Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹45.4 LAccepted-AOC NO 107 SANJAYGANDHI NAGAR NORTH IIND STREET PALLAVARAM CHENNAI 600 043 | CHENGALPATTU | TAMIL NADU | 600043 | L1 | Accepted-AOC L1 | |
| 2 | L2₹47.3 L+₹1.8 L (4.03%)Rejected-AOC NA | NA | NA | 121004 | L2 | Rejected-AOC L2 |
Tender Value
₹46 L
EMD Value
₹46,000
Closing Date
16 Jul 2024, 3:00 pmClosed
The Commissioner
New Colony 3rd Main Road, Chrompet
TCMC - Providing DI Pipe Line Inter link Arrangement With Motor From Bharathi Nagar GLR to Kulathumedu OHT in Ward No.15 Tambaram City Municipal Corporation Zone II
2024_MAWS_459844_1
65/2024/E1
Open Tender
Pipe Laying Works
Item Rate
90 days
Tambaram Corporation
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
₹46,000
22 Oct 2024
4 Jul 2024
16 Jul 2024
4 Jul 2024
16 Jul 2024
4 Jul 2024
Amount
Supply and Delivery of Ductile Iron Socket/Spigot Pipes for class K9 as per is 8329/2000 300mm Dia
Earth work excavation and depositing on bank with initial lead of 10 m and lift of 2 M in narrow trenches having bed width 1.25m & below for laying of pipes for water supply and sewerage works in the following type of soils as directed by Departmental officers Hard stiff clay, stiff black cotton, hard red earth, shales, murram gravel, stoney earth and earth mixed with small size boulders and hard gravelly soil.SS20B
Barricading work (Where the lines are in narrow width of municipality area, busy streets like Market, Bus-stand and in the Highways etc.) for laying of pipe line using casurina poles at 1.50m center to center (8cm to 10cm dia. and 1.80m height) vertical with horizontal poles in two rows, painting the vertical poles in the road facing sides with ready mix paint, tying the vertical and horizontal poles with coir rope including supplying, delivery and fixing of GI sheet (0.90m x 0.8mm thick) in the horizontal poles and fixing 75mm dia. reflectors including earth work excavation for fixing vertical posts and finally removing and stacking the materials safely for further use etc., complete and as directed by TWAD Board officers.
Supply and Delivery of Following Ductile Iron Specials,inlet, outlet, scour and overflow etc, etc., complete as per Standard Specifications
Lowering of D.I Pipes and Specials in the trenches and laying to proper grade and alignment and as directed by the TWAD Officers. 300mm Dia
Testing of pipes for water supply with hydraulic testing equipment by filling with water (including cost of water) and testing to recommended pressure in convenient stretches and attending the bursts if any occured during the test, excluding the cost of pipes but including other incidential and operational charges etc., complete for the following diametres of pipes. 300mm Dia
Supply and Delivery of Cost Iron Double Flanged sluice valve with cap/ wheel as per is 14846/2000 PN 1.0 with ISI marking and with 5 years warranty etc., complete and as directed by TWAD Board officers.
Supply and delivery of Horizontal split casing centrifugal pump conforming to IS 1520 and as amended thereafter with CI casing and split glands,stainless steel shaft, hydraulically and dynamically balanced bronze impellers capable of discharging required quantity of water against a total headnoted below due to all causes and with the accessories such as G.M air release cock, Grease cup, G.I priming funnel, M.S lifting hook, drip water G.I pipe connections, leading to the outside of pump house rubber water deflector, double flap foot valve, G.M strainer including unique tyre typecoupling, common M.S fabricated base to mount pump and motor and other standard fittings etc complete. Pump shall be capable of discharging the specified quantity at the head noted at the minimum NPSH at site conditions. The shut off head shall be atleast 25% over and above the head at duty point. The pump shall be suitable for operation in AC three phase, 415 V, 50 Hz, 1500 RPM. 3000lpmx60m
Labour Charges for erection of Horizontal shaft, centrifugal pumpset (Coupled/Monoblock) in bore well/Open well including fixing of suction pipe and foot valve upto a maximum depth of 7 metres and delivery pipes to the required length with valves, pressure gauges upto the exterior wall of pump room and erection of panel board consisting of TPIC switches starter, Voltmeter, Ammeter, Capacitor single phasing preventor and laying and jointing the cables and twin earthing as per IE rules including providing bed blocks etc., complete and operating the pumps and trial run for 10 days including signing of completion of reports as required by EB authorities.
Supply and delivery of Fully Automatic Auto Transformer Starter suitable for the motor offered.Floor mounting type air/ oil cooled Auto Transformer Starter with tapings at 50%, 65%, 80%,housed in robust steel chamber with arc and main contacts confirming to IS 8544 Part IV and as amended therafter for operation in AC three Phase 50 Hz (+/- 5%), 415V (+/- 10%) with the following components, under voltage release with no volt coil, over load relay with dash pot arrangements, single phasing preventor, LED ON/ OFF switches, Mounted Ammeter, Earth leakage relay, contactor assembly suitable for next standard KW rating, in coming and out going cable entry provisions, transformer tank including first filling of oil etc.
Supply and Fixing of 80mm kinetic air valves for handling more volumes of air in pumping main, double orifice kinetic air valve confirming to IS 14845 tamper proof design (pn-1) etc,. complete as per Standard Specifications
VIJAY ELECTRICALS (BID ID -1083357)
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .