| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹9.5 LAdmitted-Finance | -5.00% | ₹9.5 L | L1 | Admitted-Finance |
| 2 | L2₹9.8 LAdmitted-Finance | -2.00% | ₹9.8 L | L2 | Admitted-Finance |
| 3 | L2₹9.8 LAdmitted-Finance | -2.00% | ₹9.8 L | L2 | Admitted-Finance |
| 4 | Rejected-Technical | - | - | - | Rejected-Technical Not Eligible |
Tender Value
₹10.0 L
EMD Value
₹19,917
Closing Date
23 Feb 2026, 3:30 pmClosed
EXECUTIVE ENGINEER M/S
OFFICE OF THE EXECUTIVE ENGINEER M/S NDMC KIDWAI NAGAR WEST DELHI 110023
Repairing Servicing Overhauling and Cleaning coating with anti oxidant treatment on all the insulating part of SSG Make OCB Panels at ESS Lodhi Plaza and ESS Kaka Nagar in Nirman Bhawan Zone
2026_NDMC_286909_1
23/EE(M/S)/2025-26
Open Tender
Electrical Works
25 days
NIRMAN BHAWAN ZONE
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
₹19,917
13 Mar 2026
13 Feb 2026
23 Feb 2026
13 Feb 2026
23 Feb 2026
13 Feb 2026
Rose Contact 400 Amp. As per sample
Rose Contact 800 Amp. As per sample
Bus-bar supporting insulator, As per sample
Spout Insulator 400 Amp. As per sample
Spout Insulator 800 Amp. As per sample
Female Contact Tank Bushing side 400 Amp. , As per sample
Male Contact Tank Bushing side 400 Amp. , As per sample
Primary Bushing Rod (Hole type) 400 Amp. As per sample
Ampere meter digital type (Make:- A.E, Schneider, L&T ) As per sample
Volt Meter digital type (Make:- A.E, Schneider, L&T ) As per sample
Cleaning of bus bars & coating with antioxidant, treatment on all the insulating parts/ metallic parts, tightening of all contacts in Bus Bar, Chambers, replacement of minor items/parts like nut & bolts etc complete as required Coating with anti-oxidant treatment and tightening of all the contacts of 11KV cable end, Cleaning of CT's chambers, PTs connections (PT Panels) etc complete as required of the 11KV Panels
Testing of protective relay (O/C and E/F) with secondary injection set including tripping through relay closing of 11KV breaker and circuit breaker time setting test with CB timing test kit and performance should be as per IEEE C37.09, IEC 62271-100 standards. Also provide minor item like panel wiring, control wiring etc. complete job as required .
ADD: GST @ 18%
Rebate @ 2% on S.No 1 to 9
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.99 MB
BOQ_380010.xls
BOQ • 0.30 MB
Download all tender documents and submit your bid