Loading…
Loading…
Updated dates
Tender Value
₹1.2 Cr
EMD Value
₹1.9 L
Closing Date
12 Jun 2026, 6:00 pm6d left
CWE Khadki Pune
Headquarters CWE Khadki, Military Engineer Services, Range Hills Road, Khadki, Pune-411003
PROVN OF SOLID WASTE MANAGEMENT PROJECT 4 TPD AT BEG AND CENTRE KHADKI UNDER AGE EM I AT GE CENTRAL KHADKI
2026_MES_763398_1
CWE/KKE/TOKEN-01 OF 2026-27
Open Tender
Electrical and Maintenance Works
120 days
CWE Khadki Pune
AS PER TENDER DOCUMENTS
6 documents required · 6 mandatory
₹1,000
Yes
GE Central Khadki
₹1.9 L
Yes
5 May 2026
5 May 2026
15 Jun 2026
5 May 2026
12 Jun 2026
28 May 2026
5 May 2026 - 20 May 2026
PHASE-I
Supply, installation, commissioning and testing of Glass Shredder alongwith hopper all as per following specification :- (i) Preferred dimensions : 1350 mm L x 700mm W x 1700 mm H or as directed by Engineer in charge based on site requirement (ii) Power Specifications: Three Phase operated at 50 Hz and 415V. (iii) Eelctric Motor : 30 HP (iv) Blades : 24 Nos minimum (v) Capacity : 600 Kg / Hr with solid pulley with manual feeding (vi) Power Transmission : Belt based (viii) Accessories : starter controller, copper cable panel wtih its swtichgeaers & stand/foundation, machine gaurds for safety & secure operation, Dust collection device with dust collection baglifter unit for dust free operation complete all as specified and directed by Engr-in-charge. (xiv) Warranty : One year. Make:- Greenrich/ Saicharan Urja /Ent Care/ Gangotree or Equivalent Make.
Supply, installation, commissioning and testing of Weighing scale capacity upto 500kg and bagging machine with tool kite complete all as specified and directed by Engr-in-charge. (i) Warranty : One year. Make:- Greenrich/ Saicharan Urja /Ent Care/ Gangotree or Equivalent Make.
M&L replacement of galvanised iron ( GI ) strip 32 X 6 mm,with saddles and fixing screws etc. for roof conductors and down conductors above ground complete all as specified and directed by Engr-in-charge.
EXTERNAL ELECTRIFICATION WORKS
Excavation in trenches not exceeding 1.5 m width and not exc 1.5m in depth getting out in hard rockcomplete all as specified and directed by Engr-in-charge.
Excavation in trenches not exceeding 1.5 m width and not exc 1.5m in depth getting out in loose/soft soil complete all as specified and directed by Engr-in-charge.
Excavation in trenches not exceeding 1.5 m width and not exc 3m in depth getting out in soft disintegrated rock. all as spd and directed for pole foundation complete all as specified and directed by Engr-in-charge.
Returning filling in including spreading levelling watering and well ramming in layers not exceeding 25 cm in thick using excavated hard/dense soil complete all as specified and directed by Engr-in-charge.
Removal of surplus soil to a distance not exceeding 50 mtr and depositing complete all as specified and directed by Engr-in-charge.
M & L for sand cushion in trenches for cable protection complete all as specified and directed by Engr-in-charge.
Supply and lay PCC cable cover class HV type I flat size 300mm x180mmx40mm complete all as specified and directed by Engr-in-charge.
Supply and lay PCC cable cover class LV type I flat size 250mm x150mmx40mm complete all as specified and directed by Engr-in-charge.
M&L for cable route indicator duly embossed 11KV for HT UG cable of 11000 volts 80mm dia CI plate marked on HT cable bolted with 40x5mm flat iron of hight 0.4mtr embedded in PCC 1:3:6 type C2 of size20x20x30 cm block complete all as specified and directed by Engr-in-charge.
M&L cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armored, Earthed electric power cables (Heavy duty) with stranded aluminum conductor, 11000 volts grade, of size 95 sq mm 3 core complete all as specified and directed by Engr-in-charge.
Supply and lay cable XLPE insulated screened PVC beded gavanized steel strip or wire armoured electric power cables(heavy duty) 1100 volts grade with standard aluminum conductor of followng sizes complete all as specified and directed by Engr-in-charge.
All as per item No 1. 20 above for 185 Sqmm 3.5 Core (Tfr to Main Panel)
All as per item No.1.20 above for 150 Sqmm 3.5 Core (For APFC Panel)
All as per item No .1.20 above for 70 Sqmm 3.5 Core (For both starter motor Panel)
M&L for high density polyethyne pipes (HDPE) of pressure rating 6 Kgf/cm2 laid in trenches for cable protection under road crossing of size complete all as specified and directed by Engr-in-charge.
All as per item No.1.24 above for 50mm bore.
All as per item No.1.24 above for 100mm bore.
Supply & install, testing and commissioning step down transformer, out door type and conforming to IS 1180:2014, level -2 plnthe mounted, HT 11 KV, 3 phase 433 volts, 4 wire, 50 Hz delta/star connected, vector group DYN - 11 double copper wound, ONAN, manul type off load tap changing facility on HT side to vary secondary voltage from minimum 7.5% to plus7.5% in steps of 2.5 % continuous rating of capacity 160 KVA including bushing on HT end cable box on LT side. the transformer shall be complete with all standard fittings and accessories, gauges, first fill of btransformer oil IS 335 ISI marked filtered & dehydrated oil etc, complete all as specified and directed and comprision of the following accessories :-
(a) primary HV side suitable for OH Coductor(consisting of 3 Nos porcelain HT bushings with brass/gun metal bushing rods complete with nuts and washer. (b) one cable box on secondery (LV) side consisting of 4Nos porcelain busing with GM bushing roads complete with GH nuts and washer with one Nos cable bland suitable for reception of out going LT armoured cables of suitable size. (c ) oil conservator tank with filter type, drain valve and oil level gauge (d) dehydrating breather with first fill of dehydhedratig Agent. (e) thermometer pocket on tank cover (f) one Nos 100mm dia dial type thermometer vapour pressure type having range 0- 120 degree centrigrade with temp reading pointer, max temp indicato and reseting devices (g) rating plate with terminal markings.
(h) two earthing terminasl of tank/tanks cover to facilitade fixing of 32x6m GI earthing strip (j) oil level gauge. (k) oil drain and filter valves. (I) oil filter hole with cap/plug with connections complete. (m) lifting lugs. (n) air relief valve plug (o) Four plan soilid cast steel detacheble rollers. (p) first fill of fresh oil confirming to relvant IS and tested up to 50 kV dielectric strength upto top of core (q ) Extra bushing for neutal outside the LT cable box for providing independent earthing for neutral. (r ) provision of 2 Nos danger boards 250x200mm size made of 1.6mm thick MS plate, vitreous enameled white, with letters, figures of voltage and conventional skull and bones in signal red colour, one at HT side and other on LT side (s) Any other fittings/accessories so as to confirm the whole (t) construction of PCC platform of size 2.0mx2.0mx1.5m for transformer useing all PCC material including RCC gate and fencing with angle.transformer to IS-1180 part-I: 2014. complete all as specified and directed by Engr-in-charge. Note -: Transformer shall be mounted on platform/plinth.
Supply and install automatic power factor correction (APFC) panel out door type factory made of capacity 100 KVAR ready to use design confiring to relevant IS rated for short circuit rating of 100 KA front openable and lockable by keys having lower and air vent, gashket and totaly verming proof and suitable for 415/440 Volts, 3 phase 50 HZ AC and housed in elegant enclosure fabricated from minimum 3.15mm thick CRCA sheet, anty corrosive coated to achieve power factor from 0.9 t0 0.99 and finally powder coated in texture seimens gray RAL 7032 & of following suitable size complete all as specified and directed by Engr-in-charge.
(a) 100 A capacity for phase and 63 A neutral aluminium buhs bar duly insulated with colour coated heat shrincablesleeves and mounted on suitable DMC/epoxy insulator. (b) MCCB 160 Amp 25 KA TP TM based O/C and S/C Rel -01 Nos incomming (c) 6A FPMCB 10 KA -03 Nos (d ) 10 Amp TP MCB 10 KA -02 Nos (e) 20 A TP MCB 10 KA -01 Nos (f) 25 Amp TP MCB 10 KA -03 Nos (g) power contactor 9.7 KVAR TP cap duty,230 Volt AC - 03 Nos (h)power contractor 12.5 KVAR TP cap duly 230 VAC -03 Nos (j) Auxillary contact -4 NC-01 Nos 230 VAC (k) Add on Auxillary contract-4NC -01 Nos (l) add on auxillary contact- 1No +1NC -01
(m) 6Step APFC Relay MP based 230 VAC ,-CT -01 (n) indicating lamps R,Y,B -01 Nos Each (o) A/M Sel switch,1P,2W -01Nos (p) A set of heavy duty capacitor type MPPH box type 440Volts. with output step of 100 KVAR capacity bank in steps of with 6 steps (,1x5KVAR + 1x10KVAR + 1x15KVAR +1X20KVAR +1X25 KVAR +1x25KVAR) in any configuration to accommodate all posible set ups (q) Rocker switch illiminated type 230 VAC -08 Nos (r) MCB busbar connector R,y,B -06 Nos. all as specified and directed.
S & F for HT 11 KV, out door type gang operated air-break switch suitable for horizontal or vertical mounting fixed type complete with12 insulators of rating upto 200 Amps complete all as specified and directed by Engr-in-charge.
S & F cable jointing kit for 11 KV grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured AL conductor cable of size 95SQ mm.complete all as specified and directed by Engr-in-charge.
S & F cable jointing kit for 11 KV grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured AL conductor cable of size 95SQ mm.complete all as specified and directed by Engr-in-charge.
S&F for steel tubular pole 11.00 mtr long sweged and cast iron base plate, final taper plug, bolt, nuts and screws as spd type 410 SP-55 including two coat of aluminium paint over a coat of red oxide primer.complete all as specified and directed by Engr-in-charge.Note: Excavatin earth work and PCC will be measured and paid for separately .
S&F for lightning arrestor metal oxide type complete with all fitting, transmission class, discharge capacity 65 Kilo Amp.11000 Volt..complete all as specified and directed by Engr-in-charge
S & F pin type porcelain vitreous white brown or green insulator incl one galvanised mild steel spindle two GI washers and one GI iron nut 150mm height 150mm dia for 11000 Volt grade .complete all as specified and directed by Engr-in-charge
S&F loop type insulator vitreous porcelain white brown or green of over all diamention 90x140mm clearance of hole 25.5mm .complete all as specified and directed by Engr-in-charge
M&L for stay assembly complete with all accessories like GI stay rod of size 16mm GI nuts, bolts and washers etc all as per plate No 1 incl excavation and concrete stay insulator be measured and paid seperately.
S & F galvanised stay strand size of 7/4 mm from CI clamp to existing stay assembly tightly complete.
M&L for Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S clamps, bolts and nuts of approved size, forHT, size 25x20cm .complete all as specified and directed by Engr-in-charge
M&L for Plain concrete feel foundation of poles type D2 1:4:8 (using 40mm graded stone aggregate) and for pole foundation complete all as specified and directed by Engr-in-charge
M&L for Plain concrete feel foundation of poles type C-2, 1:3:6 ( using 40mm graded stone aggregate for pole copping complete all as specified and directed by Engr-in-charge
M&L for cross arms supports etc fabricated from ms sections confirming to Fe-410-0 ir Fe-310-0 of size angle 50x50x6mm and channel 100x50x6mm, flat 50x6mm including nuts bolts, washers, welding, bending hot or cold drilling holes for insulator bolts in any size or shape and including one coat of primer, one under coat and one finishing coat of aluminium paint complete all as specified and directed by Engr-in-charge
M&L for anti climbing device spikes type fabricated out of MS bars (round square and flat) indl nuts, bolts, washers, and welding in two hales made to shape to suit the cross section of the pole.
M& L for ACSR conductor jumper including alkathin pipe 20mm dia for sleeve purpose and fixing material like as lugs, nut bolt & washer etc. all as spd and directed.Note :- jumper lenghth of mimimum 0.6 mtr and maximum 1.5 Mtr complete all as specified and directed by Engr-in-charge
M&L for fabrication, supply & install LT Panel out door type with 3.15 mm thick MS sheet factory made of size not less than (1.2x1.20x0.5) Mtr and M S angle iron of size 50X50X5 mm angle iron frame, weather proof ventilated with locking arrangement for Main panel complete all as specified and directed by Engr-in-charge
(a ) MCCB 200 Amps 4pole 50 KA - 01 N0.(I/C)
(b) MCCB 3 pole 160 Amps 25 KA 415 volts - 01Nos. (For APFC Panel)
(c) MCCB 3 pole 100 Amps 25 KA 415 volts - 02Nos. (For starter Panel )
( c) MCCB 3 pole 25 Amps 16 KA -01 Nos.
(e) Indicating lamps with assembly - 3 nos.
(h) Aluminium bus bar upto 600 Amps for 3 phase and neutral 1 set .
(f) Amp meter - CT 0 to 100 , 01 Nos
M&L for providing LT panel board factory made, indoor type dust and weather proof, fabricated with 2.00 mm CRCA sheet of suitable size confirming to IP 54 protection complete including Copper bus bar 250 Amps, 4 strip mounted on porcelain insulated & enclosed in chamber, bottom cable entry comprising of following: (a) Incoming MCCB 100 Amps 4 pole with microprocessor based release having breaking capacity 25 KA.....01 Nos. (b) On load change over switch of capacity100 Amps - 01 No. (c) Outgoing MCCB 63 Amps 415 V, Triple Pole, --01 Nos. (d) Outgoing MCB 16 Amps 415 V, Triple Pole, KA---02 Nos (e) Outgoing Star Delta starter 30 HP - 01 Nos (f) Outgoing Star Delta starter 3 HP - 01 (g) Outgoing Star Delta starter 5 HP - 01 Nos (h) Outgoing MCB SPN 40 AMps - 03 Nos. ( j) Digital Voltmeter 0-500 V 96x96xm …. 01 No (k) Digital Ammeter 0 - 500 A 96x96m …. 01 No (l) Indicating lamps set RYB …. 01 set. (m) Panel mounted type digital multifunctional energy meter, CT operated, LT 3 phase, 4 wire, including CT of suitable ration- 01 Nos (i) motor protector Note-: (sutaible PCC work included in qouted rate)
M&L for Earthing complete with galvanized steel earth plate electrode 600 mm x 600 mm x 6 mm thick buried directly in ground earth pit not less than 2.25mtr deep below normal ground level with top edge of the plate not less than 1.5 mtr belo ground level connected to galvanized iron strip of size 32x6 mm as earthing lead by mean of nut/bolt and washer of galvanized iron or steel drawn through 40 mm dia light grade GI pipe as shown in electrical plate no 3 of SSR part I of 2009 including necessary excavation and earh work GI pipe 20 mm dia medium grade for watering PCC chamber with PCC cover in cement concreate 1:2:4 Type B1 (20 mm graded aggregate), funnel, wire mesh, charcoal dust, salt etc connected to panel board/ Gen set as indicated including testing complete all as specified and directed by Engr-in-charge. Note:- Earth protection pipe & earthing strip upto and including 7.5 m lenth is deemed included in unit rate quoted by the contractor.
M&L platform for installation of transformer size 2mx2mx1.50m by brick work with subclass B brick construction in cement motor 1:6,hardcore of gauge not exc. 63mm ,filling moorum/Red bajri in foundation, PCC 1:2:4 type B2( using 40 mm graded aggregate) as in floor and 15mm thick on fair faces of brick work or concrete surfaces and Earth work in geting any type of soil including two coated of antifegal paint(apex) over plaster surface complete all as specified and directed by Engr-in-charge.
M&L for chain link fencing of area 09Mtr x 11Mtr and 2.15 Mtr high rolled mild steel work of angle iron of size 65mmX65X 6 mm fixed independently for fencing post and others confirming to Gde Fe 410-A including cutting to dead end length where required, notching, drilling, fitting and/or welding or connecting with bolts and nuts incl TMT steel bars 10mm dia and over cut to length, bent to shape required, including cranking, bending spirally for hooping for columns hooking ends or as in horizontal bar for fixing in fencing and binding with and including mild steel wire (anealed) not less than 0.9mm dia or securingwith clips complete for support of chain link fencing complete all as specified and directed by Engr-in-charge
EXTERNAL WATER SUPPLY
Supply and laying in trenches, in any length, Galvanised water tubing, medium grade, nominal dia 50 mm, with all fittings, testing complete all as specified and directed by Engr-in-charge
All as per item No 1.62 above but 25 mm dia
S&F for gun-metal stop cock, valves,50 mm bore of pipe, with iron wheel head, screwed both ends for iron pipe and fixed complete all as specified and directed by Engr-in-charge
S&f for gun-metal stop cock, valves,25 mm bore of pipe, with iron wheel head, screwed both ends for iron pipe and fixed complete all as specified and directed by Engr-in-charge
M&L for construction of brick masonary valves pits, of the internal dimension 600mm x 600 mm x 600 mm complete and fabrication of 3.15 mm thick MS Sheet cover and angle iron frame made out of 40mm x 40mm x 6 mm MS angle and one side provided with hinged with locking arrangement duly painted including necessary earth work and PCC work complete all as specified and directed by Engr-in-charge
M&L for cutting and welding of existing CI/GI pipe in trenches for fixing/inserting of ferrules for taping connection of any size of pipe complete all as directed by Engineer-in-Charge
PHASE-II
M&L for AMC (Annual Maintenance charges) for 01 Year including free visiting (evevy month) and attending complaint as and when requid. (major items cost at actual as extra)complete all as specified and directed by Engr-in-charge.
M&L for AMC (Annual Maintenance charges) for 2nd Years including free visiting (evevy month) and attending complaint as and when requid. (major items cost at actual as extra)complete all as specified and directed by Engr-in-charge.
Please Enable Macros to View BoQ information
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.32 MB
Tender2.pdf
Tender Documents • 0.53 MB
BOQ_855101.xls
BOQ • 4.30 MB
Download all tender documents and submit your bid