Karnataka Power Transmission Corporation Limited
Providing New 02 Nos of additional 11kV PCVCB switchgear for load bifurcation at 66/11kV Substation Baguru KPTCL, RS & SS Division KPTCL Chitradurga. Including Supply of Equipments /Materials, Erection (Including Civil Works), Under Partial Turnkey Percentage Tender Basis, (Excluding the Major Materials Such. As Switchgears Will Be Supplied by KPTCL) Testing & Commissioning & other allied works
KPTCL/2025-26/EL/WORK_INDENT2962
KPTCL/2025-26/EL/WORK_INDENT2962
Open
Electrical
Two Tender Document System(Two Cover)
KPTCL CEE Transmission Zone Office Tumkur
₹500
₹16,263
10 Nov 2025
10 Nov 2025
3 Dec 2025
17 Nov 2025
Providing New 02 Nos of additional 11kV PCVCB switchgear for load bifurcation at 66/11kV Substation Baguru KPTCL, RS & SS Division KPTCL Chitradurga. Including Supply of Equipments /Materials, Erection (Including Civil Works), Under Partial Turnkey Percentage Tender Basis, (Excluding the Major Materials Such As Switchgears Will Be Supplied by KPTCL) Testing & Commissioning & other allied works
11KV ISOLATOR a)11kV Double break, 400 A, GOS.
b) 11 kV, 400 Amps Special Roaster GOS.
Conductor ACSR a) Coyote ACSR
b) Coyote ACSR for cross bus and line formation as per Common SR 23-24, volume-6, pg no-44, sl no:20.6
PVC insulated copper control cable with Lugs/ferrules as per specification.a)19core x 2.5 Sq.mm as per Common SR 23-24, Vol-6, pg no:40, sl no:13.16
b) 4 core x 6.0 Sq.mm
c)2 core x 6.0 Sq.mm
d) Providing Cable glands,copper lugs,Aluminium cable naming plates
e) Supply of ferrules
Alphabets- A to Z
Numerals- 0 to 9 with other notations
Hardware Clamps a)Bolted type tension clamp for Single Drake ACSR 70/90KN,16mm as per Common SR 23-24, vol-6, pg no:68, Sl no:47.1.9
b)Bolted type tension clamp for Single Coyote ACSR 70/90KN,16mm as per Common SR 23-24, vol-6, pg no:68, Sl no:47.1.11
c)C-type Wedge connectors for Coyote to Drake ACSR as per common KPTCL SR 23-24, vol-6, pg No:70, sl no:47.10.6
d)C-type wedge connectros for Coyote to Coyote ACSR as per KPTCL SR 23-24, vol-6, pg No:70, sl no:47.10.4
e)T-Clamps suitable for Single Coyote to Single coyote ACSR Conductor as per KPTCL SR 23-24, vol-6, pg no:69, Sl no:47.7.11
f)Pad Clamps for Coyote as per KPTCL SR 23-24, vol-6, pg no:67, Sl no:46.11
g)PG Clamps for Coyote as per MW ESCOM's SR 23-24, vol-6, pg no:6, Sl no:64.9.01
h)CT clamps for single coyote ACSR conductor
i) D shackles (16mm)
j)GI Eye bolts of size 5/8''x8'' length
GI bolts and nuts of different sizes
90KN Disc Insulators of 1 unit suitable for coyote ACSR as per KPTCL SR 23-24, vol-6, pg no:45, Sl no:21.2.3
C100x50 4 mtrs long GI C channels (0.036MT +0.0018 MT bolt nuts/4mtr long piece)
Assorted angles different sizes
RCC Pole of 9.5m long WL 300kg
RCC Pole GI clamps
Items like insulation tape,beads, Clamps,Welding, drilling etc and rounding off
Multi Function Transducer (MFT) & Fixing and wiring of MFT
8 Channel 110 V Opto Coupler. Fixing and wiring of Opto Coupler.
Copper control cable 4x4 sqmm for CT termination. KPTCL Material I.no-13.7 and KPTCL Labour I.no-22-b
Copper control cable 4x2.5sqmm for PT termination. KPTCL Material I.no-13.6 and KPTCL Labour I.no-22-b
Signal cable : Armoured Copper 10C x 0.5 Sq mm multistrand (2 runs - 1 run for MFM & 1 run for DI) (between C&R panel to RTU panel) KPTCL Material I.no-24.4.1 & Laying & termination of DI/DO/Communica...
Control control cables:- 10C x 1.5 Sq mm multistrand, conforming to KPTCL specification (between C&R panel to RTU panel) & Laying & termination of DI/DO/Communication Cables
item like insulation tape,beads, Clamps, Welding, PVC pipe with bends ,Drilling Etc and rounding off
Breaker Erection,alignment & fixing to the foundation,outdoor 11kV switchgear panel/unit including movement from the point of unloading to the point of erection as per common SR 23-24, vol-6, pg no:12...
Wiring & Assisting in testing and commissioning as per common SR pg No: 90 Sl No: 18 27 b b) 11kV Outdoor Switchgear
Wiring & Assisting in testing and commissioning for item 22,23,& 24 means contractors should provide labourers for wiring & commissining by RT/MT/firm Engineers.
as per as per KPTCL common SR Vol-6 p...
Laying of control cables as per KPTCL CSR pg No:120, Sl no:22b
b) Erection of 11KV Isolator Double break 400 A, 25KA,
c) Erection of special Roaster GOS 400A, Single break as per BESCOM SR
BUSBAR FORMATION b)Main bus/ cross bus(all three phases in segment) of using Coyote single/Double conductor with fixing of insulator spares,levelling of string conductors to the required height above ...
c) Erection of RCC Poles as per Common SR 23-24, pg no:44 slno:31.2.03
d) Erection of C100x50 4 mtrs long GI C channels
(0.036MT/Beam)x12Numbers =0.432 MT+(0.0018x12=0.0216)=0.4536MT
Grounding of GOS with 50X6mm GI flats and conneccting equipment to the earthmat, flats & ground pit. Each point of earthmat with all forms of works like bending,twisting ,drilling of holes & connectin...
Grounding of equipments by providing cast iron pipe of 100 mm ID 13 mm thickness, 2.75 metres long with 2 part clamp out of G.I. Flat 50 X 6 mm continuously welded alround the pipe using cast iron wel...
Supplying & providing 450mm dia 450mm hight 1.5" to 2" thick hume pipe collar(non pressure type) for earth pits including all lead and lifts etc as per CSR 23-24 pg no:124, Sl no:26i
a) Crane Hiring Charges for Loading of 11kV PCVCB complete set at Divisional Store, Davangere using mobile hydraulic crane 5 t capacity (KPWD common SR vol iii slno 73
b) Crane Hiring Charges for Unloading of 11kV PCVCB complete set at 66/11kV Sub station, Baguru using mobile hydraulic crane 5 t capacity (KPWD common SR vol I) iii)slno 73
c) Loading of mounting & supporting structures, CT from KPTCL store( Loading of steel by manual means and stacking. KPWD Vol-3 slno 1.3)
d) Unoading of mounting & supporting structures, CT at 66/11kV Sub station, Baguru.
e) Loading of control cables ,Conductors of different sizes, GOS sets, different sizes of clamps,from KPTCL store
f) Unloading of control cables ,Conductors of different sizes, GOS sets, different sizes of clamps at 66/11KV Sub station, Baguru.
g) Loading and Unloading of RCC poles as per CSR
SCADA integrationMulti Function Transducer (MFT) KPTCL Material I.no-24.5.2 & Fixing and wiring of MFT KPTCL Labour I.no-29-H-c
8 Channel 110 V Opto Coupler. KPTCL Material I.no-24.5.1 & Fixing and wiring of Opto Coupler. KPTCL Labour I.no-29-H-b
Copper control cable 4x4 sqmm for CT termination. KPTCL Material I.no-13.7 and KPTCL Labour I.no-22-b
Copper control cable 4x2.5sqmm for PT termination. KPTCL Material I.no-13.6 and KPTCL Labour I.no-22-b
Signal cable : Armoured Copper 10C x 0.5 Sq mm multistrand (2 runs - 1 run for MFM & 1 run for DI) (between C&R panel to RTU panel) KPTCL Material I.no-24.4.1 & Laying & termination of DI/DO/Communica...
Control cables:- 10C x 1.5 Sq mm multistrand, conforming to KPTCL specification (between C&R panel to RTU panel) KPTCL Material I.no-24.4.2 & Laying & termination of DI/DO/Communication Cables KPTCL L...
Configuration of RTU and Engineering along with validation of data at SLDC. KPTCL Labour I.no-29-H-d
Miscellaneous and rounding off (like welding, drilling,cutting etc)
Providing MEI make PCVCB foundation at 66/11 kV MUSS Baguru.
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .