Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.2 LAdmitted-Finance 1008 A PREMIER ENGINEERING COMPANY PURVI RITHANI MEERUT DELHI ROAD MEERUT UTTAR PRADESH 250103 INDIA UDYAM UP 56 0002873 09AARFP4205H1Z1 R M | MEERUT | UTTAR PRADESH | 250103 | ₹3.2 L | L1 | Admitted-Finance |
| 2 | L2₹3.3 LAdmitted-Finance | ₹3.3 L | L2 | Admitted-Finance |
| 3 | L3₹3.6 LAdmitted-Finance | ₹3.6 L | L3 | Admitted-Finance |
| Sl No | Description | Qty | Unit | M G Traders and Engineers L2 | Premier Engineering Company L1 | Raj Engineering Co. L3 |
|---|---|---|---|---|---|---|
| 1.01 | Dismantling of old ACB, other accessories from existing Panel ,removing of all cable connection after taking shut down with help of cutter, heavy labor etc. | 1 | Job | 4,000 ₹4,720 | 3,500 ₹4,130 | 4,500 ₹5,310 |
| 1.02 | Supply of Air Circuit Breaker (ACB), three Pole 415 V AC. Microprocessor based trip unit Manual Draw out type, of rating 3200 Ampere , breaking capacity 75 KA, Make: L&T/C&S/DJB approved make | 1 | No. | 2,30,000 ₹2,71,400 | 2,23,500 ₹2,63,730 | 2,58,000 ₹3,04,440 |
| 1.03 | Providing /fixing and making connection of bus bar of suitable size for 3200 Amp. Current carrying capacity including links, bends, aluminum bus bar will be of electrolytic grade 55% conductivity or as per relevant IS having sufficient cross section area insulated with heat shrinkable PVC sleeve in phase color identification. The bus bar support insulator shall be of class F insulation made out of non-hygroscopic material as SMC/DMC. All hard ware for connection/joints shall be in high tensle. | 1 | Job | 20,500 ₹24,190 | 20,000 ₹23,600 | 17,500 ₹20,650 |
| 1.04 | Fixing of ACB in the existing LT Panel Board including fixing of the base frames of suitable sizes for ACBs in the chamber. Modification in panel door Fixing all the measuring instruments, CT's, lamps, over current & earth fault relay calibration etc. at the metering chamber along with complete wiring through 2.5 sq mm single core copper wire including providing and fixing of necessary ferrules etc. and fixing the backup fuses as per requirement. | 1 | Job | 18,500 ₹21,830 | 18,000 ₹21,240 | 17,500 ₹20,650 |
| 1.05 | Testing and Commissioning of the Panel equipments as follow: -check equipment specification. -continuity and earthing. - meggering of all equipments for phase to phase, neutral of body, neutral of earth. - testing and comissioning of ct and digital ampere meter and volt meter. -all functional tests. - checking of all tightening of nuts and bolts Alignment of doors etc. -fixing of all above components CT and ampere meter etc. -inter locking tests. Testing on load with engineer in charge. | 1 | Job | 8,000 ₹9,440 | 5,000 ₹5,900 | 5,500 ₹6,490 |
Tender Value
Refer Docs
EMD Value
₹7,400
Closing Date
2 Mar 2026, 11:00 amClosed
Office of the Ex. Eng. (E and M) M-2
Pocket-A, Dilshad Garden, Delhi-110095
SITC of 3200 Amp ACB Of LT panel at Yamuna vihar BPS
2026_DJB_287606_5
NIT No. 29 (25-26)
Open Tender
Miscellaneous Works
30 days
Yamuna vihar BPS
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
Ac No. 50448339804
₹7,400
10 Mar 2026
23 Feb 2026
2 Mar 2026
23 Feb 2026
2 Mar 2026
23 Feb 2026
Dismantling of old ACB, other accessories from existing Panel ,removing of all cable connection after taking shut down with help of cutter, heavy labor etc.
Supply of Air Circuit Breaker (ACB), three Pole 415 V AC. Microprocessor based trip unit Manual Draw out type, of rating 3200 Ampere , breaking capacity 75 KA, Make: L&T/C&S/DJB approved make
Providing /fixing and making connection of bus bar of suitable size for 3200 Amp. Current carrying capacity including links, bends, aluminum bus bar will be of electrolytic grade 55% conductivity or as per relevant IS having sufficient cross section area insulated with heat shrinkable PVC sleeve in phase color identification. The bus bar support insulator shall be of class F insulation made out of non-hygroscopic material as SMC/DMC. All hard ware for connection/joints shall be in high tensle.
Fixing of ACB in the existing LT Panel Board including fixing of the base frames of suitable sizes for ACBs in the chamber. Modification in panel door Fixing all the measuring instruments, CT's, lamps, over current & earth fault relay calibration etc. at the metering chamber along with complete wiring through 2.5 sq mm single core copper wire including providing and fixing of necessary ferrules etc. and fixing the backup fuses as per requirement.
Testing and Commissioning of the Panel equipments as follow: -check equipment specification. -continuity and earthing. - meggering of all equipments for phase to phase, neutral of body, neutral of earth. - testing and comissioning of ct and digital ampere meter and volt meter. -all functional tests. - checking of all tightening of nuts and bolts Alignment of doors etc. -fixing of all above components CT and ampere meter etc. -inter locking tests. Testing on load with engineer in charge.
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.57 MB
BOQ_381190.xls
BOQ • 0.24 MB
NIT.pdf
Tender Documents • 0.56 MB
Download all tender documents and submit your bid