Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.4 LAccepted-Finance | L1 | Accepted-Finance Qualified | |
| 2 | L2₹3.4 L+₹1,268 (0.37%)Accepted-Finance | L2 | Accepted-Finance Qualified | |
| 3 | Rejected-Technical | - | Rejected-Technical Rejected for non compliance to technical specification |
Tender Value
₹3.4 L
EMD Value
₹6,880
Closing Date
4 Nov 2024, 11:00 amClosed
Ex Engineer ED Awantipora
ED Awantipora
Installation of 63 KVA Sub-station at indoor sports hall tral Pulwama
2024_PDD_261749_1
EDA-21of2024-25Dt-22-10-2024
Open Tender
Electrical Works
Turn-key
30 days
Tral
please refer to SBD
3 documents required · 3 mandatory
₹200
Yes
Ex. Engineer ED Awantipora
₹6,880
Yes
24 Dec 2024
22 Oct 2024
4 Nov 2024
22 Oct 2024
4 Nov 2024
23 Oct 2024
23 Oct 2024 - 23 Oct 2024
Amount
Supply,installation,testing,commissioning including Loading, Transportation , insurance, Unloading, Carriage and Delivery at Site of 63KVA, 11/0.433 kV Distribution Transformer, Energy Efficiency Level-II, Aluminium Wound, oil filled, with LT cable termination box with detachable Aluminium Gland Plate.
Supply, Errection,testing & commissioning including loading, transportation, insurance, unloading, carriage and delivery at site of 9 Mtr long ST Poles SP-33 including excavation of pole pits.
Supply, Errection,testing & commissioning including loading, transportation, insurance, unloading, carriage and delivery at site of 8 Mtr long ST Poles SP-15 including excavation of pole pits.
Supply, Laying,testing, stringing, tensioning and binding of conductor ACSR 0.05 (Rabibit) including pre-tensioning for removal of kinks, fixing of hardware fittings and jointing as per standard practices and mechanical/manual carriage upto site.
Providing & fixing of Earthing Complete by GI Pipe 40 mm 3 mtr long through GI Strip 25x3 mm. as per REC Standards/drawings.
Supply and painting of each Pole 1 coat red oxide paint and 2 coats of aluminium paint (@ 1 ltr/pole red oxide paint and 1 ltr/pole aluminium paint) inscribed with permenent marking on each pole viz. name of scheme - 2021-22/xx - xxmeans pole numbers say 01,02.....
Providing, errection, testing & commissioning of G.I channel cross arms, G.I V-Cross arms, Sub-station channels (G.I) & Angle Iron Braces (G.I), transformer beltings, including back clamps for fixing cross arms etc fabricated of different sizes (REC Standard) & to be fixed with GI Nuts & Bolts and washers without drilling/punching holes in the poles.
Providing & and fixing of 11 kV Pin Insulators (polymer) with Pins ( 5 KN)
Providing & fixing of 11 kV, G.O AB Switch , 3-phase, 200A (09 insulator post type) with arragement for pad locks & operating rod . The operating rod should be G.I Pipe (B-class) of 25 mm dia of requisite length.
Providing & fixing of 11 kV Horn, Gap Fuse 3-phase 100A
Providing & fixing Supply and installation of Gapless Surge Arrestor,9 kV,10 kA, LA with (polymer) housing, Station Type
providing and fixing of LT fuse set complete by using Angle iron of size 45x 40 x 3mm------ 6ft. Long ( cement grounting} - 2 numbers with insulators etc.
Providing & fixing of Single Core Aluminum (Al.) LT Power Cable (1.1 KV grade) 185 mm sq cross section un-armoured XLPE cable with Thermoplastic tape inner sheath from the LT bushes upto the overhead LT bare conductor.
Providing, laying of Cement bottoming 1:2:4 mix as per REC standards 0.5 cum/pole including muffing 20 cm above ground level, plaster and curing of concrete.
Providing, laying of Cement bottoming 1:2:4 mix as per REC standards 0.45cum/pole including muffing 20 cm above ground level, plaster and curing of concrete.
Providing & fixing of P.G. clamps for fixing of LT cable with distribution transformers having capacity upto 100 kVA
Providing & fixing of 185 mm sq Aluminum Thimbles for cable terminations
Providing and and fixing of 3 No. sub station earthing by GI Pipe 40 mm or GI Rod 20mm, 2.5 mtr long through GI Strip of 50X6 for neutral earthing and 25X3 mm for 2 transformer body earth, two no. pole earth, 1 no. LA Earth and 1 no. GO handle earth as per REC approved construction standards with F5, F10 & J2 drawings issued by REC as reference. Each electrode to be connected through double GI strips to be fixed on baby insulators. The termination should be bolted and not welded.
Providing and fixing of shackle insulators (polymer) ( 16 KN) with GI back clamps to be fixed without drilling/punching of poles on ST poles.
Pre and Post Geo Tagged Photograph
M/S KHAN ELECTRICAL ENTERPRISES (BID ID -2210500)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .