| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹13.5 LAccepted-AOC | L1 | Accepted-AOC Offer of the Lowest Bidder has been accepted and Contract is awarded with the above mentioned amount including GST. | |
| 2 | L2₹13.8 L+₹34,456 (2.55%)Rejected-Finance | L2 | Rejected-Finance Not Qualified in Financial Bid evaluation as L1 |
Tender Value
₹13.7 L
EMD Value
₹27,305
Closing Date
21 Jul 2023, 3:00 pmClosed
Executive Engineer (E), BSNL, Bhubaneswar
Door Sanchar Bhawan, Unit-IX, Bhubaneswar-751022
Electrical Works
2023_BSNL_160788_1
NIT No- 15/BSNL-EDB/2023-24
Open Tender
Electrical Works
Item Rate
20 days
Telephone Bhawan Bhubaneswar
3 documents required · 3 mandatory
₹590
A O (Cash), BSNL, O/o GMTD, Bhubaneswar.
₹27,305
Yes
3 Jan 2024
12 Jul 2023
22 Jul 2023
12 Jul 2023
21 Jul 2023
12 Jul 2023
12 Jul 2023 - 17 Jul 2023
Amount
Supply, installation, testing and commissioning of metal clad, floor mounted, free standing, totally enclosed, dust and vermin proof, cubicle type, indoor M.V. distribution panel suitable for 3 phase 415V 50HZ AC supply made out of 1.6mm CRCA Sheet for Doors, side and rear panels, tops, internal elements & 2.0mm for load bearing members & 3mm sheet for gland plate comprising of the following electrical accessories, Bus bars, indicators etc. with detachable gland plates at top & bottom for incoming and outgoing cable entries, lifting hooks, ventilation louvers at both sides, suitable size base channel of MS Channel /Angle iron interconnections with suitable size copper/Aluminium strip, powder painting after seven tank process treatment, sign writing with suitable engraved white on black nameplates for all switch gears, Bus bars, Indicators & cable alleys etc., providing GI earth studs at both bottom sides of the panel & interconnection with 20mmX3mm copper strips running along the perimeter of the panel as per the approved drawing and direction of the Engineer in charge conforming to applicable standards etc. complete as required. (The panel shall be fabricated and assembled by the CPRI approved panel Manufacturer. The drawing shall be got approved from the Engineer in charge of BSNL before construction) (Item sl.nos. no.1,1.1,1.2,1.3,1.4 and 1.5 are comprise of 1 job)
BUS BARS: 4 Strip solid aluminum bus bar of minimum 1600 Amps Capacity having suitable size with extended terminals for connecting the incoming cables with fixing on support insulators, heat shrinkable PVC insulation tape, brass nuts, bolts and washers etc. complete as reqd. - 01 set.
METERING : LED display Multi-function Meter - 01 no. of size 96mmX96mm panel mounted type having Input : On site Programmable - Voltage - 100 - 600 VL-L, Current - 1/5A 3Ph 3W/4W Network Accuracy Class : 1 Parameters : VAF + kW + kVAr + kVA + kWh + kVArh + kVAh + PF + PA + MM + NC + THD (aux. supply 65...300V AC/DC) with RS485 Modbus communication port with 3nos metering class cast resin CT's , inter connections etc. complete as reqd. ( Make - Rishabh ( L & T) (or) Equivalent.
INDICATIONS : RYB Phase Indicating LED lamps (22.5mm) - 03 sets. (For I/c & O/Gs). On/Off/Trip indication LED lamp (22.5mm) -02 sets (for ACBs). (Make- ESBEE/SALZER/Vaishnava/Siemens)
CONTROL WIRINGS AND INTERLOCKINGS: Two numbers of ACBs are to be Electrically and mechanically interlocked. The control wiring is to be made with 1.5sqmm PVC insulated copper conductor cable with suitable control fuses. Suitable ratings MCBs for control circuits, Connector blocks with DIN channels and copper conductor single core cable for interconnection between the Shunt/UV release /Aux. contacts/Trip Alarm contact etc. of the ACBs and connector blocks with mounting arrangements etc. complete as required. All the control wires/cables are to be numbered with ferrules.
Supply of the following sizes XLPE insulated Aluminium conductor armoured cable 1100 V. grade confirming to IS : 7098 (Part-1) 1988 etc. as required. (Make- Polycab/Havells/Gloster (or) Equivalent with ISI mark)
3½ X 240 sq.mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.
Size above 185 Sqmm & upto 400 Sqmm.
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.
Size above 185 Sqmm & upto 400 Sqmm. (Clamped with 40x3mm MS flat clamp)
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing Duct/Air as required.
Size above 185 Sqmm & upto 400 Sqmm.
Supply and making MV cable end terminations with brass compression gland and copper / aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE copper/aluminium conductor cable of 1.1 KV grade as required.
3½ X 240 sq. mm (62mm) Aluminium conductor armoured cable
Supplying and making straight through joint with heat shrinkable kit (Tubular Sleeve version) including all required jointing materials for 3½ X 240 sq. mm (62mm) size PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. (Make : Denson / 3M(M-Seal )/ Raychem)
Supply and fixing 8 way vertical type 3 phase and neutral (VTPN) MCB distribution board of sheet steel, suitable for flush mounting and surface mounting, with 250 Amps copper bus bar for each phase with neutral bar, earth bar and cable ties for cable management, fully insulated busbar & shrouded neutral bars, pre-fitted masking sheet, reversible door with IP-43 with metal door, provision for 250 Amps MCCB as incomer & four pole MCB/Isolator /RCCB/RCBO as outgoing etc. as per IEC 61439-3 and grouting in wall as required.(Make: Legrand /L&T /Havells/Schneider (or) Equivalent)
Supply and fixing of Cable End box for the following IP 43 MCBDBs suitable for mounting on the top/bottom of the DB and provision for keeping extra cables/mounting terminal blocks/use as terminal box adaptor. (Make: Legrand/ L&T / Schneider Electric/ Siemens / ABB (or) Equivalent)
For 8-way VTPN DB
Supply and fixing 250 Amps 3 pole MCCB suitable for operation on 415 volt 50 Hz 3phase A.C Supply with thermal magnetic protection, having breaking capacity of 36 KA , Thermal adjustable 0.8 to 1In, magnetic adjustable 5 to 10In and including, connection, testing etc. as required.(Make: Legrand /L&T /Schneider)
Supply and fixing 63A, 10 KA 3 pole MCB suitable for operation on 415 volt 50 Hz AC supply with IP - 20 protection terminal etc. as per IS/IEC-60898-1 2002 as required.(Make: Legrand /L&T /Havells/Schneider)
Shifting the Electrical loads from MV Sub Distribution panel (SDP-3) to MV Sub Distribution panel (SDB-1/SDB-2) located in the same room and making SDP-3 ready for providing power supply to proposed 4G core equipment by disconnecting the incoming and outgoing power cables of sizes 3½ X 185sq.mm /3½ X 240sq.mm/3½ X 300sq.mm Aluminium conductor armoured cables and reconnection in SDP-1/2 one by one as per the direction of Engineer in Charge without interruption of normal working of the exchange equipment including removing the cables from the existing cable trenches, relaying/re-fixing etc. by arranging suitable tools, tackles and man power etc. complete as required.
Shifting the Electrical loads from MV Sub Distribution panel (SDP-4) to MV Sub Distribution panel (SDB-1/SDB-2) located in the same room and making SDP-4 ready for providing power supply to proposed 4G core equipment by disconnecting the incoming and outgoing power cables of sizes 3½ X 185sq.mm /3½ X 240sq.mm/3½ X 300sq.mm Aluminium conductor armoured cables and reconnection in SDP-1/2 one by one as per the direction of Engineer in Charge without interruption of normal working of the exchange equipment including removing the cables from the existing cable trenches, relaying/re-fixing etc. by arranging suitable tools, tackles and man power etc. complete as required.
Dismantling of existing old package AC Panel, disconnection of all incoming & out going cables, shifting the load cables to other MCBDB/Panel as per the direction of Engineer in Charge without interruption of normal operation of the exchange equipment, shifting the dismantled panel from 1st floor panel room to the specified location with suitable tools/tackles and man power complete as required.
M/S PRACHI ELECTRICALS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .