Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹7.4 LAccepted-AOC | L1 | Accepted-AOC lowest and reasonable | |
| 2 | L2₹8.7 L+₹75,351.23 (9.46%)Rejected-Finance | L2 | Rejected-Finance OTHER THAN LOWEST | |
| 3 | L3₹12.4 L+₹4.4 L (55.5%)Rejected-Finance KRAL PORA BAGH I MEHTAB NEAR MANCHOWA PETROL PUMP DISTRICT BUDGAM 190019 J K | BUDGAM | BUDGAM | J K | 190019 | L3 | Rejected-Finance OTHER THAN LOWEST | |
| 4 | L4₹28.2 L+₹20.2 L (254.1%)Rejected-Finance BUDOOBAGH NOWPORA 0 KHANYAR SRINAGAR JAMMU KASHMIR 190003 | SRINAGAR | JAMMU AND KASHMIR | 190003 | L4 | Rejected-Finance OTHER THAN LOWEST |
Tender Value
₹12 L
EMD Value
₹24,000
Closing Date
6 May 2022, 6:00 pmClosed
CWE AF SRINAGAR
CWE AF SRINAGAR
REPAIR MAINTENANCE OF AHUs COMPRESSORS MOTORS AND CHILLERS INCLUDING OTHER CONNECTED WORKS AT 1 WING AF SRINAGAR
2022_MES_517150_1
CWE(AF)SGR/SGR-01/2022-23
Open Tender
Civil Works
Item Rate
180 days
AF STN SRINAGAR
AS PER NIT
8 documents required · 8 mandatory
₹500
Yes
GE AF SRINAGAR
₹24,000
Yes
9 Jun 2022
7 Apr 2022
9 May 2022
7 Apr 2022
6 May 2022
22 Apr 2022
Amount
Material and labour for servicing of Floor mounted AHU of different capacities including washing, cleaning, welding to rusted surfaces including preparing the metallic surface with one coat of primer and two coats of synthetic enamel paint matching to existing manufacturer colour including cleaning of drain pipe, dusting of all filters as well as cleaning of the outer filters and inner filters with proper cleaning of the AHU body with all necessary equipment and apparatus, complete all as specified and directed.. NOTE : The work shall be carried out by the authorized OEM.
Supply and fixing in replacement of V Belt No. B-26 for AHU, complete all as specified and directed. Make : Fenner / Unigrip / Navyug / Escon / Mitsubishi / Dunlup.
Supply and fixing in replacement of V Belt No. B-54 for AHU, complete all as specified and directed. Make : Fenner / Unigrip / Navyug / Escon / Mitsubishi / Dunlup.
Supply and fixing in replacement of V Belt No. B-56 for AHU, complete all as specified and directed. Make : Fenner / Unigrip / Navyug / Escon / Mitsubishi / Dunlup.
Supply and fixing in replacement of V Belt No. B-58 for AHU, complete all as specified and directed. Make : Fenner / Unigrip / Navyug / Escon / Mitsubishi / Dunlup.
Supply and fixing in replacement of V Belt No. B-60 for AHU, complete all as specified and directed. Make : Fenner / Unigrip / Navyug / Escon / Mitsubishi / Dunlup.
Supply and fixing in replacement HEPA filter microfibre material, 0.3 microns box type of size 610X610x305mm suitable to be installed in existing AHU of capacity 8000 CFM complete all specified and directed. Make :Athlete/Thermodyne/Indfoss/John fowlers/ Denfoss
Supply and fixing in replacement HEPA filter microfibre material,0.3 microns box type of size 600X600x305mm suitable to be installed in existing AHU of capacity 4000 CFM complete all as specified and directed. Make :Athlete/Thermodyne/Indfoss/John fowlers/ Denfoss
Servicing/Overhauling of reciprocating type compresser unit of cap 30 TR including carrying out of maintenance check as per maintenance manual alongwith following other repairs :- (a) Dismantling of compressor complete part by part cleaning of all stationary, moveable and rotary parts and displaying the parts at site for inspection of Engr-in-Charge to ascertain the serviceability /unserviceabilty of compressor parts. (b) Draining out of compressor oil and refilling after repair/servicing after checking serviceability. (c) Decarbonising of all parts such as Pistons, Assembly, Heads, crankcase, crankshaft etc. (d) Assembling of compressor complete with old serviceable parts and replacement of unserviceable parts by new parts as ordered necessary by Engr-in-Charge. (e) Testing of compressor after servicing/overhauling as per directions of OEM/Manufactures. Note : - (i) Any parts required to be replaced during servicing, overhauling of compressor shall be measured and paid separately as 'supply only' items. However, labour element involved in replacement of parts is deemed to be included in unit rate quoted against this item. (ii) Any minor parts such as split pins,screw washers, grease etc required to make the compressor functional, even if not notified by Engr-in-Charge shall be carried out by the contractor without any extra cost to the department.
Supply only the follwing parts to be incorporated against item No-09 here in before : - (a) Gasket Set complete
(b) Suction Filter
(c) Piston assembly
(d) Piston Ring Set
(e) Connecting Rod
(f) Gudgeon pin
(g) Main bearing for realigned existing crank shaft STD (Standard Size)
(h) Oil seal
Servicing/Overhauling of scroll type compresser unit of cap 11 TR including carrying out of maintenance check as per maintenance manual alongwith following other repairs. (a) Dismantling of compressor complete part by part cleaning of all stationary, moveable and rotary parts and display the parts at site for inspection of Engr-in-Charge to ascertain the serviceability /unserviceabilty of compressor parts. (b) Assembling of compressor complete with old serviceable parts and replacement of unserviceable parts by new parts as ordered necessary by Engr-in-Charge. (c) Testing of compressor after servicing/overhauling as per directions of OEM/Manufacturers. Note:- (i) Any parts required to be replaced during servicing, overhauling of compressor shall be measured and paid separately as 'supply only' items. However, labour element involved in replacement of parts is deemed to be included in unit rate quoted against this item. (ii) Any minor parts such as split pins,screw washers, grease etc required to make the compressor functional, even if not notified by Engr-in-Charge shall be carried out by the contractor without any extra cost to the department.
Supply only the follwing parts to be incorporated against item No-11 here in before :- (a) Lower bearing
(b) Counter weight
(c) Thrust washer
(d) Slider block
(e) Orbiting scroll
(f) Pressure relief valve
(g) Check valve
(h) Terminal cover
Repair to crank shaft obtained from dismantled parts of item No 09 here-in-before comprising welding turning and facing of crank shaft to true size and shape of beraing complete as all specified and directed.
Supply and topping up of compressor oil by supplying new compressor oil No A-68 as approved. Make- Servo, Castrol
Supply and fixing as in replacement copper tubing 1/4'' size for control devices of compressor including flare nuts of adequate size and connecting complete and testing for leakage all as specified and directed.
Supply and fixing in replacement microwave pre filter, 10 micron, box type of size 520x470x50mm suitable for AHU of central AC plant, complete all as specified and directed. Make - Athlete/Thermodyne/Indfoss/John fowlers/ Denfoss
Supply and fixing in replacement microwave pre filter of microfibre material , 10 micron, box type of size 500x470x25mm suitable for AHU of central AC plant, complete all as specified and directed. Make -Athlete/Thermodyne/Indfoss/John fowlers/ Denfoss
Supply and fixing in replacement microwave pre filter of microfibre material, 10 micron, box type of size 500x480x50mm suitable for AHU of central AC plant, complete all as specified and directed. Make - Athlete/Thermodyne/Indfoss/John fowlers/ Denfoss
Supply and fixing in replacement microwave pre filter of microfibre material, 10 micron, box type of size 610x305x50mm suitable for AHU of central AC plant all as specified and directed. Make - Athlete/Thermodyne/Indfoss/John fowlers/ Denfoss
Supply and fixing in replacement microwave pre filter of microfibre material, 10 micron, box type of size 590x430x25mm suitable for AHU of central AC plant, complete all as specified and directed. Make - Athlete/Thermodyne/Indfoss/John fowlers/ Denfoss
Supply and fixing in replacement microwave pre filter of microfibre material, 10 micron, box type of size 500x250x50mm suitable for AHU of central AC plant, complete all as specified and directed. Make - Athlete/Thermodyne/Indfoss/John fowlers/ Denfoss Note:- For Srl item No 16 to 21 Size of pre filter and Hepa filter may vary from 5 to 10 % in length and width. Bidders are advised to visit the site before quoting their rates.
Servicing of AHU including washing and cleaning of coils with chemical and pressure pump of capacity 8000 CFM including dusting of all filters with proper cleaning of AHU body with all necessary arrangement including cleaning of drain pipe all as specified and directed.
Servicing of AHU including washing and cleaning of coils with chemical and pressure pump of capacity 4000CFM including dusting of all filters with proper cleaning of AHU body with all necessary arrangement including cleaning of drain pipe all as specified and directed.
Servicing of AHU including washing and cleaning of coils with chemical and pressure pump of capacity 2500 CFM including dusting of all filterswith proper cleaning of AHU body with all necessary arrangement including cleaning of drain pipe all as specified and directed.
Material and labour for trouble shooting/fault detection in case of major break down of the AC plant 3 X11 TR from the authorized person/company representative of the Carrier company for the smooth functioning and servicing of the plant as well as for uninterrupted running. The job includes step by step check up of the plant with proper diagram and replacing of the burnt or unserviceable parts if any like resistors or counters or timers or repair to electronic circuit board etc.
Material and labour for opening and dismantling both sides covers of condenser and descaling including brazing work wherever required of condenser unit (set of three) for AC plant of 3X 11 TR by pumping descaling chemicals with descaling pump, brushing with rods, cleaning/ oiling of tubes, replacement of gasket and reassembling it after descaling complete all as directed. Note :- 1. The descaling of the condensers of the plant will be carried out by the authorised service representative of the OEM. 2. The chemical and descaling including accessories/equipments shall be deemed to be included in the quoted rates.
Material and labour for opening and dismantling both sides covers of Chiller/Evaporator and descaling of same (set of three) for AC plant of 3X 11 TR by pumping descaling chemicals with descaling pump, brushing with rods, cleaning/ oiling of tubes, replacement of gasket and reassembling it after descaling complete all as specified and directed. Note :- 1. The descaling of the condensers of the plant will be carried out by the authorised service representative of the OEM. 2. The chemical and descaling including accessories/equipments shall deemed to be included in the quoted rates.
Material and labour for repair of chiller/condensor of chiller (set of three) unit of cap 3x11 TR detecting leakage in the system and rectify the leakage in the chiller/condensor of system, flushing the system of any rust and dirt with antirust chemicals, nitrogen pressure testing of chiller & condensor and assembling the system and testing complete, complete all as specified and directed. Note :- 1. The descaling of the condensers of the plant will be carried out by the authorised service representative of the OEM. 2. The chemical and descaling including accessories/equipments shall deemed to be included in the quoted rates.
Material and labour for replacement of nozzle set of sprinkler for existing cooling tower cap 11 TR and testing all as specified and directed.
Material and labour for replacement of nozzle set of sprinkler for existing cooling tower cap 30 TR and testing all as specified and directed.
Material and labour for replacement of suction pressure transducer in suction pipe of compressor of central AC plant of 11 TR capacity, complete all as specified and directed. Note: The work shall be carried out by the authorized representative of OEM.
Material and labour for replacement of high pressure switch of central AC plant 3X11 TR capacity, complete all as specified and directed. Note: The work shall be carried out by the authorized representative of OEM.
Material and labour for replacement of flow switch of central AC plant 3X11 TR capacity completion, complete all as specified and directed. Note: The work shall be carried out by the authorized representative of OEM.
Material and labour for replacement of suction pressure transducer in suction pipe of compressor of central AC plant 3x11 TR capacity by pumping down/recovering of refrigerant gas from the compressor, fixing of HP switch, charging recovered refrigerant gas and testing on completion, complete all as specified and directed. Note: The work shall be carried out by the authorized representative of OEM.
Material and labour for replacement of discharge pressure transducer in suction pipe of compressor of central AC plant 30 TR capacity by pumping down/recovering of refrigerant gas from the compressor, fixing of HP switch charging recovered refrigerant gas and testing on completion, complete all as specified and directed. Note: The work shall be carried out by the authorized representative of OEM.
Material and labour for replacement of high pressure switch in discharge pipe of compressor of central AC plant of 11 TR capacity by pumping down/recovering of refrigerant gas from the compressor and testing on completion all as specified and directed. Note: The work shall be carried out by the authorized representative of OEM.
Material and labour for replacement of low pressure switch in discharge pipe of compressor of central AC plant of 30 TR capacity by pumping down/recovering of refrigerant gas from the compressor and testing on completion all as specified and directed. Note: The work shall be carried out by the authorized representative of OEM.
Material and labour for replacement of main PCB card of central AC plant of 3x11 TR capacity for sensing tepmerature by pumping down/recovering of refrigerant gas from the compressor and testing on completion all as specified and directed. Note: The work shall be carried out by the authorized representative of OEM.
Material and labour for leakage testing and gas charging including checking of leakage in both low and high side of the system by feeding dry nitrogen to maintain adequate pressure in the system, restoring the leakages including replacement of teflon sealings of all refrigerant link valves liquid lines, suction line, dicharge line of compressors, gland packages of all angle valves flaring of all connections etc for 30 TR compressor, complete all as specified and directed.
Supply and fixing in replacement of internal and external oil filters as per existing make for capacity 30 TR compresoor, complete all as specified and directed.
Material and labour for replacement of flow switch of central AC plant 3x11 TR capacity, complete all as specified and directed. Note: The work shall be carried out by the authorized representative of OEM.
Material & labour for replacement of FRP/MS/Aluminium Fan Blade of cooling tower of size 450 mm sweep complete all as specified and directed.
Supply and charging the refrigerant gas R-22 in various type and capacity AC plant including detecting leakage and rectifying the defect and testing complete all as specified and directed.
Supply and fixing in replacement of SCPM card of 11TR Chiller unit of Carrier Make Central AC Plant all as specified and directed.
Supply and fixing in replacement contactor MNX 40 Amps, 3 Pole, with Coil Voltage, 220 Volt and NO NC block MNX A1 and making electric connections all as specified and directed. Make : L & T / ABB /Indoasian
Supply and fixing in replacement contactor MNX 25 Amps, 3 Pole, with Coil Voltage, 220 Volt and NO NC block MNX A2 and making electric connections all as specified and directed. Make : L & T/ABB/Indoasian
Material and labour for Maintenance/overhauling of centrifugal/ monoblock pump set 7.5 HP capacity by means of greasing, oiling, replacement of gland of suitable size to stop water leakage from pump set, replacement of nuts, bolts etc as directed at site.
Material and labour for disconnecting the electric connections of the electric motor, dismantling from the pump foundation of AHU or from cooling tower and taking out the old unserviceable winding wire, cleaning the slots, rewinding the electric motor 3 Ph, 415 volts 30KW/40 HP with suitable size of super enamelled copper binding wire including replacement of suitable size bearings, including allied materials like cotton tapes, glass sleeves, varnishing and assembling the motor and coupling with pump and fixing on foudation or with AHU complete and testing all as specified.
Material and labour for disconnecting the electric connections of the electric motor, dismantling from the pump foundation of AHU or from cooling tower and taking out the old unserviceable winding wire, cleaning the slots, rewinding the electric motor 3 Ph, 415 volts 5.5KW/7.5 HP with suitable size of super enamelled copper binding wire including replacement of suitable size bearings, including allied materials like cotton tapes, glass sleeves, varnishing and assembling the motor and coupling with pump and fixing on foudation or with AHU complete and testing all as specified and directed.
Supply and fixing in replacement of coupling of motor-pump of different capacity 7.5 HP to 20 HP and its alignment of its shaft in proper position for smooth working all as specified and directed.
Material and labour for replacement of single phase preventer for central AC Plant main control panel as per exisiting make, complete all as specified and directed.
Supply and fixing in replacement of butterfly valves 80 mm dia all as specified and directed.
Supply and fixing in replacement of butterfly valves 100 mm dia all as specified and directed.
Supply and fixing in replacement of butterfly valves 50 mm dia all as specified and directed.
Supply and fixing in replacement of push botton starter/stop assembly complete all as specified and directed. Make: Schneider/ Seimens/ Legrand or its equivalent.
Supply and fixing in replacement three phase Ammeter digital type of size 96 X 96 mm of range 0-100 Amp with suitable CTs ratio complete all as specified and directed. Make: AE or its equivalent.
Supply and fixing in replacement of Pressure gauge analog type of measuring cap upto 150 Psi, complete all as specified and directed.
Supply and fixing in replacement of Temperature gauge analog type of measuring cap upto 0-100 Centigrade, complete all as specified and directed.
Supply and fixing of cable tray made out of MS sheet of size (6') cutting, bending, fixed to walls/ceilings/cable duct on angle iron support, passing/fixing of cable and GI earth wire in tray including providing nut, bolts washers and clips for holding cable of size as ordered, complete all as specified and directed.
Supply and fixing in replacement of MCCB 4 pole of capacity 400 Amp AC 415 Volts confirming to IS/IEC 60947-2, Breaking capacity 36 KA, positive isolation, thermal magnetic release, adjustable overload 80-100%, adjustable short circuit 5-10 Amp. Make C&S Cat No: CSCN400TM*4P or its equivalent in Legrand, Hegar, ABB all as specified and directed.
Supply and fixing in replacement of MCCB 3 pole of capacity 250 Amp AC 415 Volts confirming to IS/IEC 60947-2, Breaking capacity 36 KA, positive isolation, thermal magnetic release, adjustable overload 70-100%, with rotary handle, adjustable short circuit 5-10 Amp. Make : As per existing panel or its equivalent in Sciemens/Legrand/ Schineder/ Hegar/ ABB all as specified and directed.
Supply and fixing in replacement MCCB 3 pole of capacity 100 Amp AC 415 Volts Confirms to IS/IEC 60947-2, breaking capacity 16 KA, positive isolation, thermal magnetic release, adjustable overload 70-100%, adjustable short circuit 5-10 Amp. Make : As per existing panel or its equivalent in Sciemens/Legrand/ Schineder/ Hegar/ ABB all as specified and directed.
Dismantling and taking down existing duct of any size and type with insulation of any types complete in all respect all as specified and directed.
Supply, assembly and erection of GI sheet with C&SS rectangular/ square duct made out of 'L' shaped hollow profile, duly factory boxed, including all accessories such as corner, cleat, carriage bolt, gasket and appropriate sealant on longitudinal joints etc of size 24 gauge complete all as specifed and directed. Note: The duct shall be fabricated in factory as per IS 655-2006 and to be assembled at the site. No fabrication will be permitted at site. The whole duct shall be tested for any leakage and vibration after completion of the work all as specifed. Make : Bajaj steel industries/ Cool tech Engineers/ Puri Air Conditioner/ Pioneer Airtech.
Material and labour for framed brackets of angles or tees with web and flanges for duct supports cut to shape, drilled and countersunk for screw, including bending and welding angles as necessary, gussest plate, riveting etc n. exc 10 kg each brackets, confirming to Fe 290 Gde E-165 including taking down old unserviceable MS channel support of AC duct, complete all as specifed and directed.
Material and labour for duct insulation with resin bonded fibre glass wool roll of density 24 Kg/Cum, with factory laminated aluminium vapour barrier, thickness of insulation 50mm as specified including the following: (a) Material and labour for cleaning the duct surface (to be insulated) by scraping carefully with wire brush etc. to make the surface completely free of millscale, dirt, dust, grease and other foreign care so that all ducts jpints are sealed against any leakage. (b) Material and labour for applying rubber based adhesive CPRX compound. (c) Material and labour for sealing of all longitudinal joints and circular overlaps with and including aluminium foil tape 50mm wide, to make the insulation leakproof. (d) Material and labour for securing the insulation with and including mechanical fastened nylon/steel straps of size 12 mm/50mm at maximum intervals of 1.2 mtrs.
Taking down and removing the Old unserviceable PVC Fins from cooling tower with balancing of cap 3x11 TR and clean the cooling tower by jet pump with suitable chemical.
Material and labour for replacement of cooling tower fans including balancing of cooling tower of paharpur make of cap 3x11 TR including taking out old unserviceable fan and making the cooling tower functional all as specified and directed.
Material and labour for replacement of sprinkler with arms including balancing of cooling tower, of make paharpur of cap 30 TR of with taking out unserviceable sprinkler and making the cooling tower functional all as specified and directed.
Material and Labour for preparing the outer and inner metallic surface of cooling tower of 11 TR capacity with primer coats and two coats of grey synthetic enamel paint matching to existing colour complete all as specified and directed.
Material and labour for preparing the outer and inner metallic surface of cooling tower of 30 TR capacity with primer coat and two coats of grey synthetic enamel paint matching to existing colour, complete all as specified and directed.
Supply and laying with floor/wall of MS pipe light grade 80 mm bore in oulet of AHU of different capacity all as specified.
Supply and laying with floor/wall of MS pipe light grade 65 mm bore in oulet of AHU of different capacity all as specified.
Supply and laying with floor/wall of MS pipe light grade 50 mm bore in oulet of AHU of different capacity all as specified.
Supply and fixing of Direct acting solenoid valve 2/2 way ( on-off) based on system capacity with a minimum 0f 1 psi pressure drop as directed by Engr-in-Charge. Make : Honeywell/Uflow
Supply and fixing steel structure i.e angle iron (50x50x6mm), ISMC (75x40) in various forms of brackets for supporting the MS pipe inside and outside of the hanger including painting complete all as specified and directed.
Automatic air purger valves of nominal size 25mm. Make:- Anergy
Supply, fixing, testing, commissioning of volume control damper louvers for grills 2'x2'. Make- Ruskin titus
Supply, fixing, testing, commissioning of volume control damper louvers for grills 1'x1'. Make- Ruskin titus
Supplying, laying, testing of PVC insulated and sheathed (ISI marked) copper multistrand conductor armoured cable of 1.11 KV grade conforming to IS-1554 of following sizes all as specified. (i) 4 x 25 Sqmm Make- Havells/KEI/Plaza
4 x 6 Sqmm
3 x 4 Sqmm
Notice Board (Display Board) of size 1200mm x 900mm as shown on drawing No FD-1042 sheet 1/1 dt 29.9.1993 for displaying the duty roaster description and including chart in three languages(English, Hindi and Urdhu) for electric shock and burn injury, complete all as specified and directed.
Material and labour for supply, laying, jointing, testing & commissioning of XLPE insulated , armoured , heavy duty electric cable with aluminium conductor, 1100 volts earth grade of size 3.5 core 95 sqmm laid in tranches, on wall/poles/floor or in air, passing through pipes/ducts/roads/path/drain, complete all as specified and directed.
Material and labour for sand cushioning to under ground cable with dry sand locally available 8 cm thick before laying the cable and 15 cm above the cable including stretching and testing of cable complete all as specified and directed.
Material and labour for well burnt sub class B bricks laid dry flat to cover the cable with equal to the length of cable and cutting each other for protection of cable, complete all as specified and directed.
Excavation in trenches not exc 1.5 metre wide not exc 1.5 meter in depth and getting out in soft/loose soil complete all as specified and directed.
Returning filling in including spreading, levelling, watering and well ramming in layers not exc 25 cm thick in any type of soil, complete all as specified and directed.
Removing of excavated soil to a distance not exc 50 metre and depositing where directed at a level not exc. 1.5m above the starting point, complete all as specified and directed.
Material and labour for earthing complete with galvanised steel earth plate electrode 60cmx60cmx6mm thick burried directly in ground (earth pit not less than 2.25 M deep below normal ground level with top edge of plate not less than 1.5 M below normal ground level, connecting to the galvanised iron earth strip protected by provision of GI medium grade pipe 40mm bore including provision of concrete pit in PCC(1:2:4) type B-1 using 20 mm graded stone aggregates with 40mm thick cover of RCC (1:2:4) reinforced with XPM weight not less than 4 Kg/Sqm and frame of angle iron 40x40x6mm with lugs 02 Nos and handle of 6mm dia MS bar made of shape, GI light grade 20mm bore pipe for watering, perforated at bottom. 1.75 M long placed on top edge of earth plate, Charcoal, common salt filled 150mm thick, all around each plate, test point made out of 40x8mm flat iron galvanised with fixing arrangement, funnel wire mesh and earth work in any type of soil returning filling in and removal of surplus soil to a distance not exc. 50M all as per electrical plate No-3 of SSR part-I and connecting to earth test point all as specified or indicated including testing on completion. Note:- The quoted rate of earthing shall be deemed to include cost of 7.5 meter long galvanised strip 32x6 mm dia and protection pipe of 40mm bore medium grade(ISI marked). Any variation in length shall be adjusted through deviation order based on SSR rates.
M/S LATIF AHMAD MIR
M/S RATHER CONSTRUCTION CO
Top Mind Industries Pvt Limited
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .