Loading…
Loading…
Tender Value
₹3.0 Cr
EMD Value
₹6.1 L
Closing Date
11 Sept 2026, 3:00 pm
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
60 days
Expenditure
Capital (Works)
GENERAL
14 conditions · 3 needing a document upload
The tenderer must have minimum average annual contractual turnover of 'V/N' crores or 'V' crores whichever is less; where V= Advertised value of the tender in crores of Rupees N= Number of years prescribed for completion of work for which bids have been invited. The average annual contractual turnover shall be calculated as an average of "total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/ audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover. The tenderers shall submit requisite information as per Annexure-VIIB of PART-V of Tender Document , along with copies of Audited Balance Sheets duly certified by the Chartered Accountant/ Certificate from Chartered Accountant duly supported by Audited Balance Sheet. Please refer Clause 3.5 of PART-I of Tender Document.
Technical Eligibility Criteria:- The tenderer must have successfully completed or substantially completed any one of the following categories of work(s) during last 07 (seven) years, ending last day of month previous to the one in which tender is invited: Three similar works each costing not less than the amount equal to 30% of advertised value of the tender, or Two similar works each costing not less than the amount equal to 40% of advertised value of the tender, or One similar work each costing not less than the amount equal to 60% of advertised value of the t e n d e r . Definition of Similar Nature of work:- Design,Supply,Installation,Testing & Commissioning of HT/LT network like HT/LT Panel,Overhead distribution network,earthing,laying of HT/LT cable etc.& associated electrical works. Please refer Clause 3.4 and Clause 3.5 of PART-I of Tender Document. NOTE:- Work experience certificate from private individual shall not be considered. However, in addition to work experience certificates issued by any Govt. Organization, work experience certificate issued by Public listed company having average annual turnover of Rs 500 crore and above in last 3 financial years excluding the current financial year, listed on National Stock Exchange or Bombay Stock Exchange, incorporated/registered at least 5 years prior to closing of tender, shall also be considered provided the work experience certificate has been issued by a person authorized by the Public listed company to issue such certificates. In case tenderer submits work experience certificate issued by public listed company, the tenderer shall also submit along with work experience certificate, the relevant copy of work order, bill of quantities, bill wise details of payment received duly certified by Chartered Accountant, TDS certificates for all payments received and copy of final/last bill paid by company in support of above work experience certificate.
Special Eligibility Criteria:- Tenderers should possess a valid electrical contractor license at the time of opening of tender, issued by any state government & same should be submitted along with tender documents by all bidders including working contractors of this unit otherwise offer shall be SUMMARILY REJECTED.
29 conditions · 4 needing a document upload
Tenderer Shall submit COVER LETTER (TENDER FORM-1) as per Section 4.2 of PART-I of Tender Document duly filled. The Cover Letter must be submitted by the Tenderer on its letter head. Please refer Section 4.2 COVER LETTER , TENDER FORM-1 of PART-I of Tender Document.
The tenderer shall clearly specify whether the tender is submitted on his own (Proprietary Firm) or on behalf of a Partnership Firm / Company / Joint Venture (JV) / Registered Society / Registered Trust / Hindu Undivided Family (HUF) / Limited Liability Partnership (LLP) etc. The tenderer(s) shall enclose the attested copies of the constitution of their concern, and copy of PAN Card along with their tender. Tender Documents in such cases are to be signed by such persons as may be legally competent to sign them on behalf of the firm, company, association, trust or society, as the case may be.Tenderer shall submit the documents as mentioned in Clause 3.7 of of PART-I of Tender Document. The tenderer whether sole proprietor / a company or a partnership firm / joint venture (JV) / registered society / registered trust / HUF/ LLP etc. if they want to act through agent or individual partner(s), should submit along with the tender, a copy of power of attorney duly stamped and authenticated by a Notary Public or by Magistrate in favour of the specific person whether he/they be partner(s) of the firm or any other person, specifically authorizing him/them to sign the tender, submit the tender and further to deal with the Tender/ Contract up to the stage of signing the agreement except in case where such specific person is authorized for above purposes through a provision made in the partnership deed / Memorandum of Understanding / Article of Association /Board resolution, failing which tender shall be summarily rejected . Format of POA is given in TENDER FORM-3 of PART-I of Tender Document. A separate power of attorney duly stamped and authenticated by a Notary Public or by Magistrate in favour of the specific person whether he/they be partner(s) of the firm or any other person, shall be submitted after award of work, specifically authorizing him/them to deal with all other contractual activities subsequent to signing of agreement, if required. Note: A Power of Attorney executed and issued overseas, the document will also have to be legalized by the Indian Embassy and notarized in the jurisdiction where the Power of Attorney is being issued. However, the Power of Attorney provided by Bidders from countries that have signed the Hague Legislation Convention 1961 are not required to be legalized by the Indian Embassy if it carries a conforming Appostille certificate. The tenderer shall submit all the relevant documents mandatorily as mentioned in Clause 3.7 of PART-I of Tender Document.
Necessary information about Employment/Partnership etc. of Retired Railway Employee as per details mentioned in Clause 3.12 of PART-I of Tender Document should be given by tenderer . If no Retired Railway Employee is employed by tenderer then the tenderer shall submit an Undertaking as in Annexure-XXVI of PART-V of Tender Document that no railway employee is employed. Note:- If information as required as per above clause has not been furnished, contract is liable to be dealt in accordance with provision of clause 62 of PART-II of GCC-2022.
Tenderer should submit documents related to registration Details, PAN, GSTIN, Registered Address, Bank Details etc.
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
The tenderer shall submit along with the tender document, documents in support of his/their claim to fulfill the eligibility criteria as mentioned in the tender document. Each page of the copy of documents/certificates in support of credentials, submitted by the tenderer, shall be self-attested/digitally signed by the tenderer or authorized representative of the tendering firm. Self attestation shall include signature, stamp and date (on each page). Only those documents which are declared explicitly by the tenderer as "documents supporting the claim of qualifying the laid down eligibility criteria", will be considered for evaluating his/their tender.
The Railway reserves the right to verify all statements, information and documents submitted by the bidder in his tender offer, and the bidder shall, when so required by the Railway, make available all such information, evidence and documents as may be necessary for such verification. Any such verification or lack of such verification, by the railway shall not relieve the bidder of its obligations or liabilities hereunder nor will it affect any rights of the railway there under.
In case of any wrong information submitted by tenderer, the contract shall be terminated, Bid security, Performance Guarantee (PG) and Security Deposit (SD) of contract forfeited and agency barred for doing business on entire Indian Railways for 5 (five) years.
The GST Act 2017 will be applicable as per extant policy as notified by Central/State Govt. and as amended from time to time. All the bidders/tenderers should ensure that they are GST compliant and their quoted rates are inclusive of taxes and GST @ 18%.
No Post Tender correspondence for submission of additional documents shall be entertained after opening of the Technical & Commercial offers. Even suo-moto post tender letters of the tenderers shall be treated as NULL & VOID. (Authority HQ Letter No. 74-W/O/Pt.XXV/WA/Loose dated 07.04.15).
The contract will be governed by Indian Railways Standard General Conditions of Contract updated with correction slips issued up to date of inviting tender or as otherwise specified in the tender documents.
Conditional offer and Alternative proposal by Tenderer: Tenderers shall submit offers that fully comply with the requirements of the Tender documents including the conditions of contract, design and specification requirements if any. Conditional offer or alternative offers will not be considered in tender evaluation and will be summarily rejected. The Tenderer shall have no claims in this regard whatsoever. "Any unconditional rebate offered by the tenderer should be mentioned on of 'Schedule of Quantities' specifically. To attract the rebate mentioned each page of schedule may refer the note for the conditional rebate mentioned in the end. Any rebate mentioned at any other place in tender document shall not be considered. The unconditional rebate mentioned in "Scheduled of Quantities" shall be considered while evaluation of bid." mentioned in the end. Any rebate mentioned at any other place in tender document shall not be considered. The unconditional rebate mentioned in "Scheduled of Quantities" shall be considered while evaluation of bid."
Electrical Work for Augmentation of Power Supply in stations and Railway Areas for Passenger Amenities Including Additional Work of Facade Lighting in the Section- LRJ-HW-MOTC-YNRK & RWL-DDN.
29_SrDEE_G_MB_2026~NR
29_SrDEE_G_MB_2026
Open
Works - General
4 Months
Moradabad, Uttar Pradesh
₹0
₹6.1 L
20 Aug 2026
20 Aug 2026
28 Aug 2026
59 items across 1 schedule
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 3,02,63,619.52 | ||
| — | — | — | 9,49,900 | ||
| Design, Fabrication, Supply, Fixing and commissioning of double door IP 55 Feeder Pillar ( Size- 700 mm x 700 mm x 450mm.) made of Angle Iron size - 40x40x6 mm. covered from all sides with MS Sheet 16 SWG including door with hinge, Locking arrangement, nut & bolts, Aluminum Bus Bar Size-40 x 10 mm. RYB Aluminium Bus Bar setup typically refers to a three-phase (Red, Yellow, Blue) electrical conductor system used for power distribution, featuring an approximate current capacity of 400 A. Bakelite Gutka, cable glands, Earthing points, Cement, sand, interconnections etc. and grouting with sand & cement and painting with two coats of enamel grey paint over a coat of red oxide primer for antirust complete in all respect & as per site requirement. | — | 70.00 | — | — | |
| — | — | — | 5,68,874.68 | ||
| "Manufacture, supply, fixing and commissioning of fully automaticprogrammable control panel (as per CEE/NR spec. no. CEE/70Elect/P/90/Rev-4/2010 or latest version for 3 phase 440 V 50/40/30/25/20 HP pump set (Submersible, vertical shaft etc.). Connecting of voltmeter, Ammeter, contactor, overload relay, CT/AC step down transformer 220V/12 volts . Auxiliary relay, changeover, AC timer, motor start/stop contact, push button selector switch, indication light, auto manual, selector switch, Aluminum bus bar, MCCB FP, 100A 35KA,Time delay relay, Programmable timer with 48 hrs. memory back up, Single Phase Preventor, terminal block earthing bolt/connection as per technical specification attached & as per site requirement of following size:- (i) 35 HP" | — | 11.00 | — | — | |
| — | — | — | 5,01,724.88 | ||
| Supply, installation, connection, testing and commissioning of 11 KV ( E ), 350 MVA, 630 Amps., HT.Vacum Circuit Breaker ( VCB) type VMX with Panel Board with CT, PT, & Static Relay atc. comprising of 01 No. Incoming / Outgoing Panel including its inter connections complete in all respect as per tech. specification and site requirement. Note:- VCB/SF-6 HT breaker, Isolators, ACB's, MCCB's etc shall be of either ABB/Siemens/Schneider/L&T make or similar reputed make. | — | 1.00 | — | — | |
| — | — | — | 10,91,607.82 | ||
| Supply, installation,connection, testing and commissioning of 11 KV (E ), 350 MVA, 630 Amps., HT.Vacum Circuit Breaker( VCB) type VMX with Panel Board with CT, PT, & Static Relay atc. comprising of 01 No. Incoming & 02 Nos. Outgoing Panel including its inter connections complete in all respect as per tech. specification and site requirement.Note:- VCB/SF-6 HT breaker, Isolators, ACB's, MCCB's etc shall be of either ABB/Siemens/Schneider/L&T make or similar reputed make. | — | 1.00 | — | — | |
| — | — | — | 29,93,070 | ||
| Provision of 6KVA/192 VDC 1 Ph 1/P and 1PH O/P ON LINE UPS with 120MNS BACK UP using 14400VAH of SMF Batteries with Rack and intercell connector. | — | 19.00 | — | — | |
| — | — | — | 3,19,517.1 | ||
| "Design, manufacture, supply, installation, testing and commissioning of Microprocessor based three phase Automatic Power Factor Correction system as per relevant IS and site requirement: (i) 100 KVAR | — | 2.00 | — | — | |
| — | — | — | 13,45,800 | ||
| Supply, installation, testing , commissioning of Online 2 X 1 KVA UPS with battery backup for 120 minutes (2 Hrs) as per technical specification | — | 30.00 | — | — | |
| — | — | — | 12,43,248 | ||
| Supply of Customized Extension Board with 4 meter cord with top with the accessories. (1) 6Amp P/switch -03 nos. (2) 6Amp P/socket-3 nos.(3) 16 Amp/switch- 01 no. (4) 16 Amp P/socket -1 no. (5) Indication Lamp -01 no. (6) MCB 16 Amp SP C type 10KA complete in all respect & as per site requirement. | — | 800.00 | — | — | |
| — | — | — | 1,67,560 | ||
| Supply & fixing of 4 poles ON Load Changeover Switch in Steel Sheet Enclosure, Rating 400 Amps., 415V, 50Hz, confirming to IS/IEC 60947-3 Door Interlock and Padlock facility as per technical specifications. | — | 5.00 | — | — | |
| — | — | — | 94,282 | ||
| Supply & Fixing of 200 Amp 4 pole, 415V AC, manually operated on-load changeover, having Lever/rotary handle with positive switching, sheet steel enclosure type confirming to IS/IEC: 60947-3 or latest as per technical specifications. | — | 10.00 | — | — | |
| — | — | — | 5,83,393.92 | ||
| Supply, installation, testing & commissioning of 90W Narrow Beam RGBW LED Projector Lights with following technical features: Aluminium Die- casting body with plastic coated surface, each LED with a rod for heat transfer having UV stabilized toughened glass front cover, luminary should be round shaped to provide asymmetric beam angle suitable for architectural facade lighting, Tilt : adjustable through 180 degree or more, IP66 or greater ingress protection for outdoor application suitability, secondary optical lenses provided on each LED of fitting with suitable narrow beam angle, DMX compatibility with inbuilt decoder. Control Mode : DMX512, DMX Controller can achieve 16.7M colors, Rated Input Supply of LED: Highly reliable DC 24V constant voltage power supply which drives the RGBW LEDs High Power LED Make : PHILIPS/ CREE/ LUMINOUS/ OSRAM/ SAMSUNG/ NICHIA/ SEOUL/ LUMILEDS or similar, Power Consumption : 90W (approx.) per fixture however as per requirement wattage may be increased / decreased to meet the desired effect of Facade. Power Efficiency : >85%, Power factor : >0.9, Operating Frequency : 50 Hz, Operating temperature : -10 to +55 degree centigrade, Life Span : >50000 hours, Warranty : 5 Years, Electrical Safety Class : Class 1..OEM must have its own inhouse NABL set up with I LAC accredited lab equipped with C type Photogonio meter as per IES ANSI 2019 for all for all testing approved scope for LED fixture. The bidder should submit ISO 9001 : 2015 certificates of concerned OEM duly issued by Bureau Of Indian Standard (BIS) | — | 16.00 | — | — | |
| — | — | — | 78,631.84 | ||
| Supply, installation, testing &commissioning of 150W RGBW Projector Lights driver with necessary connections and following technical details : DC24V Constant Voltage Switch Mode Power Supply,Water proof IP65 or above ingress protection, efficiency more than 85%. Operating temperature : -30 to+65 degree centigrade, THD less than 20%, Warranty : 5 Years, Electrical Safety Class : Class 1. | — | 28.00 | — | — | |
| — | — | — | 4,85,832.4 | ||
| "Supply, installation, testing, commissioning & Programming of RGB/ DMX Controller System withfollowing features : Standalone interfaces, Input Connector, Mini USB- including mini USB Cable, Output Connector, XLR3/XLR5, DMX Output- 512 & 1024 Channels, PC DMX In triggering capability, Master/Slave connection capability, DMX speed - 1 to 45 Hz, MaB/Vk, internal clock and internal calendar enabled] inbuilt internal memory, data display system, system compatibility with Windows/MAC/LINUX with 32/ 64 bit CPU technology to be installed in IP65 Waterproof Junction Box with necessary connection. Warranty : 5 Years.. " | — | 4.00 | — | — | |
| — | — | — | 8,51,418.54 | ||
| Supply, installation, testing & commissioning of 44 watt/ 48 watt RGBW LED Linear Wall Washer with following technical features: Aluminium Die- casting body with Surface anodic oxidation and UV stabilized toughened glass front cover, luminary should be linear shaped suitable for illumination of wall facade lighting, Tilt : as per requirement, IP-66 or greater ingress protection for outdoor application suitability, secondary optical lenses provided on each LED of fitting with suitable narrow beam angle, DMX compatibility with inbuilt decoder. Control Mode : DMX512, DMX Controller can achieve 16.7M colors, Rated Input Supply of LED: Highly reliable DC 24V constant voltage power supply which drives the RGBW LEDs High Power LED Make : PHILIPS/ CREE/ LUMINOUS/ OSRAM/ SAMSUNG/ NICHIA/ SEOUL/LUMILEDS or similar, Power Consumption : 44W (approx.) per fixture however as per requirement wattage may be increased / decreased to meet the desired effect of Facade. Power Efficiency : >85%, Power factor : >0.9, Operating Frequency : 50 Hz, Operating temperature : -10 to +55 degree centigrade, Life Span : >50000 hours, Warranty : 5 Years, Electrical Safety Class : Class 1.OEM must have its own inhouse NABL set up with I LAC accredited lab equipped with C type Photogonio meter as per IES ANSI 2019 for all for all testing approved scope for LED fixture. The bidder should submit ISO 9001 : 2015 certificates of concerned OEM duly issued by Bureau Of Indian Standard (BIS) | — | 54.00 | — | — | |
| — | — | — | 1,83,815.04 | ||
| "Supply, installation, testing & commissioning of 200 watt DC24V Constant Voltage driver withfollowing features: DC24V Constant Voltage Switch Mode Power Supply, Waterproof IP65 or above ingress protection, efficiency more than 85%. Operating temperature : -30 to +65 degree centigrade, THD less than 20% with necessary connections, Warranty : 5 Years, Electrical Safety Class : Class 1." | — | 48.00 | — | — | |
| — | — | — | 53,99,773.5 | ||
| Supply, installation, testing & commissioning of 24W RGBW LED Linear Wall Washer with following technical features: Aluminium Die- casting body with Surface anodic oxidation and UV stabilized toughened glass front cover, luminary should be linear shaped suitable for illumination of wall facade lighting,Tilt : as per requirement, IP-66 or greater ingress protection for outdoor application suitability, secondary optical lenses provided on each LED of fitting with suitable narrow beam angle, DMX compatibility with inbuilt decoder. Control Mode : DMX512, DMX Controller can achieve 16.7M colors, Rated Input Supply of LED: Highly reliable DC 24V constant voltage power supply which drives the RGBW LEDs High Power LED Make : PHILIPS/ CREE/ LUMINOUS/ OSRAM/ SAMSUNG/ NICHIA/ SEOUL/ LUMILEDS or similar, Power Consumption : 24W (approx.) per fixture however as per requirement wattage may be increased / decreased to meet the desired effect of Facade. Power Efficiency : >85%, Power factor : >0.9, Operating Frequency : 50 Hz, Operating temperature : -10 to +55 degree centigrade, Life Span : >50000 hours, Warranty : 5 Years, Electrical Safety Class : Class 1..OEM must have its own inhouse NABL set up with I LAC accredited lab equipped with C type Photogonio meter as per IES ANSI 2019 for all for all testing approved scope for LED fixture. The bidder should submit ISO 9001 : 2015 certificates of concerned OEM duly issued by Bureau Of Indian Standard (BIS) | — | 550.00 | — | — | |
| — | — | — | 1,45,533.96 | ||
| Supply, installation, testing & commissioning of 120 watt RGBW/ Warm White Flood light up exterior wall facade of new building with following features: Aluminium Die- casting body with surface anodic oxidation and UV stabilized toughened glass on the front, Rectangular shaped luminary suitable for wall facade application, adjustable tilt as per site requirement, Suitable beam angle as per site requirement. LED Make : PHILIPS/ CREE/ LUMINOUS/ OSRAM/ SAMSUNG/ NICHIA/ SEOUL/ LUMILEDS or similar, IP66 ingress protection, Power Consumption : 120W per fixture however as per requirement wattage may be increased / decreased to meet the desired effect of Facade. Input Voltage: AC 220V, Power Efficiency : >85%, Power factor : >0.9, Operating Frequency : 50 Hz, Output Color : Warm white, Life Span : >50000 hours, Warranty : 5 Years, Electrical Safety Class : Class 1..OEM must have its own in house NABL set up with I LAC accredited lab equipped with C type Photogonio meter as per IES ANSI 2019 for all for all testing approved scope for LED fixture. The bidder should submit ISO 9001 : 2015 certificates of concerned OEM duly issued by Bureau Of Indian Standard (BIS) | — | 12.00 | — | — | |
| — | — | — | 1,78,070.76 | ||
| Supply, installation, testing & commissioning of Junction Box with following features : 18 SWG CRCA sheet steel enclosure. Complete with cable gland arrangement with Panel lock for fixing doors. Complete with 1 no. 16A SP MCB. | — | 6.00 | — | — | |
| — | — | — | 72,674 | ||
| Supply & laying of DWC pipe 63 mm dia. Complete in all respect & as per site requirement. | — | 700.00 | — | — | |
| — | — | — | 19,59,216 | ||
| Supply, installation, testing and commissioning of DMX Splitter cum Booster, Input Power- 100 to 240 VAC, auto-ranging, 50/60 Hz, housing rugged aluminium, Operation Temperature- 17°C - +55°C (0°F 131°F), 5/6 output ports with 3/5-pin terminal sockets, each port should be optically isolated, Protection Rating IP20 including connection complete as required. | — | 24.00 | — | — | |
| — | — | — | 3,59,430 | ||
| Supply Erection testing and commissioning of DMX signal cable/shielded Cat. 6 or better data cable shall be used for digitalcommunication networks. Size and quantity of cable shall be as persite requirement and as per site requirement. Copper lugs,glands of proper size shall be used for connections. | — | 3000.00 | — | — | |
| — | — | — | 3,51,500 | ||
| "Supply and recessing/fixing of PVC conduit pipe with accessories, junction box etc.as per technical specifications. PVC conduit pipe conforming to IS: 9537 Part-III. 1987 (Latest version) Size: 25 mm dia (Heavy) for roof. Note:- On ceiling/locations where provision of recess conduit is not possible then conduit will be provided on surface as per site condition and as per instruction by Rly. Representative." | — | 3700.00 | — | — | |
| — | — | — | 1,51,200 | ||
| Supply, laying, connecting and commissioning of 3 core 2.5 Sq mm copper flat cable. | — | 1200.00 | — | — | |
| — | — | — | 3,48,580 | ||
| Supply, laying, connecting and commissioning of 3 core 4 Sq mm copper flat cable. | — | 2000.00 | — | — | |
| — | — | — | 18,29,000 | ||
| Supply,installation,testing & commissioning of 11 kV, 630A, 21 kA/3 sec, outdoor motorized type RMU, 4-way (4 modules) comprising 1 No. VCB incomer and 3 Nos. VCB outgoing feeders, complete with motorized operating mechanism, rotary operating handle, protection relays, digital multifunction meters, CTs, VPIS, cable bushings, interlocking and all standard accessories, conforming to relevant IEC standards, complete in all respects as per technical specifications.(Make:- ABB SafePlus XT type or similar reputed make). | — | 1.00 | — | — | |
| — | — | — | 18,29,000 | ||
| Supply,installation,testing & commissioning of 11 kV, 630A, 21 kA/3 sec, outdoor motorized type RMU, 4-way (4 modules) comprising 2 No. VCB incomer and 2 Nos. VCB outgoing feeders, complete with motorized operating mechanism, rotary operating handle, protection relays, digital multifunction meters, CTs, VPIS, cable bushings, interlocking and all standard accessories, conforming to relevant IEC standards, complete in all respects as per technical specifications.(Make:- ABB SafePlus XT type or similar reputed make). | — | 1.00 | — | — | |
| — | — | — | 29,36,785.18 | ||
| Design, Supply, fixing, testing and commissioning outdoor type dust & vermin proof LT panel (floor/plinth mounted, IP:55 minimum) fabricated with 2mm thick CRCA sheet steel powder coated with siemens grey, FRP coated etc. as per detailed specification, comprising with the following MCCBs fixed in it conforming to IEC 60947 or latest with digital measuring instrument & Aluminium bus-bar arrangement panel should be confirming to IEC/IS 61439 or latest and as per IE rules and site requirement & as per explanatory note: (a) 4P MCCB 200 Amps 36 KA with adjustable thermal & fixed magnetic release having Extended Rotary Handle and Spreader Terminals - 4 Pole (Set of 4), on/off/trip Indicating Lamps, RYB Phase Indicating Lamps, Energy Meter with RS 485 Port , 6 amp control SP MCBs, Neutral Links complete in all respect with all standard accessories and hardware required at site==02 Nos (Incomer). (b) 4P MCCB 63 Amps 25 KA with adjustable thermal & fixed magnetic release=8 Nos. (Outgoing). (c) 4P MCCB 63 Amps 25 KA with adjustable thermal & fixed magnetic release=2 Nos. (ICOG). All MCCB in Outgoing/ICOG circuit will be provided with Extended Rotary Handle and Spreader Terminals - 4 Pole (Set of 4), indication lamps etc. Panel shall be complete with Aluminium busbar of 500 A with heat shrinkable PVC sleeves, spreader terminals, handle, meters, indication lamps & other accessories. | — | 7.00 | — | — | |
| — | — | — | 25,17,244.44 | ||
| "Design, Supply, fixing, testing and commissioning outdoor type dust & vermin proof LT panel (floor/plinth mounted, IP:55 minimum) fabricated with 2mm thick CRCA sheet steel powder coated with siemens grey, FRP coated etc. as per detailed specification, comprising with the following MCCBs fixed in it conforming to IEC 60947 or latest with digital measuring instrument & Aluminium bus-bar arrangement panel should be confirming to IEC/IS 61439 or latest and as per IE rules and site requirement & as per explanatory note: (a) 4P MCCB 400 Amps 36 KA with adjustable thermal & fixed magnetic release having Extended Rotary Handle and Spreader Terminals - 4 Pole (Set of 4), on/off/trip Indicating Lamps, RYB Phase Indicating Lamps, Energy Meter with RS 485 Port , 6 amp control SP MCBs, Neutral Links complete in all respect with all standard accessories and hardware required at site=01 Nos (Incomer). (b) 4P MCCB 100 Amps 25 KA with adjustable thermal & fixed magnetic release=7 Nos. (Outgoing). (c) 4P MCCB 125 Amps 25 KA with adjustable thermal & fixed magnetic release=1 Nos. (Outgoing as Spare). All MCCB in Outgoing circuit will be provided with Extended Rotary Handle and Spreader Terminals - 4 Pole (Set of 4), indication lamps etc. Panel shall be complete with Aluminium busbar of 500 A with heat shrinkable PVC sleeves, spreader terminals, handle, meters, indication lamps & other accessories." | — | 6.00 | — | — | |
| — | — | — | 7,26,935.46 | ||
| Design, Supply, fixing, testing and commissioning outdoor type dust & vermin proof LT panel (floor/plinth mounted, IP:55 minimum) fabricated with 2mm thick CRCA sheet steel powder coated with siemens grey, FRP coated etc. as per detailed specification, comprising with the following ACB and MCCBs fixed in it conforming to IEC 60947 or latest with digital measuring instrument & Aluminium bus-bar arrangement panel should be confirming to IEC/IS 61439 or latest and as per IE rules and site requirement & as per explanatory note. a) 1000A ACB (EDO type- electrically operated mechanism with motorized spring charging and with manual handle) type having Breaking capacity 50 KA having Closing release (XF),Opening Release (MX),Under Voltage release, Breaker Control Switch, Phase sequence relay, VMR Single phase Preventer, Auxiliary Contactor(2 NO +2 NC) ,A/M selector switch,8 inch exhaust fan with air filter ,CTs, Overload, Short- circuit, Instantaneous & Earth-fault protection, Multifunction meter RS .485 with port and 6 amp control SP MCBs complete in all respect with all standard accessories and hardware required at site =01 Nos. Incoming. b) 800A ACB (EDO type- electrically operated mechanism with motorized spring charging and with manual handle) type having Breaking capacity 50 KA having Closing release (XF),Opening Release (MX),Under Voltage release, Breaker Control Switch, Phase sequence relay, VMR Single phase Preventer, Auxiliary Contactor(2 NO +2 NC) ,A/M selector switch,8 inch exhaust fan with air filter ,CTs, Overload, Short-circuit, Instantaneous & Earth-fault protection, Multifunction meter RS .485 with port and 6 amp control SP MCBs complete in all respect with all standard accessories and hardware required at site =01 Nos. Incoming (including solar controller & other required accessories for 01 Nos. Incoming from Solar plant). c) 4P MCCB 400Amps 36 KA with adjustable thermal & fixed magnetic release = 01 Nos. (Outgoing). d) 4P MCCB 250Amps 36 kA with adjustable thermal & fixed magnetic release =02 Nos. (Outgoing). e) 4P MCCB 125 Amps 36 kA with adjustable thermal & fixed magnetic release =04 Nos. (Outgoing). All MCCB in Outgoing circuit will be provided with Extended Rotary Handle and Spreader Terminals - 4 Pole (Set of 4). Panel shall be complete with Aluminium busbar of 1000 A, spreader terminals, handle, meters, indication lamps & other accessories. | — | 1.00 | — | — |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
correctionslipsmerged_compressed.pdf GCC correction slips
ATTACHMENT
JPODigging.pdf
ATTACHMENT
CEESpec.no.70-Elect-P-Rev-4-2010.pdf Starter specification
ATTACHMENT
Tenderdocument-29-2026R.pdf
ATTACHMENT
I.R.GCC_April-2022.pdf
ATTACHMENT
Annexure-U.pdf
ATTACHMENT
letterofcredit.pdf
ATTACHMENT
correctionslipsmerged_compressed.pdf
ATTACHMENT
CEESpec.no.70-Elect-P-Rev-4-2010.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].