Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance GURU RAM DAS NAGAR SRI SAI VIHAR COLONY ALIGARH ALIGARH ALIGARH UTTAR PRADESH 202001 | ALIGARH | UTTAR PRADESH | 202001 | Admitted-Finance |
| 2 | Admitted-Finance 98 PANIYARE PURWA MAKRAND NAGAR SARAIMEERA KANNAUJ KANNAUJ UTTAR PRADESH 209726 | KANNAUJ | UTTAR PRADESH | 209726 | Admitted-Finance |
| 3 | Admitted-Finance AASHIYANA SECTOR N 304 KILA CHAURAHA KANPUR ROAD AASHIYANA LUCKNOW UTTAR PRADESH 226012 | LUCKNOW | UTTAR PRADESH | 226012 | Admitted-Finance |
Tender Value
₹4.0 L
EMD Value
₹9,000
Closing Date
23 Aug 2024, 12:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
SUPERINTENDING ENGINEER
SE, ETC-II KANPUR.
FOR INSPECTION AND RECTIFICATION OF INSTALLED SAS AND OTHER REQUIRED ASSOCIATED WORK, AT 132KV S/S JASWANT NAGAR UNDER ETD-ETAWAH
2024_UPTCL_944750_1
E-TENDER NO. 12/ETC-II(K)/2024-25
Open Tender
Electrical Works
Lump-sum
15 days
132KV S/S JASWANTNAGAR
Please refer Tender documents.
3 documents required · 3 mandatory
₹590
EE, ETD-II, Kanpur
₹9,000
28 Aug 2024
8 Aug 2024
23 Aug 2024
8 Aug 2024
23 Aug 2024
8 Aug 2024
Amount
Inspection and rectification of SIEMENS make Substation Automation System installed at 132KV S/S Jaswant nagar. The following works are including for healthy SCADA communication. (a) Replacing the defective armourd optical fiber cable and splicing it if required any anywhere in the Ring. (b) Replacing the defective FO multimod ST-ST port patch cords. (c) Checking & Rectifying the healthiness of LIUs and its communicating ports. (d) Checking &Rectifying the healthiness of IEC 61850-7 Ethernet switches. (e) Replacing the defective CAT-5/LAN cables and checking its healthiness. (f) Rectifying communication healthiness of MOD Bus RTU for various MFM meters. (g) Rectification/checking healthiness of GPS system and its time synchronisation with all relays. (h) Re-installation of old backup to SCADA. (I) Checking the healthiness of all protection relay's communication to SCADA. (j) Checking of all required events, alarms, numericals datas, status and signals to SCADA from various bays & feeders. (k) Checking the SLD of S/S to SCADA screen . (l) checking the all required operations of equipments from SCADA. (m) configuration of ethernet switches/modems/ RTU etc. if required. (n) installation of new window and SICAM230 software in standby PC, and reinstalling the old backup in HMI-2, making both HMI-1 & HMI-2 in all respect. at the time of rectification all required materials and computer parts will be arranged by department without extra charges, except the following given material will be provided by contractor.scada license key, activation key, old SAS backup, and software CD will be provided by department.
Configuration of Gateway / RTU for transmission of Telemetry data via IEC 104 protocol to SLDC Lucknow and Backup SLDC, Modipuram as per IP address and physical address provided by UPPTCL and validation of real time data as per existing BCU relay at 132kv S/S Jaswantnagar. solving the problem of SOE, time synchronization
Providing & Installation of 4U Rack mountable industrial CPU with following as follows:- 1. Intel core i3-3220 3rd Gen, CPU, 2. 8GB DDR3 Memory 3. 1-TB SATA HDD 4. DVD-RW Drive 5. 10/100/1000 Mbps LAN Ethernet on board 6. USB, 2*Serial and 1*VGA Part on board 7. USB, Keyboard and optical mouse 8. 400 watt single power supply 9. Window 7-64 Bit O.S. Without Monitor 10. BIS Approved HSN-Code-8471 Suitable for Existing SIEMENS Make SCADA System as Installed at132kv s/s Jaswantnagar. Work included as Installed & all Software Configuration and its testing if required as per site condition and all other associated work to complete the job satisfactory.
Supply of 27" IPS LED computer monitor HP/DELL/LG etc.
Supply of Windows 7 OS with 32/64 bit suitable for ADVANTEC PC.
Supply of Fibre Optical Multimode patch cards for ST-ST, LC-LC, LC-ST, ports (each 5 meters).
Supply of Fibre Optical Multimode patch cards for ST-ST, LC-LC, LC-ST ports (each 10 meters).
rbs engineering
SMV POWER SOLUTION
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .