Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹14.0 LAccepted-AOC 011 NAGAREWADI 612 NAGAREWADI POST PADALI TALUKA SHIRUR KASAR DISTRICT BEED 413249 BEED MAHARASHTRA 413249 UDYAM MH 05 0079863 | BEED | MAHARASHTRA | 413249 | L1 | Accepted-AOC LOWEST | |
| 2 | L2₹16.2 L+₹1.7 L (12.0%)Rejected-Finance | L2 | Rejected-Finance OTHER THAN LOWEST TENDER | |
| 3 | L3₹16.3 L+₹1.9 L (12.8%)Rejected-Finance | L3 | Rejected-Finance OTHER THAN LOWEST TENDER | |
| 4 | L4₹16.3 L+₹1.9 L (12.9%)Rejected-Finance | L4 | Rejected-Finance OTHER THAN LOWEST TENDER | |
| 5 | L5₹16.5 L+₹2.0 L (14.0%)Rejected-Finance PULGAON | L5 | Rejected-Finance OTHER THAN LOWEST TENDER |
Tender Value
₹15 L
EMD Value
₹30,000
Closing Date
7 Jul 2021, 6:00 pmClosed
GE Pulgaon
GE PULGAON CAD CAMP PULGAON PIN 442303
REPAIRS REPLACEMENT OF LT PANEL APFC PANEL LT OH LINE CABLE AND OTHER CONNECTED WORK AT DEPOT AND RA AREA UNDER GE PULGAON
2021_MES_452074_1
8924/PUL/E8
Open Tender
Electrical and Maintenance Works
Item Rate
240 days
Pulgaon
As per NIT
8 documents required · 8 mandatory
₹500
GE PULGAON
₹30,000
Yes
24 Jul 2021
17 Jun 2021
13 Jul 2021
17 Jun 2021
7 Jul 2021
30 Jun 2021
17 Jun 2021 - 28 Jun 2021
Amount
Excavation in trenches not exceeding 1.5 metre wide & not exceeding 1.5 meter in depth for foundation, laying of cable or pipe and getting out in soft/loose soil including trimming the sides and forming bottom surfaces to required levels complete all as specified and as directed by Engr-in-charge.
Returning, filling in trenches in soft/loose soil in layers n.exc. 25 cm after laying of cables including spreading, levelling, watering, and well ramming complete all as directed by Engr-in-Chrage.
Removing surplus excavated soil to a distance n.exc. 50 metre and depositing where directed at a level n.exc.1.5 metre high from the starting point all as directed by Engr-in-Chrage.
M & L for sand cushioning with dry and clean sand over and under the under ground cable in trenches , ducts for cable protection incliding levellling and consodilation complete all as specified and directed by EIC. (Note Punned thiickness shall be measured.)
Supply and laying brick sub class "B" having minimum compressive strength 75 kg/sqcm laid in trenches for cable protection etc complete all as directed by Engr-in-Chrage.
Taking out LT XLPE/PVC insulated armoured cable alongwith all joints of any size from trenches wall/roof including taking out of brick layer and sand from trenches complete all as directed by Engr-in-Chrage.
Supply, laying and testing LT XLPE insuated PVC bedded galvanised steel strip or wire armoured earthed electric power cable with aluminium conductor 1100 volts grade, heavy duty in trenches/along pole or wall of following sizes complete all as specified and directed by EIC. Note:- 1. Excavation and earth work, sand cushioning, brick pipes, clamps, and cable joint shall be measured and paid separetely under respective items :-
All as per Item No. 07... But for 50 Sq mm 3.5 core
All as per Item No. 07... But for 70 Sq mm 3.5 core
All as per Item No. 07... But for 120 Sq mm 3.5 core
All as per Item No. 07... But for 185 Sq mm 3.5 core
All as per Item No. 07... But for 240 Sq mm 3.5 core
Supply & laying in repair galvanized steel tubing "light grade" with all fittings in trenches/ under roads/ along pole/ wall for cable protection all as specified & directed by EIC for the following size 50 mm bore .
All as per Item No. 08... But for 80mm bore
Dismantling and taking out the existing unserviceable (damaged/broken) or serviceable tilted Panel of any type and any size, from Location and removal from site all as directed by Engr-in-Chrage.
Boring of holes under road/railway crossing, pavement, hardstanding by trenchless technology using ultra sound technique and necessary machine including HDPE pipe of 100mm dia suitable for 0.4mpa working pressure without any damage to existing structure and making it good to match with the adjoining surfaces/structure for cable passing complete all as specified and directed.
M&L for tesitng of faulty LT cable at CAD Pulgaon by using LT voltage. Testing kit installed on movable vehicle complete all as specified and directed by EIC Note : This job includes cost of vehicle transport from Nagpur to Pulgaon and back
Material and Labour for PCC 1:4:8 type D-2 using 40mm graded stone aggregate as in foundation of pole upto ground level complete all as directed by Engr-in-Chrage.
PCC (1:3:6) type C-1 using 20 mm graded stone aggregate as in coping/plinth block including necessary form work all as directed by Engr-in-Chrage.
S& f for GI earthing strip 32x6 mm with nut and bolts complete including taking down old one all as specified and directed by Engr-In Charge
Taking out XLPE UG cable form LT panel , removing the lugs and fix the new Alu lugs off size 16 sqmm to 25 sqmm size in qty 4 Nos with crimping tools properly , insulation tape around the burnt cable also re fixing in panel complete all as specified and directed by Engr-In Charge
All as per Item No. 18... But for but off size 50 sqmm to 70 sqmm
All as per Item No. 18... but off size 95 sqmm to 150 sqmm
All as per Item No. 18... but off size 185 sqmm to 400 sqmm
M& L for takking out LT feeder panel front and back type opening replace old clams and fix new hinges by drilling or belding as per condition , replaced burnt out lugs and insulation , proper , insulation taping to XLPE cable and painting inner and outer side , top and bottam , clamps complete all as specified and drirected by Engr-In-Charge
S&F for Indicator lamp neon/LED type (set of three )
S& F for Panel Wiring with suitable size PVC insulated PVC sheathed 1100 volts grade FRLSH type with copper conductor multistranded cable with lugs on both ends of cable.
Dismantling of the complete APFC of 125/100 KVAR 415 Volts from its position, opening for repair, preventive maintenance, servicing, including wiring, replacement of worn parts to make it fully functional, reassembling after repair, installation to its original position, connection with input/output supply, testing to its full load capacity complete all as specified and as directed. NOTE :- (a). Spares / parts except minor repairs required for replacement shall be measured and paid separately. (b)Necessary wiring with 1.5 Sqmm Single Core FRLSH included in the above Cost.
Supply only Power Contactor MOC-15 ,3 pole 415 Volts capacity 15 amps AC 50HZ (for switching of capacitor ) complete all as specified and as directed. Make : Seimen/Havell's./L&T
Supply only Power Contactor MOC-5, 3 pole 415 Volts capacity 5 amps AC 50HZ (for switching of capacitor ) complete all as specified and as directed. Make : Seimen/Havell's./L&T
Supply only 10 KVAR Heavy duty Power Capacitor 440 Volt,in APFC Panel complete all as specified and as directed. "Make : Seimen/Havell's./L&T
Supply only 5 KVAR Heavy duty Power Capacitor 440 Volt,in APFC Panel complete all as specified and as directed. Make : Seimen/Havell's./L&T
Supply only 3 KVAR Heavy duty Power Capacitor 440 Volt,in APFC Panel complete all as specified and as directed. Make : Seimen/Havell's./L&T
Supply only 2 KVAR Heavy duty Power Capacitor 440 Volt,in APFC Panel complete all as specified and as directed. Make : Seimen/Havell's./L&T
Supply only 1 KVAR Heavy duty Power Capacitor 440 Volt,in APFC Panel complete all as specified and as directed. "Make : Seimen/Havell's./L&T
Supply only CT of 200/5
Supply only CT of 100/5
Supply only CT of 60/5
Supply only CT of 66/3
Supply only APFC relay 8 Stage including adon For APFC Panel Make : Seimen/Havell's/L&T
S&F of MCCB in replacement TPN 125 amps 16 KA 415 volts thermomegnetic release adjustable setting complete all as specified and directed including taking out old one MAKE:L&T /INDOASIAN/GE/C&s/schnieder
S&F of MCCB in replacement TPN 160 amps 36 KA 415 volts thermomegnetic release adjustable settingcomplete all as specified and directed including taking out old one MAKE:L&T /INDOASIAN/GE/C&s/schnieder
S&F of MCCB in replacement TPN 200 amps 36 KA 415 volts thermomegnetic release adjustable settingcomplete all as specified and directed including taking out old one MAKE:L&T /INDOASIAN/GE/C&s/schnieder
S&F of MCCB in replacement TPN 250 amps 36 KA 415 volts thermomegnetic release adjustable settingcomplete all as specified and directed including taking out old one MAKE:L&T /INDOASIAN/GE/C&s/schnieder
Material and labour for earthing complete with galvanized steel earth plate electrode 600mm X 600mm X 6mm buried directly in ground vertically to a depth not less than 2.25 meter below normal ground level (with top edge of earth plate not less than 1.5 meter below ground level) connected to GI strip 32mm X 6mm main earthing lead by means of galvanized bolts, nuts and washers all as shown in electrical plate no 5 of MES Schedule Part-I (2009) connected to earth test point & to main switch board etc with & including adequate quantity of charcoal dust and common salt alround earth plate, PCC (1:3:6) type C-1 (using 20mm graded black trap/granite/Basalt stone aggregate) for earth pit with 40 x 40 x 6mm mild steel angle iron frame for cover, pre cast RCC (1:2:4) type B-1 (using 20mm graded stone aggregate) 50mm thick cover reinforced with 8mm dia TMT bars @ 100mm c/c both way with 12mm dia round bar handle, GI medium grade watering pipe 20 mm bore GI medium grade earth lead protection pipe, complete all as specified and directed.
RAJ ENTERPRISES
SHUBHAM SALES AND ENGG WORKS
M/s MM TRADERS
M/S Maa Durga Constructions,Pulgaon
SHREE CONSTRUCTIONS
SHRI RANI SATI TRADERS
M/s Dara Constructions, Pulgaon
Chhabra Enterprises
M/S L M Chourasia
Bidder Name
M/S L M Chourasia
RAJ ENTERPRISES
SHRI RANI SATI TRADERS
SHREE CONSTRUCTIONS
SHUBHAM SALES AND ENGG WORKS
MAHARASHTRA ENTERPRISES
M/s Dara Constructions, Pulgaon
M/S Maa Durga Constructions,Pulgaon
M/s MM TRADERS
Chhabra Enterprises
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .