| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹7.0 CrAccepted-AOC | ₹7.0 Cr | 1 | Accepted-AOC Being lowest and overall reasonable bid. |
| 2 | 2₹9.0 Cr+₹1.9 Cr (27.2%)Rejected-Finance | ₹9.0 Cr+₹1.9 Cr (27.2%) | 2 | Rejected-Finance Being other than lowest bidder. |
| 3 | 3₹9.0 Cr+₹2.0 Cr (28.5%)Rejected-Finance | ₹9.0 Cr+₹2.0 Cr (28.5%) | 3 | Rejected-Finance Being other than lowest bidder. |
| 4 | 4₹9.1 Cr+₹2.0 Cr (28.9%)Rejected-Finance VARAD PLOT NO 11 DURGA NAGAR KAMATHWADE NASIK 422010 | NASHIK | MAHARASHTRA | 422010 | ₹9.1 Cr+₹2.0 Cr (28.9%) | 4 | Rejected-Finance Being other than lowest bidder. |
| 5 | 5₹10.5 Cr+₹3.5 Cr (49.2%)Rejected-Finance 21 GURUKRIPA PATIL LAYOUT GOPLA NAGAR NAGPUR 440022 | NAGPUR | NAGPUR | MAHARASHTRA | 440022 | ₹10.5 Cr+₹3.5 Cr (49.2%) | 5 | Rejected-Finance Being other than lowest bidder. |
Tender Value
Refer Docs
EMD Value
₹6.5 L
Closing Date
29 Mar 2021, 6:00 pmClosed
Chief Engieer
HQ CE (AF) NAGPUR, VUSENA NAGAR, NAGPUR-440007
WORK SERVICES FOR SETTING UP OF FUNCTIONAL TESTING LABORATORY (FTL) AT AF STATION OJHAR
2020_MES_400099_2
CE_AF_NGP_800127
Open Tender
Civil Works
Lump-sum
540 days
OJHER
For MES Enlisted Contractors- Class A Category a (i) For other contractor meeting enlistment Criteria or MES for Class A Category a (i).
8 documents required · 8 mandatory
₹3,000
GE (AF) OJHAR
₹6.5 L
21 Jun 2021
3 Mar 2021
31 Mar 2021
3 Mar 2021
29 Mar 2021
15 Mar 2021
Amount
SCH 'A' PART XII (MISC B/R & E/M ITEMS) Note:- Excavation and earthwork to the extent required for execution of relevant item under this schedule unless otherwise specified shall be measured and paid under relevant items of Schedule 'A' Part-II.
INTERNAL ELECTRICFICATION
Supply and fixing of sheet metal enclosur for DBs when MCBs to be used single pole and neutral with acrylic double door IP 43 protection, 240 volt with 200 amps rated bus bar bar 4 way complete all as specified & as directed.
Supply and fixing of sheet metal enclosure for DBs when MCBs to be used single pole and neutral with acrylic double door IP 43 protection, 240 volt with 200 amps rated bus bar bar 8 way complete all as specified and as directed.
Supply and fixing sheet metal enclouser for distribution board 415volt,Vertical TPN 4 Way with provision for MCCB TP as incomer & MCBs as out going as per IS including compact insulated bus bar and rounded neutral bar, door earthing complete double door (acrylic door) surface/reccess mounting IP-43 protection, , including connection with the existing sub circutis, electric meter etc with proper size new copper cable, lugs,connectors etc complete all as specified and as directed.
Material & labour for point wiring with 1.5 Sqmm (nominal area) PVC (FRLS) insulated unsheathed copper stranded conductor cable run in and including concealed in wall/ceiling/floor PVC conduit medium grade not less than 20 mm as per IS with all fittings such as bends, tee, junction boxes, etc. of suitable size including 1.5 Sqmm PVC(FRLS) insulated unsheathhed copper earth continuity conductor connected to common earth dolly and including MS/GI sunken boxes with modular inner & surface plate suitable for housing modular switches, sockets, fan regulators etc. for one light/fan/call bell point controlled by one 1- way switch complete all as specified and as directed. Note: Cutting and making good of chasis in wall, roof/floor shall be deemed to be included in the quoted rate.
All as per Serial Item No 12.004 here-in-above but for one 3 pin 5 Amps socket outlet on independent board complete all as specified and as directed.
Material & labour for point wiring with 2.5 Sqmm (nominal area) PVC (FRLS) insulated unsheathed copper stranded conductor cable run in and including concealed PVC conduit medium grade with all fittings such as bends, tee, junction boxes, etc. of suitable size including 2.5 Sqmm PVC(FRLS) insulated copper earth continuity conductor connected to common earth dolly and including sunken box with modular inner & surface plate suitable for housing modular switches, sockets, fan regulators, etc. complete all as specified and as directed Note: Cutting and making good of chasis in wall, roof/floor shall be deemed to be included in the quoted rate.
Supply and fixing MCCB thermal magnatic three pole 415 Volts, 50 HZ, 25 KA 63Amps with adjustable DPX complete all as specified and as directed.
Supply & Fixing MCB SP 6 to 32 Amps 240 volts 10 KA C series complete all as specified and as directed.
Supplying and fixing MCB SPN 6 to 32 Amps 240 volts complete all as specified and as directed.
Supplying and fixing MCB SPN 40 to 63 Amps 240 volts 10 KA complete all as specified and as directed.
Supplying and fixing MCB TP 40 to 63 Amps 240 volts 10 KA complete all as specified and as directed.
Supply & fixing modular socket 16 amps, 6 pin multipin, 2 Module complete all as specified and as directed.
Supply & fixing ceiling rose 3 phase /PVC /Polycarbonate, isolated body complete all as specified and as directed.
Material & labour for wiring for circuit/ sub main wiring alongwith earth wire with 2x2.5 Sqmm+1x2.5 Sqmm earth wire of PVC (FRLS) insulated unshhheathhed copper conductor, single core, 1100 v grade cable in concealed/surface as required in and including steel conduit 20mm bore complete all as specified and as directed.
Material & labour for wiring for circuit/ sub main wiring alongwith earth wire with 2x4Sqmm+1x4 Sqmm earth wire of PVC (FRLS) insulated unsheathed copper conductor, single core, 1100 v grade cable in concealed/surface as required in and including steel conduit 20mm bore complete all as specified and as directed.
Material & labour for wiring for circuit/ sub main wiring alongwith earth wire with 2x6Sqmm+1x6 Sqmm earth wire of PVC (FRLS) insulated unsheathed copper conductor, single core, 1100 v grade cable in concealed/surface as required in and including steel conduit 20mm bore complete all as specified and as directed.
Material & labour for wiring for circuit/ sub main wiring on wall/surface/concealed as required wiring on ceiling / roof complete with 4x10Sqmm + 2x10 Sqmm earth wire PVC (FRLS) 1100 volt grade with necessary fixing arrangement using approved colour coding as per IS, but unsheathed FRLS cable of specifed size multi stranded copper conductor 1100 volt grade IS-694 marked drawn through ISI marked, ERW stove enameled steel conduit of suitable size not less than 32mm with all MS conduit / accessories / fittings as per relevant IS all and making good to disturbed surfaces, complete all as specified and as directed by engineer-in-charge.
Note for item No. 12.014 to 12.017 above:- The quoted rate shall deemed to be include the rate for conduit and accessories.
Supply & fixing of wall mounted fan operated on 230V AC single phase electric supply with oscillating mechanism and built in speed control regulator, complete with 3 core stranded copper conductor of size 0.5 sqmm for minimum 2 mtr long with 2 pin 5 Amp moulded top size of sweep 450 mm complete all as specified and as directed.
Supply & fixing of flame proof weather proof wall mounted fan 12" sweep 1440 RPM operated on 230V single phase electric supply with oscillating mechanism and built in speed control regulator, complete with 3 core stranded copper conductor of size 0.5 sqmm for minimum 2 mtr long in cast aluminium LM-6 complete all as specified and as directed.
Supply & fixing of exhaust fan 450 mm sweep with louvers, operated on 230/240V AC single phase electric supply 900 RPM complete duly grouted bolts in the wall fixed with nuts, bolts and washers including making suitable size hole in the existing wall, plastering, white washing or colour washing to the disturbed surface of wall complete matching with the existing including connecting with 3 core stranded copper conductor cable cord of size 0.5 sqmm from ceiling rose to fan connector complete all as specified and as directed.
Supply and fixing of surface/pendent mounting LED light fitting decorative ultra slim linear LED lighting fixture with extruded AIuminium, heat sink, environmental friendly, energy efficient ready to use pack 18W LED 60000K complete with tube & duly pre-wired and connecting up with 0.5 Sqmm 2 core flexible Copper cable cord from fitting to ceiling rose complete all as specified and as directed.
Supply and fixing of surface/pendent mounting LED light fitting decorative ultra slim square profile liner LED lighting fixture with extruded polycarbonate, environmental friendly, energy efficient ready to use pack 9W LED 6000K complete with tube & duly pre-wired and connecting up with 0.5 Sqmm 2 core flexible copper cable cord from fitting to ceiling rose complete all as specified and as directed.
Supply and fixing of 34W LED 6000K Ultra modern recess mounting luminaries suitable for armstrong/grid/POP ceiling complete with separate electronic driver & high brightness SMD LEDs, complete with connecting accessories & driver duly pre-wired and connecting up with 0.5 Sqmm 2 core flexible copper cable cord from fitting complete all as specified and as directed.
Supply and fixing of suspended architectural LED 40W luminaries with soft - light and glare free symmetrical illumination continuous mounting end cap with double stiff pendants, comprising of galvanised steel or chromium plated brass bell mouth connectors 2 Nos with back plate and 2 x 1.5 meter long parallel 20mm dia galvanised or stove enameled screwed steel conduit with two check nuts for fixing tube light fitting and up to 1.5 meter long twin core 0.5 sqmm copper conductor flexible wire / cable for hanging tube light complete all as specified and as directed.
Supply and fixing of air curtain extra high velocity suitable for six feet long opening, electrically operated, single phase, 220 volts, 50 HZ maximum velocity, 15 to 16 MPS efficient air throw 3 metres, with powder coated body complete all as specified and as directed.
Material and labour for point wiring concealed with PVC insulated unsheathed stranded copper conductor 1.5 Sqmm FRHR cable single core, 1100 volts grade in and including ERW rigid steel stove enameled conduit 19/20 mm dia alongwith all frame proof & weather proof accessories such as multiple junction boxes, covers, elbow, bends, tees etc. including 1.5 sqmm FRHR PVC insulated unsheathed stranded copper conductor (fire guard) cable for earth continuity and connecting up complete all as specified and as directed .
Material and labour for point wiring concealed with PVC insulated unsheathed stranded copper conductor 2.5 sqmm FRHR cable single core, 1100 Volts grade in and including ERW rigid steel stove enameled conduit 19/20 mm dia alongwith all flame proof & weather proof accessories such as multiple junction boxes, covers, elbows, bends, tees etc. including 2.5 sqmm FRHR PVC insulated unsheathed stranded copper conductor (fire guard) cable for earth continuity and connecting up complete all as specified and as directed.
Supply and fixing of flame proof LED fitting 2x20 Watt, body made out of cast aluminium alloy, epoxy painted alongwith wire guard complete with all accessories such as flame proof clear glass tubing to house LED tube, LED tube light 2 x 20 watt including suspended on ceiling with 2 Nos dia ERW conduit of suitable length including fixing arrangement and connecting up, confirming to IS-60079 and approved by CMRI complete all as specified and as directed.
Supply and fixing of flame proof switch of cast iron body, SP 16 Amp, 230 Volts, AC, LM-6 (Rotary type) certified by CMRI complete all as specified and as directed.
Supply and fixing of flame proof socket and plug 3 pin 16 Amps 250 Volt 2P + Earth combined in LM6 complete all as specified and as directed.
Supply, installation, testing & commissioning of 315A, 1000V, 50Hz, 25KA3P+N-100%+PE Air Insulated type copper bus bar trunking system as per IEC60439-1/2, outer casing made from two “omega -shaped”, ribbed, sealed section cases made of hot- galvanized steel (Senzimir), having degree of protection IP55, bus bar conductor having a rectangular cross – section with rounded corner, conductors made from a copper conductor swith purity not less than 99.9 %( electrolytic copper), conductors spaced with plastic insulators reinforced with 20% glass fibre, having a V1 self-extinguishing degree (as per UL94) and in compliance with the incandescent wire test as per EN 60695-2-1(CEI50.11) complete all as specified and as directed.
NOTE :- The electrical insulation between the conductors and the casing sall be ensured by air distances maintained by the insulators, an electrical junction “monobloc” system for fast and reliable connection of the live conductors and PE. The “monobloc” shall be made from a system of copper plates which make up the live conductor series. The “mono bloc” shall have as hear head bolt, use a 13mm-wrench to tighten the external head until the collar which connects the two heads breaks; this shall ensure the correct nominal torque to guarantee optimum electrical continuity overtime. The protective conductor (PE=casing) shall also be connected through the monobloc. (75 x196 mm)
(a) Straight lengths with opening at every1 Mtr (Including Joint cover and Plug in opening cover)- 65 Mtr (b) Suspension Brackets for Horizontal Installation at every 1 Mtr Interval - 65 Nos. (c) Horizontal Elbow - 06 Nos (d) Vertical Elbow - 02 Nos (e) End feed unit for Direct Cable Termination - 02 Nos (f) End Cover - 02 Nos (g) 32A 4P Empty tap off Box for MCB Provision (Plastic Enclosure)+32A 4PMCB C Curve 10KA - 10 Nos (h) 63A 4P Empty tap off Box for MCB Provision (Plastic Enclosure)+63A 4PMCB C Curve 10KA - 15 Nos (j) 125A 4P Empty tap off Box for MCCB Provision ( Metallic Enclosure)+125A 4P 25KA MCCB - 03 Nos (k) 160A 4P Empty tap off Box for MCCB Provision (Metallic Enclosure)+125A 4P 25KA MCCB - 03 Nos
Material & labour for earthing with galvanised steel earth plate electrode 600x600x6mm thick,buried directly in ground (earth pit not less than 2.25 Mtr deep below ground level ) with top edge of the earth plate not less than 1.5 Mtr below normal ground level,connected to galvanised iron wire 4 mm as earth lead by means of bolts,nuts ,washer and check nut of galvanized steel, protected by and including GI pipe 15 mm bore (light grade) and connected to main switch / MCB DBs box point / LP test point as directed and including cement concrete pit in 1:2:4 type B1 using 12.5mm graded aggregate, with cast iron milled steel frame embedded in the concrete enclosure finished flushed & CI cover 10 mm thick of size (300mmx300mm CI) having locking arrangement hinged to CI frame all as shown under electrical plate no 3 of SSR Pt - I 2009 including painting the external surface of chamber & cover with enamel paint in different colour as directed
and writing earth results & date of test carried out with white paint on black painted background, wiremesh funnel 20 mm bore GI pipe medium grade for watering adequate quantity of charcoal and common salt in alternate layer of 15cm 3ft x 3ft thick all around the electrode including necessary excavation & earth work in any type of soil/strata complete testing on completion complete all as speccified and as directed. NOTES :- (a) Quantity of GI wire/ protection pipe beyond 7.5mtrs length shall be measured and paid separately. (b)Rates quoted are deemed to be included with:- (i) Filling the pit with black cotton soil brought at site from outside of defence land. (ii) Testing on completion & achieving resistance less than 03 ohm & submitting report to Engineer-in-charge duly signed by user in every month after successful completion of earthing during contract period & defect liability period.
Material & Labour for earthing complete with copper earth plate electrode of size 90cmx60cmx5 mm thick ,buried directly vertically in ground earth pit in any kind of soil strata not less than 1.2 mtr x 1.2 mtr x 4.0 mtr deep with normal ground level and with top edge of electrode not less than 1.25 Mtr below ground level,connected with copper earth strip of size 50x6 mm as earthing lead by means of brazing & bolts, nuts ,washer and check nut of tinned brass, and connected with and including test point of phosphor/ bronze/gunmetal/copper all as directed at site and including cement concrete pit in 1:2:4 type B1 using 12.5mm graded aggregate with cast iron / mild steel frame embedded in the concrete enclosure finished flushed with CI cover 10 mm thick hinged to CI frame all as shown under electrical plate No 3 of SSR Pt - I 2009 including painting the external surface of chamber & cover with enamel paint in different colour as per prevailing colour coding system as directed and writing earth results & date of test carried out with white paint on black painted background,
wiremesh funnel, charcoal and salt in alternative layers of 15cm thick all around the electrode all around the electrode (the charcoal & salt shall be provided 35 cm below & above the edge of plate,15 cm thick at both side of from vertical edge of 60 cm size plate & 50 cm at both side of face of face of plate i.e 90cm × 60cm face of plate, upto top edge of the plate) and chemical treatment of pits by filling with magnesium sulphate compound minimum 2 inch layer all over the surface as directed, 80 mm bore light grade earth lead protection pipe, 25 mm bore GI pipe medium grade watering pipe of 2.5 meter lenghth duly notched to engage in plate, all as specified including necessary excavation and earth work in any type of soil/ strata including testing on completion complete all as specified and as directed. NOTES :- (a) Quantity of copper strip/ protection pipe beyond 7.5mtrs length shall be measured and paid separately. (b) The Excavated material shall be taken out of the site not more than 1.5 Km away where directed & the cost of the above shall be deemed to be included in the unit rate. The balance earth pit (after filling salt, charcoal, chemical etc) shall be filled up with black cotton soil brought at site & rates shall be deemed to be included under quoted rate of earthing. (c) Rate Quoted are deemed to be included with:-
(i) Filling the pit with black cotton soil brought at site. (ii) Earth pit made up of MS board 1×0.5 feet duly painted synthetic enamel paint over coat of red oxide primer with required colour code to be fixed closed to earth pit all as directed. (iii) Externally damaged earth pit covers & chamber to be replaced with duly chamber & chamber cover painted as per prevailing colour code scheme. (iv) Testing on completion & achieving resistance less than 01 ohm & submitting report to Engineer-in-charge duly signed by user in every month after successful completion of earthing during contract period & defect liability period complete all as specified and directed. (v) If resistance value is more than 01 ohm, Contractor shall redo or rectify the earthing within 07 days without any extra cost.
External Electrification
Supply, installation, testing & commissioning of floor mounted transformer copper wound of capacity 1000 KVA, step down, indoor type, 50 Hz AC, oil immersed, naturally air cooled having no load voltage ratio 11 KV/433 V complete with standard fitting, HT 11 KV/433 V, corresponding to principal tapping double copper wound delta connected primary side(HV) side & star connected on secondary side(LV ) side in accordance with vector symbol DYN11(vector group-4) with neutral & having tapping on HV side for constant output so as to alter/vary secondary voltage in steps of ±2.5% to 7.5 % by means of manual off load tap changing arrangement, the limit of temperature rise after continuous full load run as measured by oil thermometer shall not exceed 50°C over maximum ambient temperature prevailing at site as per IS : 1180 ammended upto date, complete including provision of following fitting and accessories complete all as specified and as directed.
(a) Oil conservator with filling hole and cap drain plug & shut valve between conservator & main tank (b) Silica gel breather with oil seal & first fill of dehydrating agent (c) Explosion vent with diaphragm & air release plug (d) Oil temperature indicator (gauge) having range 0-120 Deg C with max reading pointer 100 mm dia (e) Drain cum bottom filter valve (f) Top filter valve (g) Prismatic oil level gauge (h) Inspection cover (i) Cover lifting lugs (j) Jacking & lifting lugs (k) Bi- directional plain rollers (l) Rating & diaphram plate (m) Separate neutral bushing brought out for earthing LV side (n) One cable box on HV side(11 KV side) including material for XLPE cable upto 120 sq mm cable 3 core excluding cable joint kit (o) One cable box on LV side(433 V side) including material for XLPE cable upto 400 sq mm cable 3.5 core excluding cable joint kit (p) Earthing Terminal - 02 Nos (r) First filling of transformer oil confirming to IS -335 (s) Buchholz relay (t) Oil & winding temprature indicator & relay (u) Protection relay for internal parameters, pressure, temperature, oil level & gas detection
Supply, installation, testing and commissioning Vacuum Circuit breaker duly painted as per nine tank process 11 KV, AC, 50 Hz, 3 phase 630 Amp 350 MVA, rated breaking capacity 18.30 KA for 3 seconds with spring charging motor for 230 V AC, tripping coil & closing coil of 30V DC, Horizontal draw out & Horizontal isolation type vacuum circuit breaker, indoor type totally enclosed, floor mounting type with automatic safety shutters with IP4x degree protection with expendable copper bus bar duly colour coded having incomer & outgoing connection to existing VCB, VCB factory made designed and tested as per latest IS 13118 & IS 3427 including name plate highlighting each equipment on front & rear side with effective earth facility for cable as well as bus bar side with 230V AC, motorising in addition to manual hand operated mechanism and power pack 230V AC/30V DC in sub station to match existing site condition and other make of Equipment, CPRI approved, interlocking & interchangeability (Use as incomer) including the following complete all as specified and as directed.
(a) Cable rear box suitable for 3 core 95 to 185 sq mm HT XLPE cable (b) Current transformers per IS 2705, Burden 10 VA, CT ratio as per transformer rating, class of accuracy for core 1-1.0 (for panel metering) for core 2 -5P10 (for protection) (c) Potential transformer as per IS 3156 11KV/V3/110/V3V,CL1.0,50VA (d) Analog Ammeter+ASS 96mm×96 mm,Analog Voltmeter+VSS 96mm× 96 mm,Digital functional meter (e) Spare Heater with thermostat & door lamp illumination with necessary rating armoured cable from LT PCC bus,suitably rated & approximately located fuse/MCB for the same (f) Numerical /static relay for protection against Overload, Earth fault, Short circuit (g) Electromechanical type master trip & lockout relay (h) Emergency Push button (j) Panel Equipped with following indication by means of LED lamp (i) Spring Charged (ii) RYB phased healthy (3 LED Lamp) (iii) Breaker off (iv) Auto trip indication (v) Trip circuit healthy indication NOTES :- (i) Equipment shall be manufactured by original Equipment manufacturer(OEM) & not by system house (ii) The equipment shall be tested at manufacturer premises before transportation at site
Boring hole under the existing road, pavement, hard standing by trenchless technology using ultra sound technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 MPa working pressure, minimum 0.6 mtr below the existing top surface GL complete all as specified and as directed.
Material & Labour for earthing with galvanised steel earth plate electrode 600x600x6mm thick, buried directly in ground (earth pit not less than 2.25 Mtr deep below ground level) with top edge of the plate not less than 1.5 Mtr below normal ground level, connected to galvanised iron strip 32x6 mm as earth lead by means of bolts, nuts, washers and check nuts of galvanized steel, protected by and including GI pipe 50 mm bore (light grade) and connected to main switch / MCB DBs box point / LP test point as directed and including cement concrete pit in PCC 1:3:6 type C1 using 12.5mm graded aggregate, with precast RCC 1:1.5:3 type A1 cover slab of size 54x54x5cm reinforced with 4mm dia TMT bars @ 150mm C/C both ways with one handle for lifting made out of 8mm dia TMT bar embedded in precast cover slab wiremesh funnel, 20mm bore GI pipe (Medium grade) for watering, charcoal and salt in alternative layers of 15cm thick all around the electrode, including necessary excavation and earth work in any type of soil complete all as shown in electrical plate No. - 3 of SSR Part- I and testing on completion all as specified and as directed.
NOTES :- (a) Quantity of GI strip/ protection pipe beyond 7.5mtrs length shall be measured separately. (b)Rates quoted are deemed to be included with:- (i) Filling the pit with black cotton soil brought at site from outside of defence land. (ii) Testing on completion & achieving resistance less than 03 ohm & submitting report to Engineer-in-charge duly signed by user in every month after successful completion of earthing during contract period & defect liability period.
Supply, install, testing, commissioning main LT panel box, factory fabricated, cubical, indoor type, totally enclosed, dust and vermin proof, with angle iron pedestal frame including steel structure required for installation on cable trench, floor mounted, free standing, front and rear openable bottom cable entry made out of sheet of 2mm thick CRCA sheet IP 54 protected covering, framing with angle iron 50 x 50 x 6mm, duly powder coated over one coat of primer, suitable for working on 440 volts, 3 phase, 50 Hz, 4 wire system internally connected with suitable size copper strips to outgoing feeders and metering system completely pre-wired with suitable size copper cable suitable for housing & including provision of fitments listed herein after all as specified and as directed:-
OUTGOING :- (a) MCCB TPN, 250Amps, 415 volts, 50 Hz with 35 KA - 01 No (pump1) (b) MCCB TPN, 320 Amps, 415 volts, 50 Hz with 35 KA - 02 No (pump 2 and 3) (c) MCCB TPN, 100 Amps, 415 volts, 50 Hz with 35 KA - 01 No (priming pump-2 Nos) (d) MCCB TP, 4 pole 32 Amps, 415 volts - 02 No (crane-2 nos) (e) MCCB TP, 4 pole 63 Amps, 415 volts - 01 No (lift-1 nos) (f) MCCB TP, 4 pole 25 Amps, 415 volts - 02 No (fume extractor and spare-2 nos) (g) Colour coded copper bus bar of suitable capacity, 3 phase, 415 volts for the above feeders mounted on insulators complete - 01 Set
Supply, install, testing, commissioning main LT panel box, factory fabricated, cubical, indoor type, totally enclosed, dust and vermin proof, with angle iron pedestal frame including steel structure required for installation on cable trench, floor mounted, free standing, front and rear openable bottom cable entry made out of sheet of 2mm thick CRCA sheet IP 43 protected covering, framing with angle iron 50 x 50 x 6mm, duly powder coated over one coat of primer, suitable for working on 440 volts, 3 phase, 50 Hz, 4 wire system internally connected with suitable size copper strips to outgoing feeders and metering system completely pre-wired with suitable size copper cable suitable for housing & including provision of fitments listed herein after all as specified and as directed:-
OUTGOING :- (a) ACB 800A, 4 pole- 01 No (b) MCCB TPN, 400 Amps, 415 volts, 50 Hz with 35 KA - 01 No (APFC) (c) MCCB TPN, 320 Amps, 415 volts, 50 Hz with 35 KA - 02 No (SPS and Bldg panel) (d) MCCB TPN, 400 Amps, 415 volts, 50 Hz with 35 KA - 01 No (spare) (e) MCCB TPN, 100 Amps, 415 volts, 50 Hz with 25 KA - 04 No (spare) (f) Colour coded copper bus bar of suitable capacity, 3 phase, 415 volts for the above feeders mounted on insulators complete - 01 Set
Supply, install, testing, commissioning LT APFCR panel board, factory fabricated, cubical, indoor type, totally enclosed, dust and vermin proof, floor mounted, free standing, front and rear openable made out of sheet of 2mm thick IP 54 protected CRCA sheet covering, mounted on channel ISLC-100, framing with angle iron 50 x 50 x 6mm, 60cms height legs duly powder coated over one coat of primer, suitable for working on 415 volts, 3 phase, 4 wire system internally connected with suitable size stranded copper cables to outgoing feeders and metering system completely pre-wired with suitable size copper cable suitable for housing & including the following fitments listed herein after all as specified and as directed:-
Supply, install, testing, commissioning main LT panel box, factory fabricated, cubical, indoor type, totally enclosed, dust and vermin proof, with angle iron pedestal frame including steel structure required for installation on cable trench, floor mounted, free standing, front and rear openable bottom cable entry made out of sheet of 2mm thick CRCA sheet IP 54 protected covering, framing with angle iron 50 x 50 x 6mm, duly powder coated over one coat of primer, suitable for working on 440 volts, 3 phase, 50 Hz, 4 wire system internally connected with suitable size copper strips to outgoing feeders and metering system completely pre-wired with suitable size copper cable suitable for housing & including provision of fitments listed herein after all as specified and as directed:-
OUTGOING :- (a) MCCB TPN, 200 Amps, 415 volts, 50 Hz with 35 KA - 02 No (b) MCCB TPN, 100 Amps, 415 volts, 50 Hz with 25 KA - 02 No (c) MCCB TP, 63 Amps, 415 volts, 50 Hz with 25 KA - 08 No (d) MCB SPN 40-63 Amps, 240 volts, 50 Hz with 10 KA - 03 No (e) MCB TP, 40-63 Amps, 415 volts, 50 Hz with 10 KA - 03 No (f) MCB SPN, 6-32 Amps, 240 volts, 50 Hz with 10 KA - 06 No (g) Colour coded copper bus bar of suitable capacity, 3 phase, 415 volts for the above feeders mounted on insulators complete - 01 Set
Supply, install, testing, commissioning main LT panel box, factory fabricated, cubical, indoor type, totally enclosed, dust and vermin proof, with angle iron pedestal frame including steel structure required for installation on cable trench, floor mounted, free standing, front and rear openable bottom cable entry made out of sheet of 2mm thick CRCA sheet IP 43 protected covering, framing with angle iron 50 x 50 x 6mm, duly powder coated over one coat of primer, suitable for working on 440 volts, 3 phase, 50 Hz, 4 wire system internally connected with suitable size copper strips to outgoing feeders and metering system completely pre-wired with suitable size copper cable suitable for housing & including provision of fitments listed herein after all as specified and as directed:-
OUTGOING :- (a) MCCB TPN, 100 Amps, 415 volts, 50 Hz with 35 KA - 03 No (for 27 volts, 240 volts and 115 volts) (b) MCCB TPN, 160 Amps, 415 volts, 50 Hz with 25 KA - 01 No (for 208 volts) (c) MCCB TPN, 32 Amps, 415 volts, 50 Hz with 25 KA - 01 No (36 volts) (d) Colour coded copper bus bar of suitable capacity, 3 phase, 415 volts for the above feeders mounted on insulators complete - 01 Set
Material and labour for cable joint/root indicator fabricated from 40x6 mm angle iron 450 mm long ,riveted or welded with 100 mm dia CI or MS round disc duly engraved 'HT CABLE JOINT/HT CABLE" in letters including grouted into the ground with PCC casting (1:4:8), type D2 with 40 mm graded ston aggregate minimum size of PCC 20cmx20cmx30 cm deep from ground level complete all as specified and as directed.
Supply, installation, testing and commissioning of integral driver LED street light with a nominal system lumen output of 5760 lm, luminaire having rated system lifetime of 50000 burning hours, should have cool white colour temp (CT>5700K+300K) and CRI>70, luminaire housing made of pressure diecast aluminium epoxy powder coated with whether proof gasket for LEDs and control gear compartments, heat resistance toughened cleared glass fixed with SS screw with IP 65 protection, input voltage 140-310v, PF>0.95, total power consumption not exceeding 70 w (including driver) etc. complete all as specified and as directed.
Supply and fixing street light bracket 40 mm bore GI pipe/tubing light grade 1.5 m long bend to shape with MS flat iron 50x6 mm for clamps, nuts, boltsand washers etc. and applying two coats of aluminium paint over a coat of red oxide primer complete all as specified and as directed.
Material & labour for river sand cushioning / filling completely dry in trenches 8cm below the cable and 15cm above the cable and punning down to a total thickness of sand 18cm, complete all as specified and as directed.
Removal /Dismantling of existing 1.1 KV LT Cable of any size from trench including excavation & removing of PCC cover keep in safe custody for relaying, complete all as specified & as directed.
Lightening Protection
Material and labour for earthing complete with MS galvanised earth plate electrode 600 x 600 x 6mm thick buried directly in ground and preferably vertically in ground level (earth pit not less than 2.25 mtr deep below ground level) with top edge not less than 1.25 mtr below normal ground level, connected to galvanised iron strip 32 x 6 mm as earth lead by means of bolts, nuts, washers and check nuts of galvanised steel, earth strip protected by and including GI pipe 40mm bore (light grade) and connected to main test point as directed and including concrete pit in PCC 1:3:6 type C1 and precast RCC 1:2:4 type B1 cover slab of size 55x55x5 cm reinforced with 4mm dia TMT bars @ 150mm C/C both ways with one handle for lifting, made out of 8mm dia TMT bar embedded in precast cover slab, wiremesh funnel, 20mm bore GI pipe (medium grade) for watering, charcoal and salt in alternative layers of 15cm thick all around the electrode, including necessary excavation and earth work in any type of soil including taking out old unserviceable earth plate, electrode etc. complete all as shown in electrical plate No. - 3 of SSR Part-I and testing on completion all as specified and as directed.
Special Power Supply
Supply, installation, testing & commissioning 40 KW DC POWER SUPPLY suitable for the following complete all as specified and as directed :- • input : 340 to 460v, 47 to 53 hz, 3p4w AC • output : 27V DC • line & load regulation : ±2% or lower • output current : 1481 Amps max • output overload capacity : 110% for 30 minutes and 150% for 10 seconds • galvanic isolation by inbuilt double wound isolation transformer • overall AC to AC efficiency : ≥88% at full load and nominal input voltage • enclosure protection class : minimum IP-21 • ambient temperature : upto 45° C • protections : input over/under voltage, phase fail, output overload, output DC over/under voltage, high speed fuses for semi conductor devices & overheat • front panel indications : mains on, DC , mains abnormal, DC over/under voltage, overload & overheat • front panel LCD display for input voltage, output voltage & output current • cooling: forced air using fractioned HP fans for localised cooling
Notes:- (i) The parameters and specifications given above are minimum requirements. Manufacturers offering better or over and above the specifications mentioned are allowed at no extra cost. (ii) The rectifier technology can be 12 pulse rectifier SCR based fully controlled or any other technology being used by approved manufacturers as per Appendix B to particular specifications.
Supply, installation, testing & commissioning 5 KVA STATIC FREQUENCY CONVERTER suitable for the following complete all as specified and as directed :- • input : 340 to 460 V, 47 to 53 hz, 3p4w AC • output : 36V±1%, 400 HZ ±0.5%, 3P4P AC • rating : 5 kva / 4 kw • output voltage : 36v phase to phase/20.7v phase to neutral • line & load regulation : ±1% phase to neutral • output max current : 64 Amps rms per phase at load PF of unity • output voltage distortion : < 3% for linear load • inverter technique : IGBT based high frequency PWM or any other technique being used by approved manufacturers • output overload capacity : 150% for 10 seconds • transient response for 100% step load : ±8%
• recovery to regulation band : within 100 milli seconds • galvanic isolation : input and output isolated by inbuilt double wound isolation transformer • overall ac to ac efficiency : ≥87% at full load and nominal input voltage • enclosure protection class : minimum IP-21 • ambient temperature : upto 45° C • protections : input over/under voltage, phase fail, output overload, output over/under voltage, DC over/under voltage, high speed fuses for semi conductor devices & overheat • front panel indications : mains on, inverter on, input over/under voltage, phase fail, output over/under voltage & overheat • front panel LCD display for input voltage, output voltage, output current and output frequency • Cooling: forced air using fractioned HP fans for localised cooling
Notes:- (i) The parameters and specifications given above are minimum requirements. Manufacturers offering better or over and above the specifications mentioned are allowed at no extra cost. (ii) The rectifier technology can be 12 pulse rectifier SCR based fully controlled or any other technology being used by approved manufacturers as per Appendix B to particular specifications.
Supply, install, testing & commissioning 25 KVA STATIC FREQUENCY CONVERTER suitable for the following complete all as specified and as directed. • input : 340 to 460v, 47 to 53 hz, 3P4W AC • output : 115V±1%, 400 HZ ±0.5%, 1P2W AC • rating : 25KVA/ 20 KW • output voltage : 115V 1Phase • line & load regulation : ±1% phase to neutral • max output current : 174 amps rms at load pf of unity • output voltage distortion : < 3% for linear load • inverter technique : IGBT based high frequency PWM or any other technique being used by approved manufacturers • output overload capacity : 150% for 10 seconds • transient response for 100% step load : ±8% • recovery to regulation band : within 100 milli seconds • galvanic isolation : input and output isolated by inbuilt double wound isolation transformer
• overall AC to AC efficiency : ≥87% at full load and nominal input voltage • enclosure protection class : minimum IP-21 • ambient temperature : upto 45° C • protections : input over/under voltage, phase fail, output overload, output over/under voltage, DC over/under voltage, high speed fuses for semi conductor devices & overheat • front panel indications : mains on, inverter on, input over/under voltage, phase fail, output over/under voltage & overheat • front panel lcd display for input voltage, output voltage, output current and output frequency • Cooling: forced air using fractioned HP fans for localised cooling
Notes:- (i) The parameters and specifications given above are minimum requirements. Manufacturers offering better or over and above the specifications mentioned are allowed at no extra cost. (ii) The rectifier technology can be 12 pulse rectifier SCR based fully controlled or any other technology being used by approved manufacturers as per Appendix B to particular specifications.
Supply, install, testing & commissioning 75 KVA STATIC FREQUENCY CONVERTER suitable for the following complete all as specified and as directed. • input : 340 to 460 V, 47 to 53 Hz, 3p4w AC • output : 208V±1%, 400 HZ ±0.5%, 3P4W AC • rating : 75 KVA (25 KVA per phase) / 60 KW • output voltage : 208 V phase to phase, 120 V phase to neutral • line & load regulation : ±1% phase to neutral • max output current : 167 amps rms per phase at load PF of unity • output voltage distortion : < 3% for linear load • inverter technique : IGBT based high frequency PWM or any other technique being used by approved manufacturers • output overload capacity : 150% for 10 seconds • transient response for 100% step load : ±8% • recovery to regulation band : within 100 milli seconds • galvanic isolation : input and output isolated by inbuilt double wound isolation transformer
• overall AC to AC efficiency : ≥87% at full load and nominal input voltage • enclosure protection class : IP-21 • ambient temperature : upto 45° C • protections : input over/under voltage, phase fail, output overload, output over/under voltage, DC over/under voltage, high speed fuses for semi conductor devices & overheat • front panel indications : mains on, inverter on, input over/under voltage, phase fail, output over/under voltage & overheat • front panel LCD display for input voltage, output voltage, output current and output frequency • Cooling: forced air using fractioned HP fans for localised cooling
Notes:- (i) The parameters and specifications given above are minimum requirements. Manufacturers offering better or over and above the specifications mentioned are allowed at no extra cost. (ii) The rectifier technology can be 12 pulse rectifier SCR based fully controlled or any other technology being used by approved manufacturers as per Appendix B to particular specifications.
Supply, installation, testing and commissioning of bus bar trunking system suitable for 27 volts DC system with 2200 Amps, sandwich compact copper bus bar - 2 Nos. The enclosure shall be hot galvanised steel complete with the following and all as specified and directed. The bus bar shall be supported on FRP/DMC insulated at opening at every 1 meter. The installation shall comprise straight length with opening at 1 meter and hanger for ceiling / wall insualtion at every 1 meter and including horizontal and veritical elbow as required at site. The installation shall as end feed unit for direct cable termination at bottom and shall have tee connection, end cover, empty tap off box as required including 63A 2 pole empty plug in box transparent cover (2P DC MCB provision), Max cable size 35sqmm) + 63A 2 pole MCB-24 Nos
NOTES :- (a) The conductors shall be made of electrolytic copper with purity not less than 99.9%. (b) BLANK (c) BLANK (d) An electrical junction block for automatically connecting live conductors and the PE shall be provided. (e) The block shall be made of 4 silver-plated copper contacts with independents springs which shall make up the live conductor series. (f) The continuity of the protective Conductor(casing) shall be completed when the screws on the casing are tightened earth joint. (g) A silver-Plated contact, integral with the electrical junction block, sets up and ensures the continuity of the PE conductor. (h) The connection between two straight lengths shall be quick: with only one operation both the electrical and mechanical connections shall be made. (i) An IP55 degree of protection shall be standard with using additional IP protection kits. (j) The whole bus bar shall be “fire retardant” in compliance with standard EN 60332-3
Supply, installation, testing & commissioning of bus bar trunking system suitable for 36V 400Hz system with 160A, sandwich compact copper bus bar-4 Nos. The enclosure shall be hot galvanised steel complete with the following and all as specified and directed. The bus bar shall be supported on FRP/DMC insulated at opening at every 1 meter. The installation shall comprise staight length with opening at 1 meter and hanger for ceiling / wall insulation at every 1 meter and including horizontal and vertical elbow as required at site. The installation shall as end feed unit for direct cable termination at bottom and shall have tee connection, end cover, empty tap off box as required including 6A 4 pole empty plug in box transparent cover (4P MCB provision), Max cable size 10sqmm + 6A 4 pole MCB-24 Nos
NOTES :- (a) The conductors shall be made of electrolytic copper with purity not less than 99.9%. (b) BLANK (c) BLANK (d) An electrical junction block for automatically connecting live conductors and the PE shall be provided. (e) The block shall be made of 4 silver-plated copper contacts with independents springs which shall make up the live conductor series. (f) The continuity of the protective Conductor(casing) shall be completed when the screws on the casing are tightened earth joint. (g) A silver-Plated contact, integral with the electrical junction block, sets up and ensures the continuity of the PE conductor. (h) The connection between two straight lengths shall be quick: with only one operation both the electrical and mechanical connections shall be made. (i) An IP55 degree of protection shall be standard with using additional IP protection kits. (j) The whole bus bar shall be “fire retardant” in compliance with standard EN 60332-3
Supply, installation, testing & commissioning of bus bar trunking system suitable for 115V, AC, 400Hz system with 350 Amps, sandwich compact copper bus bar-2 Nos. The enclosure shall be hot galvanised steel complete with the following and all as specified and directed. The bus bar shall be supported on FRP/DMC insulated at opening at every 1 meter. The installation shall comprise straight length with opening at 1 meter and hanger for ceiling / wall insulation at every 1 meter and including horizontal and vertical elbow as required at site. The installation shall as end feed unit for direct cable termination at bottom and shall have tee connection, end cover, empty tap off box as required including 40A, 2pole empty plug in box transparent cover (2P MCB provision), max cable size 4sqmm + 16A, 2 pole MCB-24 Nos.
NOTES :- (a) The conductors shall be made of electrolytic copper with purity not less than 99.9%. (b) BLANK (c) BLANK (d) An electrical junction block for automatically connecting live conductors and the PE shall be provided. (e) The block shall be made of 4 silver-plated copper contacts with independents springs which shall make up the live conductor series. (f) The continuity of the protective Conductor(casing) shall be completed when the screws on the casing are tightened earth joint. (g) A silver-Plated contact, integral with the electrical junction block, sets up and ensures the continuity of the PE conductor. (h) The connection between two straight lengths shall be quick: with only one operation both the electrical and mechanical connections shall be made. (i) An IP55 degree of protection shall be standard with using additional IP protection kits. (j) The whole bus bar shall be “fire retardant” in compliance with standard EN 60332-3
Supply, installation, testing & commissioning of bus trunking system suitable for 208V, AC, 400Hz system with 400 Amps, sandwich compact copper bus bar-4 Nos. The enclosure shall be hot galvanised steel complete with the following and all as specified and directed. The bus bar shall be supported on FRP/DMC insulated at opening at every 1 meter. The installation shall comprise straight length with opening at 1 meter and hanger for ceiling / wall insulation at every 1 meter and including horizontal and vertical elbow as required at site. The installation shall as end feed unit for direct cable termination at bottom and shall have tee connection, end cover, empty tap off box as required including 16A, 4pole empty plug in box transparent cover (4P MCB provision), max cable size 10sqmm) + 16A, 2 pole MCB-24 Nos
NOTES :- (a) The conductors shall be made of electrolytic copper with purity not less than 99.9%. (b) BLANK (c) BLANK (d) An electrical junction block for automatically connecting live conductors and the PE shall be provided. (e) The block shall be made of 4 silver-plated copper contacts with independents springs which shall make up the live conductor series. (f) The continuity of the protective Conductor(casing) shall be completed when the screws on the casing are tightened earth joint. (g) A silver-Plated contact, integral with the electrical junction block, sets up and ensures the continuity of the PE conductor. (h) The connection between two straight lengths shall be quick: with only one operation both the electrical and mechanical connections shall be made. (i) An IP55 degree of protection shall be standard with using additional IP protection kits. (j) The whole bus bar shall be “fire retardant” in compliance with standard EN 60332-3
Supply & fixing junction box made out of 2mm thick CRCA sheet indoor type consisting of copper busbars/termination/ glands etc. as interface between DC power supply unit and PDUs of suitable rating complete all as specified and as directed.
Supply, laying, testing & commisioning of LT UG cable XLPE sheathed PVC insulated, screened PVC bedded, galvanised steel strip of wire armored electric power cable heavy 4 core 25 Sq mm (suitable for 27V DC) duty with stranded copper conductor 1100 volts grade, laid in trenches / surface of wall / in GI pipe along with pole for connection including brass cable glands, clamps etc including making good damaged surfaces as required from LT panel to frequency convertor of following sizes complete all as specified and as directed.
All as per item No. 12.059 above but of size 4 core 10 Sqmm (suitable for 36 V, 400 Hz) complete all as specified and as directed.
All as per item No. 12.059 above but of size 4 core 16 Sqmm (suitable for 115 V, 400 Hz) complete all as specified and as directed.
All as per item No. 12.059 above but of size 4 core 25 Sqmm (suitable for 208 V, 400 Hz) complete all as specified and as directed.
Supply, laying, testing & commisioning of LT UG cable XLPE sheathed PVC insulated, screened PVC bedded, galvanised steel strip of wire armored electric power cable heavy 2 core 400 Sq mm (suitable for 27V DC) duty with stranded copper conductor 1100 volts grade, laid in trenches / surface of wall / in GI pipe along with pole for connection including brass cable glands, clamps etc including making good damaged surfaces as required from frequency convertor to bus bar trunking of following sizes complete all as specified and as directed.
All as per item No.12.063 above but of size 4 core 50 Sqmm (suitable for 36V 400Hz) complete all as specified and as directed.
All as per item No.12.063 above but of size 2 core 185 Sqmm (suitable for 115V, 400Hz) complete all as specified and as directed.
All as per item No.12.063 above but of size 4 core 95 Sqmm (suitable for 208V, 400Hz) complete all as specified and as directed.
Material and labour for circuit/sub main wiring in surface/recessed complete FR PVC FR 1100V grade insulated unsheathed multi stranded copper conductor cable drawn in and including PVC conduit 40mm dia and conduit accessories insulated unsheathed multistranded copper conductor connected to common earth duly as an earth continuity conductor complete and making good the disturbed surface from bus bar to board complete all specified and directed by Engineer-in-charge of following sizes:- (i)2 run of 16sqmm + 1 run of 16 sqmm(for 27V DC)
All as per item No. 12.067 above but for 4 run of 2.5sqmm + 2 run of 2.5sqmm (suitable for 36V, 400Hz).
All as per item No. 12.067 above but for 2 run of 4 sqmm + 1 run of 4 sqmm (suitable for 115V, 400Hz).
All as per item No. 12.067 above but for 4 run of 4sqmm + 2 run of 4sqmm (suitable for 208V, 400Hz).
Supply and fixing MCCB 4pole, 35KA with microprocessor protection 100 Amp, 415 V with enclosure complete all as specified and as directed.
Supply and fixing MCCB 4pole,25KA with microprocessor protection 32 Amp, 415 V with enclosure complete all as specified and as directed.
Supply and fixing MCCB 4pole,25KA with microprocessor protection 25 Amp, 415 V with enclosure complete all as specified and as directed.
Supply and fixing cable tray 150mm width 18 swg approx 1.20 mm height all as specified and as directed.
Material and labour for sub main wiring with two single core 4 sqmm (nominal area) PVC insulated copper conductor FRLSH / FRLS, multi stranded, unsheathed 1100 volts grade IS-694 marked in PVC conduit including 4 sqmm copper conductor cable FRLSH / FRLS as earth wire, complete all as specified and as directed.
Supply and fixing plug top 15 Amps with cable connection complete all as specified and as directed.
Material & Labour for earthing with galvanised steel earth plate electrode 600x600x6mm thick, burried directly in ground (earth pit not less than 2.25 Mtr deep below ground level ) with top edge of the plate not less than 1.5 Mtr below normal ground level,connected to galvanised iron strip 32x6 mm as earth lead by means of bolts,nuts ,washers and check nuts of galvanized steel, protected by and including GI pipe 50 mm bore (light grade) and connected to main switch / MCB DBs box point / LP test point as directed and including cement concret pit in PCC 1:3:6 type C1, precast RCC (1:1.5:3) type A1 cover slab of size 54 x 54 x 5cm, reinforced with 4mm dia TMT bars embeded in precast cover slab, all as shown under electrical plate no 3 of SSR Part - I 2009 and as directed including painting the external surface of chamber & cover with enamel paint in different colour as directed and writing earth results & date of test carried out with white paint on black painted background, wiremesh funnel 20 mm bore GI pipe medium grade for watering adequate quantity of charcoal and common salt in alternate layer of 15cm 3ft x 3ft thick all around the electrode including necessary excavation & earth work in any type of soil/strata complete testing on completion, complete all as specified & as directed.
NOTES :- (i) Filling the pit with black cotton soil brought at site from outside of defence land. (ii) Quantity of GI strip/ protection pipe beyond 7.5mtrs length will be measured separately. (iii) Testing on completion & achieving resistance less than 03 ohm & submitting report to Engineer-in-charge duly signed by user in every month after successful completion of earthing during contract period & defect liability period.
AIR CONDITIONING
Supply, installation, testing & commissioning hi wall split Air conditioner indoor/out door complete with rotary compressor, electric driven single Phase of capacity of 1.5 TR, BEE Star rating 5, cordless remote control unit and with in built air ioniser and plasma filter for better indoor air quality, duly mounted on MS Brackets & copper tubing for inter connection complete all as specified and as directed.
Supply , installation, testing & commissioning hi wall split air conditioner indoor/out door complete with rotary compressor, electric driven single phase of capacity of 2.0 TR, BEE Star rating 5, cordless remote control unit, duly mounted on MS brackets & copper tubing for inter connection complete all as specified and as directed.
Supply installation, testing and commissioning of Flameproof split type Air conditioner indoor/outdoor complete with rotary/scroll compressor electric driven single phase of capacity 1.5TR duly mounted on MS bracket and copper tubing for inter connection complete all as specified and as directed.
Supply installation, testing and commissioning of Flameproof Air conditioner indoor/outdoor complete with rotary compressor electric driven single phase of capacity 2TR duly mounted on MS bracket and copper tubing for inter connection complete all as specified and as directed.
Supply and fixing voltage stabilizer for automatic operation SP 50 Hz, 220, voltage variation 90 to 300V for 4-6 sec initial delay, 15 Amps of capacity 5KVA complete all as specified and as directed.
Supply and fixing power unit of 3.5 KW capacity for AC complete all as specified and as directed.
PNEUMATIC COMPRESSED AIR
Supply & laying heavy grade class 'C' MS tubing (confirming to IS 1239 :Part I) 50 mm bore in trenches/floor/fixed to wall/ ceiling with suitable MS clamps & fitting fixture, complete with class 'C' fittings such as bends, Elbow, Tees, Reducer Tee, Short pieces, Caps plug union & flanges & rubber gasket joints & adapter to accommodate rubber hoses, nuts & bolts (Confirming to IS 1239 :Part II) etc. duly welded to each other (As per IS :10234 amended up to date) for carrying compressed air supply at pressure 15 Kg per Sq cm quick released coupling of 1/4" female × 1/4" hose for outlet as per requirement, including painting to pipe line with two coats of synthetic enamel paint over one coat of red oxide primer as per colour code as specified in relevant IS, complete all as specified and as directed.
All as per item No 12.084 above but bore dia of pipe 40 mm, complete all as specified & as directed.
All as per item No 12.084 above but bore dia of pipe 25 mm, complete all as specified and as directed
All as per item No 12.084 above but bore dia of pipe 20 mm, complete all as specified and as directed
All as per item No 12.084 above but bore dia of pipe 15 mm, complete all as specified and as directed.
All as per item No 12.084 above but MS pipes- C class confirming to IS: 1239/3589 heavy class including all fittings like couplings, bends, elbows, tees etc. Piping shall be supported with frame structure, necessary hardware’s clevis support i.e. U strap clamps etc. Insulation shall be with two half round sections of PUF (Polyurethane) in density 36±2 kg/m3 conforming to IS: 12436. Sections shall be bonded to the surface of pipe with adhesive fevicol SR 998 and binded with metal binding wire, apply fevicol AC duct Lag coating AF:5590 on insulated surface uniformly and wrap the Glass Cloth tightly with over laping so that no gaps are left and no air pockets are formed. Immediately apply additional coating as a finish layer on the wrap cloth and finally finish with aluminum cladding 28 gauge with necessary hardware fitting for pipe NB 25 mm dia pipe and 25 mm thick insulation, complete all as specified and directed.
All as per item No 12.089 above pipe NB 15 mm dia of pipe with 25mm thick insulation, complete all as specified and directed.
Supply & fixing full way ball valve for gas / air body made out of hot pressed brass and nickle or chrome plated, with steel ball and teflon seal with steel handle with PVC grip manufactured accordance with EN-2900 suitable for 8 Kg per Sq cm working pressure of size 50 mm bore, complete all as specified and as directed.
All as per item No 12.091 above but 40 mm bore complete all as specified and as directed.
All as per item No 12.091 above but 25 mm bore complete all as specified and as directed
All as per item No 12.091 above but 20 mm bore complete all as specified and as directed
All as per item No 12.091 above but 15 mm bore complete all as specified & as directed
All as per item no 12.091 above but 15mm bore duly insulated complete all as specified and directed.
Supply & fixing filter regulator casted in zinc die casting with pressure gauge proportional standard mist lubricator, 40 micron grade of filtration suitable for pressure range of 0.5 to 12 bar ( pressure drop 0.2 bar), standard flow rate 2.6 Cum/min, corrosion resistance classification : 2, consisting of PC glass bowl with metal bowl guard & manual condensate drain, housing for air filter elements etc. suitable for 15 mm bore, complete all as specified and as directed.
Supply, installation, testing and commissioning refrigerated type chiller having capacity of 300 CFM with air regulating valve (hot gas by pass system) and dew point temp. 4˚ C with all standard accessories at working pressure of 12 Kg/Sqcm complete all as specified and as directed.
Supply, installation, testing and commissioning Pre filter of capacity 300 CFM suitable for RTD 300 CFM, complete all as specified and as directed.
Supply, installation, testing and commissioning active carbon filter of capacity 300 CFM suitable for RTD 300 CFM, complete all as specified and as directed.
EOT CRANE
Design, supply, erection, testing & commissioning of electrically operated traverse overhead crane (EOT) transverse crane 01 ton capacity, single girder confirming to relevant IS, limit switches and control panels DSL, rail welded and 'X' ray checking of welding including wiring with multi core copper flexible cable & main switch fuse unit of required capacity alongwith push button station operated from ground, 'fail to safe' type, brakes, track wheels of suitable alloys for crane complete with all accessories & fixture including sub main wiring of suitable size of copper conductor with copper insulated as earth wire drawn in and including MS steel conduit with wire drawn in with accessories from main DB/ panel to crane control panel with VVVF drive, breaking mechanism for all motions, including painted with one coat of red oxide and two coats of epoxy paints, hook height 3.5metre, span of crane 5 to 7 metre with all accessories complete all as specified and as directed.
NOTE : Design, supply & commissioning shall be done by OEM & commissioning report shall be furnished by OEM only and serviceability report shall be submitted quarterly from OEM during defect liability period of 02 years.
Design, supply, erection, testing & commissioning of electrically operated traverse overhead crane (EOT) transverse crane 0.5 ton capacity, single girder confirming to relevant IS, limit switches and control panels, DSL, rail welded and 'X' ray checking of welding including wiring with multi core copper flexible cable & main switch fuse unit of required capacity alongwith push button station operated from ground, 'fail to safe' type, brakes, track wheels of suitable alloys for crane complete with all accessories & fixture including sub main wiring of suitable size of copper conductor with copper insulated as earth wire drawn in and including MS steel conduit with wire drawn in with accessories from main DB/ panel to crane control panel with VVVF drive, breaking mechanism for all motions, including painted with one coat of red oxide and two coats of epoxy paints, hook height 3.5metre, span of crane 7 to 8 meter with all accessories complete all as specified and as directed.
NOTE: Design, supply & commissioning shall be done by OEM & commissioning report shall be furnished by OEM only and serviceability report shall be submitted quarterly from OEM during defect liability period of 02 years.
Supply, installation, testing and commissioning of 1000Kgs freight elevator with AC variable voltage variable frequency automatic centre opening sliding steel doors meeting following requirements complete all as specified and as directed. (a) Type of lift : Freight elevator (b) Load capacity : 1000 Kg (c) Speed : 1 mtr/sec (d) Power : 400Volts, 3 phase, 50Hz (e) Type of control : AC variable voltage variable frequency (f) Machine : Gear (g) Machine Room : Not required, the equipment shall be located above the Hoist way (h) Car inside size: 1300 mm wide x 2400 mm deep
(j) Car door : Centre opening sliding (k) Car enclosure : Stainless steel (l) Terminal Buffers : Special spering buffers (m) Door opening : 1400 mm wide x 2000 mm height (n) Hoist way construction : RCC wall (included in Sch 'A' Part-I) (o) Car and counter weight guide : Guide rails of T-section (p) Clear hoist way size : 3000mm x 3000mm (q) Flooring : Vinyl tiles (r) Combined luminous hall buttons with 16 segment digital hall position indicators at all floors. (s) 16 segment Digital car position indicator in car. (t) One No car operating panel with luminous buttons in car. (u) Car direction indicator in car. (v) Interphone (w) Battery operated alarm bell and emergency light along with suitable rechargeable battery (x) Overload warning feature in car. (y) Automatic rescue device (z) All signal fixtures on stainless steel face plates. (aa) Voice synthesizer (ab) Travel :- 5.2 mtr (ac) Stops & Opening :- 2-2 (ad) Operation :- Simplex full collective with/without attendant. The following shall be provided: (i) ISMB required for fixing of equipment (ii) Hooks required for supporting the loads (iii) complete control wiring (iv) Any other minor civil works/ electric and power wiring required for entire complete of project shall be deemed to be included in the schedule.
Note :- Necessary arrangement shall be provided by the contractor to bring the goods lift to nearest platform in case of main power supply failure. The cost shall be deemed to be included in the unit rate quoted.
FUME EXTRACTOR
Supply ,install, testing ,commissioning ceiling suspended centrifugal blower ,DIDW forward curved ,V belt driven fabricated from heavy duty sheets and plates of capacity 1350 CFM, static pressure 25 mm W.G., reinforced with angle iron for sturdy and smooth performance, dynamically balanced impeller directly mounted on suitable electric motor shaft of 0.5 Hp, 1450 RPM, single phase, 230V, AC/TEFC having IS Quality mark duly mounted on suitable MS stand (cantilever base frame) including making necessary electrical connections complete all as specified and as directed.
Supply, installation, testing & commissioning direct on line starter in sheet -steel enclosure type MF, MK, MU & MB suitable upto 2 Hp motor, AC-3 duty, 230 V, 50 Hz, single phase with suitable relay complete all as specified and as directed.
Supply and fixing in duct fabricated out of PGI sheet 0.63 mm thick of dimension 2.5×1.5 feet ceiling mounted including MS supports, nuts, bolts & washers, anchor fasteners etc. complete all as specified and as directed.
Material and labour for Earthing complete with galvanised steel earth plate electrode 600x600x6.0mm thick and buried directly in ground (earth pit not less than 2.25 meters deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level, connected to galvanised strip 25 x 4 mm as earth lead by means of bolts, nuts, washers and check nuts of galvanised steel, protected by and including GI pipe 40m bore (light grade) and connected to main switch / MCB DBs box point / LP test point as directed and including cement concrete pit in 1:2:4 type B1 using 12.5mm graded aggregates, with cast iron milled steel frame embedded in the concrete enclosure finished flushed & CI cover 10mm thick of size (300mm x 300mm CI) having locking arrangement hinged to CI frame all as shown in electrical plate no 3 of SSR Part-I 2009 and as directed
including painting the external surface of chamber & cover with enamel paint in different colour as directed and writing earth results & date of test carried out with white paint on black painted background, wiremesh funnel 20mm bore GI pipe medium grade for watering adequate quantity of charcoal and comman salt in alternate layer of 15cm 3 ft x 3 ft thick all around the electrode including necessary excavation & earth work in any type of soil complete including testing on completion complete all as specified and as directed. NOTE :- Filling the pit with black cotton soil brought at site shall be deemed to be included in the unit rate quoted.
FIRE DETECTION
Supply, installation, testing & commissioning fire alarm panel with 250 device capacity complete all as specified and as directed.
Supply, installation, testing & commissioning addressable photoelectric smoke detector with base complete all as specified and as directed.
Supply, installation, testing & commissioning addressable manual call point complete all as specified and as directed.
Supply, installation, testing & commissioning control relay for module for hooter complete all as specified and as directed.
Supply, installation, testing & commissioning hooter cum strobe complete all as specified and as directed.
Supply, installation, testing & commissioning isolator module complete all as specified and as directed.
Supply and laying 2 core 1.5 sqmm armored FRLS copper cable for interconnecting devices in concealed PVC conduit of 20mm dia complete all as specified and as directed.
Material & labour for GI tubing light grade with all fitting laid in trenches or fixed to wall or ceiling with clamps or fixed to floor of size 20mm bore complete all as specified and as directed.
Total amount of Schedule 'A' Part XII (MISC B/R & E/M ITEMS) C/o to General Summary on Ser Page No. 129(R)(R)
GENERAL SUMMARY
Lumpsum price worked out by the contractor for “BUILDINGS AND STRUCTURE" as listed in Schedule ‘A” Part I representing above / below the lumpsum price as inserted by MES for Schedule ‘A’ Part I on Srl Page No. 30
Lumpsum price worked out by the contractor for “EXCAVATION, EARTH WORK AND SITE CLEARANCE” as listed in Schedule ‘A' Part II representing above / below the lumpsum price as inserted by MES for Schedule ‘A’ Part II on Srl Page No. 32
Lumpsum price worked out by the contractor for “ROAD / PATH/ HARDSTANDING” as listed in Schedule ‘A' Part III representing above / below the lumpsum price as inserted by MES for Schedule ‘A’ Part III on srl page No. 34
Lumpsum price worked out by the contractor for “INTERNAL WATER SUPPLY” as listed in Schedule ‘A' Part IV representing above / below the lumpsum price as inserted by MES for Schedule ‘A’ Part IV on Srl Page No. 36
Lumpsum price worked out by the contractor for “EXTERNAL SEWAGE DISPOSAL” as listed in Schedule ‘A' Part V representing above / below the lumpsum price as inserted by MES for Schedule ‘A’ Part V on Srl Page No. 39
Lumpsum price worked out by the contractor for “AREA DRAINAGE” as listed in Schedule ‘A' Part VI representing above / below the lumpsum price as inserted by MES for Schedule ‘A’ Part VI on Srl Page No. 41
Lumpsum price worked out by the contractor for “INTERNAL ELECTRIFICATION" as listed in Schedule ‘A' Part VII representing above/below the lumpsum price inserted by MES for Schedule ‘A’ Part VII on Srl Page No. 43
Lumpsum price worked out by the contractor for “EXTERNAL ELECTRIFICATION " as listed in Schedule ‘A' Part VIII representing above/below the lumpsum price as inserted by MES for Schedule ‘A’ Part VIII on Srl Page No. 46
Lumpsum price worked out by the contractor for “EXTERNAL WATER SUPPLY” as listed in Schedule ‘A' Part IX representing above / below the lumpsum price as inserted by MES for Schedule ‘A’ Part IX on Srl Page No. 47
Lumpsum price worked out by the contractor for “LIGHTENING PROTECTION” as listed in Schedule ‘A' Part X representing above / below the lumpsum price as inserted by MES for Schedule ‘A’ Part X on Srl Page No. 49
Lumpsum price worked out by the contractor for “SPECIAL POWER SUPPLY” as listed in Schedule ‘A' Part XI representing above / below the lumpsum price as inserted by MES for Schedule ‘A’ Part XI on Srl Page No. 51
Total amount of SCHEDULE 'A' PART XII (MISC B/R & E/M ITEMS) brought forwarded from Serial Page No. 123(R)(R)
M/s Gujarat Construction Company
KARNI BUILDERS
Samruddhi Construction
Asha Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .