| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹11.0 CrAccepted-AOC C1 C2 HIG 05 M P NAGAR KORBA KORBA CHHATTISGARH 495677 | KORBA | CHHATTISGARH | 495677 | ₹11.0 Cr | L-1 | Accepted-AOC Awarded value is Inclusive of GST at the rate of 18 percent |
| 2 | L-2₹11.1 CrRejected-Finance 15 402 ASHOKA RATAN SHANKAR NAGAR DISTT RAIPUR CG | RAIGARH | CHHATTISGARH | 492007 | ₹11.1 Cr | L-2 | Rejected-Finance Rejected being not L-1 bidder |
| 3 | L-3₹12.3 CrRejected-Finance | ₹12.3 Cr | L-3 | Rejected-Finance Rejected being not L-1 bidder |
| 4 | Rejected-Technical | - | - | Rejected-Technical Details in pdf file. |
Tender Value
₹13.0 Cr
EMD Value
₹26.0 L
Closing Date
22 Dec 2022, 5:00 pmClosed
GM(CMC),SECL
Office of the GM(CMC),SECL Headquarters , Seepat Road Bilaspur,C.G.
Planning, Design, Engineering, Construction, Fabrication, Supply, Erection, Trial Run and Commissioning of 2 X 6.3 MVA, 33/6.6-3.3 kV Township Substation on Turnkey Basis at Kusmunda Area, SECL as detailed in NITand BoQ
2022_SECL_260666_1
SECL/BSP/CMC/KSM/e-T_Turnkey/ 559 Dt 27.10.22
Turnkey
Electrical and Maintenance Works
2190 days
Kusmunda Area.
As per NIT
7 documents required · 7 mandatory
₹26.0 L
Office of the GM(CMC),SECL
29 Apr 2023
29 Oct 2022
24 Dec 2022
29 Oct 2022
22 Dec 2022
10 Nov 2022
29 Oct 2022 - 7 Dec 2022
7 Nov 2022
Amount
DESIGN AND ENGINEERING COST (for 2X6.3 MVA, 33/6.6-3.3 kV TOWNSHIP SUBSTATION)
Design and Engg on PLANT & MACHINERY ( P&M - Electrical) to be supplied by bidder inlcusive of Overhead constuction cost, Contigencices, but excluding GST
Design and Engg on Civil & Structural work
CIVIL CONSTRUCTION AND STRUCTURAL WORKS for 2X6.3 MVA, 33/6.6-3.3 kV TOWNSHIP SUBSTATION on Turnkey Basis at Kusmunda inclusive of Insurance,Contingencie but excluding GST
Sub-station Building
Outdoor steel structures
Foundation of outdoor structures including Transformer foundation
Cable Trench
Barbed wire fencing
Boundary wall
Surface dressing
Stone laying
Anti weed treatment
Bore well with submersible pump
Path way
Security Room
RC sump and Pump House
Shed for DG & oil filter unit
Drain along boundary wall
Parking Shed
Oil Overflow Chamber
Oil Drain Pipe
Survey & Soil testing
SUPPLY OF PLANT & MACHINERY inclusive of Overhead Construction cost, Insurance, Contingencies , but excluding GST for substation ( 2X6.3 MVA, 33/6.6-3.3 kV TOWNSHIP SUBSTATION )
Isolators, 33 kV (nominal),3 poles, pole mounted, 1250 A, 25 kA, arrangement for interlocking with 33 kV Vacuum Circuit breaker (minimum 2 sets)
Isolators, 33 kV (nominal), 3 poles, pole mounted, 1250 A, 25kA, arrangement for interlocking with 33 kV Vacuum Circuit breaker with Earthing switch (min. 4 sets)
Isolators, 33 kV (nominal), 3 poles, pole mounted, 630 A, 25 kA, arrangement for interlocking with 33 kV Vacuum Circuit breaker (min. 2 sets)
Isolators, 33 kV (nominal), 3 poles, pole mounted, 630 A, 25 kA, arrangement for interlocking with 33 kV Vacuum Circuit breaker with Earthing switch (min. 2 sets)
Isolators, 33 kV (nominal), 3 poles, pole mounted, 630 A, 25 kA, with D.O. Fuses. (min. 4 sets)
Lightning Arrestors, station class, 30 kV,10 kA, suitable for 33 kV, solidly earthed (each set consists of 3 nos.) with counters/surge monitors (min. 6 sets)
Single phase current transformer ,outdoor type with required CT ratio for 33 kV system for metering and protection (1 set consists of 3 units for 3 phase supply) min.5 sets
Potential transformer ,outdoor type 33kV, 100 VA each 33/√ 3 kV/ 110/ √ 3 V for metering and protection each for three phase system (min. 2 sets)
Vacuum Circuit Breaker, 33kV,630 A/1250 A, outdoor type, 25 kA with remote control panel having IDMTL relay for O/L and E/F protection, ammeter, energymeter (min. 5 sets)
Power Transformer outdoor type plinth mounted 33/6.6-3.3kV, 6.3 MVA, ONAN cooled, DY-11 conforming to IS:2026 (current) having OFF-LOAD tap changer on HV side and LV neutral effectively earthed through required value of Resistance ( Restricted Neutral System) with all accessories including 33 kV remote control panel for on load tap changer as per IS:3639 (Current) with the rating as given below 2 sets Rated kVA: 6300 Rated Voltage(primary):33000V Rated Voltage(secondary):6600-3300V Connection and vector group:Dy11
Neutral Grounding Resistors with Protection ( min 2 sets)
3.3 kV switch-board, indoor type, 13 panel, with vacuum circuit brakers 75 MVA symmetrical breaking capacity ( 1 set). The function of each panel is as given below: All panels will conform to IS:3427 (Current) and relevant parts to IS:2516 ( current). These will be provided with cable entry boxes. The incoming panels will be provided with restricted earth fault protection. All panels will be provided with IDMTL relays for over current and earth fault protection. The incoming and outgoing panels shall be provided with Trivector meters.
6.6 kV switch-board, indoor type, 13 panel, with vacuum circuit brakers 75 MVA symmetrical breaking capacity (1 set). The function of each panel is as given below: All panels will conform to IS:3427 (Current) and relevant parts to IS:2516 ( current). These will be provided with cable entry boxes. The incoming panels will be provided with restricted earth fault protection. All panels will be provided with IDMTL relays for over current and earth fault protection. The incoming and outgoing panels shall be provided with Trivector meters.
Station Transformer,outdoor type rated as follows: (min 1 set) Rated kVA: 160 Rated Voltage(primary):33000 V Rated Voltage(secondary):433 V , Cu wound , Plinth mounted
Lighting Transformer,outdoor type rated as follows: (min. 1 set) Rated kVA: 100 Rated Voltage(primary): 33000 V Rated Voltage(secondary): 230V(L-L) , plinth mounted
415V switch board, indoor type with 4 nos MCCB having O/L, S/C and E/L protection, 25 MVA symmetrical breaking capacity (All out going panels will be provided with ammeter, and incoming panel with ammeter and voltmeter). ( min. 1 set)
230 V (L-L) Main Lighting Distribution boards ( min. 1 set)
Capacitor bank, 6.6 kV indoor type 1500 kVAR including APFC. (min. 2 sets)
Capacitor bank, 3.3 kV indoor type 500 kVAR including APFC. (min. 2 sets)
Battery (110 V) lead Acid type, 200 AH and battery charging (with one stand bye battery charging unit) equipment, control panels, wooden racks etc.
Earthing system (Safe Earth Electrode type) including earth pits, required galvanised strips/flats for inter connection etc.
Lightning protection system consisting of spikes, earth pits, galvanised strips/flats, shield conductors etc.
Luminaries
Decorative, 1x12/15/18W and 2x15/18 W LED (req.rating) light fittings
Suitable rating LED Bulbs for indoor lighting
Tubular steel poles,11m height along with 90 W LED lamps with fittings
Lighting masts, 16m height (Min) along with required nos. of 200 W LED lamps with fittings.
90 W LED fitted on substation building
Emergency lighting system suitable for operation on 110 V DC supply in substation building.
Accessories such as sub distribution board, junction boxes, individual control cables, PVC conduits/ casings, back up fuses, switches, sockets, ceiling roses, single core PVC cable with copper conductors, flexible wire etc.
Cable and accessories
HT power cable, 6600 V grade, XLPE, FRLS, Copper conductor
HT power cable, 3300 V grade, XLPE, FRLS, Copper conductor
LT Power cable, 1100V grade, PVCSWA, 10 sq. mm.(minimum), 3/4 core copper stranded conductors
Outdoor Lighting cable, 1100V, PVCSWA , 2 cores, 10 sq mm (minimum) stranded Al conductors
Outdoor Control cables, 1100V grade, PVCSWA, not less than 2.5 sq mm , copper conductors of with required number of cores
Wires for internal wiring of 1.5 sq mm and 6 sq mm size, PVC insulated copper conductor cable of 1100 V grade.
Cables for internal control wiring of illumination, ceiling fans, power sockets etc. 2.5 sq mm size, PVC insulated copper conductor of 1100 V grade
Cable trays, cable racks, binding materials, cable glands/lugs, cable jointing kit, bolts, nuts, washers, termination kit etc.
Overhead conductors,Insulators,Towers, poles, insulators, strung bus, ACSR conductors, steel hardware etc for 33 kV sides in the out door 2 pole structure fitted with gang operated AB switch, lightning arrester etc for out going feeders
Fire Fighting System
Fire fighting equipment consisting of fire hydrants hose cabinets, hose reels, valves, pipes, fire detection alarming system, Nitrogen injection fire prevention and extinguishing system for transformers,diesel pump, electric pump with electricals and cables , jockey pump etc
Supply of portable fire extinguisher system
Sand buckets with stand
Miscellaneous items
Room air conditioners, 1.5 t capacity min. ( 5 star rating ) including servo stabilizer
Supply of 63 kVA Diesel Generator set (silent type) with 3 ph, 50 Hz ,415 V output supply with cable, change over switch and earthing etc (min. 1 set)
Exhaust fans, 600 mm sweep.
Ceiling fan ,1200 mm sweep along with electronic regulator
Water cooler with water purifier (min. 1 set)
Vacuum Cleaner Set ( min. 1 set)
Erection and commissioning of Plant and Machinary for substation to be suplied by bidder as above inclusive of Overhead Construction cost, Insurance, Contingencies , but excluding GST
Training of O&M staff
Store cost for maintenance of P&M during Defect Liability Period (DLP) of five years.
Cost of Maintenace during during Defect Liability Period (DLP) of five years.
Total impact of GST for the purpose of CTC
R.R. ENGINEERS AND SURVEYORS
ADEPT POWER PRIVATE LIMITED