GE DEOLALI
GE DEOLALI, 422401
PROVN OF 01X 10KVA ONLINE UPS 3 PHASE INPUT AND THREE PHASE OUTPUT AND 0X7.5KVA ONLINE UPS3 PHASE INPUT AND 3 PHASE OUTPUT IN BUILDING NO T 03 UAV I LEVEL OF STATIC WKSP DEVLALI AND CERTAIN E M MINOR WORKS UNDER THE AOR OF GE DEOLALI
2020_MES_395890_1
8913/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE DEOLALI
CLASS E cat b i
8 documents required · 8 mandatory
₹500
GE DEOLALI
₹22,000
Yes
29 Dec 2020
17 Nov 2020
17 Dec 2020
17 Nov 2020
15 Dec 2020
1 Dec 2020
Amount
S&F 10KVA Online UPS having three phase input and three phase output power KW CAPACITY =80% OF rated KVA, voltage=400VAC (-/+)1%, Power factor 0.8 Lag to unity within the specified KW rating, it should have a electronic protection such as input over/under voltage , battery over/under voltage, overload,short circuit, output over/under voltage, over temperature, over heat, battery should be 42AH Capacity =20Nos it should be lead acid sealed maintanance free with minimum 30 minutes backup including Racks & links make:-Luminous,microtek or equivalent
S&F 7.5KVA Online UPS having three phase input and three phase output having input voltage 415v,50Hz,while outgoing voltage 400v,50Hz ,it should include IGBT Bridge inverter,IGBT Rectifier WITH pfc, input PF up to 0.99,THDi</=5%,input isolation Transformer,LCD Display,solar compatibility ,Power factor 0.8 Lag to unity within the specified KW rating, it should have a electronic protection such as input over/under voltage , battery over/under voltage, overload,short circuit, output over/under voltage, over temperature, over heat, battery should be 26AH 12v=16Nos it should be lead acid sealed maintanance free with minimum 30 minutes backup including Racks & links make:-Luminous,microtek or equivalent
Excavation in trenches n. exc. 1.5 mtr in wide and n. exc. 1.5 mtr in depth for laying of underground cable and getting out in soft/loose soil complete all as specified and directed.
Excavation in trenches n.exc. 1.5 mtr in wide and exc. 1.5 mtr but n. exc 3.0 m in depth and getting out in soft/loose soil complete all as specified and directed.
Returning, filling in excavated soil in trenches including spreading, leveling, watering and well ramming in layers n. exc. 25 cm thick complete all as specified and directed
Removing of excavted soil to a distance n. exc. 50 mtr and deposited where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed.
M&L for sand , filling in trenches around under ground cable complete all as specified and directed.
M&L for providing of new sub class 'B' bricks, old size, well burnt laid flat dry for protection of under ground cable complete all as specified and directed.
Supply, Laying , jointing and testing 50Sqmm 3.5 core LT underground cable, heavy duty, 1100 Volts, XLPE insulated and sheathed, armoured with multi-stranded aluminium conductor cable , laid in trenches/ducts or fixed to poles/walls or laid under roads/paths/drains/culverts duly encased in galvanised steel pipe of suitable sizes including cable gland of suitable sizes and aluminium lugs for connection complete all as specified and directed of sizesNote: Excavation and GI Tubing earthwork shall be measured and paid seperately under respective item of Sch 'A'.
S&F 40mm bore tubing 'light grade' galvanised iron with all fittings and fixed to poles, walls etc. with flat iron clamps/bolts/nuts/washers or laid in floors/under roads complete all as specified and directed Note: Earthwork shall be measured and paid seperately under respective item of Sch 'A'.
S&F double door Vertical Triple pole +Neutral DBs, protection class of IP-43, Conforms to IS 8623-1 &3,AS Per IEC 61439- 1&3, Available in CRCA Sheet Metal,provided with insulated vertical phase bus-bars/neutral bars with shrouds/earth bars/sticking saddles/cement spill protector/color -coded interconnecting wire sets/cable ties/ blanking plates and circuit identification labels,with provision for MCCB as incomer and SP/TP Mcbs as outgoings Make:-L&T DBVTLOO4DD,Legrand or siemens
M&L for MCCB TP 100 Amps, 16KA, 440V 50Hz, SKB 7. Make L&T,Legrand cat part num:- 420005,standard cat part:-ISLGH0080/100 or equivalent in L & T / Legrand / Siemens.
S&F MCBs Single Pole of 240 volts 5-32 Amps,10KA Capacity, 'C' Series of Make:-Legrand,Cat No: 4085-87 to 90,92,93,94,95 or eqivalent in Siemens/L&T
S&F MCBs Single pole + Neutral 240 Volts,32-63 Amps,10KA Capacity 'C' SERIES OF MAKE:Legrand,Cat No : 4086-17 to 20 or equivalent in siemens/L&T
S&F Triple pole + Neutral 415 Volts,40-63 Amps,10KA Capacity 'C' SERIES OF MAKE:Legrand,Cat No : 4086-81 to 83 or equivalent in siemens/Hanger
S & F in replacement double door sheet metal enclosures factory made TPN DBs, protection class IP-43, Conforms to 8623-1 & IEC 61439-1 & 3 ,IK Double door DBs ,Available in CRCA Sheet metal, ready to use DBs-Provided with 100A insulated phase bus-bars/neutral bar/s with shroud/earth bar/sticking saddles/cement spill protector/colour coded interconnecting wire set/Cable ties/blankingbplates and circuit identification lables,with provision for FP MCCB/Isolator / as incomer and incomer and SP MCBs as outgoing Make:-L&T,Cat No:DBTPE004DD or equilavent in /Legrand/Siemens/L&T
M & L in repair sub main wiring with 4 single core, 6 Sq. mm, PVC insulated unsheathed,multi stranded copper conductor FR cable 1100 Volts grade including 4 Sqmm PVC insulated unsheathed multi stranded copper conductor FR as continuous earth wire drawn through conduit /casing caping and connecting to common earth terminals complete all as specified and as directed. Note :- (i) four runs of copper cable and two run of earth wire including conduit /PVC casing/caping shall be measured as one length.
Cutting through existing bituminous road /PCC/floor/approx size width 50cm X 60cm depth along length 3 mtr to 6 mtr cross section of the road for laying of GI tubing/RCC pipe for encasing of cable and repairing the road to match with the original finish complete all as specified and directed.
M&L earthing GI Strip complete with galvanized steel plate electrode 600 mm x 600 mm x 6.0 mm thick, burried directly in ground vertically in pit of depth not less than 2.25 metre below normal ground level with top edge of the earth plate at a depth not less than 1.5 metre below normal ground level surrounded from all sides with mixture of charcoal and common salt in alternate layers and electrode connected to galvanized iron strip 32 x 6 mm size by means of GI bolts, nuts, check nuts and washers, earth strip protected by galvanized steel pipe 40 mm bore (light grade) connected to main switch board or any other electrical equipment all as shown in electrical plate No. 3 of SSR-2009 Part I and including necessary excavation and earth work in any type of soil, 20 mm bore medium grade GI pipe for watering, funnel with wire mesh, PCC (1:3:6), type C-1 chamber, RCC (1:2:4), type B-1, reinforced with 6 mm dia MS round bars @ 15 cm c/c both way for cover and MS frame etc., complete all as specified and directed. Note: The unit rate includes earth strip and protection pipe upto (maximum 7.5 metre from earth plate) earth point/test point.
M&L for galvanised iron ( GI ) strip 32 X 6 mm complete all as specified and directed. NOTE: The unit rate includes earth strip in Per RM and work of connected earth point/test point .
Supply,erection,testing and commissioning of outdoor type LT Bus bar Chamber box,platform mounted,suitable for 3 phase 4 wire,415V AC Supply and having 4 Nos steeped type 200Amps aluminium bus bar for looping & branch connection system .the chamber shall be painted with powder coated paint. the bus bar chamber shall be provided with suitable Neoprene rubber gasket to make it completely dust and vermin proof and degree of protection not less then IP-55. The bus bar chamber shall be made out of 3.0mm thick CRCA mild steel sheet and 3.0mm thick gland plate,front door (01 layer) and rear door (01 layer) openi ng facility and 4 side slanting canopy type roof on top and angle iron pedastal frame 600mm high above the ground level.the bus bar chamber shall be provided with ventilation facility in the form of louvers for better heat dissipation (Note:- The bus bar chamber Box shall be designed in such a waybthat adequate workable space is made available inside the compartments and the size of the chamber shall not less than 600mm height (without base frame & canopy 600mm width and 500mm depth).
M&L for making underground boring(Manually/Mech) through existing bituminous road/PCC/Floor along cross section of the road for laying of GI tubing for encasing of cable all as specified and directed at site.
Taking down carefully unserviceable PL Ceiling Lights before fixing LED Ceiling Lights all as specified and directed
S & F of Recess mounting 34W LED 6000K luminaire fixture diffused suitable for ceiling size 2'X2'(Feet) (580X580 mm), fixture size (595X595 MM) armstrong / grid/ POP Ceiling with separate eletronic driver & High brightness LEDs including required accessories and eletric connections complete all as specified and as directed. Make : Havells cat part No: PLUTONEO2X2PLR34WLED857S or equivalent in Wipro/Philips
M&L submain wiring with two single core PVC insulated, unsheathed, stranded copper conductor cable (FRLS), 1100 volts grade of size 2.5 Sqmm (nominal area) each and one single core 1.5 Sqmm (nominal area) as earth continuity conductor drawn into PVC casing capping complete all as specified and directed. NOTE: (i) Rates for PVC casing capping with accessories are deemed to be included in the unit rate. (ii) Two run of 2.5 Sqmm and one run of 1.5 Sqmm copper cable shall be measured as one length.
Supply and fix switch socket combination 2 in 1, 5/6 pin, 5 and 15 amp flush type universal complete all as specified and as directed.
S&F Deep freezer hard top 300 to320 litre capacity having double door, operating on single phase AC electric supply 230Volts all as specified and directed at site. Make- Godreg/ Blue star/ Voltas
S&F Plug & Socket DB, CRCA Sheet steel, powder coated, with metal plug & socket 3 pin with 20 Amps MCB SP complete as specified and directed .Make : Standard/L&T or equivalent in HPL / Legrand
M&L submain wiring with two single core PVC insulated, unsheathed, stranded copper conductor cable (FRLS), 1100 volts grade of size 6 Sqmm (nominal area) each and one single core 4.0 Sqmm (nominal area) as earth continuity conductor drawn into PVC casing capping complete all as specified and directed. NOTE: (i) Rates for PVC casing capping with accessories are deemed to be included in the unit rate. (ii) Two run of 6 Sqmm and one run of 4.0 Sqmm copper cable shall be measured as one length.
S&F Sheet Metal enclosure for SPN DBs, 4 Ways, Double Door(IP-43), suitable for 240 Volts, AC, 50 Hz complete all as specified and directed Make : Legrand /L&T/ABB
S&F MCBs, SPN, 240 volts, breaking capacity 10 KA, rating 32 Amps, complete all as specified and directed.
S&F MCB, SP,240 volts, breaking capacity 10 KA, rating 20 amps, complete all as specified and directed.
Supply and install high wall split AC units indoor/outdoor complete with cordless remote control unit and with in built air ioniser and Plasma filter for better indoor air quality with minimum 3 star rating of capacity 2.0 TR.Make :- Godrej / Hitachi / Samsung
Supply, install, testing and commissioning of solar standalone street light LED 24 W consisting of inbuilt SCC, SPV panel, Low maintenance Lead acid battery with powder coated 5mtr long above ground MS tubular pole with necessary Excavation, PCC foundation and necessary fixing arrangements complete all as specified and directed. Make :- Havells HSN code 8541 or equivalent from Bajaj / Crompton Greaves
Note: Amount of sch of credit of Rs.5,200.00/-will be deducted from total amount of BOQ.
DHARMESH ENTERPRISES
stage.html
html • 0.04 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .