Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹26.1 LAccepted-AOC | ₹26.1 L | L1 | Accepted-AOC ACCEPTED BEING L1 |
| 2 | L2₹26.9 LRejected-Finance F 402 AMBIKA APARTMENT PLOT A 9 SECTOR 20 NERUL W NAVI MUMBAI 400 706 | THANE | MAHARASHTRA | 400706 | ₹26.9 L | L2 | Rejected-Finance Rejected for being other than L1 |
| 3 | L3₹27.6 LRejected-Finance 0 | ₹27.6 L | L3 | Rejected-Finance Rejected for being other than L1 |
| 4 | L4₹27.7 LRejected-Finance ROOM NO A 46 GALI NO 11 GANESH MURTHY NAGAR PART NO 3 CAPT PRAKASH PETHE MARG CUFFE PARADE COLABA MUMBAI 400005 | MUMBAI | MUMBAI | MAHARASHTRA | 400005 | ₹27.7 L | L4 | Rejected-Finance Rejected for being other than L1 |
| 5 | L5₹27.7 LRejected-Finance | ₹27.7 L | L5 | Rejected-Finance Rejected for being other than L1 |
| Sl No | Description | Qty | Unit | A S ENTERPRISES L3 | Advait Enterprises L2 | jkconstruction L4 | Nitish Nandkumar Bothale L5 | R N KHARWAR & SONS L6 | Ruhi Construction L1 | SHRIKALP ENGINEERS AND CONTRACTORS L7 |
|---|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Supply, installation, testing and commissioning of Servo controlled voltage stabilizer (confirming to BIS 9B15(Part-I):1994, reaffirmation 2019 latest version), Three phase, four wire (RYBN), 50 Hz, Naturally Oil cooled, outdoor type IP 55 protection, with canopy, unbalanced type, copper wound, metallic body duly powder coated with lifting Hooks two nos, digital display type, relay free smooth and silent operation with first filling of Transformer oil up to level having following specification:
(a) Capacity 800 KVA
(b) Type-Suitable for unbalanced load and unbalanced input
(c) Input voltage 360V-480V, Input frequency 50 Hz
(d) Output voltage - stabilized at any deigned/ desired voltage 415 ± 1 %
(e) Rated frequency- 50 Hz
(f) Wave form distortion - Nil
(g) Response time- not to exceed 20 milli seconds
(h) Sensitivity-(+/-)1%
(j) Rate of correction - Not less than 6 Volt/second between phase and neutral
(k) Efficiency- more than 95%
(l) Type of load-three phase, unbalanced type
(m) Metering- Digital display Voltmeter/ Ammeter with multi-functional meter
(n) Operating temperature- For outdoor use up to maximum ambient temperature +55°C
(o) Dimmer rating- 125A*2
(p) Dimension of tanks- (74x48x75) in inches | 1 | Each | 20,25,000 ₹20.3 L | 20,00,000 ₹20 L | 20,40,000 ₹20.4 L | 20,50,000 ₹20.5 L | 20,80,000 ₹20.8 L | 19,50,000 ₹19.5 L | 21,00,000 ₹21 L |
| 1.10(q) Oil Capacity- 1100 Litres (r) Class of insulation- Class F (s) Mode of operation- Automatic/manual along with bypass option (t) Winding Temperature rise- Max 55°C (10°C above operating temp) (u) Transformer oil - IS 335 marked (v) Core- CRGO M4Grade/CRNO (Cold Roll Grain Oriented)/ (Cold Rolled Non- Oriented) (w) Auto transformer (Variac)-100percent Copper wound Electrolytic Grade (x) Losses-As per IS Norms (y) Power Factor-Not less than 0.95 (z) Protecton- (i) Overload protections (ii) Short Circuit protections (iii) High/Low voltage cutoff (iv) By pass arrangement in case of Emergency (v) Single phase sequence change /phase fail protection (vi) Earth fault protection (aa) Standard Fitting & Accessories e.g Marking plate, lifting lugs, Cl Rollers, Earthing Terminals etc cable box. Note: The voltage stabilizer should be placed on a suitable foundation of size recommended by OEM. (Note: Cost of foundation deemed to be included in the quoted rate) | ||||||||||
| 2.00 | Supply, laying and testing cable XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 500 sqmm 3.5 core complete all as specified and directed by Engineer-in-Charge. | 60 | RM | 2,550 ₹1.5 L | 2,500 ₹1.5 L | 3,000 ₹1.8 L | 2,800 ₹1.7 L | 2,700 ₹1.6 L | 2,400 ₹1.4 L | 3,000 ₹1.8 L |
| 3.00 | Earth work in excavation by mechanical means (Hydraulic excavator)/ in foundation trenches or drains (not exceeding 1.5 metres in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift up to 1.5 metres, including getting out the excavated hard rock (blasting prohibited) and disposal of surplus excavated hard rock as directed, within a lead of 50 metres complete all as specified and directed. | 4.05 | Cum | 1,150 ₹4,657.50 | 1,000 ₹4,050 | 1,100 ₹4,455 | 1,200 ₹4,860 | 900 ₹3,645 | 950 ₹3,847.50 | 1,000 ₹4,050 |
| 4.00 | Supply and laying HDPE duct pipe of bore 100 mm for protection of electric cables complete all as specified and directed by Engineer-in-charge. | 35 | RM | 700 ₹24,500 | 700 ₹24,500 | 750 ₹26,250 | 600 ₹21,000 | 800 ₹28,000 | 750 ₹26,250 | 750 ₹26,250 |
| 5.00 | Returning, filling in, including spreading, levelling watering and well ramming in layers not exceeding 25 cm in disintegrated soil complete all as specified and directed. | 3.48 | Cum | 185 ₹643.80 | 180 ₹626.40 | 180 ₹626.40 | 150 ₹522 | 200 ₹696 | 200 ₹696 | 150 ₹522 |
| 6.00 | Removing of excavated rock not exceeding 50 metres from starting points complete all as specified and directed. | 0.57 | Cum | 450 ₹256.50 | 400 ₹228 | 440 ₹250.80 | 450 ₹256.50 | 400 ₹228 | 350 ₹199.50 | 400 ₹228 |
| 7.00 | Material and Labour in repairs for GI tubing medium grade including accessories for protection of cables on poles / under road crossing of 100 mm bore size complete all as specified and directed. | 12 | RM | 1,000 ₹12,000 | 900 ₹10,800 | 900 ₹10,800 | 925 ₹11,100 | 1,050 ₹12,600 | 1,000 ₹12,000 | 925 ₹11,100 |
| 8.00 | Supply & fix of ACB 4 Pole, 415 Volt, 50 kA with Thermal Magnetic Release (Manual draw out type) of capacity 1250 Amps embedded in a closed enclosure LT panel ( from CPRI approved manufacturer) ground mounted out door type Panel of suitable size, centre opening in two halve front, hinged type door made out of CRCA sheet and outer door made out of 3 mm thick with locking arrangement on it duly powder coated and fixed with MS angle iron frame of size 40X40X6 mm duly embedded in PCC platform and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour along with gable roof, ventilation louvers & including control wiring with suitable Copper wire including copper bus bar of 1250 amps capacity complete to accommodate the ACB as incoming with two run 500 sqmm cable and busbar as outgoing with two run 500 sqmm cable all as specified and directed by Engineer-in-Charge. Note:-
(a) Rates quoted must be included of panel accessories like cable gland, Aluminium Lugs, control wiring, Bus bar, Digital Ammeter, Voltmeter, danger plate, indicator lamp, push button, ACB and disconnecting existing cable from the transformer Panel and re connecting and fixing of the same in Panel along with proper dressing of cables etc.
(b) Rate quoted does not include the item cost of LT Cable and it will be paid separately under BOQ.
(c) The panel design and drawing should get approved by the department before placing order to the manufacturer. | 1 | Each | 3,75,500 ₹3.8 L | 3,50,000 ₹3.5 L | 3,50,000 ₹3.5 L | 3,60,000 ₹3.6 L | 3,55,000 ₹3.5 L | 3,25,000 ₹3.3 L | 3,65,000 ₹3.6 L |
| 9.00 | Supplying and laying synthetic Rubber insulated mats 2 mm thick for voltage up to 3.3 KV for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2 x1 metre complete all as specified and directed by Engineer-in-Charge. | 5 | Each | 1,750 ₹8,750 | 1,500 ₹7,500 | 1,800 ₹9,000 | 1,500 ₹7,500 | 1,650 ₹8,250 | 1,600 ₹8,000 | 1,600 ₹8,000 |
Tender Value
₹25.3 L
EMD Value
₹50,500
Closing Date
20 Jan 2026, 6:00 pmClosed
GE I CG RATNAGIRI
Military Engineer Service Garrison Engineer I CG Ratnagiri SLUY Shed Plot, W19 23 MIDC Mirjole Ratnagiri 415 639
PROVISION OF SERVO VOLTAGE STABILIZER AND ALLIED WORKS AT ICGAS RATNAGIRI.
2025_MES_746566_1
8286/E8
Open Tender
Electrical and Maintenance Works
180 days
RATNAGIRI
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE I CG RATNAGIRI
₹50,500
Yes
6 Mar 2026
30 Dec 2025
27 Jan 2026
31 Dec 2025
20 Jan 2026
13 Jan 2026
Supply, installation, testing and commissioning of Servo controlled voltage stabilizer (confirming to BIS 9B15(Part-I):1994, reaffirmation 2019 latest version), Three phase, four wire (RYBN), 50 Hz, Naturally Oil cooled, outdoor type IP 55 protection, with canopy, unbalanced type, copper wound, metallic body duly powder coated with lifting Hooks two nos, digital display type, relay free smooth and silent operation with first filling of Transformer oil up to level having following specification: (a) Capacity 800 KVA (b) Type-Suitable for unbalanced load and unbalanced input (c) Input voltage 360V-480V, Input frequency 50 Hz (d) Output voltage - stabilized at any deigned/ desired voltage 415 ± 1 % (e) Rated frequency- 50 Hz (f) Wave form distortion - Nil (g) Response time- not to exceed 20 milli seconds (h) Sensitivity-(+/-)1% (j) Rate of correction - Not less than 6 Volt/second between phase and neutral (k) Efficiency- more than 95% (l) Type of load-three phase, unbalanced type (m) Metering- Digital display Voltmeter/ Ammeter with multi-functional meter (n) Operating temperature- For outdoor use up to maximum ambient temperature +55°C (o) Dimmer rating- 125A*2 (p) Dimension of tanks- (74x48x75) in inches
Supply, laying and testing cable XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 500 sqmm 3.5 core complete all as specified and directed by Engineer-in-Charge.
Earth work in excavation by mechanical means (Hydraulic excavator)/ in foundation trenches or drains (not exceeding 1.5 metres in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift up to 1.5 metres, including getting out the excavated hard rock (blasting prohibited) and disposal of surplus excavated hard rock as directed, within a lead of 50 metres complete all as specified and directed.
Supply and laying HDPE duct pipe of bore 100 mm for protection of electric cables complete all as specified and directed by Engineer-in-charge.
Returning, filling in, including spreading, levelling watering and well ramming in layers not exceeding 25 cm in disintegrated soil complete all as specified and directed.
Removing of excavated rock not exceeding 50 metres from starting points complete all as specified and directed.
Material and Labour in repairs for GI tubing medium grade including accessories for protection of cables on poles / under road crossing of 100 mm bore size complete all as specified and directed.
Supply & fix of ACB 4 Pole, 415 Volt, 50 kA with Thermal Magnetic Release (Manual draw out type) of capacity 1250 Amps embedded in a closed enclosure LT panel ( from CPRI approved manufacturer) ground mounted out door type Panel of suitable size, centre opening in two halve front, hinged type door made out of CRCA sheet and outer door made out of 3 mm thick with locking arrangement on it duly powder coated and fixed with MS angle iron frame of size 40X40X6 mm duly embedded in PCC platform and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour along with gable roof, ventilation louvers & including control wiring with suitable Copper wire including copper bus bar of 1250 amps capacity complete to accommodate the ACB as incoming with two run 500 sqmm cable and busbar as outgoing with two run 500 sqmm cable all as specified and directed by Engineer-in-Charge. Note:- (a) Rates quoted must be included of panel accessories like cable gland, Aluminium Lugs, control wiring, Bus bar, Digital Ammeter, Voltmeter, danger plate, indicator lamp, push button, ACB and disconnecting existing cable from the transformer Panel and re connecting and fixing of the same in Panel along with proper dressing of cables etc. (b) Rate quoted does not include the item cost of LT Cable and it will be paid separately under BOQ. (c) The panel design and drawing should get approved by the department before placing order to the manufacturer.
Supplying and laying synthetic Rubber insulated mats 2 mm thick for voltage up to 3.3 KV for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2 x1 metre complete all as specified and directed by Engineer-in-Charge.
Material and Labour for end outdoor jointing kit suitable for XLPE/ PVC Cable 1100 volts grade, heat shrinkable type for indoor/ outdoor applications complete including preparing ends of cable of size 500 sqmm 3.5 core all as directed and specified by Engineer-in-Charge.
Supply and installation of fast earth electrode 3.0 metre length size model F84, having two Mild Steel pipe one inside the other with proper not deep galvanised outer dia 88 mm and inner dia 48 mm and the cavity between the rod pipes is filled with ground resistance improment powder, sealed with both end the outer pipe of electrode should be zinc coated, the electrode should buried directly in the ground by making boring of diameter 10'' with boring machine highly conductive non-magnetic and non-corrosive is to be connected with GI strip 25 X 4 mm of required length to facilitate further connection to earth dolly and provision of earthing chamber in bricks wall size 45 x 45 x 15 cm an having PCC cover of required size complete as per IS 3034 and as directed.
Supply and Fix earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 25x4mm galvanised iron strip complete all as specified & directed.
Material and Labour for GI tubing medium grade in repairs including accessories for protection of cables on poles / under road crossing of 40 mm bore size complete all as specified & directed.
Material and labour for laying of 40 mm graded stone aggregate in layers not exceeding 15 cm thick including spreading, levelling all around the Voltage stabilizer and substation complete all as specified & directed.
Please Enable Macros to View BoQ information
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.22 MB
8286TENDER.pdf
Tender Documents • 0.38 MB
BOQ_835985.xls
BOQ • 0.45 MB
Download all tender documents and submit your bid