Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹2.3 LAccepted-AOC 222 346 LUKERGANJ LUKERGANJ LUKERGANJ ALLAHABAD UTTAR PRADESH 211003 | PRAYAGRAJ | UTTAR PRADESH | 211003 | 1 | Accepted-AOC L1 | |
| 2 | 2₹2.6 L+₹29,060 (12.5%)Rejected-AOC 257 132 KRISHNA NAGAR KYDGANJ PRAYAGRAJ | 2 | Rejected-AOC L2 |
Tender Value
₹2.4 L
EMD Value
₹3,000
Closing Date
22 Apr 2025, 5:00 pmClosed
Suprintending Engineer
Superintending Engineer Electricity Transmission Circle I 57 George Town Prayagraj 211002 PH- 0532-2256499/9415311005
Overhauling of transformer cooling fan, supply and fixing of fan contactor, overload relay, MCB at 132 KV S/S Handia, Saidabad and Gyanpur Pump Cannal and overhauling of 63 MVA DG Set at 132 KV S/S Saidabad, under Electy. Trans. Division-I, Prayagraj
2025_UPTCL_1016302_2
49-ETC-I(A)/ 2024-2025
Open Tender
Electrical Works
Item Rate
60 days
Prayagraj
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
SE ETC-I PRAYAGRAJ
₹3,000
26 Jun 2025
16 Apr 2025
23 Apr 2025
16 Apr 2025
22 Apr 2025
16 Apr 2025
Amount
Overhauling of cooling fans of transformer at 132KV substation Handia, Gyanpur (PC) and Saidabad Prayagraj under ETD-I Prayagraj. The job includes disconnection of supply cable, dismantling the fan from fan mounting frame then opening of fan motor, bearing, straightening of motor shaft, replacement of defective bearing, refitting of fan motor. Fixing of cooling fan at fan mounting frame and checking performance of fan upto 02 hours after connecting proper supply.
132KV S/S Handia
40 MVA T/F-I
40 MVA T/F-II
40 MVA T/F-III
132KV S/S Gyanpur
20 MVA T/F-I
20MVA T/F-II
132KV S/S Saidabad
20 MVA T/F-I
20 MVA T/F-II
Supply and fixing of 01 no,415 volt,32 A,4NO,contactor for main supply of cooling fans installed on T/F .Work includes proper connection of contactor with ACDB or AC cubical installed in the switchyard.
132KV S/S Handia
40MVA T/F II
132KV S/S Saidabad
20MVA T/F-I
Supply of,415 volt,32 A,4NO,contactor of L & T, Siemens, ABB make as per sample.
132KV S/S Handia
132KV S/S Saidabad
132KV S/S Gyanpur PC
Supply and fixing overload relay (Type 3US5000) of rating (0.5-2A) for cooling fan of transformers on the front side of the marshaling box.
132KV S/S Handia
40MVA T/F I & T/F-II
132KV S/S Gyanpur PC
20MVA T/F- II
Supply of overload relay (Type 3US5000) of rating (0.5-2A) for cooling fan of transformers of L & T, Siemens, ABB make as per sample.
132KV S/S Handia
132KV S/S Saidabad
132KV S/S Gyanpur PC
Supply and fixing of fan control contactors of rating 440 V,16A,08 NO,for auto function of cooling fans and relays of rating 230 V,10A,02 NO+02NC for supply monitoring for cooling fans.
132KV S/S Handia
40MVA T/F I
132KV S/S Saidabad
20MVA T/F- II
Supply of fan control contactors of rating 440 V,16A,08 NO,for auto function of cooling fans.
132KV S/S Handia
132KV S/S Saidabad
132KV S/S Gyanpur PC
Supply of 4 pole MCB of rating 230 V, 16A 4pole of L & T, Siemens, ABB make as per sample.
132KV S/S Handia
132KV S/S Saidabad
132KV S/S Gyanpur PC
Complete overhauling of 62.5 KVA Kirloskar Green make diesel generator set installed at 132 KV S/S Saidabad. Work includes replacement of feed pump kit cam beering tapped roller, control rod starting spring, oil seal, packing kit, including radiator cleaning, self starting making effective one and associated work to complete the work satisfactory
Supply and fixing of 150AH lead acid battery make luminous/exide suitable for 63 KVA DG set. Work includes changing damaged lead acid battery with new one and testing of proper functionig of DG set under supervision of JE/SDO at 132 KV S/S Saidabad.
M/S Maa Enterprises (BID ID -5137442)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .