GE DEOLALI
MILITARY ENGINEER SERVICES, ON SLOW ROAD, DEOLALI CAMP, NASHIK MAHARASHTRA PIN 422401
PROVISION OF ROOF TOP SOLAR POWER PLANT AT 116 TA PARA UNDER THE AOR OF GE DEVLALI
2026_MES_750894_1
8169/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE DEOLALI
CLASS D cat b i
10 documents required · 10 mandatory
₹500
GE DEOLALI
₹86,000
Yes
2 Feb 2026
2 Feb 2026
2 Mar 2026
2 Feb 2026
28 Feb 2026
14 Feb 2026
2 Feb 2026 - 9 Feb 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, installation testing and commissioning of solar PV modules of 545Wp of type Mono Perc Half Cut (Mono crystalline) - Minimum 545 Wp each panel Solar Mono Perc144 Cells Module, with module efficiency, 21 % at Standard test conditions with anti reflective coating and anti dust coating confirming to IEC 61215 and IEC 61730 complete including AC DB (with NVR, contactor) & DC DB electrical connection and mounting on GI structure frame all as specified and directed.
Total of 45KW Solar Power Plant @ OR Line 1, 116 TA PARA
Makes: Havells/RenewSys/WAAREE/ Equivalent ALLM | 45 | Per KW | - | - |
| 1.02 | Supply, installation, testing and commissioning of 50KW, 100KW of Grid Tied String Inverter: 415V AC, 50Hz, 50 KW or 100KW respectively at given load condition) IP 65 out door wall mountaing, with efficiency not less than 97% confirming to IEC 600682-2/vde standards with multifunctional LED indications with alarm and complying the following:-
(1) Operating frequency/ range- 50 Hz (49 to 51 Hz), Grid Frequency Synchronization range ± 1 Hz or more (shall also compatible for Synchronization with DG Set) Waveform- Sine Wave
Harmonics AC side total.
(2) Ripple DC voltage ripple content shall not be more than1%
(3) Harmonic current distortion(<3%)
(4) The benchmarking efficiency criteria for the Grid tied ( central/string) inverter • At nominal voltage and full load is >95% • For load >25% is >94%. (5) No load losses should not be more than 5%.
Power Factor > 0.9 complete all as specified and directed by the engineer- in- charge. Makes: FIMER (ABB) , Hitachi, Havells. | - | - | - | - |
| 1.03 | S&F Outdoor type IP 55, powder coated, 1.6 mm thickness, with stand of minimum height 2 feet, 1 In 1 Out LT Panel configuration with 160A/100A/80a MCCB, AC SPD Type 2 complete, minimum Size of Enclosure shall be 700 mm x600 mm x300 mm (IP 55) along with 4 pole MCCB 160/100/80 Amps, AC Surge Protection Device-3 ph of 40 kA (as per IEC 60364-5-53), 4 Indication Lamp- R, Y, B.,with multi functional meter 3 phase, 415 Volt (Voltage , Current, Power and Energy unit measurement (KWH)), including Copper Busbar including connecting lugs and Double compression glands etc complete as specified and directed.
Make: Switchgear: Siemens, L&T, Legrand , Schneider, SPD: Citel/ Phoenix/ OBO. (Note:- Rate quoted is inclusive of integration & synchronisation with existing three phase LT panel supply source.) | - | - | - | - |
| 1.04 | Supply, installation connection & testing of AC DB Panel shall be metal clad, totally enclosed, rigid,wall mounted, air ventelator, cubical type suitable for operation on three phase / single phase, 415 or 230 volts, 50 Hz, 160/100/80 Amp with type 2 SPD NVR & contactor having provision of incoming & outgoing armoured cable) The panels shall be designed for minimum expected ambient temperature of 45 degree Celsius, 80 percent humidity and dusty weather. All indoor panels will have protection of IP54 or better. All outdoor panels will have protection of IP65 or better. All the 415 AC or 230 volts devices / equipment like bus support insulators, circuit breakers, SPDs, VTs etc., mounted inside the switchgear shall be suitable for continuous operation and satisfactory performance. | - | - | - | - |
| 1.05 | Supply, installation connection & testing of DC DB, IP65 Panel shall be metal clad, totally enclosed, rigid, wall mounted, air ventelator, with 20 Amp, 1000 Volts string fuses, DC MCB of 20 Amp, 1000 Volts & DC SPD 1000 Volts as per DC input rating of invertor.
Short Circuit & Overload Protected, Over Voltage Protected (Y-PV), No Air Condensation, Cu Wired with FR Insulation & Tested Wire Harnessing ot Ensure High Conductivity, Plug &Play Solution for Rooftop Solar PV Installations. | - | - | - | - |
| 1.06 | M&L 1.1 kV grade 3.5 core 35/50/70 mm² PVC or, XLPE insulated and PVC sheathed, multi-core multi- stranded copper armoured cables shall be used; Outdoor AC cables shall have a UV- stabilized outer sheath all as specified and directed. | - | - | - | - |
| 1.07 | M&L 4 sq mm (single core) DC Cable XLPE insulated and sheathed, UV-stabilized, multistranded flexible copper cable, should be colour coded, complete as all specified and directed. It should include DWC HDPE pipe of conduit pipe of suitable size and clamps. Makes : Havells/Polycab | - | - | - | - |
| 1.08 | S & F FRP (Hensel or equivalent make)/PP/ABS with dust, water and vermin proof. provided with proper locking arrangements. Series / Array Junction Box (SJB/AJB) (whichever is required): All the arrays of the modules shall be connected to DC DB. AJB shall have terminals of bus-bar arrangement of appropriate size. Male & Female pair of MC4 connectors compatible with 4 mm 2 DC solar cable. Make: Staubli or any reputed Indian Manufacturer as approved by GE. | - | - | - | - |
| 1.09 | M&L copper strip 20 x 3.15mm with saddles and fixing screws etc. for roof conductors and down conductors above ground all as specified and directed. | - | - | - | - |
| 1.1 | M&L Chemical earthing in any type of strata (hard/loose) with Material/ Backfill compound shall be Highly Conductive Compound, maintenance free. The watering shall be required at the time of its installation only. No re-charging with water, salts or any other chemical shall be required and it shall maintain almost constant earth resistance during its life cycle without manual watering.(Earthing Rod of 19 mm D X 2m Long 250 micron Cu bonded rod with chemical material) with Laying of Earthing copper Strip of 25x3 mm complete all as directed. | - | - | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.25 MB
BOQ_841003.xls
BOQ • 0.24 MB
ps.pdf
Additional Documents • 0.30 MB
gnlpgs.pdf
Tender Documents • 1.11 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .