Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹15.2 LAccepted-AOC | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹16.6 L+₹1.2 L (8.08%)Rejected-AOC | L2 | Rejected-AOC Other than lowest bidder | |
| 3 | L3₹18.6 L+₹3.2 L (21.1%)Rejected-AOC | L3 | Rejected-AOC Other than lowest bidder | |
| 4 | L4₹22.5 L+₹7.1 L (46.4%)Rejected-AOC | L4 | Rejected-AOC Other than lowest bidder |
Tender Value
₹25 L
EMD Value
₹50,000
Closing Date
4 Mar 2020, 6:00 pmClosed
GE(S) Jaipur
GE(S) Jaipur, MES, Kalyan Marg, Bani park,Jaipur-302006
MANNING AND OPERATION OF STP NO 4,5 THROUGH OUTSOURCING AND ITS ALLIED WORKS UNDER AGE E/M II OF GE SOUTH JAIPUR
2020_MES_321030_1
GE (S)J-54P/2019-20 8545/ /E8
Open Tender
Civil Works
Item Rate
335 days
GE (S) Jaipur
Category D a(ii) and d(v)
9 documents required · 9 mandatory
₹500
Yes
GE (S) Jaipur
₹50,000
Yes
26 Mar 2020
1 Feb 2020
6 Mar 2020
1 Feb 2020
4 Mar 2020
15 Feb 2020
1 Feb 2020 - 8 Feb 2020
Amount
Manning and operation of Sewage treatment plant 500 KLD at Ajaymeru by providing 01 (One) FGM in each shift. Operation consists of two shift in a day (each shift is having 8 hours of duration) i.e. from 0600 hours to 1400 hours & 1400 hours to 2200 hours on all working days including Sundays and holidays. The installation comprising of following items/ machinery / fittings etc complete all as specified and directed by the Engr-in-charge. (a) Sewage pumping set 5.0 HP to 12.5 HP capacity – 05 Nos (b) Filter feed pumping set 7.5 HP capacity – 02 Nos (c) Root air blower 20 HP capacity - 02 Nos (d) Centrifugal pumping set 25 HP capacity – 02 Nos (e) Filter press pump set 1.37 HP - 02 Nos (f) LT Panel complete with MCCBs and Starters - 02 Nos (g) Main Header alongwith sluice valves of different size (h) UG Sump 50000 Glns - 01 Nos
Manning and operation of Sewage treatment plant 500 KLD at Gothic line by providing 01 (One) FGM in each shift. Operation consists of two shift in a day (each shift is having 8 hours of duration) i.e. from 0600 hours to 1400 hours & 1400 hours to 2200 hourson all working days including Sundays and holidays. The installation comprising of following items/ machinery / fittings etc complete all as specified and directed by the Engr-in-charge. (a) Sewage pumping set 5.0 HP to 12.5 HP capacity – 05 Nos (b) Filter feed pumping set 7.5 HP capacity – 02 Nos (c) Root air blower 20 HP capacity - 02 Nos (d) Centrifugal pumping set 25 HP capacity – 02 Nos (e) Filter press pump set 1.37 HP - 02 Nos (f) LT Panel complete with MCCBs and Starters - 02 Nos (g) Main Header alongwith sluice valves of different size (h) UG Sump 50000 Glns - 01 Nos
[Note for srl item No 1 &2 :- The details of operation of above mentioned sewage installations also comprising the following works :- (a) Operation of sewage plant and pumping set time to time as directed by Engr-in-Charge. (b) Installation shall be maintained and operated daily including Sunday & Holidays. (c) Adding Bleaching powder/Altoch GP/Aquafit grannular as directed in the treated water through chemical dozing pump installed at sewage treatment plant or as per requirement as directed by Engr-in-charge . (d) Operation of pumps and opening of sluice valves at collection well to supply the raw material to sewage treatment plant time to time as laid down or as directed by Engr-in-Charge. (e) Operation of pumps and opening of sluice valves at sewage treatment plant to supply the treated water to the users time to time as laid down or as directed by Engr-in-Charge. (f) The contractor shall be responsible to keep the sewage installation neat and clean on every day including 15 mtrs all around the installation and maintain seasonal flower/decorative plants in front of pump house.
Supply & Laying 2.5 sqmm 10 core multy standard copper condutor cable (for Sludge pump) PVC insulated over all sheethed roundof 1100 volts ISI marked complete all as specified and directed . (Make:- Finolex/L&T/Havells)
Taking out Non clog sewage lifting pump set of Cap 5.0 HP, 3 phase, 415 volts, 50Hz, AC supply along with pipe from the sewage collection well after disconnecting electric connection, dismentling of pump and motor, repairing/ replacing defective parts as ordered and re-assembling and testing including replacing worn out nuts, bolts, washers complete and lowering the same after repairing and making electrical and delivery pipe connections complete all as specified and directed for replacement of u/s parts if any as supply only under item Nos 4.01 to 4.05.. ( Note :- Spare parts required for replacement shall be measured and paid for separately and cost of taking out old & fixing new if any ordered for item No. 4.01 to 4.04 shall be deemed to be included in quoted rate of this item.)
Supply only upper/lower mechanical seal .
Supply only 'O' ring gasket
Supply only ball bearing as per existing No ( Make : NBC/SKF).
Supply only lubricant oil 20W40
Rewinding the stator with super enamelled copper wire of suitable size and class of insulation including insulation paper, sleeves, thimbles etc.
Taking out Non clog sewage lifting pump set of Cap 7.5 HP, 3 phase, 415 volts, 50Hz, AC supply along with pipe from the sewage collection well after disconnecting electric connection, dismentling of pump and motor, repairing/ replacing defective parts as ordered and re-assembling and testing including replacing worn out nuts, bolts, washers complete and lowering the same after repairing and making electrical and delivery pipe connections complete all as specified and directed for replacement of u/s parts if any as supply only under item Nos 5.01 to 5.05.. ( Note :- Spare parts required for replacement shall be measured and paid for separately and cost of taking out old & fixing new if any ordered for item No. 5.01 to 5.04 shall be deemed to be included in quoted rate of this item.)
Supply only upper/lower mechanical seal .
Supply only 'O' ring gasket
Supply only ball bearing as per existing No ( Make : NBC/SKF).
Supply only lubricant oil 20W40
Rewinding the stator with super enamelled copper wire of suitable size and class of insulation including insulation paper, sleeves, thimbles etc.
Taking out Raw sewage lifting (submersible) pump set of Cap 12.5 HP, 3 phase, 415 volts, 50Hz, AC supply along with pipe from the sewage collection well after disconnecting electric connection, dismentling of pump and motor, repairing/ replacing defective parts as ordered and re-assembling and testing including replacing worn out nuts, bolts, washers complete and lowering the same after repairing and making electrical and delivery pipe connections complete all as specified and directed for replacement of u/s parts if any as supply only under item Nos 6.01 to 6.05 N. ( Note :- Spare parts required for replacement shall be measured and paid for separately and cost of taking out old & fixing new if any ordered for item No. 6.01 to 6.04 shall be deemed to be included in quoted rate of this item.)
Supply only upper/lower mechanical seal .
Supply only 'O' ring gasket
Supply only ball bearing as per existing No ( Make : NBC/SKF).
Supply only lubricant oil 20W40
Rewinding the stator with super enamelled copper wire of suitable size and class of insulation including insulation paper, sleeves, thimbles etc.
Dismantling of monoblock pump set (Filter feed pump) after disconnecting from power mains & pipe line of Capacity 5 - 7.5 HP, 3 phase, 415 volts, 50Hz, AC supply & re connect to pipe line & power mains after carrying out repairs if any under item No. 7.01 to 7.04 complete all as specified and directed. ( Note :- Spare parts required for replacement shall be measured and paid for separately and cost of taking out old & fixing new if any ordered for item No. 7.01 to 7.04 shall be deemed to be included in quoted rate of this item.) :-
Transportation of motor to contractor’s work shop cutting of burnt winding & rewinding the stator with super enamelled copper wire of suitable size and class of insulation incl insulation paper, sleeves,thimbles etc.
Supply only, stainless steel pump shaft.
Supply only, gun metal impeller with neck key, distance bush.
Supply only ball bearing as per existing No ( Make : NBC/SKF).
Dismantling of centrifugal pump set (Sewage treated water pump) after disconnecting from power mains & pipe line of Capacity upto 15 HP, 3 phase, 415 volts, 50Hz, AC supply & re connect to pipe line & power mains after carrying out repairs if any under item No. 8.01 to 8.02 complete all as specified and directed. ( Note :- Spare parts required for replacement shall be measured and paid for separately and cost of taking out old & fixing new if any ordered for item No. 8.01 to 8.02 shall be deemed to be included in quoted rate of this item.) :-
Transportation of motor to contractor’s work shop cutting of burnt winding & rewinding the stator with super enamelled copper wire of suitable size and class of insulation incl insulation paper, sleeves,thimbles etc.
Supply only ball bearing as per existing No ( Make : NBC/SKF).
Dismantling of centrifugal pump set (Sewage treated water pump) after disconnecting from power mains & pipe line of Capacity 15 to 25 HP, 3 phase, 415 volts, 50Hz, AC supply & re connect to pipe line & power mains after carrying out repairs if any under item No. 9.01 to 9.04 complete all as specified and directed. ( Note :- Spare parts required for replacement shall be measured and paid for separately and cost of taking out old & fixing new if any ordered for item No. 9.01 to 9.04 shall be deemed to be included in quoted rate of this item.) :-
Transportation of motor to contractor’s work shop cutting of burnt winding & rewinding the stator with super enamelled copper wire of suitable size and class of insulation incl insulation paper, sleeves,thimbles etc.
Supply only, stainless steel pump shaft.
Supply only, gun metal impeller with neck key, distance bush.
Supply only ball bearing as per existing No ( Make : NBC/SKF).
Dismantling of Root Air blower of capacity 20 HP , 3 phase, 415 volts, 50Hz, AC supply after disconnecting from power mains & pipe line and reconnecting the same after carrying out repairs under if any under item No. 10.01 to 10.02 complete all as specified and directed. ( Note :- Spare parts required for replacement shall be measured and paid for separately and cost of taking out old & fixing new if any ordered for item No. 10.01 to 10.02 shall be deemed to be included in quoted rate of this item.) :-
Transportation of motor to contractor’s work shop cutting of burnt winding & rewinding the stator with super enamelled copper wire of suitable size and class of insulation incl insulation paper, sleeves,thimbles etc.
Supply only ball bearing as per existing No ( Make : NBC/SKF).
Supply and fix in replacement of MCCB of the following sizes complete all as specified and directed :- Make - L&T/Havells/HPL or equivalent.
MCCB Four pole 250 Amp, 36 KA, Type DN2, 415 Volts, 50 Hz.
MCCB Four pole 160 Amp, 30 KA,Type DU, 415 Volts, 50 Hz.
MCCB Four pole 100 Amp, 25 KA, Type DN0, 415 Volts, 50 Hz.
MCCB TP 63 Amp, 25 KA, Type DN0, 415 Volts, 50 Hz.
Surface excavation not exceding 30 cm deep in hard and dense soil and averaging 15 cm deep and getting out green vegetation, roots, bushes, etc surrounding of pump house, cutting anxious green growth / vegetation growth for cleaning out the area around OH tank / pump house at ground level by cutting up root, un- wanted plants / trees bushes and removal the same to a distance not exceeding than 50 mtr complete all as specified and directed.
Supply and fix in repair of fully automatic star delta starter (MUG-10) comprising of combo volt and ammeter single phase preventor, over load relay and timer housed in MS sheet power coated enclosure up to 10 HP Capacity complete all as specified and directed. (Make:- L&T Cat part No SS-95974 or equivalent
Supply and fix in repair of fully automatic star delta starter (MUG-20) comprising of combo volt and ammeter single phase preventor, over load relay and timer housed in MS sheet power coated enclosure 10 to 25 HP Capacity complete all as specified and directed. (Make:- L&T Cat part No SS-95975 or equivalent
M&L for Replacement of U/S contactor of MNX 9 complete all as specified and directed. Make :- L&T/ Havells/Siemens or equivalent.
M&L for Replacement of U/S contactor of MNX 18 complete all as specified and directed. Make :- L&T/ Havells/Siemens or equivalent.
M&L for Replacement of U/S contactor of MNX A2 complete all as specified and directed. Make :- L&T/ Havells/Siemens or equivalent.
M&L for Replacement of U/S Bimetal over load relay range 4.5 - 7.5 /6.0 - 10 Amps, 415 Volts complete all as specified and directed by Engr-in-charge.Make- L&T/Minilec/Technica or equivalent.
M&L for Replacement of U/S Bimetal over load relay range 9.0 - 15 Amps, 415 Volts complete all as specified and directed by Engr-in-charge.Make- L&T/Minilec/Technica or equivalent.
M&L for Replacement of U/S Bimetal over load relay range 14 - 23 Amps, 415 Volts complete all as specified and directed by Engr-in-charge.Make- L&T/Minilec/Technica or equivalent.
M&L for Replacement of u/s electronic timer 0 - 60 sec complete all as specified and directed. Make Technica/L&T /Havells or equivalent
M&L for Replacement of u/s single phase preventor complete all as specified and directed. Make- L&T/Minilec/Technica or equivalent.
M&L for Replacement of U/S MCB TPN 40 Amps, 10 KA , 415 volts complete all as specified and directed. Make- L&T/Havells/Legrand or equivalent.
M&L for Replacement of U/S MCB TPN 63 Amps, 10 KA , 415 volts complete all as specified and directed. Make- L&T/Havells/Legrand or equivalent.
Supply of UCTECH -01 (liquid floculants ) using for the de- established colloidal particales together to form large aggregates of Sewage water ,dozing for two times /day and using at the time of peak water flow in a Settling tank complete all as specified and directed
Supply of UCTECH -02(liquid coagulants )using for neutralizing the non - settleable particles & allow to form clumps of Sewage water ,dozing for two times /day and using at the time of peak water flow in a Settling tank complete all as specified and directed
Supply of UCTECH -03(liquid coagulants ) using for stop biological fouling in working zone and make odorless water to provide healthy environment of Sewage water ,dozing for two times /dayand using at the time of peak water flow in a Collection tank complete all as specified and directed
Supply of UCTECH -04 (liquid disinfectant ) using for deal with bacterial problem and make fare color of water ,dozing for two times /day and using at the time of peak water flow in a Holding tank complete all as specified and directed
Supply of UCTECH -07 (liquid neutralizer ) using for maintain the pH in 7-8 rangeto sustain quality of water as per pollution control norm of water , dozing for two times /day and using at the time of peak water flow in a Aeration tank complete all as specified and directed
Supply of Bleaching powder grade I of approved make all as specified and directed Make - Shriram/ Vikram or equivalent in ISI marked
M & L and repalcement of U/S sluice valves,class PN 1.0 of undermentioned type and size with cast iron body with forged brass spindle, non rising type and cast iron wheel head, both ends flanged, IS-14846 marked comlete with neoprene rubber gasket ,jointing material and incl nuts/bolts/washer of suitable size etc complete all as specified and directed .
80 mm bore
100 mm bore
150 mm bore
M & L and replacement of U/S non return valves,class PN 1.0 of undermentioned type and size 100 mm dia with cast iron body and both ends flanged, ISI marked comlete with neoprene rubber gasket ,jointing material and incl nuts/bolts/washer of suitable size etc complete all as specified and directed.
S & F in repair detachable joints suitable for CI/DI ppe complete with cast iron ring , rubber rings nut, bolts, excavation and earthwork, cutting of pipe etc of following sizes complete all as specified and directed . (Note. Excavation and earth work shall be measured and paid separately)
80 mm dia
100 mm dia
150 mm dia
M & L and repalcement of U/S Butterfly vlave 80 mm dia , ISI marked complete with all fittings/accessories, required for fixing complete all as specified and directed
M&L and repalcement of U/S foot valve cast iron of size 100 mm flanged type with all accessories complete all as specified and directed by Engr-in-charge
Supply and laid in trenches High density polyethylene pipes (HDPE), PE 80 grade and pressure rating 6 Kgf/cm of size 63 mm dia including taking out complete all as specified and directed.
Supply and laid in trenches High density polyethylene pipes (HDPE), PE 100 grade and pressure rating 6 Kgf/cm of size 110 mm dia including taking out complete all as specified and directed..
Excavation & earth work in trenches n.exc 1.5m wide and n.exc 1.5m in depth and getting out in soft and loose soil including trimming of sides and bottom of trenches complete all as specified and directed.
Returning, filling-in, including spreading, watering and well ramming in layers n.exc 25cm thick each in soft/loose soil complete all as specified and directed.
Removing excavated surplus soil to a distance n.exc 50m and depositing where directed at a level n.exc 1.5m above the starting point complete all as specified and directed.
M & L for 3- layer PP-R (Polypropylene Random Copolymer) pipes SDR 7.4 & SDR 11 UV stabilised and antimicrobial fusion welded having thermal stability for sewage treated water supply and including all types required fittings with PP-R plain & brass threaded polypropylene random fittings laid in trenches including taking out old U/S pipe complete all as specified and directed of the following sizes :- (Make- Prince / SFMC)
75 mm dia
63 mm dia
50 mm dia
25 mm dia
Desludging underground sewage sump at Queens road of internal dia 3.2 meter and depth upto7.5 meter and removing away sludge to a distance not less than 150 meters including burying sludge into pits and covering pits with excavated earth and including cleaning of pump house inside and surrounding all around up to complete fencing of sewage installation by removing of all vegitation, bushes, mud, dirt, dust etc and shift to a distance not exceeding 150 meter including applying two coats of white wash internally after preparation of surface, complete all as specified and directed by the Engineer in Charge.
Desludging underground sewage sump at Old Gothic line and Ajay Meru of internal dia 4.9 meter and depth upto 7.5 meter and removing away sludge to a distance not less than 150 meters including burying sludge into pits and covering pits with excavated earth and including cleaning of pump house inside and surrounding all around up to complete fencing of sewage installation by removing of all vegitation, bushes, mud, dirt, dust etc and shift to a distance not exceeding 150 meter including applying two coats of white wash internally after preparation of surface, complete all as specified and directed by the Engineer in Charge. Note:- For item No 42 & 43 Sewage well not clean by Mannual ,only cleaning through Machinery stricly follow. (a) Quoted rates shall also include for excavation of pits for burying sludge and removing of surplus soil to a distance not exceeding 150 meters. (b) T&P, Manpower, labour & transportation charges etc is deemed to be included in the quoted rates. (c ) The complete sludge to be removed for which adequate man power, T&P, sludge removing vibrator and sludge carrying vehicle including diesel driven non-clog pump set for pumping out the sewage / sludge to be made available with in the overall cost of the quoted rate. (d) The bidder to visit the site along with AGE E/M - II to know about the condition of sewage installation and criticality of the work. (e) Necessary arrangements viz pipeline, pumpset, starter etc. should also be made for pumping out of the daily receiving sewage from the nearby manhole of raw sewage sump to JDA line till the time the cleaning of raw sewage completely carried out for which cost is included in the quoted rate of the item. (f) Depth of thick sludge/Viscons matter for item No. 41and 42 is approximately 2.50 Meter. (g) Any other items / work which involve to carry out the work should also be considered after visiting the site and no extra cost will be paid if anything required.
Lakshmi Enterprises
KARNI CONSTRUCTION COMPANY
Ms Hari Deva Builders
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .