| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹16.3 LAccepted-AOC | ₹16.3 L Quoted ₹16.6 L | L1 | Accepted-AOC Accepted being L1 |
| 2 | L2₹18.8 L+₹2.2 L (13.2%)Rejected-Finance NO 439 AHIV ADAN 11ND FLOOR 2RD STAGE INDIRA NAGAR BANGALORE 560 075 | BENGALURU URBAN | KARNATAKA | 560075 | ₹18.8 L+₹2.2 L (13.2%) | L2 | Rejected-Finance Rejected. Quoted rates are higher than L1 |
| 3 | L3₹19.6 L+₹3.0 L (18.1%)Rejected-Finance 101 1ST FLOOR JASOL RESIDENCY 14TH CROSS KANAKANAGAR R T NAGAR POST BANGALORE 560032 | BANGALORE | BANGALORE | KARNATAKA | 560032 | ₹19.6 L+₹3.0 L (18.1%) | L3 | Rejected-Finance Rejected. Quoted rates are higher than L1 |
| 4 | L4₹20.0 L+₹3.4 L (20.6%)Rejected-Finance | ₹20.0 L+₹3.4 L (20.6%) | L4 | Rejected-Finance Rejected. Quoted rates are higher than L1 |
| 5 | L5₹20.3 L+₹3.7 L (22.5%)Rejected-Finance NO 68 ANJANEYA TEMPLE CROSS OPP M S RAMAIAH HOSPITAL NEW BEL ROAD BANGALORE 560 094 | BENGALURU URBAN | KARNATAKA | 560094 | ₹20.3 L+₹3.7 L (22.5%) | L5 | Rejected-Finance Rejected. Quoted rates are higher than L1 |
Tender Value
₹19 L
EMD Value
₹38,000
Closing Date
29 Sept 2021, 6:00 pmClosed
Garrison Engineer M AF Jalahalli
Garrison Engineer M AF Jalahalli BANGALORE 560013
8585REPAIR MAINT OF CHEMICAL CONVENTIONAL EARTHING INFRASTRUCTURE INTERNAL ELECTRIFICATION LIGHTNING CONDUCTOR IN EIT 16 TS IW SCHOOL SIGNAL SECTION AND LOGISTIC SECTION UNDER AGE E M EAST OF GE M AFS JALAHALLIBANGALORE
2021_MES_472063_1
8585/E8
Open Tender
Electrical and Maintenance Works
Item Rate
242 days
Garrison Engineer M AF Jalahalli
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
Garrison Engineer M AF Jalahalli
₹38,000
10 Nov 2021
1 Sept 2021
1 Oct 2021
1 Sept 2021
29 Sept 2021
17 Sept 2021
1 Sept 2021 - 8 Sept 2021
Amount
Taking down carefully copper/aluminum point wiring (light, fan,Power) complete fittings such as switches , ceiling roses pendents , regulators sockets light fittings etc removing to store for keeping in safe costody or for taking credit and making good disturbed surface of wall, floors , roof etc all as specified.
Material and labour for point wiring with two runs of FRLS PVC insulated unsheathed, 1100 V grade cable multi stranded copper conductor of size 1.5 sqmm drawing through in and including PVC conduit size of not less than 20mm on surface of wall including provn of PVC box of suitable size in sunken portion of wall for mounting switch, socket and regulator along with earth wire of PVC insulated, unseathed, 1100 V grade cable multi stranded copper conductor of size 1.5 sqmm for One light point controlled by one switch one way 5 Amps all as specified and directed.
All as per item Srl No 2 above but One light point controlled by one two way switch 5 Amps
All as per item Srl No 2 above but One ceiling fan point controlled by one switch one way 5 Amps
All as per item Srl No 2 above but One Exhaust fan point controlled by one switch one way 5 Amps
All as per item Srl No 2 above but One call bell point controlled by one switch one way 5 Amps
All as per Sl Item no.2 but with One 2/3 pin socket outlet 5Amps on independent board
All as per item No 2 above but one switch socket combination 15 Amps on independent board with cable 2.5 sq mm size and earth wire 2.5 sqmm
Supply and fixing switch piano flush type single pole one way 5 Amps
Supply and fixing switch piano flush type single pole two way 15 Amps
Supply and fixing ceiling rose surface bakelite 3 terminals 65x50mm
Supply and fixing Call bell push flush type single pole one way 5 Amps
Supply and fixing in repair stepped type electronic fan regulator flush type 100 Watts
Supply and fixing switch socket combination 2 in 1, 3 pin 5 Amps flush type
Supply and fixing Switch socket combination multipurpose 5/16 Amps, 5 in 1, 4 / 5 hole flush type
Supply & fix in repair decorative ultra slim square profile LED lighting fixture with extruded polycarbonate, environmental friendly, energy efficient ready to use pack of 20 Watt.Make : Bajaj. Item Code-830338 Ivora LED Battan 20 W CDL or equivelent WIPRO/CG/Havells/Philips
Repairs to recessed /Surface mounted / ceiling mounted / Flame proof/ Bracket mounted light fitting incl Bldg security light fitting of any type of 9/14/20/28/36 watt including replacing all the unserviceable parts such as, LED light fitting, tube rod, LED bulb, building security light fitting & bulb holder all as directed. Note: (i) The unit rate quoted shall be deemed to include for replacement of worn out bolts, nuts, screws ,washers, partly wiring etc wherever required. (ii) Spares such as tube rod of any type, LED light fitting & LED bulb etc. will be paid separately under respective items as supply only.
Supply only T-5 tube rod 28 watt.Havells/Bajaj/CG
Supply only tube rod T-5, 14 watt.Havells/Bajaj/CG
Supply only LED Retro bar tube rod 18/20 watt.Havells/Bajaj/CG
Supply & fix in repair decorative ultra slim square profile LED lighting fixture with extruded polycarbonate, environmental friendly, energy efficient ready to use incluiding taking down pack of 20 Watt.Make : Bajaj. Item Code-830338 Ivora LED Battan 20 W CDL or equivelent WIPRO/CG/Havells/Philips
Supply & fix in repair decorative ultra slim square profile LED lighting fixture with extruded polycarbonate, environmental friendly, energy efficient ready to use including taking down pack of 20 Watt.Make : Bajaj. Item Code-830379 or equivelent WIPRO/CG/Havells/Philips
Supply & fix in repair decorative ultra slim square profile LED lighting fixture with extruded polycarbonate, environmental friendly, energy efficient ready to use including taking down pack of 10 Watt.Make : Bajaj. Item Code-830206 Ivora LED Battan 10 W CDL or equivelent WIPRO/CG/Havells/Philips
Supply and fixing LED luminaire 600 mm x 600 mm, 35/36 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up & taking down with driver three core flexible copper conductor cases of suitable size complete.
Supply and fixing square/round shape 15 watt 220 volts AC recessed type with high efficiency PMMA diffuser soft glare free light complete with drivers, holders, LED lamp suitable for roof ceiling including connecting up& taking down with three core flexible copper conductor cable of suitable size complete. Make : CG or equivelent WIPRO/Havells/Bajaj/Philips
Supply and fixing building security/ LED street light fitting 35 Watt, 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal, management in multiple optics including down complete with IP 65/66 protection complete. make Bajaj/ Philips/OSRM/KRIPA/CG.
Supply and fixing in repair LED Lamp 9 watt. Including taking down. Make :Bajaj. Item Code-830213 or equivelent WIPRO/CG/Havells/Philips
Supply and fix in repair Modular switch 1way 6A,1module Including taking down.
Supply and fix in repair Modular socket, 6A-2/3 pin combined 2 module including taking down.
Supply and fix in repair Modular switch, 16 A 1 module including taking down.
Supply and fix in repair Modular socket, 6A/16A-2/3 pin combined 2 moduleincluding taking down.
Supply and fix in repair Modular fan step regulator, 120w-2moduleincluding taking down.
Supply and fixing in repair of switch socket combination 2 in 1, 3 pin 5 Amps flush type complete including taking down.all as specified & directed.
Supply and fixing in repair of Switch socket combination multipurpose 5/16 Amps, 5 in 1, 4 / 5 hole flush type including taking down.complete all as specified & directed.
Supply and fixing in repair stepped type electronic fan regulator flush type on the existing phenolic laminated sheet etcincluding taking down.
Supply and fixing in repair Lamp holder angle type made of PVC/Polycarbonate with back plate.including taking down.
Supply and fixing in repairs Plastic laminated sheet for switch boards, MCB DB Covers cutting to suitable size including making slots for fixing swithces, sockets regulator,MCBs etc.including taking down & other purposes as required complete including replacement of rusted screws, nuts bolts. .
Supply and fixing in repair of MCCB 100 amps 4 pole 16 KA 415 volt complete including taking down all as specified & directed.
Supply and fixing in repair of MCCB 63 amps 4 pole 16 KA 415 volt complete including taking down all as specified & directed.
Supply and fixing in repair, sheet metal enclosure distribution box suitable for MCB'S 4 way TPN 415 volts with 200 Amps rated bus bar double door complete including connecting up & taking down all as specified and making good distrubed surface
All as per item No. 40 above but 8 way SPN with 200 Amps rated bus bar , 240 volts
Supply and fixing 240V, 10 KA 'B' curve miniature circuit breaker (MCB) of single poles and current carrying capacity 5 to 32 AMP, in the MCB DB including taking down Complete with connection testing and commissioning.
Supply and fixing amp rating 240V, 10 KA 'C' curve miniature circuit breaker (MCB) SPN 32 AMP current carrying capacity in the MCB DB including down complete with connection testing and commissioning.
Supply and fixing 415V 10KA 'C' curve miniature circuit breaker (MCB) of TPN 25 To 63 AMP current carrying capacity in the DB including taking down complete with connection testing and commissioning.
Taking down sub main wiring of any size complete all as specified and directed.
Material and labour for sub main wiring with two single core stranded copper conductor unsheathed PVC insulated cable 1100V grade, 4 sq mm drawn through suitable size of non-metallic PVC rigid conduit with 4 sqmm copper conductor cable as earth conductor of 4.0 sq mm and conduit accessories fixed up in surface including connecting up complete all as specified and directed.
All as per item no 46 but cable size of 6.0 sqmm
Material and labour for sub main wiring with Four single core stranded copper conductor unsheathed PVC insulated cable 1100V grade, 6 sq mm drawn through suitable size of non-metallic PVC rigid conduit with 6 sqmm copper conductor cable as earth conductor of 6.0 sqmm and conduit accessories fixed up in surface including connecting up complete all as specified and directed.
All as per item no 48 but cable size of 10.0 sqmm Note for item No 46 to 49 :-Two/four run of cable and one run of earth continuity copper conductor and non metalic PVC conduit shall be measured as one unit length.
Taking down ceiling fan of any size, type and make after disconnecting the electrical connections, cleaning, servicing , greasing removing and replacing all the unserviceable spare and re-fixing the same back to the original location all as directed
Taking down Exhaust fanof size 250/300/450 mm of any type & make after disconnecting the electrical connections ,cleaning, servicing , greasing removing and replacing all the unserviceable spare re-fixing the same back to the original location all as directed. Note for item No. 51 to 54 : (i) All the replaced spare for unserviceable spares, rewinding will be measured and paid separately (ii) The rate quoted shall be deemed to include the cost of painting and minor spares such as split pin , screws washers etc.
Taking down wall fan of any size, type and make after disconnecting the electrical connections, cleaning, servicing , greasing removing and replacing all the unserviceable spare and re-fixing the same back to the original location all as directed
Supply only ball bearing suitable for ceiling fans 1200 / 1400 mm dia sweep.
Supply only ball bearing suitable for exhaust fans 300/450 mm dia sweep.
Supply only ball bearing suitable for wall mounted fans 300/400 mm dia sweep.
Supply only Capacitor 2.5 mfd for ceiling fans.
Supply only Capacitor 4 mfd for exhaust fans.
Supply only the mounting clamps and rubber bush with nut, bolt, washers, locking clip etc complete suitable for fixing at the down rod suitable for fixing the ceiling fan.
Supply only GI pipe down rod made out of 15 mm dia GI pipe suitably cut into service including necessary threading / cutting for necessary suitable modifications according to the requirement to fix downrod complete all as specified & directed.
Supply only the gun metal bush for ceiling fan/exhaust fan of any size complete suitable for fixing at the down rod suitable for fixing the ceiling fan.
Supply only twin core flexible wire 1 Sqmm for connecting up ceiling fans, exhaust fans/wall mounting fan etc.
Taking down old burnt out copper winding wire from ceiling fan of 1200/ 1400 mm sweep and rewinding by using same gauge of copper wire insulating and varnishing,heating, cleaning, servicing,greasing,refixing at site,testing, commissioning for smooth functioning complete all as specified & directed.
Taking down old burnt out copper winding wire from exhaust fan of 230/300/450 mm sweep and rewinding by using the same gauge of copper wire super enameled including heating and varnishing,cleaning, servicing,greasing, cement work refixing at site and testing commissioning for smooth functioning complete all as specified & directed.
Taking down old burnt out copper winding wire from wall fan of 450/600 mm sweep and rewinding by using the same gauge of copper wire super enameled including heating and varnishing,cleaning, servicing,greasing, cement work refixing at site and testing commissioning for smooth functioning complete all as specified & directed.
Testing of earth resistance of any type of earth pit and writing of earth resistance value in existing board. Note:-The rate quoted by the contractor shall be deemed to be included for the followings:- (i) Visual inspection of earthing strips for corrosion, rust, tightening of joints, vegetation clearance, . (ii) The contractor has to arrange his own testing kit of suitable range for checking of earth resistence. (iii) Checking of earth countinuity upto equipment for any disconnection if found so it will be repired. (iv) Testing and submission of earth result and saperate register to be maintained for the same for record.
Material and labour for earthing with galvanised steel earth plate electrode 600x600x6mm thick buried directly in ground earth pit not less than 2.25M deep below ground level with top edge of the plate not less than 1.5M below normal ground level connected to galvanised strip 32x6mm by means of nuts, bolts, check nuts, washers of galvanised iron or steel all as shown in electrical plate No. 03 of SSR Part I connected to earthing test point including excavation/ earth work in any type of strata, removal of surplus excavated material, GI pipe for watering and funnel, PCC 1:3:6 type C1 chamber with RCC 1:2:4 type B1 in cover slab without GI protection pipe including taking down but all as specified and directed by Engineer-in-Charge.
Labour only for maintenance of Chemical/conventional earth pits shown at site in the area of E&ITI, TS, IW School, signal section and Logistic Section in AGE E/M East. During the maintenance period the following works shall be carried out :- (i) Common Salt 5 Kg mixed with Potable water of 5 Litrs shall pour to each earth pits. (ii) Contractor shall test each eath pits and maiintain the register showing location where maitained and submitt the test result to engr-in-charge for record. (iii) Earthing whichever showing high resistance value is to be repaired and the same will be measured & paid saperately under relevent item. (iv) Cleaning of vegitation inside the pit and its surounding up to 1 feet Notes :- Common salt supply only shall be measured and paid separately under appropriate items
Repairing , maintenance and recharging of old existing chemical earth pit by excavating 4.25 mtr depth and taking out earth plate,watering pipe, earth lead / strip protection pipe, earth pit with cover carefully and cleaning the same after removing sludge from the plate, srips & pipes, etc. and re connecting the same as it is by brazing the plate and strip, inluding connecting up the existing GI strip / Aluminium strip / copper strip by means of new nuts, bolts, check nuts, washers of galvanised iron to test point / equipment including connecting the dismantled existing serviceable water pipe line and bib taps of any size, funnel including testing and commissioning complete to the entire satisfaction of Engineer-in Charge all as specified and as directed. Note:- (i)The rate quoted by the contractor shall be deemed to be included earth work, reconnection of existing servicable earth plate, earth strip, watering pipe, seating earth pit with cover, funnel, including new nuts, bolts, checknuts and washers as required and testing. (ii) Contractor shall be submitted the test result to engr-in-charge duly. (iii) Test result should be less than 1 ohms (iv) Unsv GI Pipes, GI Funnel with mesh, bib taps, Mixture of salt / Charcoal / MGSO4, chemical compound and Brazing,shall be measured and paid separtely under relevent items.
Repairing , maintenance and recharging of old existing conventional GI Plate earthing pit by excavating and taking out earth plate,watering pipe, earth lead / strip protection pipe, earth pit with cover carefully and cleaning the same after removing sludge from the plate, srips & pipes, etc. and re connecting the same as it is by brazing the plate and strip, inluding connecting up the existing GI strip / Aluminium strip / copper strip by means of new nuts, bolts, check nuts, washers of galvanised iron to test point / equipment including connecting the dismantled existing serviceable water pipe line and bib taps of any size, funnel including testing and commissioning complete to the entire satisfaction of Engineer-in Charge all as specified and as directed. Note:- (i)The rate quoted by the contractor shall be deemed to be included earth work, reconnection of existing servicable earth plate, earth strip, watering pipe, seating earth pit with cover, funnel, including new nuts, bolts, checknuts and washers as required and testing. (ii) Contractor shall be submitted the test result to engr-in-charge duly sigmed by user. (iii) Test result should be less than 1 ohms (iv) Unsv GI Pipes, GI Funnel with mesh, bib taps, Mixture of salt / Charcoal, Brazing, shall be measured and paid separtely under relevent items.
Supply only of common salt commercial all as directed by Engineer - in-Charge
Supply only of charcoal dust all as directed by Engineer - in-Charge
Supply only of back filling compound
Supply only magnesium sulphate (MGSO4)
Material and labour for brazing of earth connecting terminals
Supply and fixing in replacement of galvanised iron strip of size 32x6mm burried in ground or fixed on wall with suitable epoxy base insulator on wall/floors and connected to test point including bending, jointing at test points with 2 Nos GI nuts, bolts, with lead washers, jointing strips at all joints as directed by Engineer-in-Charge.
Supply and fixing in replacement of aluminium strip 25x3mm fixed with epoxy based insulator for down conductor air terminal network including drilling two Nos holes at each joint, one set of lead washers between strips, two sets GI nut and bolt, gutties, screws etc.
Supply and fixing in replacement earth continiuty copper conductor or main earthing lead fixed on wall on batten or recess or chases or buired in ground or drawn in conduit / pipe or fixed to pole or any other indicated suituation for loop earthing etc, as required for copper strip 32 mm x 6 mm with proper saddles/spacer, screw etc, alll as specified and directed. Note : All joints of copper shall be of brazing only
Taking down and refixing of existing aluminium strip 25x3 mm by brazing at each joints between strip including saddle/insulator/PCC block where required. all as directed by Engineer-in-Charge.
Taking down and refixing of existing GI strip 32 X 6 mm brazing at each joints between strip including saddle/insulator/PCC block where required. all as directed by Engineer-in-Charge.
Taking down and refixing of existing copper strip 32 X 6 mm brazing at each joints between strip including saddle/insulator/PCC block where required. all as directed by Engineer-in-Charge.
Supply and fixing in repair test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm longhex. head screw all as specified and directed by Engineer - in - Charge
Supply and fixing in replacement of air termination single pointed aluminium rod of 12mm dia 300 mm long fixed to strip/pipe including drilling holes, nuts, bolts washers for resting/ supporting of air terminals etc. complete all as directed.
Supply and fixing in replacement of air termination single pointed copper rod of 12mm dia 300 mm long fixed to copper strip including drilling holes, nuts, bolts washers for resting/ supporting of air terminals etc. complete all as directed.
Supply and fixing in replacement of air termination single pointed copper rod of 12mm dia 900 mm long fixed to copper strip including drilling holes, nuts, bolts washers for resting/ supporting of air terminals etc. complete all as directed.
Refixing of air termiantion single pointed Aluminium rod 12mm dia 300mm.
Refixing of air termiantion single pointed copper rod 12mm dia 300mm.
Supply and fixing in repair GI funnels for earthing.
Supply only PCC block of size 150 x 150 x 150mm in PCC (1:3:6) type C-1 with 20mm graded aggregate for fixing of roof conductor/air termination rod/GI strip etc all as directed.
Brazing of copper/Aluminium/GI strip for continuity all as specified and directed by Engr-in-Charge
Supply and fixing in repair for 40 mm bore galvanised steel water tubing light grade with all fitting fixed to wall and ceiling or laid in trenches complete all as specified. Note:-Earth work will be measured ans oaid saperately
Supply and fixing in repair for 25 mm bore galvanised steel water tubing medium grade with all fitting fixed to wall and ceiling or laid in floors complete all as specified.
Supply and fixing in repair for 25 mm bore galvanised steel water tubing medium grade with all fitting laid in trenches complete all as specified. Note:-Earth work will be measured ans oaid saperately
Supply and fixing in replacement Bib Tap of 20 mm dia standard of PTMT any colour high pressure screwed for iron pipe (Minimum weight 125 gms ) all as specifed and directed. Make Prayag, Princes, Supreme
Cutting the existing GI pipe of any size for tapping or new connection with 25 mm including required fitting all as directed.
Material and labour for earthing pit chamber of size 0.45 x 0.45x 0.45 m and 150 mm thick by PCC 1:3:6 type C1 with 20 mm graded stone chamber with RCC 1:2:4 type B1 in cover slab all as specified and directed by Engineer-in-Charge.
Material and labour for earthing pit chamber cover of size 0.45 x 0.45x .04 m with RCC 1:2:4 type B1 with 20 mm graded stone all as specified and directed by Engineer-in-Charge.
Supply and fixing of CI pit cover of suitable of suitable size for existing earthing pit all as directed by Engr - in - Charge.
Supply and fixing of iron plate as earth pits indetifier board as per standerd size and specification/Colour scheme of various type of size(Rectangular/Tringle/Square/Oval) 300 x 300 x 3.15 mm thick and angle iron for stand 02 feet height including all frame work,welding,cutting and painting the board as per direction of Air HQ colour code and writing the letters such as connected eqpt,type of earthing,resistence value,date of installation,date of check including of PCC works for fixing of earth sign board at the site of various location all as specified and directed.
Supply only Galvanised, steel earth plate, size of 60cmx60cmx6.30mm
Supply only copper earth plate, size of 60cmx60cmx3.15mm
Shiva Shakthi Electrical Enterprises
Vasavi Electricals
H S S ENGINEERS AND CONTRACTORS
devan enterprises
M/S SRI BALAJI ENTERPRISES
kamadhenu Electricals
CITIZEN ELECTRICALS
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .