Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹52.5 LAdmitted-Finance | L1 | Admitted-Finance | ||
| 2 | L2₹58.8 L+₹6.3 L (12.0%)Admitted-Finance 01 AMLAL PADIYAL TEHSIL KUKSHI DIST DHAR M P 454331 | KUKSHI | DHAR | MADHYA PRADESH | 454331 | L2 | Admitted-Finance | ||
| 3 | L3₹59.4 L+₹6.9 L (13.1%)Admitted-Finance | L3 | Admitted-Finance | ||
| 4 | L4₹60.3 L+₹7.7 L (14.7%)Admitted-Finance | L4 | Admitted-Finance | ||
| 5 | L5₹60.4 L+₹7.9 L (15.0%)Admitted-Finance | L5 | Admitted-Finance |
Tender Value
₹75.4 L
EMD Value
₹37,715
Closing Date
28 Sept 2026, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
EE PHED DIVISION NATHDWARA
EE PHED DIVISION NATHDWARA
NIT 30
2026_PHCJA_599483_1
EE NATHDWARA NIT 30-69/2026-27
Open Tender
Civil Works - Water Works
Percentage
NATHDWARA
Please refer Tender documents.
5 documents required · 5 mandatory
₹2,000
EE PHED DIVISION NATHDWARA
₹37,715
28 Oct 2026
24 Sept 2026
29 Sept 2026
24 Sept 2026
28 Sept 2026
24 Sept 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Construction and commissioning of RCC INTZE type Over Head Service Reservoir of following capacity and staging as per the Scope of work and Technical specifications, consisting of the following main activities: - | - | - | - | - |
| 2 | a) Topographic survey, preparation of site contour plan, conducting SBC test and its approval from department before construction. Submission and approval of concrete mix design and water quality test report for water to be used in construction.
b) Excavation in all types of soil, PCC below foundation, all RCC Work, Plinth protection all around the structure including all material, labour, shuttering, scaffolding etc.
c) OHSR shall be provided with adequate plinth protection all around the structure in a width starting from edge of structure at GL and extending at least up to 1.0m beyond the edge of outer most projection of OHSR. The plinth protection shall consist of 150mm thick PCC in M-15 grade concrete laid over 150mm thick layer of compacted soil.
d) Providing and applying two coats of food grade epoxy paint on the inside surface on the top dome, edge beam and 600 mm height of the vertical wall.
e) Conducting successfully hydro test and water tightness test as per I.S. code.
f) Providing and applying three coats of anti-carbonation paint on the top surface of the Top Dome.
g) Providing and applying three coats of cement-based paint on the external surface of the container, balcony, cone wall, columns & beams etc..
h) Providing and fixing SS-304 ventilator, SS 304 manhole frame and cover and SS-304 ladder from top dome/Slab to bottom dome/Slab inside container.
i) Providing and fixing of MS section ladder from the last landing to balcony having railing all around it and MS ladder with safety cage from balcony to top dome/slab.
j) Providing and fixing water level indicator (float type). | - | - | - | - |
| 3 | k) Providing and fixing of hand railing all around the balcony, top dome and staircase consisting of 25mm diameter Class-B GI pipe in two rows and 1000 mm high, 50X50X6mm angle iron vertical post at a maximum spacing of 1500mm centres.
l) All MS parts to be painted with two coats of the enamel paint over the primer coat of red oxide.
m) Providing and fixing of 150mm wide PVC water bar for the construction joints in the container (vertical wall & cone wall).
n) Providing one Aluminium portable ladder of appropriate length to access first landing (3.5 to 4.5m above GL) from ground.
o) Lighting arrestor consisting of providing and fixing of 2 Nos. of chemical earthing and connecting it to the conical cover of SS ventilator with two separate GI strips of 50mmX3mm.
p) CI/DI puddle collar shall be fixed in the bottom dome/ slab for connecting inlet, outlet, overflow and washout pipe of the reservoir.
q) Painting the name of the scheme and other details on the reservoir, and any other work related to structure as per the directions of Engineer-in- Charge, Technical Specification and Scope of Work.
r) Inlet, outlet, overflow, washout pipes and valves are not included in this work, provision for the same shall be taken separately. | - | - | - | - |
| 4 | Rates for RCC OHSR,SBC 10 T/sqm, SEISMIC ZONE-II & STAGING 18 M | - | - | - | - |
| 5 | 100 KL capacity | 1,00,000 | Per Ltr | 27.53 | ₹27,53,000 |
| 6 | Providing, lowering, aligning, fixing in position in pipe line, CI D/F Sluice valves straight and pocket less body passage of approved make of following Pressure rating & dia complete, confirming to IS:14846 (amended up to date) and of following specifications: Body, Bonnet, Wedge, Gland, Thrust Plate, Cap & Hand wheel of Grey cast iron of IS:210/ FG200 Stem - AISI- 410 ,Body Seat ring, Wedge facing ring & Bushes - LTB2/ SS , Face to face dimensions as per IS 14846/2000 (amended up to date) ,Epoxy ( Non-Toxic- suitable for drinking water) applied inside and outside, Flanges Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367/ CS/ galvanised steel Insertion rubber of black EPDM 6mm thick . Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer-in-charge.
Note: Rates are exclusive of tail piece/ dismantling joints and earth work. | - | - | - | - |
| 7 | Manually Operated CI Sluice valve of Class PN-1.0 | - | - | - | - |
| 8 | 100 mm | 6 | Each | 8,649 | ₹51,894 |
| 9 | Supply & Installation of 3 phase ISI marked submersible motor pump set of three star or better rating of BEE and as per IS: 8034-2018 (pump) and IS 9283-2013 (motor) or as amended up to date of approved make of following duty condition with required accessories including making connection suitable for tube well/DCB. The job includes lowering of motor pump, installation of complete fitting & accessories, jointing of electrical cables up to switch board, testing of submersible pump set and interconnection up to water mains, complete in all respect. | - | - | - | - |
| 10 | 7.5 KW (10 HP) & head above 120 mtr. | 15 | KW | 8,320 | ₹1,24,800 |
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.26 MB
Tendernotice_2.pdf
PDF • 0.11 MB
BOQ_1062520.xls
BOQ • 0.27 MB
TD30.pdf
Tender Documents • 29.43 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .