Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.6 CrAccepted-AOC 258 A LAKE TOWN BLOCK B | ₹1.6 Cr | L1 | Accepted-AOC L1 Bidder |
| 2 | L2₹1.9 Cr+₹30.9 L (18.8%)Rejected-Finance BALTIKURI INDUSTRIAL ESTATE PLOT NO A 01 DASNAGAR HOWRAH 711113 | HOWRAH | HOWRAH | WEST BENGAL | 711113 | ₹1.9 Cr+₹30.9 L (18.8%) | L2 | Rejected-Finance HIGHEST |
| 3 | L3₹2.0 Cr+₹36.2 L (22.1%)Rejected-Finance | ₹2.0 Cr+₹36.2 L (22.1%) | L3 | Rejected-Finance HIGHEST |
Tender Value
Refer Docs
EMD Value
₹4.4 L
Closing Date
3 Jul 2024, 2:00 pmClosed
Superintending Engineer PWD Electrical
Superintending Engineer PWD North Bengal Electrical Circle P.W.D Inspection Bungalow Annex Building 1ST Floor Kutchery Road Venus More Siliguri
Construction of new proposed G6 Integrated Court building at Alipurduar district SITC of Central Air conditioning system
2024_WBPWD_689805_1
WBPWD/SENBEC/NIT-01/2024-2025
Open Tender
ELECTRICAL WORKS ORG
Item Rate
180 days
Alipurduar
Please refer Tender documents.
4 documents required · 4 mandatory
₹4.4 L
Siliguri
1 Dec 2025
6 Jun 2024
5 Jul 2024
6 Jun 2024
3 Jul 2024
21 Jun 2024
18 Jun 2024
Amount
SUB-HEAD 1-- Supply of Low side items & Installation, Testing & Commissioning of the VRF System: -
14 HP Top Discharge
28 HP Top Discharge
Supply, fabrication & fixing 12 nos MS angle/ MS Channel of size 75mm x 75mm x 6mm for placing the outdoor unit of VRF incl. drilling 5 nos holes in each angle incl. cutting holes into the wall & grouting the same (1:1.5:3) etc for outdoor untis. Supply, fabrication & fixing 4 nos MS U channel of 6 mm thick of size 75mm x 40mm x 40mm & ISA 50mm x 50mm x 6mm for making base frame table type for installation incl drilling 2 nos holes in each channel. [NS]
Supply, Installation, testing and commissioning of following minimum capacity 4 way flow VRV/ VRF Cassette type indoor ceiling mounted unit equipped with synthetic washable media pre-filter, fan section with low noise fan/ dynamically balanced blower, multi speed motor, coil section with DX copper coil, electronic expansion valve, outer cabinet, drain pump, grill, necessary supports, vibration isolation, chord less remote control etc, suitable for operation on single phase, 230 volt, 50 Hz AC Supply. The units shall have automatic force shut down provision in case of fire on receiving signal from BMS system. The cooling capacity of indoor unit will be at Air Inlet Conditions of 27 degree C DB and 19 degree C WB temperature. (Make: similar to the make of VRF ODU) [NS]
2.0 to 2.2 TR (4-Way Cassette Unit)
2.5 to 2. 8 TR (4-Way Cassette Unit)
3.0 to 3.3 TR (4-Way Cassette Unit)
4 to 4.5 TR (4-Way Cassette Unit)
Supply, Installation, testing and commissioning of ceiling suspended type air cooled precision units comprising of indoor & outdoor units with microprosessor based controls & complete in all respects inclusive of 15 mtr of refrigerent piping, thermal insulation & cabling, thermostat & operating switches as required & of following capacities suitable to run with R407C/R410A refrigerent & three phase, 415 V, 50 Hz power supply. (Make- Stulz/ Vertiv/ Trane) [NS]
SUB-HEAD 2-- Copper Tubing and Accessories: -
Supply, installation, testing and commissioning of VRF Grade copper pipe with 13/19 mm thick closed cell elastomeric nitrile rubber insulation. [NS]
6.4 mm (13 mm thick insulation)
9.5 mm (13 mm thick insulation)
12.7 mm (13 mm thick insulation)
15.9 mm (13 mm thick insulation)
19.1 mm (13 mm thick insulation)
22.2 mm (13 mm thick insulation)
12.7 mm (19 mm thick insulation)
15.9 mm (19 mm thick insulation)
19.1 mm (19 mm thick insulation)
22.2 mm (19 mm thick insulation)
25.4 mm (19 mm thick insulation)
28.6 mm (19 mm thick insulation)
31.8 mm (19 mm thick insulation)
34.9 mm (19 mm thick insulation)
38.1 mm (19 mm thick insulation)
41.3 mm (19 mm thick insulation)
44.5 mm (19 mm thick insulation)
Supply & Installation of copper individual Refnet 'Y' distribution joints. [NS]
Supply, installation, testing and commissioning of PVC condensate drain water piping with 6 mm thick closed cell elastomeric nitrile rubber insulation. [NS]
25 mm dia
32 mm dia
40 mm dia
Supply & Laying of Fire Retardant (FR) under deck insulation with Expanded Polystyrene EPS (Thermocol) Sheet 50 mm thick (density not less than 18kg/Cu.mtrs.) stuck with bitumin to slab and held by cadmium plated G.I. Nut-Bolt with washers. (6th floor Vacant Court & Vacant Court- 4, Vacant Court & Vacant Court- 5, Vacant Court 1 & 6, Vacant Court 2 & 7, Vacant Court 3 & 8 & 5 nos Judges Room) [NS]
Supply and charging of R407C/R410A Refrigerant. [NS]
SUB-HEAD 3-- Electrical wirings & Installation of PC Monitoring System: -
Supplying and fixing 415V, 63A TPN SFU with sheet steel enclosure on angle iron frame on wall with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating. [4(a)/D-3]
Supply of 2/4 Core XLPE Insulated & Sheathed Armoured stranded Aluminium Conductor cables for Working Voltage up to 1100 Volts of following sizes [Make Polycab / RR /KEI/ Havells/ Gloster as approved by E.I.C] [NS]
4 Core 35 Sqmm
Supply & wiring with 4 core 16 Sq.mm XLPE Insulated, PVC tape innersheathed unarmoured copper cable. Make Polycab / RR /KEI/ Havells/ Gloster as approved by E.I.C] [NS]
Supply & wiring with 3 core 0.75 Sq.mm XLPE Insulated, PVC tape innersheathed unarmoured copper cable. Make Polycab / RR /KEI/ Havells/ Gloster as approved by E.I.C] [NS] (Communication Line)
Supply & wiring with 3 core 2.5 Sq.mm XLPE Insulated, PVC tape innersheathed unarmoured copper cable. Make Polycab / RR /KEI/ Havells/ Gloster as approved by E.I.C] [NS] (For Indoor Unit Connection)
Supply & Fixing of perforated GI cable tray with perforation not more than 17.5% suspended from ceiling incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support. [34(a)/D-14]
100x50x1.25mm (18SWG) with out angle iron support
300x50x1.25mm (18SWG) with 25x25x3mm angle iron support
Connecting the equipments body to earth busbar including S&F 20 mm x 3 mm galvanised (Hot Dip) MS flat on wall/floor with GI saddles as required and connection to equipments incl. drilling holes, with bolts, nuts, washers etc. [5(C )/G-3]
TERMS & CONDITIONS
(i) Rate should be quoted inclusive of all applicable taxes and Duty etc.
(ii) The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them.
(iii) Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill.
(iv) If any refurbished material is supplied and installed, penal action will be taken as per existing rules.
NATIONAL AIRCON
RS COOLING APPLIANCES
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .