| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹5.3 CrAccepted-AOC 583 URBAN ESTATE II HISAR 125005 | HISAR | HISAR | HARYANA | 125005 | ₹5.3 Cr Quoted ₹5.4 Cr | L1 | Accepted-AOC Being lowest |
| 2 | L2₹6.0 Cr+₹61.1 L (11.3%)Rejected-Finance OFFICE NO 304 305 3RD FLOOR PLOT NO 1 USHA CHAMBERS L S C NEW RAJDHANI ENCLAVE DELHI 110092 | DELHI | EAST DELHI | DELHI | 110092 | ₹6.0 Cr+₹61.1 L (11.3%) | L2 | Rejected-Finance Other than lowest. |
| 3 | L3₹6.3 Cr+₹93.4 L (17.3%)Rejected-Finance F 18 ANSAL COMPLEX OPP JWALA HARI MARKET PASCHIM VIHAR NEW DELHI 110063 | NEW DELHI | WEST DELHI | DELHI | 110063 | ₹6.3 Cr+₹93.4 L (17.3%) | L3 | Rejected-Finance Other than lowest. |
| 4 | L4₹6.6 Cr+₹1.3 Cr (23.4%)Rejected-Finance | ₹6.6 Cr+₹1.3 Cr (23.4%) | L4 | Rejected-Finance Other than lowest. |
| 5 | L5₹6.8 Cr+₹1.5 Cr (26.9%)Rejected-Finance 00 00 NAPASAR ROAD NENO KA BASS BIKANER RAJASTHAN BIKANER RAJASTHAN 334022 UDYAM RJ 08 0001676 | BIKANER | RAJASTHAN | 334022 | ₹6.8 Cr+₹1.5 Cr (26.9%) | L5 | Rejected-Finance Other than lowest. |
Tender Value
Refer Docs
EMD Value
₹5.3 L
Closing Date
13 Mar 2023, 6:00 pmClosed
Chief Engineer
HQ Chief Engineer Delhi Zone, Delhi Cantt-10
PROVN OF DEFICIENT ACCN FOR IHQ OF MOD (ARMY) CAMP UNDER GE (P) EAST DELHI CANTT-10
2023_MES_575485_1
CA No CEDZ/TOKEN-02 of 2023
Open Tender
Civil Works
Lump-sum
365 days
Delhi Cantt
MES contractor enlisted in MES under class A cat a i having deposited Standing Security of Rs 700000.00 with department. Contractors not enlisted in MES should meet the MES enlistment criteria corresponding to appropriate class and category
9 documents required · 9 mandatory
₹3,000
GE (P) East Delhi Cantt
₹5.3 L
Yes
20 Mar 2023
18 Jan 2023
15 Mar 2023
18 Jan 2023
13 Mar 2023
6 Mar 2023
18 Jan 2023 - 13 Feb 2023
Amount
INTERNAL ELECTRIC SUPPLY S&F slim thickness surface mounting LED light fitting 300mm x 300mm (1' x1') 15watt, 220 VAC, 50 Hz, IP20 protection, powder coated CRCA steel sheet housing with high efficiency opal/clear diffuser soft glare free light complete with built in electronic driver & Surge protection 4 kV, power factor shall be greater than 0.90, Day cool white colour, total harmonic distortion (THD) should not be more than 10%, lumen efficacy 120 lumens per watt, total input voltage range 140-270 VAC, colour rendering index should not be less than 80, corelated colour temp should be 4500-6500 degree kelvin, operating temprature 0 degree C to 45 degree C, life should be more than 50Khr , complete all as specified and directed
S&F LED building security light fitting 25 watt, 220 VAC, 50Hz, IP66 protection, with pressure die cast aluminium housing, high efficiency PMMA diffuser soft glare free light complete with Electronic driver & built in Surge protection 4 kV, power factor shall be greater than 0.95, Day cool white colour, total harmonic distortion (THD) should not be more than 10%, lumen efficacy 120 lumens per watt, total input voltage range 140-270 VAC, colour rendering index should not be less than 70, life should be more than 50Khr, corelated colour temp should be 4500-5600 degree kelvin, operating temprature Minus(-)10 degree C to Plus (+) 45 degree C complete pre-wired, incl GI pipe bracket made using 32mm dia light grade, bend to shape for fixing light on wall or any indicated location using necessary clamps all as specified and as directed
S&F LED light fitting, 9/10 watt, Square/round/ovel shape, 220 VAC, 50Hz, IP20 protection, wall/ceiling mounting type, high efficiency PMMA diffuser soft glare free light complete with built in electronic driver & Surge protection 4 kV, power factor shall be greater than 0.90, Day cool white colour, total harmonic distortion (THD) should not be more than 10%, lumen efficacy 120 lumens per watt, total input voltage range 140-270 VAC, colour rendering index should not be less than 70, corelated colour temp should be 4500-6500 degree kelvin, operating temprature 0 degree C to 45 degree C, life should be more than 50Khr complete all as specified and as directed
AREA DRAINAGE S&F SFRC drain covers with perforated holes factory made of size 0.50m x 1m x 75mm complete all as specified and directed.
EXTERNAL WATER SUPPLY M&L for Cast iron air valves double air out lets conforming to IS 14845 of size 150mm dia bore and fiing up in cast iron water supply mains of size 150mm complete all as specified and directed
Supply, laying, jointing & testing centrifugally cast (spun) Ductile Iron pressure pipes, 150mm Dia, socketed & spigot ends, class K-7 with push on joints ISI (IS:8329-2000) marked in any length, laid in trenches complete all as specified and directed
Supply, laying, jointing & testing centrifugally cast (spun) Ductile Iron pressure pipes, 100mm Dia, socketed & spigot ends, class K-9 with push on joints ISI (IS:8329-2000) marked in any length, laid in trenches complete all as specified and directed
Transportation at site of work at site, rotary combination rig plant equipment etc required for drilling, developing, testing tube well and removal of the same from site on completion of work complete all as specified and directed
Trial bore of 250 mm bore hole by rotary method to any depth below the ground level in any kind of rock/soil upto 200 mtr deep including disposal of surplus soil to a distance not exc 50 mtr away all as specified and directed . Note : In case of incountering rock prior to 30 mtr depth from ground level the decision of the Garrison Engineer for reboring shall be final and binding. Specific order in writing shall be issued by Garrison Engineer for reboring and the quantities shall vary accordingly.
Devlopment of trail bore by reaming in steps upto 675mm for 60 RM from ground level complete all as specified and directed
Devlopment of trail bore by reaming upto 525mm form depth exceeding 60 RM to 200 RM complete all as specified and directed
Supplying, lowering & fixing into borehole 675mm for 20 Mtr from ground level including MS casing slotted pipe 250 mm dia as per IS 4270-1992 minimum 8.00 mm thick ERW having duly welded both side socketed ends complete all as specified and directed
Supplying, lowering & fixing into borehole 675mm for 40 Mtr from depth exceeding 20 RM and upto 60 RM including casing slotted pipe 250 mm dia as per IS 4270-1992 minimum 8.00 mm thick ERW having duly welded both side socketed ends complete all as specified and directed
Supplying, lowering & fixing into bore by reaming upto 525 mm from depth exceeding 60 RM to 100 RM including casing slotted pipe 200mm dia as per IS 4270-1992 minimum 8.00 mm thick ERW slotted tube having 1000 slots of size 1.58 x 75 mm per mtr length uniformly distributed on surface, duly welded both side socketed ends complete all as specified and directed
Supplying, lowering & fixing into bore by reaming upto 525 mm from depth exceeding 100 RM to 190 RM including casing caping pipe 200mm dia as per IS 4270-1992 minimum 8.00 mm thick ERW slotted tube having 1000 slots of size 1.58 x 75 mm per mtr length uniformly distributed on surface, duly welded both side socketed ends complete all as specified and directed
Development of tube well with air compressor of suitable CFM rating at suitable pressure Kg/cm2 as required complete all as specified and directed
Supply, lowering and fixing MS Column pipe 80 mm bore C-grade not exceeding 3.1 mtr in length GI flanged heavy grade threading ends and screwed with GI flanged having collar & flange drilled and welded to GI column pipe minimum PCD of the flange should be 125 mm, thickness of flange 12 mm including all necessary cutting in flanged for passing of submersible cable incl all jointing material such as bolts, nuts,washers, & packing sheets and connecting complete all as specified and as directed Note :- Holding clamp for column pipe made of MS flat 800 mm x 60 mm x12 mm thick, 02 Nos shall be provided by the contractor and cost of the same deemed to be included in the qouted rate of item
OUTGOING :- (f) MCCB TP, 32 Amps 10 KA -01 Nos (for pump). (g) MCB SPN,06 Amps 10 KA -01 No (for light ) (h) Providing single phase preventer- 01Nos (for starter) (j) Star delta Starter, 415 V, 3 phase for suitable HP for submersible Motor - 01 Nos (k) Fully automatic phase sequence corrector to correct input reverse phase and also protect against single phasing voltage unbalancing, low high voltage with time delay 4 to 7 second and automatic digital timer switch with automatically on/off the motor starter upto 20 HP as per time setting-02 No. (l) Complete internal wiring with suitable size copper conductor and cable lugs & glands complete. (m) Masonry and concrete work for grouting of legs in foundation for mounting of panel -01 Job (n) Cable glands of suitable sizes for cable entry and exit.
Supply, Installation, lowering, testing and commissioning submersible pumping set having discharge capacity 4 LPS at 120 mtr head complete with submersible motor of suitable HP, 3 Phase 415 volt complete all as specified and directed
M&L for Pea Gravel 10mm for filling around casing pipe upto ground level complete all as specified and directed
EXTERNAL ELECTRIC SUPPLY Supply, laying & testing HT cable XLPE, insulated cable screened, bedded, galvanised steel strip or wire armourd cable (heavy duty) 11000 volt grade with aluminium conductor having cross sectional area 95 Sq mm 3 core conforming to IS-7098 (Part-I -1988) laid in trenches/ ducts/ through pipes/ in floors / under roads/ hard standing /along poles and testing complete all as specified.
Supply, installing, testing and commissioning out door type step down transformer, 11 KV/433 volts (at no load) AC 3 Phase 50 Hz 100 KVA capacity, core type double copper wound, oil immersed, naturally cooled, ONAN with external cooling tubes, delta connected on primary side (HV) and star connected on secondary side (LV side) and having tapping at (+-)2.5% to (+-) 10% respectively in step of2.5% on HV side to be changed by means of hand operated off load tap changer gear. The maximum temperature rise should not exceed 45 degree celsius in oil and 55 degree celsius in HV/LV winding when measured by resistance method after contineous full load run on an ambient temp of 40 degree celsius. The transformer shall be confirming to IS-1180-2014 (not below level II) with standard fittings and shall conforming of the following :- (a) One cable box for HT connection, three Nos procelain bushing suitable for 11 KV on HV side, complete with copper rods, nuts and washers. (b) One cable box on LT side (secondary side) consisting of connection through cable. Of size 95 Sqmm all as directed by Engr-in-Charge. (c) Oil conservatror with filter type drain valve and oil level guage (d) De-hydrating breather with first fill fo dehydrating agent (Sillica gel). (e) Explosive vent, Thermometer pocket on tank cover, oil level gauge, oil drain filter valve, lifting lugs, oil filling hole with cap/plug with connection plate complete, Air release valve plug and four nos plain soild cast steel detachable rollers.
(f) One No 100 mm dia dial type thermometer, vapour pressure type, having range 0-120 degree celsius with metal guard having maximum perimter temperature reading indicator with re-setting device. (g) Two earthing terminals on tank cover to facilitate fixing of 32 x 6 mm galvanised iron earth stirp earthing of body. (h) Rating plate and terminal marking plate. (j) Extra bushing for neutral in the LT cable box for providing independent set of earthing for neutral. (k) First filling of new and unused transformer oil, IS-335 marked filtered and tested upto 40 KV dielectric strength at 2.5 mm air gap between testing electrodes. (l) Lifting lugs. (m) Pressure release valve.
Supply, installations, testing and commissioning factory made out door cubical type LT panel board dust and vermin proof , free standing, floor mounting type mounted on and incluidng 1:3:6 PCC foundation as requried at site and of fabricated by 3.0 mm thick SS sheet over MS 50 X 50 x 6 mm thick angle iron frame of requried type for support with double door both sides open type with necessary locking arrangement with slopped roof on top duly painted with two coats of powder coated semense gray paint over a coat of red oxide primer complete and having separate doors inside for accomodating all incomming / out going feeders of suitable sizes all as specified and directed :-
Supply, laying and Testing LT XLPE insulated cable screened, bedded, galvanised steel strip or wire armourd cable (heavy duty) 1100 volt grade with aluminium conductor conforming to IS-7098 (Part-I -1988) laid in trenches/ ducts/ through pipes/ in floors / under roads/ hard standing /along poles and testing complete all as specified of sectional area: - (a) 120sq mm x 3 ½ core
(b) 95 sq mm x 3 ½ core
(c) 25 sq mm x 4 core
(d) 10 sq mm x 2 core
(k) Indicating light for capacitor ON / OFF position. (l) Main incoming MCCB 100 Amps 36 KA 4 pole 01 No,for fix in APFC Panel. Note : The equipment offered shall be complete in all respects. Any material and components not specifically stated in this specification but which is necessary for trouble free operation of the equipment and accessories specified in this specification, shall be deemed to be included unless specifically excluded. The equipment shall conform in all respects to high standards of engineering design and workmanship and shall be capable of performing in continuous operation.
Construction of transformer platform of size 2500 x 2500 x 1200mm with brick construction in cement mortar 1:4 PCC M-10 nominal mix in foundation, 100mm thick RCC M-25 grade slab, with 8mm MS TMT bars 120mm c/c on both ways, brick masonry steps on one side, XPM Jali fixed on angle iron 40x40x6mm post upto height of 8 feet above ground level and openable gate with locking arrangement including steps made to access to the top of platform including plastering to bricks masonry complete including painting with 2 coats of white wash on plastered surface and painting steel surface with 2 coats of synthetic enameled paint over a coat of red oxide primer complete all as specified and directed. Note : Quoted rates deems tobe include cost of necessary earthwork and PCC in foundation work and filling in soft rock soil, watering and well ramming in layers to achieve desired compaction before casting surface slab.
Supplying , installation, testing and commissioning of 11 KV, 630 Amps having short circuit capacity 21kA/3-sec, Outdoor (IP54), RMU (Ring main unit) 3 way, comprising of 01 No motorized operated Load Break Switch and 02 Nos 630 Amp Fixed-Type motorized spring-charging VCB electrolytic grade copper busbars all inside single, gas-filled, robotically welded stainless steel 304 (Non Ferrite Non Megnetic Grade) tank with min. thickness min 2.5 mm, IP 67 Degree of Protection , internal-arc classified 21kA/1sec, on-site-repairable with site replacable bushing/coupling/mechanism, gas refilling etc. The enclosure shall have padlockable double-door access with anti-theft higes, fully covering the front facia and cable boxes to ensure fail-safe anti-theft protection. The unit alongwith Bus-connected, fixed-type Auxiliary transformer shall include the following along with all necessary accessories and fittings as required at site : -(A) 01 Nos. Incoming Load Break Switch module each consisting of following accessories :- (i) Each switching-unit is designed as a three position switch. This three function switch combines the functions of switch-disconnector and earthing switch. (ii) 11kV, 630A Load Break Switch with interlocked line-earthing scheme both short circuit current - 21kA/3-sec, Making Capacity - 50kAp -01 No (iii) Auxiliary contacts - 1NO + 1NC-01 No (iv) Spring-assisted snap-action motorized mechanism with un-inhibited operating shaft for emergency manual operation with integrated earthing switch -01 Nos
(v) Cable terminals (site replacable Cable bushings situated not beyond 300mm from cable-cover to allow ease of access for installation/testing/replacement purposes) with double-door arrangement for enhanced safety (IP54+IP3X) interlocked to prevent access upto 11 KV , 120-185 Sqmm , 3 Core , XLPE AL cable termination in live-condition. Each Set of 03. (vi) Right angle boots (push on type)-Each Set of 03 (vii) Arc proof cable covers having cable entry from bottom , front with Interlocking mechanism including earth switch -01 No (viii) Capacitive voltage indication fixed type system as per IEC61243 with LED - 01 Set (ix) Fault Passage Indicator - It is to be provided for each incomer load break unit, FPI with LED/digital display to be added for detection of cable fault-01 No (x) ON, OFF, EARTH mechanical indication on the front mimic of the panel - 01 Nos (B) 02 Nos Outgoing VCB module each consisting of following accessories :- (i) Each function-unit consists of a vacuum-circuit breaker in combination with a three position-switch. The three-position-switch fulfills the operation of the disconnector-function and earthing function. (ii) 11kV, 630A Fixed-Type VCB module with series disconnector cum earthing switch of short circuit breaking current/withstand - 21kA/3-sec, Making Capacity - 50kAp-01 No (iii) Aux. contacts - 1NO+1NC-01 No (iv) Stored-energy motorized high-endurance spring charging mechanism (M1+), with inbuilt spring-charging lever and mechanically latched ON/OFF push-buttons to allow handle-less and un-inhibited operation -01 No (v) Cable terminals (site replaceable Cable bushings situated not beyond 300mm from cable-cover to allow ease of access for installation/testing/replacement purposes) with double-door arrangement for enhanced safety (IP54+IP3X) interlocked to prevent access upto 11 KV , 120-185 Sqmm , 3 Core, XLPE AL cable termination in live-condition. Each Set of 3 (vi) Right angle boots (push on type)-Each set of 3 (vii) 3O/C + 1E/F self powered numerical protection relay with Low and High set for Over current and Earth Fault. Relay should have facility to display the maximum loaded phase current also.Relay shall record minimum 5 fault records with time stamping. Relay shall be communicable with RS 485 Port on MODBUS Protocol-01 No (viii) Associated ring-core cast-resin insulated CTs 100/50-1 Amp , 2.5 VA, 10P10 for protection (Each Set of 3)-02 Nos (ix) Arc proof cable covers with self Interlocking mechanism with earth switch -01 No (x) Capacitive voltage indication fixed type system as per IEC61243 with LED -01 No
(xi) Push button for breaker trip (xii) Shunt trip coil 24V DC - 01 (xiii) ON, OFF, TRIP mechanical indication on the front mimic of the panel - 01. (xiv) Emergency Trip Push Button – 01 (C) 01 No. Bus-connected, fixed-type Auxiliary transformer to provide required aux. supply and metering consisting of following accessories :- (i) 1-Ph (11kV/rt3):230VAC, 500VA Auxiliary transformer-01 No (ii) 2 x12 Volt DC battery-01 Set (iii) Battery charger-01 No (iv) HRC fuse-links for primary side isolation and AC/DC MCBs for secondary isolation-01 Set (v) Indications to confirm AC/DC supply availability-01 Set (vi) Anti-condensation space-heater-01 No (vii) CFL lamp for illumination and 3-pin socket with switch -01 No (viii) 1 x Master trip relay, Auxliary relay for transformer protection -01 Nos with TAFU Card. (D) Additional equipment deliverd separately or mounted separately :- (i) Operating Handle for Manual Isolator/Disconnector/Earthing Operation-02 Nos (ii) Standard Manometer -01 No (iii) Operation and Maintenance Manual -01 No (iv) Installation & Commissioning Manual -01 No (v) Cable clamping provision (standard) -01No Note:-(i) It is preferable to have all feeder-switches inside single stainless steel compartment with incomer feeders at the extremities to prevent chances of failure due to plug-in coupling arrangement. (ii) Necessary interlocking arrangement shall be provided for safety and operations (iii) Above switchgear shall confirm to relevant IEC (62271-200) for design, manufacturing and internal arc compliance. Any claims towards internal arc compliance, number of mechanical/electrical/short-circuit operations, gas-leakage rates etc. shall not be accepted unless proven via type-test reports of model being offered. (iv) Danger Plate for 11 KV should be provided. (v) All the incoming and outgoing feeders should be marked by FLOURCENT REFELCTIVE LETTERING as approved colours, in capital letters of size not less than 35 mm width and 40 mm height . (vi) Cost of provn of plinth for RMU as per OEM drawing is deemed to be included in the cost.
M&L for making alteration to existing HT electric cable supply connections at power house substation near IHQ Camp by removing carefully existing 11kV HT cable from VCB panel by disconnecting HT 11kV electric supply, removing carefully outgoing HT cable (of existing transformer) from VCB and making connections with outgoing VCB Module of new 4 way RMU unit. Making Input Supply electric connection from the said VCB panel to Input supply of Load brake switch of of new RMU Unit with new HT Cable 95sqmm and end joint kit all as specified and directed. Note : Quoted rate does not include cost of New HT Electric cable 95Sqmm, 3 Core, indoor type end joints kit, and necessary earth work which shall be measured and paid separately. However any damage caused during alteration to existing MES assets shall be rectified contractor at his own cost.
SUMMER APPLIANCES Supply and install Frost free double door, inverter type refrigerator electric driven single phase 230 volts, AC 50 Hz,of capacity 310 litre with BEE approved, 5 star rating with inbuilt stablizer complete including electric connection complete all as specified
Supply and install Frost free double door, inverter type refrigerator electric driven single phase 230 volts, AC 50 Hz,of capacity 100 litre with BEE approved, 5 star rating with inbuilt stablizer complete including electric connection complete all as specified .
Supply & installed Deep Freezer metal top 200 ltr capacity having single door complete all as specified and directed
Supply & installed Deep Freezer metal top 120 ltr capacity having single door complete all as specified and directed
S&F Water cooler fully stainless steel, electric driven single phase having storage capacity 80 litre and nominal cooling capacity 40 litre per hour mounted on locatiion as directed complete including connecting inlet water connection and making electric connection and testing complete all as directed and specified.
s&F Desert Cooler of size 26 x 26 x 33 inch having nominal air flow capacity 4000 cubic metre per hour single phase 240 volts 50 hz made out of plain GI sheet 18 SWG & side panels of 22 SWG , fixed on directed location and connecting complete all as specified .
S&F Voltage stabilizer for automatic operation single phase naturally air cooled indoor type and designed for input variation between 170 volt to 250 volt with output voltage stabilized 230 Volt with accuracy of +/- 2.5% of capacity 1 KVA with mounting bracket complete with time delay relay.(For refrigerators and deep freezer) complete all as specified .
S&F Voltage stabilizer for automatic operation single phase naturally air cooled indoor type and designed for input variation between 170 volt to 250 volt with output voltage stabilized 230 Volt with accuracy of +/- 2.5% of capacity 2 KVA with mounting bracket complete with time delay relay.(For Water Cooler) complete all as specified .
SEWAGE DISPOSAL M&L for DWCPE (SN8) 180 (OD)/ 163 (ID) mm pipe laid and jointed complete with collars Grade “A” laid in trenches and jointed with cement joint and tested complete all as specified and directed
Description of Work / Item(s)
Amount
Total amount of revised Sch 'A' Section I (Building work) (Pre Priced Amount as in Col 5, brought forward from Total of Sch A section I)
Total amount of revised Sch 'A' Section II (Internal Water Supply) (Pre Priced Amount as in Col 5, brought forward from Total of Sch A section II)
Total amount of revised Sch 'A' Section III (Internal Electric Supply) (Pre Priced Amount as in Col 5, brought forward from Total of Sch A section III)
Total amount of Sch 'A' Section IV (Area Drainage) (Pre Priced Amount as in Col 5, brought forward from Total of Sch A section IV)
Total amount of revised Sch 'A' Section V (Sewage Disposal) (Pre Priced Amount as in Col 5, brought forward from Total of Sch A section V)
Total amount of Sch 'A' Section VI (Road, Path & Culvert) (Pre Priced Amount as in Col 5, brought forward from Total of Sch A section VI)
Total amount of revised Sch 'A' Section VII (External Water Supply) (Pre Priced Amount as in Col 5, brought forward from Total of Sch A section VII)
Total amount of revised Sch 'A' Section VIII (External Electric Supply) (Pre Priced Amount as in Col 5, brought forward from Total of Sch A section VIII)
Total amount of revised Sch 'A' Section IX (Hot Water Supply) (Pre Priced Amount as in Col 5, brought forward from Total of Sch A section IX)
Total amount of revised Sch 'A' Section X (Demolition & Dismantling) (Pre Priced Amount as in Col 5, brought forward from Total of Sch A section X)
Total amount of revised Sch 'A' Section XI (Excavation, Earth work & Site Clearance) (Pre Priced Amount as in Col 5, brought forward from Total of Sch A section XI)
G and G Infratech Private Limited
R K GOEL ABHEY KUMAR JAIN
Siya constructions
City Promoter and Buildwell Pvt. Ltd.
A.S. CONSTRUCTION CO.
M/s. Lakhbir constructions
M/s Madan Lal Bansal and Co. Contractors Pvt. Ltd.
G and G Infratech Private Limited
City Promoter and Buildwell Pvt. Ltd.
A.S. CONSTRUCTION CO.
M/s. Lakhbir constructions
RSP Contractors India Private Limited
M/s Madan Lal Bansal and Co. Contractors Pvt. Ltd.
R K GOEL ABHEY KUMAR JAIN
Bidder Name
M/s. Lakhbir constructions
City Promoter and Buildwell Pvt. Ltd.
R K GOEL ABHEY KUMAR JAIN
A.S. CONSTRUCTION CO.
M/s Madan Lal Bansal and Co. Contractors Pvt. Ltd.
Siya constructions
G and G Infratech Private Limited
RSP Contractors India Private Limited
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .