Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.5 LAccepted-Finance | L1 | Accepted-Finance OK | |
| 2 | L2₹9.1 L+₹56,030 (6.57%)Accepted-Finance 6A GAU KRIPA MOHKAMPUR PHASE 1 INDUSTRIAL AREA DELHI ROAD MEERUT UTTAR PRADESH 250002 | MEERUT | UTTAR PRADESH | 250002 | L2 | Accepted-Finance OK | |
| 3 | Rejected-Technical | - | Rejected-Technical NON FULFILMENT OF PQR |
Tender Value
Refer Docs
EMD Value
₹21,000
Closing Date
15 Feb 2021, 5:00 pmClosed
SE ETC NOIDA
220 KV SUB STATION SECTOR-20 NOIDA
Replacement of damaged 132 kV Main Bus-I and connected jumpers, hardware etc. including its supply at 220 kV S/S Sector-20 Noida under ETD-I Noida
2021_UPTCL_547298_1
E-T-55/ETCN/2020-21
Open Tender
Electrical Works
Item Rate
21 days
NOIDA
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,770
EE ETD NOIDA
₹21,000
25 Feb 2021
19 Jan 2021
16 Feb 2021
19 Jan 2021
15 Feb 2021
19 Jan 2021
Amount
Work Portion (Replacement of 132 kV Main Bus Bar)
Opening / cutting & Dismentling of R, Y & B phase jumper of 132 KV existing Main Bus Made of Single Tarantulla between Bus sections below gantries, step by step during bus bar replacement work includes dismantling of all types of associated clamps & fittings.
Dismantling of existing jumper of ACSR Single Panther/ Zebra/ Moose conductor of ICT , bus coupler & feeder bay from main bus bar – I & II by opening of all associated clamps, step by step during bus bar replacement.
Dismantling of 132 KV old / damaged main bus bar-I,II bus section (R,Y & B) of Single Tarantulla conductor and lowering down of conductor from Sub-Station gantry to complete dismantling works including dismantling of all associated tension clamps fitting & disc insulator etc.
Complete cleaning of 132 KV disc insulators for all phases by suitable liquid cleaner, testing of IR value by insulation tester, making series connection & ready for hoisting with all cost of men, T & P to complete the work.
Fixing of quadruple Moose suspension fitting under bus section of main bus-I below gantries with suitable hardware such as hoisting of disc insulators etc. to complete the work in all respect satisfactorily.
Stringing and proper sagging of new 132 KV main bus bar-I (R,Y & B) by Twin Moose conductor the work includes fitting of tension clamps hoisting of 120 KN disc, tension fitting, spacers PG-clamps etc. and cutting of conductor as required.
Re-connecting of R, Y & B phase of 132 KV main bus bar-I,II of Twin Zebra/Moose conductor between bus sections below gantries, step by step during bus bar replacement work including jointing of Zebra conductor below the gantries with the help of suitable PG-clamps through the quadruple suspension fitting & spacers etc. and cutting of conductor as required.
Re-connecting new jumpers of ACSR Twin Moose/Zebra conductor of ICT, bus coupler bays & feeder bays after fixing spacers, clamps as required.
Replacement of damaged jumper of Single Moose/ Zebra of different bays in the 220 KV switchyard after opening of damage jumper & re-fixing of fresh jumper with the help of suitable PG clamp etc. and cutting of conductor as required.
Supply Portion :-
Supply of 132 KV bolted type single tenson fitting for Twin Moose conductor 1x10 No disc insulator with turn buckle complete with hardware fitting d-shackle, d-sockete, Ball hook, yoke plate, d-cilip it tenson clamp etc. as per technical specification.
Supply of 132 KV bolted type tenson fitting for Twin Zebra/Moose conductor 1x10 No disc insulator without turn buckle complete with hardware fitting d-shackle, d-sockete, Ball hook, yoke plate, d-cilip it tenson clamp etc. as per technical specification.
Supply of 132 KV bolted type Supension fitting for Quardruple Twin Moose conductor 1x10 No disc insulator complete with hardware fitting as per technical specification.
Spacers for Twin Moose conductor 250 mm spacing as per technical specification.
Spacers for Twin Moose conductor 100 mm spacing as per technical specification.
Spacers for Twin Zebra conductor 100 mm spacing as per technical specification.
4 Bolted Type PG clamp suitable for Moose to Moose Conductor Complete with HDG nut bolt & washer as per technical specification.
4 Bolted Type PG clamp suitable for Zebra to Zebra Conductor Complete with HDG nut bolt & washer as per technical specification.
4 Bolted Type PG clamp suitable for Zebra to Moose Conductor Complete with HDG nut bolt & washer as per technical specification.
Bimetallic 132 KV Tandom Isolator clamp made of aluminum alloy LM-6 for Twin Moose conductor with HDG nuts & bolts and washer as per technical specification .
Bimetallic 132 KV Tandom Isolator clamp made of aluminum alloy LM-6 forTwin Zebra conductor with HDG nuts & bolts and washer as per technical specification .
Bimetallic 132 KV Bus Isolator clamp made of aluminum alloy LM-6 for Twin Moose conductor with HDG nuts & bolts and washer as per technical specification .
Bimetallic 132 KV Bus Isolator clamp made of aluminum alloy LM-6 for Twin Zebra conductor with HDG nuts & bolts and washer as per technical specification .
Anushree Electrical Engineers Private Limited
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .