Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.6 LAccepted-AOC SHIV BARI ROAD NEAR KASUMAL HOTEL BIKANER 334003 RAJASTHAN | BIKANER | BIKANER | RAJASTHAN | 334003 | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹19.7 L+₹1.8 L (10.1%)Rejected-Finance 1ST SHAKUNTALA SADAN 04 RAMPURA BASTI LALGARH BIKANER RAJASTHAN 334001 | BIKANER | RAJASTHAN | 334001 | L2 | Rejected-Finance Not lowest bidder | |
| 3 | L3₹21.8 L+₹3.9 L (22.0%)Rejected-Finance BEHIND POWER HOUSE WARD NO 6 UDASAR BIKANER RAJASTHAN 334022 | BIKANER | RAJASTHAN | 334022 | L3 | Rejected-Finance Lowest bidder |
Tender Value
₹20 L
EMD Value
₹40,000
Closing Date
18 Jul 2022, 6:00 pmClosed
GE (P) Kanasar
GE (P) Kanasar Military Engineer Service Kanasar, Bikaner
Repair/maintenance of external electrification including replacement of LT Cable, feeder pillar box and allied works at Military Station Kanasar
2022_MES_530527_1
CA NO. GE (P) KNS/Token No. 06/2022-2023
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Kanasar
Contractor shall be enlisted with MES in Class E and above and category b(i) subject to satisfactory remarks wrt performance in respect of works in hand as reflected in WLR. Contractor not enlisted with MES should meet the enlistment criteria of E
8 documents required · 8 mandatory
₹500
GE (P) Kanasar
₹40,000
Yes
30 Aug 2022
13 Jun 2022
20 Jul 2022
13 Jun 2022
18 Jul 2022
4 Jul 2022
21 Jun 2022 - 27 Jun 2022
Amount
Excavating in trenches, not exc 1.5 metre wide and not exc 1.5 metre in depth, for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. laying cables, pipes, etc. not exc 10 Sqm on plan & not exc 1.5m in depth and getting out in soft/loose soil complete all as specified and as directed.
Returning, filling in, including spreading, leveling watering and well ramming in layers not exc 25 cm thick in soft/loose soil complete all as specified and as directed.
Removing excavated soil/material to a distance not exc 50 metre and depositing where directed at a level not exc 1.50 metre above the starting point complete all as specified and as directed.
M&L for bricks sub class ‘B’ laid flat and dry abutting each other with gap between adjacent bricks not exc. 10mm for protection of underground cable complete all as specified and as directed.
M&L for sand (Local Tibba sand) filling under floors and similar locations including spreading, leveling, watering and well ramming in layers not exc 25 cm thick complete all as specified and as directed. Notes : (i) Approved local Tibba dry sand free from vegetations, grass and other deleterious substances shall be used. (ii) For the purpose of payment, only consolidated thickness shall be measured
Supply, laying, jointing and testing LT XLPE insulated screened, bedded, galvanised steel strip or wire armoured heavy duty electric cable with aluminium stranded conductor 1100 Volt grade cross sectional area 16 sqmm 4 core laid in trenches/ducts, through pipe, under floors or roads/ along poles etc complete all as specified including dismantling & taking out old unserviceable cable. Notes :- (i) Sand cushioning, cable protection, GI protection pipe, clamps, jointing kits and excavation & earth work shall be measured & paid for separately. (ii) Road cutting/floor cutting /cutting holes etc in walls required for laying/fixing of cable etc shall be made good as per existing. Nothing extra shall be admissible on this account. Quoted rates shall be inclusive of the above provisions.
All as per item No. 6.00 here-in-before but cable of size 25 Sqmm 3.5 core.
All as per item No. 6.00 here-in-before but cable of size 35 Sqmm 3.5 core.
All as per item No. 6.00 here-in-before but cable of size 50 Sqmm 3.5 core.
All as per item No. 6.00 here-in-before but cable of size 70 Sqmm 3.5 core.
All as per item No. 6.00 here-in-before but cable of size 120 Sqmm 3.5 core.
All as per item No. 6.00 here-in-before but cable of size 240 Sqmm 3.5 core.
Testing and checking of faulty LT under ground cable with cable fault locating machine, repair the same after removing the fault of cable, any size, any type and testing of the same complete all as specified and as directed. Notes: (i) Sand cushioning, cable protection, GI protection pipe, jointing kits and excavation & earth work shall be measured & paid for separately (ii) If cable is damaged by the contractor’s workmen during the execution of work the same shall be provided/repaired by the contractor at his own cost complete to the entire satification of GE. (iii) Road cutting/floor cutting/cutting holes etc in wall required for laying/fixing of cable etc shall be made good as per existing . Nothing extra shall be admissible on this account. Quoted rates shall be inclusive of the above provisions.
S&F in replacement for cable jointing kit for 1.1 KV (Earthed) grade cabe for straight through heat shrinkable type joint complete with jointing material and accessories suitable for 3.5 Core XLPE armoured aluminium conductor cable of size 150 Sqmm to 240 Sqmm, including dismantling & taking out old unserviceable joint kit, complete all as specified & as directed.
All as per item No. 14.00 here-in-above but suitable for cable size 95 mm to 120 mm 3.5 core
All as per item No. 14.00 here-in-above but suitable for cable size 70 Sqm 3.5 core.
All as per item No. 14.00 here-in-above but suitable for cable size 50 Sqm 3.5 core.
All as per item No. 14.00 here-in-above but suitable for cable size 35 Sqm 3.5 core.
S&F MCB, 4 Pole, 32 Amps rating, with over load and short circuit protection 'C' curve and rupturing capacity 10 kA , 415 Volt grade, AC, 50 Hz and making connections using suitable size copper lugs/thimbles, including disconnecting & taking down old unserviceable MCB, complete, all as specified & directed.
S&F MCB, 4 Pole, 63 Amps rating, with over load and short circuit protection 'C' curve and rupturing capacity 10 kA, 415 Volt grade, AC, 50 Hz and making connections using suitable size copper lugs/thimbles, including disconnecting & taking down old unserviceable MCB, complete, all as specified & directed.
S&F in replacement aluminium thimble suitable for 25 Sqmm to 70 Sqmm of size of cable complete all as specified & as directed.
S&F in replacement aluminium thimble suitable for 95 Sqmm to 120 Sqmm of size of cable complete all as specified & as directed.
M&L for preparation of surface of feeder piller box size 2.00x1.00x1.00 mtr and applying two coats of synthetic enamel paint (grey/red) over a coat of anticorrosive primer including patch work, welding replacement of defective hinges, repair inner/outer surface of feeder pillar box /door etc complete all as specified and as directed.
S&F MCCB, 4 Pole, 800 Amps rating, rupturing capacity 36 KA, 415 Volt grade, AC, 50 Hz, with adjustable Thermal - Magnetic release and making connections using suitable size copper lugs/thimbles and crimping tool, including disconnecting & taking down old unserviceable MCCB, complete, all as specified & directed
S&F onload changeover switch enclosed type, 4 pole, 800 Amp rating to be mount on wall and making connections using suitable size lugs/thimbles and crimping tool including disconnecting & taking down old unserviceable changeover switch etc complete all as specified & as directed.
S&F Ultra heavy duty power capacitor enclosed box type 3 phase having the technical specification :- 480V-25KVAr-30.07A, 440V-21.01 KVAr – 27.57A,415V-18.69 KVAr-2600A, 3 x 115.1 Mfd, 50Hz, App, Ui 3/Kv as per IEC 30931:2002, 13585: 2012 including disconnecting & taking down old unserviceable etc complete all as specified & as directed.
S&F contactor 3 pole, model 3TS47, coil voltage 230V, suitable for capacity 50HP make simens including disconnecting & taking down old unserviceable, etc complete all as specified & directed
S&F contactor 3 pole, model 3TF47, coil voltage 230V, suitable for capacity 50HP make simens including disconnecting & taking down old unserviceable, etc complete all as specified & directed.
S&F contactor 3 pole, model 3TF49, coil voltage 230V, capacity 50HP make simens including disconnecting & taking down old unserviceable, etc complete all as specified & as directed.
S&F contactor 3 pole, model A110-30 of 110 Amps, make ABB or equivalent including disconnecting & taking down old unserviceable, etc complete all as specified & as directed.
S&F contactor 3 pole, model KMIA of 63 Amps, make ABB or equivalent including disconnecting & taking down old unserviceable, etc complete all as specified & as directed.
S&F contractor MNX18, 4 pole, NO type, coil voltage 220V alongwith auxiliary contract MNXA1 of NC/NO 4 Amp type including disconnecting & taking down old unserviceable, complete all as specified & as directed.
S&F contractor MNX 25, 3 pole, NO type, coil voltage 220V alongwith auxiliary contact MNXA2 of NC/ON 4 Amp type including disconnecting & taking down old unserviceable, complete all as specified & as directed.
S&F contractor MNX 32, 3 pole, NO type, coil voltage 220V alongwith auxiliary contact MNXA2 of NC/ON 4 Amp type including disconnecting & taking down old unserviceable, complete all as specified & as directed.
S&F overload protector 3 pole of capacity 50 Amps max including disconnecting & taking down old unserviceable, complete including disconnecting & taking down old unserviceable, complete all as specified & as directed.
S&F electronic timer star delta rang 30/60/90/120 sec, pause time 60/90/120/150 mSEc including disconnecting & taking down old unserviceable etc complete all as specified & as directed.
S&F sentron super switch/switch disconnector (breaker) HRC fuse type of capacity 200 Amps 4 pole having front mounted rotating handle, for operation including disconnecting & taking down old unserviceable complete all as specified & directed.
M&L for maintenance of ACB 440 Volts, 800 Amps to 100 Amps including removal of ACB trolley, overhauling and general maintenance including cleaning of all copper mail and female contract, tightening of all connections, checking all auxiliary contracts, control wiring etc, re-fixing the ACB trolley to its original position including proper setting of manual/odorized operation of ACB, checking /setting of tripping system etc complete all as specified and as directed. Note : (i) Maintenance to be carried out by authorized OEM of company (ii) After completion test certificate shall be furnished from OEM.
S&F in replacement bus bar chamber type of size 50x50x40 cm (Box size) with MCCB100 Amps, capacity and 16 KA backing capacity, bus bar chamber having 4 wire 415 Volts, factory made dust proof vermin proof for outdoor using made out of CRCA sheet 3.15mm thick power coated, machine pressed, single side opening, provision of rubber beading and locking system, including aluminium bus bar of 200 Amp capacity (considering 1 Sqmm = 1Amps) 4 strip mounted on DMC/epoxy insulator, bus bar chamber shall be provided with inspection cover, penal shall be mounted on angle iron frame and legs made from angle of size 40x40x6mm, frame and legs duly spray painted internally and externally with two coats of synthetic enameled paint over a coat of red oxide primer, leg grouted in PCC (1:3:6) type C1 (using 20 mm graded crushed stone aggregate). Note : Cost of MS frame work, painting, platform, locking arrangement with lock and key and any minor addition/alteration required at site shall be deemed to be included in the quoted rates.
Supply, installing, commissioning and testing in replacement LT panel board (outdoor type) cubical type made out of CRCA sheet 3.15 mm thick, dust and vermin proof and angle iron of size 50x50x6 mm, pedestal frame grouted in PCC 1:4:8 (type B1) 20 mm graded stone aggregate thimble and cable entry boxes with cable glands, panel should be covered from all sides with front and back lockable door and hinges complete including copper bus bar of capacity 600 Amps, TPN, three phase, 04 wire (in separate chamber). Panel shall be painting with two coat of synthetic enameled paint over a coat of red oxide primer and consisting of the followings:- (a) incoming MCCB, 4 pole, 315 Amp, 415 volts, breaking capacity not less than35 KA with microprocessor release – 01 Nos. (b) Outgoing MCCB, 3 pole, 200 Amps, breaking capacity not less than 25 KA. Fixed type – 01 Nos. (c) Outgoing MCCB, 3 pole, 100 Amps, breaking capacity not less than 16 KA. Fixed type – 02 Nos. (d) Outgoing MCCB, 3 pole, 63 Amps, breaking capacity not less than 16 KA. Fixed type – 02 Nos. (e) MCB TPN 40 Amp – 04 Nos (f) Digital Voltmeter 0-500 Volts – 01 Nos. (g) Digital Ameter 0- 200 with suitable ratio of CTs - 01 Nos (h) Changeover switch 200 amps -01 No (j) Indicator Set RYB “LED” type (Set of three) - 01 Set. Note :- (i) LT panel base frame shall be grouted in PCC (1:2:4) type B-1 using 20mm graded stone aggregate. The base shall be 60cm height from the nearest road level/floor level or as directed.(ii) All incoming MCCB shall be connected through MCCB spreaders with incoming bus bar and incoming cable shall be connected with incoming bus bar.(iii) Drawing of LT Panel shall be got approved well in advance from GE before fabrication of LT Panel. (iv) The quoted rate shall deemed to include supply & provision of 65mm lock with 2 keys. Make of Lock :- Godrej / Harrison / Link.(v) Cost of platform, MCCB spreaders, cable glands, locking arrangement with lock and key and any minor addition/alteration if required at site (the decision of GE will be final and binding regarding extent to which the change can be considered as minor addition/alteration) shall be deemed to be included in the quoted rates.
J.D INFRA ENGINEERING
BIDAWAT ENTERPRISES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .