Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹19.0 LAdmitted-Finance | L1 | Admitted-Finance | |
| 2 | L2₹21.6 L+₹2.6 L (13.8%)Admitted-Finance | L2 | Admitted-Finance | |
| 3 | Not Admitted-Fee/PreQual/Technical | - | Not Admitted-Fee/PreQual/Technical Others-MSME not accepted for work contracts. |
| Sl No | Description | Qty | Unit | M/S APR CONSTRUCTIONS L1 | JASMEET SINGH L2 |
|---|---|---|---|---|---|
| 1.00Creation of 11/0.433kV, 400 KVA, 3-phase Distribution Substation | |||||
| 1.01 | Supply, Installation & commissioning of 11/0.433 KV, 400 KVA 3-Phase Distribution Transformer with Bi-metallic terminal Connectors, Energy Level: 2, "BIS Marked" (Copper Wound) along with LV Cable Box having detachable Alumnium Gland plate including Transportation (As per Latest Amendment upto date ) | 1 | No | 8,00,000 ₹8,00,000 Lowest | 11,90,960 ₹11,90,960 |
| 1.02 | Supply, Transportation, Erection of 9 Mtr Long ST Pole (ST-410 SP33) including excavation of pit and back filling of soil & consolidating by ramming, watering etc. Including painting with two coats of Red Oxide and Al. Paint for smooth surface. | 2 | No | 17,000 ₹34,000 | 15,000 ₹30,000 Lowest |
| 1.03 | Supply & Fixing of Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type | 1 | Set | 4,000 ₹4,000 Lowest | 7,000 ₹7,000 |
| 1.04 | Supply, Installation, Testing & Commissioning of 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type | 1 | Set | 9,000 ₹9,000 Lowest | 10,000 ₹10,000 |
| 1.05 | Supply, Installation, Testing & Commissioning of 11 kV Horn Gap Fuse Set 3 Phase 200A | 1 | Set | 4,000 ₹4,000 Lowest | 7,000 ₹7,000 |
| 1.06 | Providing & Fixing of Single Phase PVC Cable 400 mm² ,1.1K V Grade, PVC Insulated Stranded Un-Armoured FRLS type alongwith Al. Thimbles for 400 mm² Cable termination with four colored PVC Tapings to distinguish the LT Phases and the Neutral. (2 Ckt) | 88 | Mtr | 800 ₹70,400 | 350 ₹30,800 Lowest |
| 1.07 | 11kV Polymeric composite Disc Insulator 12kV with fitting, min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm | 3 | No | 300 ₹900 Lowest | 300 ₹900 Lowest |
| 1.08 | Supply, Transportation, Fabrication & Fixing of GI Channel Iron, GI Cross arms, GI Angle Iron Braces, GI Clamps etc duly fabricated including all necessary GI Nut & Bolts & Washers etc. | 308 | Kg | 150 ₹46,200 Lowest | 150 ₹46,200 Lowest |
| 1.09 | Providing of Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover. | 3 | No | 2,500 ₹7,500 | 1,500 ₹4,500 Lowest |
Tender Value
Refer Docs
EMD Value
₹58,000
Closing Date
26 Jul 2025, 4:00 pmClosed
Executive Engineer ED2
Office of Executive Engineer ED2
Supply, Installation, Testing, Commissioning of 400KVA, 11/0.415KV distribution substation along with HT/LT line at Village Satowali Scheme Code ( PDD2526100388) under UT Capex Budget 2025-26 on Turnkey Basis under the jurisdiction of Xen ED2
2025_PDD_280664_1
Enit No 25 of 2025 Dated 30-06-2025
Open Tender
Electrical Works
Turn-key
45 days
Miran Sahib/Bishnah
As per Enit/SBD
9 documents required · 9 mandatory
₹1,000
Executive Engineer ED2
₹58,000
14 Aug 2025
7 Jul 2025
28 Jul 2025
7 Jul 2025
26 Jul 2025
7 Jul 2025
Amount
Creation of 11/0.433kV, 400 KVA, 3-phase Distribution Substation
Supply, Installation & commissioning of 11/0.433 KV, 400 KVA 3-Phase Distribution Transformer with Bi-metallic terminal Connectors, Energy Level: 2, "BIS Marked" (Copper Wound) along with LV Cable Box having detachable Alumnium Gland plate including Transportation (As per Latest Amendment upto date )
Supply, Transportation, Erection of 9 Mtr Long ST Pole (ST-410 SP33) including excavation of pit and back filling of soil & consolidating by ramming, watering etc. Including painting with two coats of Red Oxide and Al. Paint for smooth surface.
Supply & Fixing of Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type
Supply, Installation, Testing & Commissioning of 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type
Supply, Installation, Testing & Commissioning of 11 kV Horn Gap Fuse Set 3 Phase 200A
Providing & Fixing of Single Phase PVC Cable 400 mm² ,1.1K V Grade, PVC Insulated Stranded Un-Armoured FRLS type alongwith Al. Thimbles for 400 mm² Cable termination with four colored PVC Tapings to distinguish the LT Phases and the Neutral. (2 Ckt)
11kV Polymeric composite Disc Insulator 12kV with fitting, min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Supply, Transportation, Fabrication & Fixing of GI Channel Iron, GI Cross arms, GI Angle Iron Braces, GI Clamps etc duly fabricated including all necessary GI Nut & Bolts & Washers etc.
Providing of Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
Providing & Fixing of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Providing & Fixing of Pole mounted LT Distribution Box for 400 KVA DTR with 2 No. Triple Pole MCCB of 400 Amp with adjustable overload release of (80-100%) for incomer & & switch fuse unit for Out Going 2No Ckts. including Busbar arrangements for Phases & Neutral of EC Grade Aluminium,PVC Insulated Sleeved Busbar of required load handling capacity with colour code for Phases and Neutral differentiation, including Aluminium thimbles of required sizes for proper termination etc.
Construction of Cement Platform 8'x8'x3' (3 feet above & 3 feet below ground level ) for 400 KVA SubStation along with the mesh fencing around the Periphery. (complete Job)
Providing & Fixing of Wedge Connectors / PG Clamps
Providing & Fixing of Danger Plates with Clamps
Providing & Fixing of Anti Climbing device with Clamps
Providing of Cement bottoming 1:2:4 mix as per REC standards 0.5cum/pole
Providing & Fixing of Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GI stay rod & 7/3.15 mm dia GI stranded wire complete
Particulars of works for erection of 0.69 km 11KV line with ACSR Weasel Conductor on 9 Mtrs PCC poles
Supply, Erection, Testing & Commissioning of 9 Mtr Long PCC Pole (WL-300Kg) including Transportation to erection site, excavation of pit and back filling of soil & consolidating by ramming, watering etc.
Supply, Transportation, Fabrication & Fixing of GI Channel Iron, GI Cross arms, GI Angle Iron Braces, GI Clamps etc duly fabricated including all necessary GI Nut & Bolts & Washers etc.
Supply, Laying & Stringing of ACSR Weasel Conductor on Cross arms through insulators including proper binding & twisting with soft Aluminium Wire
Providing & Fixing of PG Clamps for 30mm² ACSR Conductor.
Providing & Fixing of 11kV Polymeric composite Pin Insulator 12kV, 10kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm.
Providing & Fixing of 11kV Polymeric composite Disc Insulator with fitting 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Providing & Fixing of Danger Plates with Clamps
Providing & Fixing of Anti-Climbing Device with Clamps
Providing of Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip.
Providing & Fixing of Stone Pad (300 mm x 300 mm x 75 mm)
Providing & Fixing of Aluminium Jointing Sleeves
Providing & installation of Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GI stay rod & 7/3.15 mm dia GI stranded wire complete
Supply, Erection ,Testing and Commissioning of 0.74 km L T line on 8mtrs PCC 250 kg Poles with 120 mm2 AB Cable
Supply Erection, Testing and Commissioning of 8 Mtr Long PCC Pole (WL-200Kg) including Transportation to erection site, excavation of pit and back filling of soil & consolidating by ramming, watering etc.
Supply Erection, Testing and Commissioning of LT AB Cable, 120 mm2 , FRLS, (3x120+70 mmsq) (1.1KV, 3C,Al)
Providing and fixing of Suspension/Tension Clamp with eye hook including all necessary arrangements
Supply Erection, Testing and Commissioning of Straight Through Cable Jointing Kit.
Providing and fixing of Galvanized Nuts and Bolts.
Providing and fixing of Danger Plates
Providing and fixing of Anti-Climbing Device with Clamps
Providing, Testing and Commissioning of Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI strip
Providing of Stone Pad (300 mm x 300 mm x 75 mm)
Providing and Fixing of Insulating Piercing Connetors
Supply ,Erection, Testing and Commissioning of Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GI stay rod & 7/3.15 mm dia GI stranded wire complete
JASMEET SINGH (BID ID -2416408)
stage.html
html • 0.03 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .