breaker-failure alarm, (c) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (d) Integrted arc flash protection with current and light sensing
The relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with current measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(iv) Metering Equipment including:- (a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port.
(v) LED Indications - (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) Trip Circuit Healthy
(vi) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip (c) Trip Circuit Failure, (d) Inter-Tripping Fault, The Annunciator will be complete with required Acknowledge/Test buttons as required
(b) All Multi-function-meters shall be connected in a ModBus loop terminating into 01 No. ModBus-to-TCP/IP converter to be provided for sending data to SCADA console via networking switch.
(viii) Control Equipment incl. (a) 01 x TNC Switch, (b) 01 x Emergency Trip Push Button, (c) 01 x Local/Remote Switch, (d) MCBs for AC/DC isolation (e) Heater Switch with Thermostat - 01no. (f) 3-pin socket with ON/OFF switch - 01no. (g) LED Lamp with ON/OFF switch - 01no.
(ix) Flush mounted Auxillary Protection Relays incl. (a) Trip Circuit Supervision Relay, (b) Master trip Relay,
(x) Suitable Disconnecting Link type terminal arrangement shall be provided for interfacing PS-Class CTs installed in the panel with existing VCB panel relay suituated in the 11 KV CRP for achieving the required protection.
Supplying, installing, testing and commissioning of Indoor arc flash protected Draw-Out with roll on floor type Vacuum Circuit Breaker Panel , rated for 11kV, 800 Amp, 26.3kA/3-sec, both side extendable type with suitable size of bus bar/blank complete as Outgoing VCB Panels-03 Nos at Cassel Road Extn substation under AGE(U) E/S-III and Top mounted Bus PTs /Line PTs on panel for each bus section, confirming to IEC 62271-200, Internal Arc Classified IAC AFLR – 26.3kA for 1sec, Accessibility Class LSC2B-PM Class, comprising of 800 Amp, continuous rated Copper insulated busbars and droppers in all bus / breaker/ adaptor and and cable chambers, The busbars to be covered with insulating material, The earthing busbar is made of electrolytic copper and it runs longitudinally throughout the switchgear Encapsulated feeder connections IS3427 and IS12729. with 02nos. . Rack-In-Rack-Out Handles, structure made from AluZinc/GI/powder coated CRCA sheets to prevent corrosion and rusting. The complete panel incl. HT and LT chamber with FRLS wiring and acessories shall be manufactured by approved OEM at its own mancufacturing in house facility, and same will be verified via stage/final inspection. system house integrator / channel partner products arenot accepted .complete all as specified and directed Note: These HT pannels shall be clubbed in with the existing / fixed with the existing VCB and Bus Coupler
(A) (i) 11kV, 630Amp, 26.3KA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100. Vacuum Circuit Breaker having 03nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24VDC).
(ii) Current Transformers 11kV, 100-50/5A, Core1: Class 5P10, 5VA, Core2: Class 0.5, 5VA - Set of 03 Nos.
(iii) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) over-current or earth-fault in any of the three phases, (b) circuit-breaker-failure alarm, (c) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (d) Integrted arc flash protection with current and light sensing The relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with current measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(iv) Metering Equipment including:- (a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port.
(v) LED Indications - (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) Trip Circuit Healthy
(vi) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip (c) Trip Circuit Failure, (d) Inter-Tripping Fault, The Annunciator will be complete with required Acknowledge/Test buttons as required
(b) All Multi-function-meters shall be connected in a ModBus loop terminating into 01 No. ModBus-to-TCP/IP converter to be provided for sending data to SCADA console via networking switch.
(viii) Control Equipment incl. (a) 01 x TNC Switch, (b) 01 x Emergency Trip Push Button, (c) 01 x Local/Remote Switch, (d) MCBs for AC/DC isolation (e) Heater Switch with Thermostat - 01no. (f) 3-pin socket with ON/OFF switch - 01no. (g) LED Lamp with ON/OFF switch - 01no.
(ix) Flush mounted Auxillary Protection Relays incl. (a) Trip Circuit Supervision Relay, (b) Master trip Relay,
(x) Suitable Disconnecting Link type terminal arrangement shall be provided for interfacing PS-Class CTs installed in the panel with existing VCB panel relay suituated in the 11 KV CRP for achieving the required protection.
Supplying, installing, testing and commissioning of Indoor arc flash protected Draw-Out with roll on floor type Vacuum Circuit Breaker Panel , rated for 11kV, 800 Amp, 26.3kA/3-sec, comprising of 01 No. Incomer, 01 No. Bus Coupler and 09 Nos. Outgoing VCB Panels for 1 Signal Regmt Sub station under AGE(U)E/S-III and Top mounted Bus PTs /Line PTs on panel for each bus section, confirming to IEC 62271-200, Internal Arc Classified IAC AFLR – 26.3kA for 1sec, Accessibility Class LSC2B-PM Class, comprising of 800 Amp, continuous rated Copper insulated busbars and droppers in all bus / breaker/ adaptor and and cable chambers, The busbars to be covered with insulating material, The earthing busbar is made of electrolytic copper and it runs longitudinally throughout the switchgear Encapsulated feeder connections IS3427 and IS12729. with 02nos. . Rack-In-Rack-Out Handles, structure made from AluZinc/GI/powder coated CRCA sheets to prevent corrosion and rusting. The complete panel incl. HT and LT chamber with FRLS wiring and acessories shall be manufactured by approved OEM at its own mancufacturing in house facility, and same will be verified via stage/final inspection. system house integrator / channel partner products arenot accepted .The panel shall consist of following OEM / Makes: ABB/ Siemens/ Schnider/ crompton Note: These HT pannels shall be clubbed in with the existing / fixed with the existing VCB and Bus Coupler of Make: Areva/Crompton
(A) 01 x Incomer Panel, each comprising of :-
(i) 11kV, 800 Amp, 26.3kA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100 with roll on floor type Vacuum Circuit Breaker having 03 Nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24V DC).
(ii) Current Transformers 11kV, 400-200/5A, Core1: Class 5P10, 5VA, Core2: Class 0.5, 5VA, Core3: Class PS-X - Set of 03 Nos per breaker
(iii) Potential Transformers, Draw-out type for easy maintenance, 11kV/rt3:110V/rt3, 50VA, Cl.0.5 with associated gun-type HRC fuses and MCBs for HT/LT isolation - complete set per breaker
(iv) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT+05PT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) Directional over-current or earth-fault in any of the three phases, (b) Synchronism and Energizing Check before breaker closing to prevent un-syncronized mixing of supplies (c) circuit-breaker-failure alarm, (d) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (e) Integrted arc flash protection with current and light sensing The relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Line-Voltage, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), AC Supply Fail, PT Fuse failure relay, Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with power & frequency measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(v) Metering Equipment including:- (a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port.
(vi) LED Indications :- (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) R-Y-B, (c) DC Available LED with push-button (d) AC Supply Fail (e) Trip Circuit Healthy
(vii) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip (c) Trip Circuit Failure, (d) Inter-Tripping Fault, (e) Synchro-Check. (f) PT Fuse Failure The Annunciator will be complete with required Acknowledge/Test buttons as required
(viii) Control Equipment incl. :- (a) 01 x TNC Switch, (b) 01 x Local/Remote Switch, (c) 01 x Emergency Trip Push Button, (d) MCBs for AC (e) MCBs for DC (f) Heater Switch with Thermostat - 01no. (g) 3-pin socket with ON/OFF switch - 01no. (h) LED Lamp with ON/OFF switch - 01no.
(ix) Flush mounted Auxillary Protection Relays incl:- (a) Trip Circuit Supervision Relay, (b) Master trip Relay, (c) PT Fuse failure relay. (d) DC Supervision Scheme
(x) Suitable Disconnecting Link type terminal arrangement shall be provided for interfacing PS-Class CTs installed in the panel for achieving the required protection.
(B) 01 x Bus Coupler Panel, each comprising of :- (i) 11kV, 800 Amp, 26.3KA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100 with roll on floor type Vacuum Circuit Breaker having 03nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24V DC).
(ii) Current Transformers 11kV,400-200/5A Core1: Class 5P10, 5VA, Core2: Class 0.5, 5VA, Core3: Class PS-X - Set of 03 Nos per breaker
(iii) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04PT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) Synchronism and Energizing Check before bus-coupler closing to prevent un-syncronized mixing of supplies (b) circuit-breaker-failure alarm.
(c) circuit-breaker-failures and interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. The relay shall be fully integrated with the feeder, internally capturing feeder statuses incl. various status, Bus-Voltage and display the same locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with power & frequency measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(iv) LED Indications - (a) Breaker ON/OFF/TRIP/Spring-Charged (b) Trip Circuit Healthy
(v) Control Equipment incl. :- (a) 01 x TNC Switch, (b) 01 x Local/Remote Switch, (c) 01 x Emergency Trip Push Button, (d) MCBs for AC (e) MCBs for DC (f) Heater Switch with Thermostat - 01 No. (g) 3-pin socket with ON/OFF switch - 01 No. (h) LED Lamp with ON/OFF switch - 01 No.
(vi) Flush mounted Auxillary Protection Relays incl. (a) Trip Circuit Supervision Relay, (b) Master trip Relay,
(vii) 08-Window Annunciator with Hooter to indicate following alarms :- (a) Trip Circuit Failure, (b) Inter-Tripping Fault, (c) Synchro-Check. (d) PT Fuse Failure The Annunciator will be complete with required Acknowledge/Test buttons as required
(C) 09 x Outgoing Panel, each comprising of :- (i) 11kV, 630Amp, 26.3KA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100. Vacuum Circuit Breaker having 03nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24V DC).
(ii) Current Transformers 11kV, 300-150/5A- for 02 outgoing 150-75/5A, for 04 outgoing and 100-50/5A for 02 no outgoing Core1: Class 5P10, 10VA, Core2: Class 0.5, 10VA - Set of 03 Nos. Per breaker
(iii) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) over-current or earth-fault in any of the three phases, (b) circuit-breaker-failure alarm, (c) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (d) Integrted arc flash protection with current and light sensing. (e )Transformer protection (Marshalling Box and Buchhloz relay).
The relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with current measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(iv) Metering Equipment including:- (a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port.
(v) LED Indications - (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) Trip Circuit Healthy
(vi) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip (c) Trip Circuit Failure, (d) Inter-Tripping Fault, The Annunciator will be complete with required Acknowledge/Test buttons as required
(vii) Control Equipment incl. (a) 01 x TNC Switch, (b) 01 x Emergency Trip Push Button, (c) 01 x Local/Remote Switch, (d) MCBs for AC/DC isolation (e) Heater Switch with Thermostat - 01no. (f) 3-pin socket with ON/OFF switch - 01no. (g) LEDLamp with ON/OFF switch - 01no.
(viii) Flush mounted Auxillary Protection Relays incl. (a) Trip Circuit Supervision Relay, (b) Master trip Relay,
(ix) Transformer protection each comprising of :- (a) Oil Temperature high. (b) Winding Temperature high. (c ) Tank oil level low. (d) OLTC oil level low. (e) Buchhloz relay trip or sudden gas and sudden oil pressure relay trip. (f) Pressure relief.
Supplying, installing, testing and commissioning of Indoor arc flash protected Draw-Out with roll on floor type Vacuum Circuit Breaker Panel , rated for 11kV, 800 Amp, 26.3kA/3-sec, comprising of 01 No. Incomer, and 02 Nos. Outgoing VCB Panels for OTM-III Sub station under AGE(U)E/S-III and Top mounted Bus PTs /Line PTs on panel for each bus section, confirming to IEC 62271-200, Internal Arc Classified IAC AFLR – 26.3kA for 1sec, Accessibility Class LSC2B-PM Class, comprising of 800 Amp, continuous rated Copper insulated busbars and droppers in all bus / breaker/ adaptor and and cable chambers, The busbars to be covered with insulating material, The earthing busbar is made of electrolytic copper and it runs longitudinally throughout the switchgear Encapsulated feeder connections IS3427 and IS12729. with 02nos. . Rack-In-Rack-Out Handles, structure made from AluZinc/GI/powder coated CRCA sheets to prevent corrosion and rusting. The complete panel incl. HT and LT chamber with FRLS wiring and acessories shall be manufactured by approved OEM at its own mancufacturing in house facility, and same will be verified via stage/final inspection. system house integrator / channel partner products arenot accepted complete all as specified and directed
(A) 01 x Incomer Panel, each comprising of :-
(i) 11kV, 800 Amp, 26.3kA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100 with roll on floor type Vacuum Circuit Breaker having 03 Nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24V DC).
(ii) Current Transformers 11kV, 200-100/5A, Core1: Class 5P10, 5VA, Core2: Class 0.5, 5VA, Core3: Class PS-X - Set of 03 Nos per breaker
(iii) Potential Transformers, Draw-out type for easy maintenance, 11kV/rt3:110V/rt3, 50VA, Cl.0.5 with associated gun-type HRC fuses and MCBs for HT/LT isolation - complete set per breaker
(iv) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT+05PT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) Directional over-current or earth-fault in any of the three phases, (b) Synchronism and Energizing Check before breaker closing to prevent un-syncronized mixing of supplies (c) circuit-breaker-failure alarm,
(d) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (e) Integrted arc flash protection with current and light sensing The relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Line-Voltage, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), AC Supply Fail, PT Fuse failure relay, Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with power & frequency measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(v) Metering Equipment including:- (a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port.
(vi) LED Indications :- (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) R-Y-B, (c) DC Available LED with push-button (d) AC Supply Fail (e) Trip Circuit Healthy
(vii) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip (c) Trip Circuit Failure, (d) Inter-Tripping Fault, (e) Synchro-Check. (f) PT Fuse Failure The Annunciator will be complete with required Acknowledge/Test buttons as required
(viii) Control Equipment incl. :- (a) 01 x TNC Switch, (b) 01 x Local/Remote Switch, (c) 01 x Emergency Trip Push Button, (d) MCBs for AC (e) MCBs for DC (f) Heater Switch with Thermostat - 01no. (g) 3-pin socket with ON/OFF switch - 01no. (h) LED Lamp with ON/OFF switch - 01no.
(ix) Flush mounted Auxillary Protection Relays incl:- (a) Trip Circuit Supervision Relay, (b) Master trip Relay, (c) PT Fuse failure relay. (d) DC Supervision Scheme
(x) Suitable Disconnecting Link type terminal arrangement shall be provided for interfacing PS-Class CTs installed in the panel for achieving the required protection.
(C) 02 x Outgoing Panel, each comprising of :- (i) 11kV, 630Amp, 26.3KA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100. Vacuum Circuit Breaker having 03nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24V DC).
(ii) Current Transformers 11kV, 150-75/5A, for 01 outgoing and 50-25/5A for 01 no outgoing Core1: Class 5P10, 10VA, Core2: Class 0.5, 10VA - Set of 03 Nos. Per breaker
(iii) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) over-current or earth-fault in any of the three phases, (b) circuit-breaker-failure alarm, (c) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (d) Integrted arc flash protection with current and light sensing. (e )Transformer protection (Marshalling Box and Buchhloz relay). The relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with current measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(iv) Metering Equipment including:- (a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port.
(v) LED Indications - (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) Trip Circuit Healthy
(vi) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip (c) Trip Circuit Failure, (d) Inter-Tripping Fault, The Annunciator will be complete with required Acknowledge/Test buttons as required
(vii) Control Equipment incl. (a) 01 x TNC Switch, (b) 01 x Emergency Trip Push Button, (c) 01 x Local/Remote Switch, (d) MCBs for AC/DC isolation (e) Heater Switch with Thermostat - 01no. (f) 3-pin socket with ON/OFF switch - 01no. (g) LEDLamp with ON/OFF switch - 01no.
(viii) Flush mounted Auxillary Protection Relays incl. (a) Trip Circuit Supervision Relay, (b) Master trip Relay,
(ix) Transformer protection each comprising of :- (a) Oil Temperature high. (b) Winding Temperature high. (c ) Tank oil level low. (d) OLTC oil level low. (e) Buchhloz relay trip or sudden gas and sudden oil pressure relay trip. (f) Pressure relief.
Supplying, installing, testing and commissioning of Indoor arc flash protected Draw-Out with roll on floor type Vacuum Circuit Breaker Panel , rated for 11kV, 800 Amp, 26.3kA/3-sec, comprising of 01 No. Incomer, 01 No. Bus Coupler VCB Panels for Bhana Singh Sub station under AGE(U)E/S-III and Top mounted Bus PTs /Line PTs on panel for each bus section, confirming to IEC 62271-200, Internal Arc Classified IAC AFLR – 26.3kA for 1sec, Accessibility Class LSC2B-PM Class, comprising of 800 Amp, continuous rated Copper insulated busbars and droppers in all bus / breaker/ adaptor and and cable chambers, The busbars to be covered with insulating material, The earthing busbar is made of electrolytic copper and it runs longitudinally throughout the switchgear Encapsulated feeder connections IS3427 and IS12729. with 02nos. . Rack-In-Rack-Out Handles, structure made from AluZinc/GI/powder coated CRCA sheets to prevent corrosion and rusting. The complete panel incl. HT and LT chamber with FRLS wiring and acessories shall be manufactured by approved OEM at its own mancufacturing in house facility, and same will be verified via stage/final inspection. system house integrator / channel partner products arenot accepted complete all as specified and directed Note: These HT pannels shall be clubbed in with the existing / fixed with the existing VCB and Bus Coupler
(A) 01 x Incomer Panel, each comprising of :-
(i) 11kV, 800 Amp, 26.3kA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100 with roll on floor type Vacuum Circuit Breaker having 03 Nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24V DC).
(ii) Current Transformers 11kV, 200-100/5A, Core1: Class 5P10, 5VA, Core2: Class 0.5, 5VA, Core3: Class PS-X - Set of 03 Nos per breaker
(iii) Potential Transformers, Draw-out type for easy maintenance, 11kV/rt3:110V/rt3, 50VA, Cl.0.5 with associated gun-type HRC fuses and MCBs for HT/LT isolation - complete set per breaker
(iv) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT+05PT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) Directional over-current or earth-fault in any of the three phases, (b) Synchronism and Energizing Check before breaker closing to prevent un-syncronized mixing of supplies (c) circuit-breaker-failure alarm, (d) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (e) Integrted arc flash protection with current and light sensing The relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Line-Voltage, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), AC Supply Fail, PT Fuse failure relay, Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with power & frequency measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(v) Metering Equipment including:- (a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port.
(vi) LED Indications :- (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) R-Y-B, (c) DC Available LED with push-button (d) AC Supply Fail (e) Trip Circuit Healthy
(vii) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip (c) Trip Circuit Failure,
(d) Inter-Tripping Fault, (e) Synchro-Check. (f) PT Fuse Failure The Annunciator will be complete with required Acknowledge/Test buttons as required
(viii) Control Equipment incl. :- (a) 01 x TNC Switch, (b) 01 x Local/Remote Switch, (c) 01 x Emergency Trip Push Button, (d) MCBs for AC (e) MCBs for DC (f) Heater Switch with Thermostat - 01no. (g) 3-pin socket with ON/OFF switch - 01no. (h) LED Lamp with ON/OFF switch - 01no.
(ix) Flush mounted Auxillary Protection Relays incl:- (a) Trip Circuit Supervision Relay, (b) Master trip Relay, (c) PT Fuse failure relay. (d) DC Supervision Scheme
(x) Suitable Disconnecting Link type terminal arrangement shall be provided for interfacing PS-Class CTs installed in the panel for achieving the required protection.
(B) 01 x Bus Coupler Panel, each comprising of :- (i) 11kV, 800 Amp, 26.3KA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100 with roll on floor type Vacuum Circuit Breaker having 03nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24V DC).
(ii) Current Transformers 11kV,200-100/5A Core1: Class 5P10, 5VA, Core2: Class 0.5, 5VA, Core3: Class PS-X - Set of 03 Nos per breaker
(iii) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04PT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) Synchronism and Energizing Check before bus-coupler closing to prevent un-syncronized mixing of supplies (b) circuit-breaker-failure alarm. (c) circuit-breaker-failures and interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol.
The relay shall be fully integrated with the feeder, internally capturing feeder statuses incl. various status, Bus-Voltage and display the same locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with power & frequency measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(iv) LED Indications - (a) Breaker ON/OFF/TRIP/Spring-Charged (b) Trip Circuit Healthy
(v) Control Equipment incl. :- (a) 01 x TNC Switch, (b) 01 x Local/Remote Switch, (c) 01 x Emergency Trip Push Button, (d) MCBs for AC (e) MCBs for DC (f) Heater Switch with Thermostat - 01 No. (g) 3-pin socket with ON/OFF switch - 01 No. (h) LED Lamp with ON/OFF switch - 01 No.
(vi) Flush mounted Auxillary Protection Relays incl. (a) Trip Circuit Supervision Relay, (b) Master trip Relay,
(vii) 08-Window Annunciator with Hooter to indicate following alarms :- (a) Trip Circuit Failure, (b) Inter-Tripping Fault, (c) Synchro-Check. (d) PT Fuse Failure The Annunciator will be complete with required Acknowledge/Test buttons as required
Supplying, installing, testing and commissioning of Indoor arc flash protected Draw-Out with roll on floor type Vacuum Circuit Breaker Panel , rated for 11kV, 800 Amp, 26.3kA/3-sec, comprising of 01 No. Incomer, and 02 Nos. Outgoing VCB Panels for VRC-1 Sub station under AGE(U)E/S-III and Top mounted Bus PTs /Line PTs on panel for each bus section, confirming to IEC 62271-200, Internal Arc Classified IAC AFLR – 26.3kA for 1sec, Accessibility Class LSC2B-PM Class, comprising of 800 Amp, continuous rated Copper insulated busbars and droppers in all bus / breaker/ adaptor and cable chambers, The busbars to be covered with insulating material, The earthing busbar is made of electrolytic copper and it runs longitudinally throughout the switchgear Encapsulated feeder connections IS3427 and IS12729. with 02nos. Rack-In-Rack-Out Handles, structure made from AluZinc/GI/powder coated CRCA sheets to prevent corrosion and rusting.The rated characteristics of the switchgear should be guaranteed for Minimum ambient temperature: – 5 °C, Maximum ambient temperature: + 40 °C, with standard degrees of protection:IP4X for the enclosure and IP2X for the partition between compartments The complete panel incl. HT and LT chamber with FRLS wiring and acessories shall be manufactured by approved OEM at its own mancufacturing in house facility, and same will be verified via stage/final inspection. system house integrator / channel partner products arenot accepted complete all as specified and directed
(A) 01 x Incomer Panel, each comprising of :-
(i) 11kV, 800 Amp, 26.3kA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100 with roll on floor type Vacuum Circuit Breaker having 03 Nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24V DC).
(ii) Current Transformers 11kV, 200-100/5A, Core1: Class 5P10, 5VA, Core2: Class 0.5, 5VA, Core3: Class PS-X - Set of 03 Nos per breaker
(iii) Potential Transformers, Draw-out type for easy maintenance, 11kV/rt3:110V/rt3, 50VA, Cl.0.5 with associated gun-type HRC fuses and MCBs for HT/LT isolation - complete set per breaker
(iv) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT+05PT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) Directional over-current or earth-fault in any of the three phases, (b) Synchronism and Energizing Check before breaker closing to prevent un-syncronized mixing of supplies (c) circuit-breaker-failure alarm, (d) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (e) Integrted arc flash protection with current and light sensing
The relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Line-Voltage, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), AC Supply Fail, PT Fuse failure relay, Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with power & frequency measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacture
(v) Metering Equipment including:- (a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port.
(vi) LED Indications :- (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) R-Y-B, (c) DC Available LED with push-button (d) AC Supply Fail (e) Trip Circuit Healthy
(vii) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip (c) Trip Circuit Failure, (d) Inter-Tripping Fault, (e) Synchro-Check. (f) PT Fuse Failure The Annunciator will be complete with required Acknowledge/Test buttons as required
(viii) Control Equipment incl. :- (a) 01 x TNC Switch, (b) 01 x Local/Remote Switch, (c) 01 x Emergency Trip Push Button, (d) MCBs for AC (e) MCBs for DC (f) Heater Switch with Thermostat - 01no. (g) 3-pin socket with ON/OFF switch - 01no. (h) LED Lamp with ON/OFF switch - 01no.
(ix) Flush mounted Auxillary Protection Relays incl:- (a) Trip Circuit Supervision Relay, (b) Master trip Relay, (c) PT Fuse failure relay. (d) DC Supervision Scheme
(x) Suitable Disconnecting Link type terminal arrangement shall be provided for interfacing PS-Class CTs installed in the panel for achieving the required protection.
(C) 02 x Outgoing Panel, each comprising of :- (i) 11kV, 630Amp, 26.3KA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100. Vacuum Circuit Breaker having 03nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24V DC).
(ii) Current Transformers 11kV, 150-75/5A, for 01 outgoing and 50-25/5A for 01 no outgoing Core1: Class 5P10, 10VA, Core2: Class 0.5, 10VA - Set of 03 Nos. Per breaker
(iii) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) over-current or earth-fault in any of the three phases, (b) circuit-breaker-failure alarm, (c) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (d) Integrted arc flash protection with current and light sensing.
(e )Transformer protection (Marshalling Box and Buchhloz relay). The relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with current measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer.
(iv) Metering Equipment including:- (a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port.
(v) LED Indications - (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) Trip Circuit Healthy
(vi) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip (c) Trip Circuit Failure, (d) Inter-Tripping Fault, The Annunciator will be complete with required Acknowledge/Test buttons as required
(vii) Control Equipment incl. (a) 01 x TNC Switch, (b) 01 x Emergency Trip Push Button, (c) 01 x Local/Remote Switch, (d) MCBs for AC/DC isolation (e) Heater Switch with Thermostat - 01no. (f) 3-pin socket with ON/OFF switch - 01no. (g) LEDLamp with ON/OFF switch - 01no.
(viii) Flush mounted Auxillary Protection Relays incl. (a) Trip Circuit Supervision Relay, (b) Master trip Relay,
(ix) Transformer protection each comprising of :- (a) Oil Temperature high. (b) Winding Temperature high. (c ) Tank oil level low. (d) OLTC oil level low. (e) Buchhloz relay trip or sudden gas and sudden oil pressure relay trip. (f) Pressure relief.
Note for Item 09 to 30 Make of VCB Panel/breaker: ABB/SIEMENS/SCHNIDER/CROMPTON/AREVA Make of Relays: Relays shall be of self powered with feeder protection options for Incommer breakers and Bus couplers , Transformer /feeder protection relays on out going side as per the site requirement. The make of VCB Panel VCB breaker and protection relay should be of the same make /OEM, any third party /channel partner will not be accepted and the contractor should verify it from the company/OEM before quoting. (i) Cost of construction of foundation as per manufacturer design, including foundation frame (supplied by OEM), channels etc. for HT Panel as required at site are deemed to be included in the quoted rate. (ii) Each VCB panel being floor-mounted, air-insulated, fully-compartmentalizeds The OEM shall supervise and certify the commissioning/charging of equipment. (iii) Foundation frames shall be inclusive in the scope of supply of OEM.
(iv) All Multi-function-meters shall be connected in a ModBus loop terminating into 01 No. ModBus-to-TCP/IP converter to be provided for sending data to SCADA console via networking switch.
(vii) All Incomers and BusCouplers will have suitable schemes in place to prevent mixing of un-syncronized supplies using Line/BusPT signals. Any such attempt will be reported by a suitable alarm. This facility should be implemented over soft-logic, and can be disabled by authorized personnel without requiring any on-site re-wiring. (viii) All Outgoing VCBs will have inter-tripping logic in place to ensure that Incomer breaker immediately trips in case of failure of opening of outgoing VCB experiencing feeder fault. Special and dedicated Alarm shall be in place to issued the user. This facility should be implemented over soft-logic, and can be disabled by authorized personnel without requiring any on-site re-wiring. (ix) Rate quatoted includues the cost of making new/ modification of the existing PT supply for controlls/ instrument system with necesssray controll wiring and controll contactors of rated capacity and voltage levels (x) Ring core current transformers / The toroidal transformers are to be of epoxy resin insulated type and are used to measurement and protection devicesfor measuring phase currents or for detecting the earth fault current. confirming to the IEC 61869-1, IEC 61869-2 (xi)The voltage transformers are of the epoxy resin insulated type and are for measurement and protection devices conform to the IEC 61869-1, IEC 61869-3 installed on removable or withdrawable trucks they are fitted with medium voltage protection fuses.The withdrawable trucks also to allow replacement of the fuses with the switchgear in service. Truck racking-out with the door closed automatically operates closure of a metallic segregation shutter between the live parts of the switchgear and the instrument compartment.
Supply and fix cable jointing kit for 11 KV grade cable for indoor termination , heat shrink type , joint complete with jointing material and accessories suitable for 3 core XLPE , armoured , Al conductor cable of size 240 to 300 Sqmm complete all as specified and directed
Supply and fix cable jointing kit for 11 KV grade cable for indoor termination , heat shrink type , joint complete with jointing material and accessories suitable for 3 core XLPE , armoured , Al conductor cable of size 120 to 185 Sqmm complete all as specified and directed
Supply and fix cable jointing kit for 11 KV grade cable for indoor termination , heat shrink type , joint complete with jointing material and accessories suitable for 3 core XLPE , armoured , Al conductor cable of size 70 to 95 Sqmm complete all as specified and directed
Supply and fix cable jointing kit for 11 KV grade cable for straight through , heat shrink type , joint complete with jointing material and accessories suitable for 3 core XLPE , armoured , Al conductor cable of size 240 to 300 Sqmm complete all as specified and directed
Supply and fix cable jointing kit for 11 KV grade cable for straight through, heat shrink type , joint complete with jointing material and accessories suitable for 3 core XLPE , armoured , Al conductor cable of size 120 to 185 Sqmm complete all as specified and directed
Supply and fix cable jointing kit for 11 KV grade cable forstraight through, heat shrink type , joint complete with jointing material and accessories suitable for 3 core XLPE , armoured , Al conductor cable of size 70 to 95 Sqmm complete all as specified and directed
Supply laying, testing and commisioning (HT cable in existing duct or fixed with pole structure) cable XLPE insulated screened PVC bedded galvanised steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 11000 volts grade of size 3 core 95 sqmm complete all as specified and directed
Supply laying, testing and commisioning (HT cable in existing duct or fixed with pole structure) cable XLPE insulated screened PVC bedded galvanised steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 11000 volts grade of size 3 core 120 sqmm complete all as specified and directed
Supply laying, testing and commisioning (HT cable in existing duct or fixed with pole structure) cable XLPE insulated screened PVC bedded galvanised steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 11000 volts grade of size 3 core 185 sqmm complete all as specified and directed
Supply laying, testing and commisioning (HT cable in existing duct or fixed with pole structure) cable XLPE insulated screened PVC bedded galvanised steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 11000 volts grade of size 3 core 240 sqmm complete all as specified and directed
Supply laying, testing and commisioning (HT cable in existing duct or fixed with pole structure) cable XLPE insulated screened PVC bedded galvanised steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 11000 volts grade of size 3 core 300 sqmm complete all as specified and directed
Supply, installation & commissioning and testing in replacement of SHF/VRLA Battery, Battery charge panel comprising 12 Nos. 2 Volts 100 AH tubular Maintance free Lead Acid cell, self contained floor mounted sheet steel cabinet with two tiers for housing the batteries. The charging equipment will be operated from 240Volt +/- 10%, 50 c/s supply. with heavy duty copper wound transformer, Mosfet rectifiers, electronic cards microprocessor based. The cabinet should be complete and internally wired auto/mannual switch. The charger unit should house, resistance control DC ammeter , Voltmeter and fuses, AC supply failure alarm. Complete accessories required for commissioning is included in the scope of work. DC distribution board comprising of 63 Amps DPMCB as incomer and 2 nos of 15 A DP MCB as O/G Battery Charger with batteries Automatic Float cum Boost charger of 16 A to give 24 V DC output at 100 Ah capacity complete all as specified and directed Note: Rate quoted incldes the cost of 3 core 6Sqmm copper cable run trough 25mm rigid conduit with acessories from DB/ power socket to charger not exceeding 15 mts length and 2 core 2.5 sqmm copper cable run through 20mm rigid conduit withacessories per circuit of the DC distrubution panel of charger to 11KV VCB panel DC thimbiles/connectors/ MCBs not exceeding 25 mtr length per circuit
B D Raizada Projects Pvt Ltd
FRIZO INDIA PVT LTD
Shree Balaji Construction
Global Enterprises
Suncity Enterprises
AMIT ASSOCIATES
surendra infrastructure pvt ltd
NITASHA CONSTRUCTIONS
Bidder Name
AMIT ASSOCIATES
Global Enterprises
NITASHA CONSTRUCTIONS
B D Raizada Projects Pvt Ltd
FRIZO INDIA PVT LTD
surendra infrastructure pvt ltd
M P TYAGI ENGINEERS AND CONTRACTORS
Shree Balaji Construction
Suncity Enterprises
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .