Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹47.3 LAccepted-AOC INDEX NO E 29 CWE JRC 352 3 GURU NANAK PURA EAST JALANDHAR CITY PIN 144001 | JALANDHAR CITY | JALANDHAR | PUNJAB | 144001 | L1 | Accepted-AOC L1 | |
| 2 | L2₹49.6 L+₹2.3 L (4.77%)Rejected-Finance | L2 | Rejected-Finance other than lowest bid | |
| 3 | L3₹51.3 L+₹4.0 L (8.41%)Rejected-Finance 25 25 SADAR BAZAR JALANDHAR CANTT | JALANDHAR | JALANDHAR | PUNJAB | L3 | Rejected-Finance other than lowest bid |
Tender Value
₹49 L
EMD Value
₹98,000
Closing Date
25 Feb 2023, 6:00 pmClosed
Garrison Engineer (East) Jalandhar Cantt
Garrison Engineer (East) Jalandhar Cantt
REPAIR/ MAINTENANCE OF LT SWITCHGEAR AND ALLIED DISTRIBUTION NETWORK AND CONNECTED E/M INSTALLATIONS WK UNDER AGE E/M OF GE (EAST) JALANDHAR CANTT
2023_MES_576084_1
GE/JULL/ET-79/2022-23
Open Tender
Civil Works
Item Rate
273 days
Jalandhar Cantt
As per tender documents
8 documents required · 8 mandatory
₹500
Garrison Engineer (East) Jalandhar Cantt
₹98,000
Yes
6 Apr 2023
19 Jan 2023
4 Mar 2023
19 Jan 2023
25 Feb 2023
4 Feb 2023
Amount
Supplying, Laying, jointing and testing LT underground XLPE insulated, PVC sheathed (heavy duty) electric strip/ wire armoured, electric cable of size 185 Sqmm 3.5 core with stranded aluminium conductor, 1100 volts grade, laid in trenches, in floor, in duct, through pipes or along the pole including taking up existing defective cable complete all as specified and directed. Note : Testing of cables shall be done as per CA clause in presence of JE.
All as per Srl Item No. 1.00 here-in-before but of size 240 Sqmm 3½ core
All as per Srl Item No. 1.00 here-in-before but of size 300 Sqmm 3½ core
All as per Srl Item No. 1.00 here-in-before but of size 16 Sqmm 4 core
All as per Srl Item No. 1.00 here-in-before but of size 70 Sqmm 3½ core
Excavation in trenches in soft/ loose soil not exceeding 1.5 m wide and not exceeding 1.5 m in depth for laying of cables, erecting poles, stay assembly etc. and getting out complete all as specified and directed.
Returning filling in, including spreading, levelling, watering and well ramming in layers n.exc 25 cm thick each layer complete all as specified and directed.
Removal of surplus spoil to a distance n. exc. 50 mtr and depositing where directed at a level n.exc. 1.5 mtr above the starting point complete all as specified and directed
Material and labour for sand cushioning with 8cm thick layer of sand before laying of cable and 15cm thick after laying of cable in trenches complete all as specified and directed Note : Punned down thickness of 18cm will be measured for payment to contractor.
Supply & laying old size sub class 'B' bricks laid flat in trenches over the cable with the length of brick perpendicular to the direction of cable length complete all as specified and directed
Supply and fixing in replacement 1100 volts grade heavy duty PVC insulated & PVC sheathed stranded aluminium conductor of size 16 Sqmm flat twin core cable in service connection all as specified and directed.
Material and labour for scraping old paint from LT panels/ feeder pillars outside off size with emery paper, preparing old surface of painting, applying two coats of synthetic enamel paint by spray painting machine with colour approved/ decided by Engineer-in-Charge from top of PCC coping and marking number/ name of panel and feeders in alphabets not less than 150mm in size including disconnection of electric supply before starting of work complete all as specified and directed. Note : The computerized colour making/ mixing may require within quoted rate.
Material and labour for applying two coats of aluminium oxide paint from top of PCC coping/ brick work to chain link fencing/ XPM jalli inside and outside around transformers/LT panels/ feeder pillars/ 2/4 pole structures off size and angle iron/ cross arms of fencing complete all as specified and directed. Note : The overall area of fencing shall be measured for payment. However, contractor have to paint iron structure/ posts alongwith fencing within overall quoted rate.
Supply and fixing in replacement panel meter 96x96 mm with LED display , accuracy class 1.0, having parameters Voltage, Current, Frequency, Power factor, Power & Energy complete all as specified and directed. Make : Schneider/ Siemens/ L&T/ HPL/ AE
Spraying chemical (approved by Engr-in-Charge) around electric installations, near package Sub Station and LT Panels area complete all as specified and directed. Note : Grass should be collected and disposed off upto 200 mtr distance & rates to deemed to be included in quoted rates. Chemical rates are deemed to be inclusive in overall quoted rates.
Material and labour for connecting and testing CT ring core type copper wire, ISI marked in repair suitable for 415 volts, 50 HZ LT supply of ratio 400/5 A with necessary connections inlcuidng opening of bus bar connection and refixing complete all as specified and directed.
Material and labour in replacement 3 pole contactors (heavy duty) with built in auxiliary contacts AC 415 volts ratings 16 Amps complete all as specified and directed.
Material and labour in replacement 4 pole contactors (heavy duty) with built in auxiliary contacts AC 415 volts ratings 32 Amps complete all as specified and directed.
Material and labour in replacement 4 pole contactors (heavy duty) with built in auxiliary contacts AC 415 volts ratings 40 Amps complete all as specified and directed. Make for Srl Item No. 17 to 19 : Siemens/ BCH/ L&T
Material and labour in replacement Microprocessor based automatic power factor control relay unit suitable for eight stages of capacitor bank complete all as specified and directed. Make : ABB/ Neptune/ L&T/ EPCOS
Material and labour in replacement MCCB 630 Amps, 4 pole, with thermal release, 415 volts, 50 HZ, 36 KA with inbuilt over current, earth fault and instantaneous protection, ICS=ICU=100% complete all as specified and directed.
Material and labour in replacement MCCB 400 Amps, 4 pole, with thermal release, 415 volts, 50 HZ, 36 KA with inbuilt over current, earth fault and instantaneous protection, ICS=ICU=100% complete all as specified and directed.
Material and labour in replacement MCCB 400 Amps, 3 pole, with thermal release, 415 volts, 50 HZ, 36 KA with inbuilt over current, earth fault and instantaneous protection, ICS=ICU=100% complete all as specified and directed. Make for Srl item No. 21 to 23 : Legrand/ Siemens/ Schneider/ L&T/ Indoasian/HPL/ Havells
Material and labour in replacement MCCB 250 Amps, 4 pole, with thermal magnetic release, ICS=ICU=100%, 415 volts, 50 HZ, 25 KA complete all as specified and directed.
Material and labour in replacement MCCB 200 Amps, 4 pole, with thermal magnetic release, ICS=ICU=100%, 415 volts, 50 HZ, 25 KA complete all as specified and directed.
Material and labour in replacement MCCB 160 Amps, 3 pole, with thermal magnetic release, ICS=ICU=100%, 415 volts, 50 HZ, 16 KA complete all as specified and directed.
Material and labour in replacement MCCB 160 Amps, 4 pole, with thermal magnetic release, ICS=ICU=100%, 415 volts, 50 HZ, 16 KA complete all as specified and directed.
Material and labour in replacement MCCB 100 Amps, 4 pole, with thermal magnetic release, ICS=ICU=100%, 415 volts, 50 HZ, 16 KA complete all as specified and directed.
Material and labour in replacement TP MCB, 240 Volts, 50 Hz, having rupturing capacity 10 KA, of rating 63 Amps complete all as specified and directed.
Material and labour in replacement of bakelite terminal block suitable for 35 sqmm Al cable complete all as specified and directed.
Material and labour in replacement of bakelite terminal block suitable for 50 sqmm Al cable complete all as specified and directed.
Material and labour in replacement of copper cable for connection in LT panels of size 6 sqmm single core duly crimped with copper thimbles complete all as specified and directed (Cost of copper thimbles and crimping included).
Periodical inspection of SCADA system of make : TRINITY TOUCH for periodical testing, calibration, servicing of complete system by site visit of Engineer/ tech qualified rep of TRINITY TOUCH with necessary parameters setting for healthy functioning, repair etc of system. Note : The quoted rate include the submission of servicing, healthy state of equipements.
Material and labour in replacement earthing complete with GI or steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground vertically in a pit not less than 2.25 meter below ground level with top edge of earth plate at a depth not less than 1.5 meter below level covered on all sides with alternative layers of charcoal dust and common salt 15 cm thick connected to galvanised earth lead Galvanised Iron strip 32 x 6 cm by means of bolts, nuts, check nuts and washers of Galvanised Iron or steel with protection pipe earth wire protected by galvanized steel pipe light grade 40 mm bore from top of the earth plate electrode upto test point and watering pipe 20mm bore, GI light grade with funnel and wire mesh all as shown in electrical plate No 3 of SSR Part-1 and connected to earthing test point all as specified or indicated and testing on completion, including PCC earth pit (1:3:6) type C-2 RCC covered with CI cover hinged with frame including excavation and earth work complete all as specified and directed.
Supply and fixing 25 mm x 3 mm aluminium strip as earth continuity conductor including fixing from test point to equipement complete all as specified and directed
Supply, fixing and connecting in glow sign board of size 90cm x 75cm x 25cm made of aluminium sheet 2mm thick with frame of stainless steel with UV printing on star flex in blue and white colour with 02 Nos of 09 Watt LED fitting 2 feet complete all as specified and directed.
Material and labour for locating & pinpointing conductor and insulation faults of low and high resistance, intermittent or flashing nature in XLPE HT/ LT underground power cables of the rating 1.1 KV with the help of pre-locator with time domain laptop based reflectometer/ electrometer using pulse echo method, impulse current method & decay method and using DC high voltage surge generator to produce surge to trace route and pinpointing fault with the help of dual channel digital sound system, magnetic & acoustic for location of fault with acoustic transducer (pickup) and the amplifier with headphones, after pinpointing of fault location necessary excavation upto 10 mtr and taking out of faulty cable for repair/ replacement and insertion of straight through joints, relaying of cable, refilling of soil and removal of surplus soils etc, at Jalandhar Cantt complete all as specified and directed Notes : (i) The joint shall be measured and paid separately under relevant item. (ii) The qty of item will be executed at different times during currency of contract as directed by Engineer-in-Charge. (iii) Contractor shall quote his rate accordingly for arranging and executing the items accordingly
Supply and fixing heat shrinkable straight through joint suitable for 1100 V, XLPE/ PVC cable for size 240 Sqmm to 400 Sqmm 3½ Core complete all as specified and directed
Supply and fixing heat shrinkable straight through joint suitable for 1100 V, XLPE/ PVC cable for size 70 Sqmm to 185 Sqmm 3½ Core complete all as specified and directed
Supply and fixing heat shrinkable straight through joint suitable for 1100 V, XLPE/ PVC cable for size 25-50 Sqmm 3½/4 Core complete all as specified and directed
Material and labour for servicing of ACBs upto 800 Amp installed in existing panel, cleaning of whole unit, cleaning of contacts with chemical/ gel, testing of mechanical system, testing of tripping system on required voltage complete all as specified and directed
Material and labour for fixing of AC coil of 220 Volt complete with testing as required all as specified and directed
Material and labour for fixing of DC coil of 24 Volt complete with testing as required all as specified and directed
Supply and fixing URV for tripping of ACBs upto 800 Amps testing complete as required all as specified and directed
Material and labour for heat shrinkable end joint kit suitable for XLPE cable of size 240 Sqmm to 400 Sqmm, 3½ core including opening cable connections, taking down LT cable from ACB/ LT Panel/ Pole/ Transformer or any location including taking out loop, cleaning with cleaning tissue and gel and reconnected the same to electrical system with new aluminium lugs of proper size and restore the power supply complete all as specified and directed
Material and labour for heat shrinkable end joint kit suitable for XLPE cable of size 120 Sqmm to 185 Sqmm, 3½ core including opening cable connections, taking down LT cable from ACB/ LT Panel/ Pole/ Transformer or any location including taking out loop, cleaning with cleaning tissue and gel and reconnected the same to electrical system with new aluminium lugs of proper size and restore the power supply complete all as specified and directed
Material and labour for heat shrinkable end joint kit suitable for XLPE cable of size 50 Sqmm to 95 Sqmm, 3½ core including opening cable connections, taking down LT cable from ACB/ LT Panel/ Pole/ Transformer or any location including taking out loop, cleaning with cleaning tissue and gel and reconnected the same to electrical system with new aluminium lugs of proper size and restore the power supply complete all as specified and directed
Taking down LT cable of any size from ACB/ LT Panel/ Pole in disconnecting cable and taking out loop and refixing the same as directed and clean the connected cable from cleaning tissue and gel and fixing a PVC sleeve on 4 core of cable and reconnected the same to electrical system with new aluminium lugs of proper size and restore the power supply complete all as specified. Note : Each sleeve length should not be less than 0.5mtr and rate quoted inclusive of new lugs and heating arrangement
Material and labour for reshifting of existing LT panel within 1 mtr distance after taken out panel/ cable dismantling PCC and refixing the same with PCC (1:2:4) at new location in such a way that each leg of iron angle must be 30cm in ground and 60cm above ground (PCC should be 30cm in gound and 30cm above ground) complete all as specified and directed.
Supply and fixing new angle iron of any size including i.e. cutting, welding, bendign, cold or hot, drilling holes, grinding or bolt in any shape or size including two coats of aluminium paint over one coat of red oxide primer including taking out unserviceable complete and fixing to existing angle iron legs of LT panel or as specified and directed.
Supply, installing, testing and commissioning in-replacement feeder pillar, outdoor cubicle type weather and vermin proof totally enclosed made out of 3mm thick CRCA sheet machine pressed of min size 2m x 1.1m x 0.6m, suitable to operate on 3 phase 4 wire system, 415 volts, 50 Hz double door with front and rear openable with locking arrangement with sliding bolt including inner independent enclosures for all switches/ MCCBs/ metering equipments with hinged (bottle type) shutters, bottom gland plate with sufficient numbers of circular cable entry holes with cable glands of suitable size of cable & with suitable cable glands as per number of outgoings, prewired complete duly powder coated with 7 tank process with base frame made of angle iron 50 mm x 50 mm x 6 mm, legs 100 cm long having openable apron on all three sides of panel 30 cm wide and grouted 45 cm in PCC (1:3:6) type C-1 including brick masonary platform 45cm above ground level all as specified and directed by Engineer-in-Charge, comprising with following complete:- (a) Bus bar suitable for 3 phase, 415 volts, 50 Hz, 4 wire system of rating 600 Amps made out copper strip of suitable size with coloured heat shrinkable sleaves in four colours (Red, yellow, blue and black) fixed on resin cast insulators including galvanised nuts, bolts and washers etc fitted with and including the following :-
(ii) INCOMING : - (a) MCCB 400 Amp, 415V, 25 KA, 4 pole with thermal magnetic release, ICS=ICU=100%.-01 No Make : Legrand/ Siemens/ Scheinder/ Havells (b) Multifunction panel meter of size 96x96 mm with LCD display , accuracy class 1.0, having parameters Voltage, Current, Frequency, Power factor, Power & Energy complete all as specified, duly prewired with suitable size of copper insulated FRLS wire with universal code including suitable CTs complete. (c) Indicator with LED lamps for RYB, 3 Phase with MCBs set of three -01 set (iii) OUTGOING:- (a) MCCB 200 Amp, 415 V, 16 KA, 4 pole with thermal magnetic release ICS=ICU=100% -04 Nos. (b) Indicator with LED lamps for RYB, 3 Phase with MCBs set of three -04 sets
Supply, installing, testing and commissioning in-replacement feeder pillar, outdoor cubicle type weather and vermin proof totally enclosed made out of 3mm thick CRCA sheet machine pressed of min size 1.1m x 1.1m x 0.6m, suitable to operate on 3 phase 4 wire system, 415 volts, 50 Hz double door with front and rear openable with locking arrangement with sliding bolt including inner independent enclosures for all switches/ MCCBs/ metering equipments with hinged (bottle type) shutters, bottom gland plate with sufficient numbers of circular cable entry holes with cable glands of suitable size of cable & with suitable cable glands as per number of outgoings, prewired complete duly powder coated with 7 tank process with base frame made of angle iron 50 mm x 50 mm x 6 mm, legs 100 cm long having openable apron on all three sides of panel 30 cm wide and grouted 45 cm in PCC (1:3:6) type C-1 including brick masonary platform 45cm above ground level all as specified and directed by Engineer-in-Charge, comprising with following complete:- (a) Bus bar suitable for 3 phase, 415 volts, 50 Hz, 4 wire system of rating 600 Amps made out copper strip of suitable size with coloured heat shrinkable sleaves in four colours (Red, yellow, blue and black) fixed on resin cast insulators including galvanised nuts, bolts and washers etc fitted with and including the following :-
(ii) INCOMING : - (a) MCCB 400 Amp, 415 V, 25 KA, 4 pole with thermal Magnetic release, ICS=ICU=100%-01 No. (b) Multifunction meter of size 96x96 mm with LCD display , accuracy class 1.0, having parameters Voltage, Current, Frequency, Power factor, Power & Energy complete all as specified, duly prewired with suitable size of copper insulated FRLS wire with universal code including suitable CTs complete. (c) Indicator with LED lamps for RYB, 3 Phase with MCBs set of three -01 set (iii) OUTGOING:- (a) MCCB 250 Amp, 415 V, 16 KA, 4 pole with thermal magnetic release, ICS=ICU=100%-03 Nos. (b) MCCB 200 Amp, 415 V, 16 KA, 4 pole with thermal magnetic release, ICS=ICU=100%-01 No (c) MCCB 63 Amp, 415 V, 16 KA, 4 pole with thermal magnetic release, ICS=ICU=100%-01 No (d) Indicator with LED lamps for RYB, 3 Phase with MCBs set of three -05 sets
Supply, installing, testing and commissioning in-replacement feeder pillar, outdoor cubicle type weather and vermin proof totally enclosed made out of 3mm thick CRCA sheet machine pressed of min size 1.1m x 1.1m x 0.6m, suitable to operate on 3 phase 4 wire system, 415 volts, 50 Hz double door with front and rear openable with locking arrangement with sliding bolt including inner independent enclosures for all switches/ MCCBs/ metering equipments with hinged (bottle type) shutters, bottom gland plate with sufficient numbers of circular cable entry holes with cable glands of suitable size of cable & with suitable cable glands as per number of outgoings, prewired complete duly powder coated with 7 tank process with base frame made of angle iron 50 mm x 50 mm x 6 mm, legs 100 cm long having openable apron on all three sides of panel 30 cm wide and grouted 45 cm in PCC (1:3:6) type C-1 including brick masonary platform 45cm above ground level all as specified and directed by Engineer-in-Charge, comprising with following complete:- (a) Bus bar suitable for 3 phase, 415 volts, 50 Hz, 4 wire system of rating 600 Amps made out copper strip of suitable size with coloured heat shrinkable sleaves in four colours (Red, yellow, blue and black) fixed on resin cast insulators including galvanised nuts, bolts and washers etc fitted with and including the following :-
(ii) INCOMING : - (a) MCCB 400 Amp, 415 V, 25 KA, 4 pole with magnetic release, ICS=ICU=100% -01 No. (b) Multifunction meter of size 96x96 mm with LCD display , accuracy class 1.0, having parameters Voltage, Current, Frequency, Power factor, Power & Energy complete all as specified, duly prewired with suitable size of copper insulated FRLS wire with universal code including suitable CTs complete. (c) Indicator with LED lamps for RYB , 3 Phase with MCBs set of three -01 set (iii) OUTGOING:- (a) MCCB 100 Amp, 415 V, 16 KA, 4 pole with thermal magnetic release, ICS=ICU=100% -06 Nos. (b) Indicator with LED lamps for RYB, 3 Phase with MCBs set of three -06 sets
Supply, installing, testing and commissioning in-replacement feeder pillar, outdoor cubicle type weather and vermin proof totally enclosed made out of 3mm thick CRCA sheet machine pressed of min size 0.9m x 0.9m x 0.9m, suitable to operate on 3 phase 4 wire system, 415 volts, 50 Hz double door with front and rear openable with locking arrangement with sliding bolt including inner independent enclosures for all switches/ MCCBs/ metering equipments with hinged (bottle type) shutters, bottom gland plate with sufficient numbers of circular cable entry holes with cable glands of suitable size of cable & with suitable cable glands as per number of outgoings, prewired complete duly powder coated with 7 tank process with base frame made of angle iron 50 mm x 50 mm x 6 mm, legs 100 cm long having openable apron on all three sides of panel 30 cm wide and grouted 45 cm in PCC (1:3:6) type C-1 including brick masonary platform 45cm above ground level all as specified and directed by Engineer-in-Charge, comprising with following complete:- (a) Bus bar suitable for 3 phase, 415 volts, 50 Hz, 4 wire system of rating 600 Amps made out copper strip of suitable size with coloured heat shrinkable sleaves in four colours (Red, yellow, blue and black) fixed on resin cast insulators including galvanised nuts, bolts and washers etc fitted with and including the following :-
(ii) INCOMING : - (a) MCCB 400 Amp, 415 V, 25 KA, 4 pole with magnetic release ICS=ICU=100%-01 No. (b) Multifunction meter of size 96x96 mm with LCD display , accuracy class 1.0, having parameters Voltage, Current, Frequency, Power factor, Power & Energy complete all as specified, duly prewired with suitable size of copper insulated FRLS wire with universal code including suitable CTs complete (c) Indicator with LED lamps for RYB , 3 Phase with MCBs set of three -01 set (iii) OUTGOING:- (a) MCCB 125 Amp, 415 V, 16 KA, 4 pole with thermal magnetic release ICS=ICU=100%-06 Nos. (b) Indicator with LED lamps for RYB , 3 Phase with MCBs set of three -06 sets Note for Srl item No. 51.00 to 54.00 : Danger notice plate and FRONT and REAR marking should be marked on panels.
Material and labour for boring hole under the road/ pavement/ hardstanding and inserting HDPE pipe of 100mm at a depth not less than one metre below ground level complete all as specified and directed. Note : The quoted rate includes cost of HDPE pipe 100 pipe min.
Material and labour for processing unit system complete with cabinet having Intel Xeon processor i5, 10th Gen, 16 GB RAM, 1 TB HDD 7200 RPM, 10/100/1000 Gigabit LAN, 2 GB Graphic Card port & card, DVD-RW, Windows 10 Pro complete with other suitable compatible accessories and Laser Jet printer for functioning of supervisory control and Data Acquisition all as specified and directed
Supply, installation and testing of solar module of minimum 330 Wp, photo voltaic poly crystalline silicon, minimum 72 Nos of solar cells per module, max power voltage (Vmp) 37.13V, max power current (Imp) 8.89A, open circuit voltage (Voc) 45.95V, short circuit current (Isc) 9.57A, max system voltage 1500V DC, all values at STC 250C, 1000W/Sq Mtr, AM 1.5, dimensions 1960 x 990mm or as approved by Engineer-in-Charge. Make of solar Module : Waaree, IP 67 rated, approx weight of each module not less than 22.50 Kgs, approval as per IEC61215-ED2 & IEC 61730-1 & 2, safety class II, having RFID tag inside the module laminate and BIS marking complete all as specified and directed. Note : Solar modules and solar cells shall meet to DCR (Domestic Content Requirements), made in INDIA. Module shall carry a performance warrangy of more than 90% during the first 10 years and more then 80% during the consecutive 15 years. Module shall have performance warranty of more than 97.5% during 1st year. The necessary data sheet and test certificate required by Deptt shall be provided within overall cost. The PV module shall perform satisfactorily in humidity upto 100% with temperature between -50C to +550C. Since the modules would be used in a high voltage circuit, the high voltage insulation test shall be carried out on each module and a test certificate to that effect needs to be provided
Supply, laying, testing, jointing of annealed tinned copper conductor cable 1.8 KV DC EBXL Halogen free XLPO/ XLPO 1200C ZH-FRLS single core 4 sqmm solar sheathed industrial cable of 1100 volts grade conforming to IS solar cable, UV Resistive, Operating Temp (-5 to 550C) designed for low losses, certified under TUV confined to latest IEC standards) complete all as specified and directed
Supply, laying, testing, jointing of annealed tinned copper conductor cable 1.8 KV DC EBXL Halogen free XLPO/ XLPO 1200C ZH-FRLS single core 6 sqmm solar sheathed industrial cable of 1100 volts grade conforming to IS solar cable, UV Resistive, Operating Temp (-5 to 550C) designed for low losses, certified under TUV confined to latest IEC standards) complete all as specified and directed
Supply and fixing MC4 connector to connect 4 Sqmm solar cable complete all as specified and directed
Supply and fixing MC4 connector 2 in 1 to connect 6 Sqmm solar cable complete all as specified and directed
Supply and fixing 125mm size MS butt hinges heavy weight cold rolled and fixed properly on MS sheet of thickness 2 to 3.15mm after dismantling old one from panel and fixing panel door on other side complete with welding/ brazing and spray painting to match existing surface.
Material and labour for mild steel sliding door bolts 300mm long stove enameled black, with bright bolt not less than 12mm dia with and including a minimum of 6 bolts and nuts, four on bolt plate and two on staple plate and fixed complete to LT panel door with welding or suitable means all as specified and directed.
Material and labour for transformer differential protection multi function relay RET615E_D or higher model of ABB having suitable BI channels 6U, BI, BO, RTD, mA, and MODBUS, IEC 61850 comm protocol on RS 485 serial port & 1 No rear RJ 45 ethernet port, (lo1/5A) required at site suitable for Uaux=48-250V DC/ 100-240V AC, 50 Hz complete with necessary programming all as specified and directed.
Bains Enterprises
CHOUDHARY AND SONS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .