Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.8 CrAccepted-AOC DOOR NO 48 50 PRAKASAM STREET SKCL HARMONY SQUARE T NAGAR T NAGAR CHENNAI TAMIL NADU 600017 | CHENNAI | TAMIL NADU | 600017 | ₹1.8 Cr | L1 | Accepted-AOC L1 bidder against e-RA |
| 2 | L2₹1.8 Cr+₹1.1 L (0.58%)Accepted-AOC 2ND ROSHAN TOWER S B SHOP BISTUPUR AREA EAST SINGHBHUM JHARKHAND | BISTUPUR | EAST SINGHBHUM | JHARKHAND | 831001 | ₹1.8 Cr+₹1.1 L (0.58%) | L2 | Accepted-AOC L2 bidder against --RA |
| 3 | L3₹1.9 Cr+₹3.2 L (1.74%)Accepted-AOC 6TH FLOOR CG HOUSE DR ANNIE BESANT ROAD WORLI MUMBAI MAHARASHTRA 400030 | MUMBAI | MAHARASHTRA | 400030 | ₹1.9 Cr+₹3.2 L (1.74%) | L3 | Accepted-AOC L3 bidder against e-RA |
Tender Value
Refer Docs
EMD Value
₹8 L
Closing Date
17 May 2019, 3:30 pmClosed
Sr.Manager(E/M), PEM, AGBP
Sr. Manager (E/M), PEM, AGBP, NEEPCO LTD., Bokuloni, Dibrugarh, Assam
Design, Engineering, Manufacturing, Supply, Dismantling, Retrofitting, Testing and Commissioning of 8 no. 245KV SF6 Spring operated Circuit Breakers for replacement of old existing 245KV SF6 hydraulic operated CB at AGBP, NEEPCO LTD. Dibrugarh, Assam
2019_NEEPC_21736_1
NEEPCO/AGBP/PEM/01/2018-19/06 dtd.13/02/2019
Open Tender
Electrical Works
Tender cum Auction
450 days
AGBP, NEEPCO LTD., Bokuloni
As per Detailed NIT/NIB
4 documents required · 4 mandatory
₹5,900
Yes
AC No 34098989892 IFSC SBIN0009143 SBI Bokuloni
₹8 L
Yes
4 Jul 2020
15 Feb 2019
18 May 2019
15 Feb 2019
17 May 2019
15 Feb 2019
15 Feb 2019 - 17 May 2019
Amount
For Supply
245 KV, 2000 Amps. continuous current, 40kA short circuit Breaking current, Triple pole outdoor type, SF6 circuit Breaker suitable for high speed single/ Three phase rapid auto reclosing features for line breaker(1no) and three phase gang operated for generator breaker (7nos) (as applicable) complete with SF6 Gas (+20% extra), mounting structure, control cubicle, terminal connectors suitable for Zebra conductor, auxiliaries etc. as specified in NIB….. Set
Mandatory Spare Parts required for 5 years of normal operation of the Circuit Breaker as per detailed given below. Itemized prices of the spares to be given….1 complete Set
Complete set of CB complete with pole column (support insulator stack) and interrupter but without support structure and operating mechanism…set
Relays, power contactors, limit switches, push buttons, timers and resistors for electrical control circuit as per approved schematic (consisting of one no. each of all item) ….. Set
Rubber Gaskets, O rings and seals for SF6 Gas….. Set.
Molecular filter for SF6 CB……..Nos
Density Monitor for SF6 Gas. ……..Nos
Closing coil assembly. ……..Nos
Trip coil assembly….Nos
Terminal pads. ……..Nos
Terminal connectors of each type.
Auxiliary switch assembly consisting of 24 nos. of reversible type contacts….Set.
Auxiliary / multiplied contacts with 9 NO + 9NC as spare in addition to the auxiliary contacts required for breaker’s own operational requirements…… Set
Special contacts for use with trip coils and automatic reclosing operation at least 2 (two) nos. of spare potential free contacts for a) Local/Remote switch position; b) Gas pressure normal; c) Gas pressure low; d) Breaker lockout signal, etc. shall be provided.. Complete Set
Operations counter…. Nos.
SF6 Gas 20% of total gas required for 8 CBs. The unit shall vary depending on standard capacity…..50kg/1 SF6 Gas cylinder
Pressure switches (For SF6 circuit)….. Set
All type of coupling for SF6 gas… Set (1 of each type)
Any other recommended spares, if not listed above but required for servicing and AMC periods shall be provided. The list of the same spares shall be submitted in tech-commercial bid and the Price shall be included in the Price Bid….set
Total Price for Supply (A)
For Service: Retrofitting /Installation, testing & commissioning
Dismantling, Retrofitting /Installation, testing &commissioning of 8 (7+1) no SF6 CB with accessories as stated in the NIB (sl.no:1.01 above).
AMC for periods of 5(five) years effective from the date of expiry of warrantee/guarantee periods or concern equipment’s as stated in NIB
AMC for 1st year (Preventive maintenace for 8 nos CB in lots)
AMC for 2nd year (Preventive maintenace for 8 nos CB in lots)
AMC for 3rd year (Preventive maintenace for 8 nos CB in lots)
AMC for 4th year (Preventive maintenace for 8 nos CB in lots)
AMC for 5th year (Preventive maintenace for 8 nos CB in lots)
Total Price for AMC for periods of 5(five) years ©
Total Price for Supply; Retrofitting /Installation, testing & commissioning and AMC for a period 5 years (Preventive maintenace for 8 nos CB in lots)
Bidder Name
Amount in Words
ABB INDIA LIMITED
SIEMENS LTD
CG Power and Industrial Solutions Ltd
ABB INDIA LIMITED
SIEMENS LTD
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .