Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.3 CrAdmitted-Finance 1ST FLOOR HRECF OFFICE NEAR JNV SCHOOL MIAN GATE TIA RAY RONG CHOGLAMSAR LEH LADAKH 194101 | LEH LADAKH | LADAKH | 194101 | ₹1.3 Cr | L1 | Admitted-Finance |
| 2 | L2₹1.4 Cr+₹9.0 L (7.14%)Admitted-Finance | ₹1.4 Cr+₹9.0 L (7.14%) | L2 | Admitted-Finance |
| Sl No | Description | Qty | Unit | HIMALAYAN RENEWABLE ENERGY AND CONSTRUCTION FIRM (HRECF) L1 | TL CONSTUCTION COMPANY L2 |
|---|---|---|---|---|---|
| 1.00 | Supplying and fixing following rating double pole 240 volts MCB 10 KA in the existing MCB DB complete with connections, testing and commissioning as required .
63 Amps. | 9 | Each. | 1,800 ₹16,200 | 1,600 ₹14,400 Lowest |
| 2.00 | Supplying and fixing folllowing rating 240 Volts DP RCCB having a sensitivity current of 30 mA in the existing MCB DB complete with connections, testing and commissioning as required.
63 Amps. | 9 | Each. | 3,000 ₹27,000 Lowest | 3,900 ₹35,100 |
| 3.00 | Supply and fixing of 1.1 KV PVC insulated and PVC sheathed XLPE Power Cable of following sizes 0.5 Mtr below GL etc as required including carriage upto site of work.
4C x 16 mm² LT XLPE (A2XFY) insulated Aluminium conductor PVC outer sheathed Armoured cable. | 6,060 | Rmt. | 320 ₹19,39,200 | 315 ₹19,08,900 Lowest |
| 4.00 | Supply and installation of the indoor terminations with Double compression heavy duty type Brass-Nickel cable gland , lugs & PVC Shrouds. , etc. complete as required.
4C x 16 mm² LT XLPE (A2XFY) insulated Aluminium conductor PVC outer sheathed Armoured cable. | 6 | Each. | 18,000 ₹1,08,000 | 1,500 ₹9,000 Lowest |
| 5.00 | Supply and laying 25mm x5mm GI Strip at 0.5mtr below ground as strip of electrode including connection / terminating with GI nuts Bolt, spring washer etc as required ( Jointing shall be done by overlaping and with 2 sets of GI nuts bolts and spring washers spaced at 50mm). | 300 | Rmt. | 340 ₹1,02,000 Lowest | 600 ₹1,80,000 |
| 6.00 | Supply, installation, testing & commissioning of GI Electrode Earthing with 75mm dia and 3 meter length, with 40mmx5mm thick, the electrode should be hot-dip galvinised. The GI Electrode shall be pre-filled with Cristaline Conductive Materila (CCM). The GI electrode shall be surrounded with BEE MOIST compound to provide maximum contact betwen the electrode and compound should be eco-friendly GI Electrode Earthing should be maintinance free and does not require regular manual addition of water . The earthing pit should be covered with PVC cover. | 50 | Nos. | 16,000 ₹8,00,000 | 2,000 ₹1,00,000 Lowest |
| 7.00 | Supplying and Laying 6 SWG G.I Wire at 0.50 mt below ground level for conductor earth electrode including connection /Termination with G.I thimble etc. as required. | 6,060 | Rmt. | 150 ₹9,09,000 Lowest | 280 ₹16,96,800 |
| 8.00 | Fabrication, supplying, installation testing and commissioning of following pannel made out of 2mm thick M.S. sheet, floor mounted, vermin and dust proof, outdoor type with suitable size of angle iron legs for grouting in the ground, with lockable type hinged doors, duly painted with provision for fixing of 1 no incomer MCCB, 1 set of Aluminium Bus Bar, providing & fixing of 1 Nos. strip for housing 12 MCB's and other allied accessories etc. as required. (Make as per annexure). a) 100 A FP-MCCB,30 KA-1No. b) Contactor MNX- 1 No. of suitable rating as per main MCCB. c) Daily Timer-1 No. d) Selector Switch,Indicator etc. Completed as Required e) MFM - 1 No | 3 | Set. | 1,70,000 ₹5,10,000 Lowest | 1,90,000 ₹5,70,000 |
| 9.00 | Supply and eraction of swaged steel tubular swaged and welded pole of suitable pole conforming to IS 2713 - 1969 (part I to III)1980 and IS 1161-1979 (UTS 42 kgf/mm sq ) to fixwd upto a required planting depth below ground level in a hole of excavation about 45 cm dia and 1.5Mtr depth to be filled below GL with 1:2:4cement concrete muff of dia 450mm , 80 cm long above ground level sufficient to completely flush MCB distribution board SPN 4 Way (Double Door) with hinged water tight cover with locking arrangement having one single pole MCB of required capacity fixed on din bar and contactor strip 25 Amp rating including threaded earth stud (2 nos ) the outer surface of the plinth to be finished with pure cement including painting of pole with two coats of approved aluminium paint as required . Overall length 9 mtr planting depth 1.5 Mtr (in 1.5 Mtr long 200mm dia RCC readymade muff ) length of section 5 mtr , 2 mtr and 2 mtr ( Bottom , middle and top respectively) Outer dia and thickness of sections 114.3mm x 5.4mm, 88.9mmx 4.85mm and 76.1mmx 3.25mm (Bottom ,Middle and top respectively) complete with base plate with approximate weight 108 kg (410 SP - 27) including supply and erection of G.I pipe 50mm dia (Medium) single arm bracket 1.0metre long each arm welded with M.S Canopy 80mm inner dia. outer dia 89.5mm (Medium), 450mm long suitable for 3 stepped steel tubular swaged and welded pole with top outer section dia 76.1mm. The MS Canopy should have 3 Nos holes for fixing the bracket at the top end of the pole with the help of 3nos 1 1/2"x1 1/2" size nut bolt of full thread. The bracket should have MS ROUND SHEET 3mm thick 90mm dia welded with MS ring of 90mm dia and 50mm long, 1.62mm thick for covering the top end of the Caonpy. The MS Canopy and GI Bracket should be weled at tentative angle 105Deg inclination with MS sheet 5mm thick triangular in shape having dimensions 225mmx150mmx5mm thick with two coats of an approved aluminium paint as desired by Engineer-In-Charge. | 245 | Each. | 23,000 ₹56,35,000 Lowest | 23,100 ₹56,59,500 |
| 10.00 | Supplying, Installation, Testing & Commissioning of pre-wired Street Light 120 W LED Fitting complete. Wipro LR02 - 132-XXX-57-G2 or equivalent approved make. | 245 | Each. | 9,000 ₹22,05,000 Lowest | 11,800 ₹28,91,000 |
Tender Value
Refer Docs
EMD Value
₹2.7 L
Closing Date
26 Aug 2021, 4:00 pmClosed
Executive Engineer Construction Division Leh
Executive Engineer Construction Division Leh
Installation of Street Lights from Saboo road to Sindu Ghat Via Mahabodhi at Leh
2021_PWD_4037_1
137 of CDL Leh of/2021-22
Open Tender
Electrical Works
Item Rate
120 days
LEH
Please refer Tender documents.
5 documents required · 5 mandatory
₹3,000
District Superintending Engineer PWD Circle Leh
₹2.7 L
27 Dec 2021
10 Aug 2021
28 Aug 2021
11 Aug 2021
26 Aug 2021
11 Aug 2021
Amount
Supplying and fixing following rating double pole 240 volts MCB 10 KA in the existing MCB DB complete with connections, testing and commissioning as required . 63 Amps.
Supplying and fixing folllowing rating 240 Volts DP RCCB having a sensitivity current of 30 mA in the existing MCB DB complete with connections, testing and commissioning as required. 63 Amps.
Supply and fixing of 1.1 KV PVC insulated and PVC sheathed XLPE Power Cable of following sizes 0.5 Mtr below GL etc as required including carriage upto site of work. 4C x 16 mm² LT XLPE (A2XFY) insulated Aluminium conductor PVC outer sheathed Armoured cable.
Supply and installation of the indoor terminations with Double compression heavy duty type Brass-Nickel cable gland , lugs & PVC Shrouds. , etc. complete as required. 4C x 16 mm² LT XLPE (A2XFY) insulated Aluminium conductor PVC outer sheathed Armoured cable.
Supply and laying 25mm x5mm GI Strip at 0.5mtr below ground as strip of electrode including connection / terminating with GI nuts Bolt, spring washer etc as required ( Jointing shall be done by overlaping and with 2 sets of GI nuts bolts and spring washers spaced at 50mm).
Supply, installation, testing & commissioning of GI Electrode Earthing with 75mm dia and 3 meter length, with 40mmx5mm thick, the electrode should be hot-dip galvinised. The GI Electrode shall be pre-filled with Cristaline Conductive Materila (CCM). The GI electrode shall be surrounded with BEE MOIST compound to provide maximum contact betwen the electrode and compound should be eco-friendly GI Electrode Earthing should be maintinance free and does not require regular manual addition of water . The earthing pit should be covered with PVC cover.
Supplying and Laying 6 SWG G.I Wire at 0.50 mt below ground level for conductor earth electrode including connection /Termination with G.I thimble etc. as required.
Supply and eraction of swaged steel tubular swaged and welded pole of suitable pole conforming to IS 2713 - 1969 (part I to III)1980 and IS 1161-1979 (UTS 42 kgf/mm sq ) to fixwd upto a required planting depth below ground level in a hole of excavation about 45 cm dia and 1.5Mtr depth to be filled below GL with 1:2:4cement concrete muff of dia 450mm , 80 cm long above ground level sufficient to completely flush MCB distribution board SPN 4 Way (Double Door) with hinged water tight cover with locking arrangement having one single pole MCB of required capacity fixed on din bar and contactor strip 25 Amp rating including threaded earth stud (2 nos ) the outer surface of the plinth to be finished with pure cement including painting of pole with two coats of approved aluminium paint as required . Overall length 9 mtr planting depth 1.5 Mtr (in 1.5 Mtr long 200mm dia RCC readymade muff ) length of section 5 mtr , 2 mtr and 2 mtr ( Bottom , middle and top respectively) Outer dia and thickness of sections 114.3mm x 5.4mm, 88.9mmx 4.85mm and 76.1mmx 3.25mm (Bottom ,Middle and top respectively) complete with base plate with approximate weight 108 kg (410 SP - 27) including supply and erection of G.I pipe 50mm dia (Medium) single arm bracket 1.0metre long each arm welded with M.S Canopy 80mm inner dia. outer dia 89.5mm (Medium), 450mm long suitable for 3 stepped steel tubular swaged and welded pole with top outer section dia 76.1mm. The MS Canopy should have 3 Nos holes for fixing the bracket at the top end of the pole with the help of 3nos 1 1/2"x1 1/2" size nut bolt of full thread. The bracket should have MS ROUND SHEET 3mm thick 90mm dia welded with MS ring of 90mm dia and 50mm long, 1.62mm thick for covering the top end of the Caonpy. The MS Canopy and GI Bracket should be weled at tentative angle 105Deg inclination with MS sheet 5mm thick triangular in shape having dimensions 225mmx150mmx5mm thick with two coats of an approved aluminium paint as desired by Engineer-In-Charge.
Supplying, Installation, Testing & Commissioning of pre-wired Street Light 120 W LED Fitting complete. Wipro LR02 - 132-XXX-57-G2 or equivalent approved make.
Supplying and Laying of PVC Sheathed Unarmoured wire copper conductor of 3 core 1.5 sqmm including connections etc as required.
TL CONSTUCTION COMPANY
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .