| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹24.2 LAdmitted-Finance | ₹24.2 L | L1 | Admitted-Finance |
| 2 | L2₹32.8 LAdmitted-Finance | ₹32.8 L | L2 | Admitted-Finance |
| 3 | Rejected-Technical | - | - | Rejected-Technical Not enlisted in requisite category |
| Sl No | Description | Qty | Unit | S.S.ENGINEERING CORPORATION L1 | EXELLENT POWER CORPORATION L2 |
|---|---|---|---|---|---|
| 1.00 | Opening covers of covers AHU, descaling of the AHU coil to bring down the high pressure, cleaning of the dust particles formed on the coil system with diluted 'ASFOCLEAN' chemical or Caustic Soda by pouring on the coil with leg pump or mechanical system till the clearing of the dust on the coil as primary wash and using detergent powder or surf water as final wash, testing complete all as directed. | 71 | Each Job | 900 ₹63,900 | 2,800 ₹2.0 L |
| 2.00 | Dismantling and taking out unserviceable canvas cloth box from AHU unit, supply and fixing new canvas cloth box including mild steel frames, refixing with new nuts, bolts, washers, gasket etc., testing complete all as directed. | 5 | Each Job | 2,500 ₹12,500 | 2,359 ₹11,795 |
| 3.00 | Disconnecting Induction motor electrically and mechanical connections upto 5 HP capacity and dismounting from mono block / centrifugal pumpset / AHU motor, cooling tower by arranging dummy plates to suction and delivery line, rewinding, varnishing, insulation, overhauling, greasing the mono block pumpset, replacing of bearings etc., with new ones and fixing back in original position, connecting and testing complete all as directed. | 5 | Each Job | 4,500 ₹22,500 | 7,470 ₹37,350 |
| 4.00 | All as per item No 3 above but, above 5HP and upto 15 HP capacity | 3 | Each Job | 9,000 ₹27,000 | 7,384 ₹22,152 |
| 5.00 | All as per item No 3 above but, above 15 HP and upto 20 HP capacity | 3 | Each Job | 15,500 ₹46,500 | 15,687 ₹47,061 |
| 6.00 | Disconnecting blower shaft of AHU 7.5TR to 40 TR capacity, taking out the defective shaft, remetalling grinding, machining and balancing the shaft, refixing and realigning the blower including testing complete all as directed. | 2 | Each Job | 10,000 ₹20,000 | 13,892 ₹27,784 |
| 7.00 | Disconnecting the mono block pumpset upto 5 HP capacity by arranging dummy plates to suction and delivery line, supply and fixing new mono block pumpset (motor and pump) 5HP, 5 star Rating of 7.1 Litres per Second discharge at not less than 40 m head complete all as specified and directed. | 1 | Each Job | 37,500 ₹37,500 | 56,320 ₹56,320 |
| 8.00 | All as per item No 7 above but, above 5 HP and upto 10 HP capacity of 7.8 LPS at not less than 40 mtr Head | 1 | Each Job | 57,000 ₹57,000 | 60,907 ₹60,907 |
| 9.00 | All as per item No 7 above but, above 10 HP and upto 15 HP capacity of 12.5 LPS at not less than 40 mtr Head
Make for item No 07 to 09 : Grundfos, Kirloskar, Crompton Greaves, Jyothi | 1 | Each Job | 85,000 ₹85,000 | 79,464 ₹79,464 |
| 10.00 | Disconnecting electrically operated mono block/ centrifugal pumpset / AHU upto 5 HP capacity and mechanical connections from position by arranging dummy plates to suction and delivery line, removing from the existing position, overhauling, cleaning the impeller, replacing the worn out bearing, impeller, gland bush, gland nut, gland rope, etc., with new ones, greasing, fixing back and testing complete all as directed.
Note: 1. Impeller,Bearing, gland bush will be measured and paid separately. 2. Gland bush,gland nut, gland rope etc are deemed to be included in quoted rate. | 5 | Each Job | 3,500 ₹17,500 | 3,400 ₹17,000 |
Updated dates
Tender Value
₹45 L
EMD Value
₹90,000
Closing Date
26 Nov 2025, 6:00 pmClosed
GE(I) R AND D RCI, HYDERABAD
GE(I) RND RCI, MILITARY ENGINEER SERVICES, VIGNYANAKANCHA, RCI, HYDERABAD
REPAIRS OF AIR HANDLING UNITS TOWERS CONDUCTOR UNITS CHILLER WATER LINES SUPPLY AND RETURN DUCTS MODULATORY VALVES PCBs SENSOR AND FILITERS OF AHUs AT RCI EMU AND CCE RND SOUTH UNDER GE I RND RCI HYDERABAD
2025_MES_737496_1
8338
Open Tender
Civil Works
270 days
GE(I) R AND D RCI, HYDERABAD
MES enlisted Class D category c i Un enlisted Meeting enlistment criteria of D class in MES and having no recovery pending. For further details ref NIT
8 documents required · 8 mandatory
₹500
Yes
GE(I) R AND D RCI, HYDERABAD
₹90,000
Yes
15 Dec 2025
29 Oct 2025
28 Nov 2025
29 Oct 2025
26 Nov 2025
12 Nov 2025
Opening covers of covers AHU, descaling of the AHU coil to bring down the high pressure, cleaning of the dust particles formed on the coil system with diluted 'ASFOCLEAN' chemical or Caustic Soda by pouring on the coil with leg pump or mechanical system till the clearing of the dust on the coil as primary wash and using detergent powder or surf water as final wash, testing complete all as directed.
Dismantling and taking out unserviceable canvas cloth box from AHU unit, supply and fixing new canvas cloth box including mild steel frames, refixing with new nuts, bolts, washers, gasket etc., testing complete all as directed.
Disconnecting Induction motor electrically and mechanical connections upto 5 HP capacity and dismounting from mono block / centrifugal pumpset / AHU motor, cooling tower by arranging dummy plates to suction and delivery line, rewinding, varnishing, insulation, overhauling, greasing the mono block pumpset, replacing of bearings etc., with new ones and fixing back in original position, connecting and testing complete all as directed.
All as per item No 3 above but, above 5HP and upto 15 HP capacity
All as per item No 3 above but, above 15 HP and upto 20 HP capacity
Disconnecting blower shaft of AHU 7.5TR to 40 TR capacity, taking out the defective shaft, remetalling grinding, machining and balancing the shaft, refixing and realigning the blower including testing complete all as directed.
Disconnecting the mono block pumpset upto 5 HP capacity by arranging dummy plates to suction and delivery line, supply and fixing new mono block pumpset (motor and pump) 5HP, 5 star Rating of 7.1 Litres per Second discharge at not less than 40 m head complete all as specified and directed.
All as per item No 7 above but, above 5 HP and upto 10 HP capacity of 7.8 LPS at not less than 40 mtr Head
All as per item No 7 above but, above 10 HP and upto 15 HP capacity of 12.5 LPS at not less than 40 mtr Head Make for item No 07 to 09 : Grundfos, Kirloskar, Crompton Greaves, Jyothi
All as per item No 10 above but, for above 5 HP and upto 10 HP capacity
All as per item No 10 above but, for above 10 HP and upto 15 HP capacity
S&F in repairs various size/capacity of electrical terminal box including terminal plate for monoblock/motor/pump motor complete all as directed.
Supply only gland bush of any size and type complete all as directed.
Supply only air release stud for pumps of various capacities complete all as directed.
Supply only impeller for pumps upto 15HP capacity complete all as directed.
Supply only ball bearing of size 6205 ZZ to 6209 ZZ complete all as directed.
Supply only ball bearing of size 6210 ZZ to 6213 ZZ complete all as directed.
Supply only ball bearing of size 6305 ZZ to 6309 ZZ complete all as directed.
Supply only ball bearing of size 6310 ZZ to 6313 ZZ complete all as directed.
Supply only various sizes of pillow block bearing suitable for 5000 CFM to 10000 CFM AHUs complete all as directed. Make for item No 17 to 21 : SKF, NBC
S&F in repairs, supporting system of air conditioning plant including all accessories of plants ie AHU, Pumps, Cooling tower, pipe lines etc., modification/alternation of existing elements using size of steel elements, plates, angles iron, flat, cross arms, bracing supports, clamps from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts in any shape or size including painting with two coats of synthetic enamel paint over a coat of primer complete all as specified and directed.
S&F in repairs, cooling fan blades for motors of various capacities complete all as directed.
S&F in repairs, mechanical seal for centrifugal pumpset of capacity upto 15 HP complete all as directed.
Disconnecting and removing the unserviceable burnt out timer, supply and fixing new Star Delta timer 0.3 to 30 Sec complete all as directed. Make: GE, SIEMENS, L&T, C&S, SCHNEIDER
Disconnecting and removing of the unserviceable fused dual element time delay fuse, supply and fixing new dual element time delay fuse unit TR S30R or FRN-R, 30Amps, 600V AC, 330V DC complete all as specified and directed. Make: FERRAZ SHAWMUT / FUSETRON / Bussmann or equivalent
S&F in repairs, Power contactor 50Hz, 415 Volts grade, MNX 185 Amp capacity, AC3 rating complete all as specified and directed. Make : GE, SIEMENS, L&T, C&S, SCHNEIDER
All as per item No 28 above, but for MNX 70 Amps
All as per item No 28 above, but for MNX 32 Amps
All as per item No 28 above, but for MNX 25 Amps
All as per item No 28 above, but for MNX 18 Amps
All as per item No 28 above, but for MNX 12 Amps
All as per item No 28 above, but for MNX 9 Amps
All as per item No 28 above, but for ML 1.5 Amps
All as per item No 28 above, but for ML 4 Amps
All as per item No 28 above, but for ML 3 Amps
All as per item No 28 above, but for SC N3 65 Amps
All as per item No 28 above, but for SC 03 (11) 20 Amps
All as per item No 28 above, but for CL 25 Amps
All as per item No 28 above, but for CL 45 Amps
All as per item No 28 above, but for CL 50, 125 Amps
All as per item No 28 above, but for 00/01/SFK, 25 Amps
Disconnecting and removing of unserviceable chilled water sensor / Oil Sensor from the existing position, supply and fixing new chilled water sensor / oil sensor for Trane, Dhanham bush, Carrier, York, Voltas chillers including testing complete all as directed. Make: Danfoss, ALERTON
Taking down the unserviceable burnt out HRC fuses of 32 Amp capacity and supply and fixing new HRC fuses BS size A1 to A4, F1, A1L, B1 to B3, C1 to C3 type offset / open / closed slot / single / double slot complete all as directed.
All as per item No 45 above but of 63 Amp capacity
All as per item No 45 above but of 125 Amp capacity Make for item No 45 to 47 : Seimens, L&T, Standard, Havells, C&S, Schneider
S & F in repairs, 15 mm bore steel water tubing, medium grade, ISI marked, galvanized, including all fittings such as bends, tees, elbows, reducers, unions, plugs, sockets etc., laid in trenches or fixed to walls and ceilings or concealed in walls, ducts/ceilings or laid in floors complete all as specified and directed. Make : TATA / JINDAL / PRAKASH
All as per item No 48 above but 20 mm bore of pipe.
All as per item No 48 above but 25 mm bore of pipe.
All as per item No 48 above but 40 mm bore of pipe.
S&F in repairs, 15 mm dia Gun metal, globe or gate valves with iron wheel head, ISI marked screwed both ends for iron / GI pipe and fixed complete all as specified and as directed.
All as per item No 52 above but 20 mm dia globe or gate valve.
All as per item No 52 above but 25 mm dia globe or gate valve.
All as per item No 52 above but 40 mm dia globe or gate valve.
Supply, laying welding, fixing, leak proof testing and commissioning of 50 mm bore, medium grade mild steel ERW pipes conforming to IS 1239 / 3589 with bitumen wrap coating over the external surface of the pipe including necessary specials / fittings and taking down old unserviceable pipe complete all as specified and directed. Note: Excavation and earthwork will be measured and paid separately.
All as per item No 56 above but for 80 mm bore of pipe but conforming to IS 1239 / 3589
All as per item No 56 above but for 100 mm bore of pipe but conforming to IS 1239 / 3589
All as per item No 56 above but for 150 mm bore of pipe but conforming to IS 1239 / 3589 Make for item No 56 to 59 : TATA, JINDAL, PRAKASH
S&F in repairs, 50 mm dia Butterfly valve in CI body with stainless steel disc & stem, lever operated, ISI marked, nitrile/EPDM liner with necessary bolts and nuts complete all as specified and directed.
All as per item No 60 above but 80mm dia.
All as per item No 60 above but 100mm dia.
All as per item No 60 above but 150mm dia.
S&F in repairs, 50mm dia non return valve in CI body flanged ends, swing type, gun metal seat ISI marked, with necessary bolts, nuts and washers complete all as specified and directed.
All as per item No 64 above but 80mm dia.
All as per item No 64 above but 100mm dia.
All as per item No 64 above but 150mm dia. Make for item No 64 to 67 : Audco, Leader, Zolotto, Kartar
Supply and weld in repairs, mild steel flanges thickness 6mm, class 'C' duly drilled holes with nuts, bolts, washers, rubber gasket etc., for 50mm bore complete all as specified and directed.
All as per item No 68 above but for 80mm bore.
All as per item No 68 above but for 100mm bore.
All as per item No 68 above but for 150mm bore.
M&L, painting of mild steel pipes lines of any sizes, and types, LT panel board, dehumidifier, all accessories of AC plant with one coat of synthetic enamel paint by using spray gun machine after removing all dust and rust and writing date of painting with black synthetic enamel paint complete all as directed.
Removing unserviceable existing fills from cooling tower and Supply and fixing new CPVC (Chlorine and poly vinyl chloride) fills with honeycomb design including maintenance of basement of fills of any capacity cooling tower complete all as directed.
S&F in repairs, Sprinkler assembly / Nozzle assembly with PVC pipes including dummies for any capacity cooling towers complete all as directed.
S&F in repairs, fibre reinforcing polyester (FRP) sheet of cooling tower bottom complete all as directed.
S&F in repairs, to cooling tower body by fibre reinforcing polyester (FRP) complete all as specified and directed.
S&F in repairs, side PVC screen for cooling tower complete all as directed..
Repairs to existing Modulating Valve make HoneyWell of size 50mm, including gear box fixed in chilled water line by servicing, reprogramming BMS system, servicing of DC Motor 24V, replacing the thermostat and limit switch complete all as directed.
EXPANSION TANK FOR CHILLED WATER AND S & F in replacement of PVC/HDPE expansion tank of 1000 litre capacity with pressure rating to suit the system pressure and sized adequately to compensate for water expansion due to operating temperature variations, conforming to IS: 2825- 1969 for 'non-fired pressure vessels' complete with inter-connection piping, non-return valve, safety relief valve and pressure gauge, insulated with 50 mm thick elastomeric insulation and cladded with 26 gauge aluminium complete with accessories as specified and directed by the engineer-in-charge.
Leak testing for AC plant any capacity with Nitrogen (N2) pressure (Nitrogen to be arranged by the contractor) after evacuating the existing gas from the system into empty cylinder by separating the entire system like compressors, condenser, cooling coil refrigerant lines and rectifying the leakage including cutting welding brazing etc., re-connecting including replacement of ‘O’ rings, washers, gaskets etc.,with new ones flushing out the Nitrogen, vacuumising, charging the gas complete all as directed.
Descaling of condenser any capacity by circulating descaling agent (DC-96) through condensers by forced feed method by removing the end covers of the condensers, cleaning the each tube of condenser thoroughly by brushing, re-fixing the end covers with new rubber gasket, nuts bolts, washers and testing complete all as directed.
Supply and re-filling of Refrigerant gas R-134A / R-22 / 407 complete all as directed. Make : Refron/Mefron/Freon
Supply and fix High (micro) efficiency filters to remove dust particles down to 5 micron with minimum efficiency 99% when tested as per BS 6540 - Part I made out of non woven synthetic/polyester/polypropylene media sandwiched between HPDE mesh on one side for additional coarse filtration and aluminium expanded mesh on the other side for mechanical support, media is encased and sealed in sturdy aluminium for longer life including rubber gasket on flanged with final drop of 20mm Hg, approximate size 600x600x303mm complete all as specified and directed.
Disconnecting microprocessor based control panel of chiller package AC plant 95 TO 125 TR Make BlueStar/Voltas/Carrier/ DhanhamBush and removing unserviceable PCB , supply and fixing new PCB to microprocessor based control panel, refixing to chiller package and programming the entire panel for smooth functioning, testing complete all as di
All as per item No 98 above but for 150mm dia. make for item No 97 to 99: Audco, Leader, Zolotto, Kartar
S&F in repairs, motor bearing bushes for pumpset for KDS-7.5HP/ KDS-10HP/ KDA -15HP complete all as directed.
Disconnecting of Induction motor electrically and mechanically connections upto 20HP capacity and dismounting from mono block/centrifugal pumpset / AHU motor, cooling tower by arranging dummy plates to suction and delivery line, varnishing, insulation, greasing the mono block pumpset, replacing of bearings etc., with new ones and fixing back in original position, connecting and testing complete all as directed.
Dismantling and taking out unserviceable insulation, supply and fixing thermal insulation to exposed duct with fibre glasswool 50mm thick (Density 48Kg/Cum) covered with polythene sheet faced hessian cloth, GI chicken wire mesh, protected with 10mm thick cement plaster in cement mortar 1:4 and painted with two coats of cement based paint complete all as directed.
rected. Note: Work shall be carried out through OEM after obtaining prior approval of Accepting Officer
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.09 MB
8338PS.pdf
Tender Documents • 0.38 MB
BOQ_825785.xls
BOQ • 0.32 MB
Download all tender documents and submit your bid