| 1 | L1₹7.7 LAccepted-AOC 329 COD COLONY KOYLA NAGAR PO KIDWAI NAGAR KANPUR 208011 | KANPUR | KANPUR | UTTAR PRADESH | 208011 | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹8.2 L+₹22,000 (2.77%)Rejected-Finance | L2 | Rejected-Finance Not Being L1 | |
| 3 | L3₹8.9 L+₹96,110 (12.1%)Rejected-Finance 212 B 8 PARDEWANPUR LAL BANGLA KANPUR 208007 | KANPUR | KANPUR NAGAR | UTTAR PRADESH | 208007 | L3 | Rejected-Finance Not Being L1 | |
| 4 | L4₹9.9 L+₹1.9 L (24.4%)Rejected-Finance | L4 | Rejected-Finance Not Being L1 | |
| 5 | L5₹9.9 L+₹2.0 L (25.2%)Rejected-Finance | L5 | Rejected-Finance Not Being L1 |
Tender Value
₹13.5 L
EMD Value
₹27,000
Closing Date
30 Jan 2023, 6:00 pmClosed
GE I R and D Kanpur
GE I R and D Kanpur DMSRDE Complex, GT Road Kanpur 208013
REPAIR/ REPLACEMENT OF DG SETS, GLOW SIGN BOARD, FLOOD LIGHT AND OTHER CONNECTED WORKS AT RV COLONY UNDER GE (I) R and D KANPUR.
2022_MES_556372_2
8301/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
R V Colony GE I R and D Kanpur
As Per NIT
8 documents required · 8 mandatory
₹500
GE I R and D Kanpur
₹27,000
Yes
24 Mar 2023
7 Jan 2023
1 Feb 2023
7 Jan 2023
30 Jan 2023
16 Jan 2023
Amount
Dismantling fuel pump, radiator assembly, and other accessories of DG sets installed at Pump House No 04 and 05 at R V Colony under GE (I) R&D Kanpur all as specified and directed by Engr- In -Charge.
Cleaning and overhauling of Fuel pump including replacement of SET OF HIGH PRESSURE PIPES (DHA394) of diesel engine all as specified and directed by Engr- In -Charge.
Cleaning of radiator assy including leakage rectification, replace ment of hose pipe and minor spares all as specified and directed by Engr- In -Charge.
Cleaning of fuel tank assy including leakage rectification, replace ment of fuel indication pipe/ glass all as specified and directed by Engr- In -Charge.
Servicing of Diesel generating set as per manufacturers instruction including replacement of all defective parts required for making smooth functional of the DG Set complete all as directed by Engr-in-Charge.
Supply & fixing Engine START PUSH BUTTON - SCHNIDER MAKE (XB5AA31N) all as directed by Engr-in-Charge.
Supply & fixing Engine STOP PUSH BUTTON - SCHNIDER MAKE (XB5AA31N) all as directed by Engr-in-Charge.
Supply & fixing RED, GREEN & YELLOW INDICATION LAMP 12V DC all as directed by Engr-in-Charge.
Supply & fixing LUB OIL FILTER ELEMENT all as directed by Engr-in-Charge.
Supply & fixing set of fuel filter ( primary and secondary) element all as directed by Engr-in-Charge.
Supply & fixing fuel supply pipe line of fuel tank to FIP of DG set all as directed by Engr-in-Charge.
Supply & changing engine oil suitable for diesel engine of DG set installed at RV Colony all as directed by Engr-in-Charge.
Supply & filling of coolent for DG set of any cap all as directed by Engr-in-Charge.
S & F Automatic voltage regulator for DG set of cap up a\110 KVA complete all as specified and directed.
Supply and Fix in replacement Change over Switch, on load type in open execution, front handle operated, 415V with rating of 160 A , four pole including fixing in panel with all accessaries complete all as specified and directed by GE (I). Make Indo Asian/ Legrand / Havells/L&T as approved by GE (I).
M&L for fully automatic star delta starter in replacement suitable for 40 HP pump set with relay 45-75 Amp in sheet metal enclosure complete with all electric connection. Make- L&T MU-G 50 FASD cat part No CS 96009 /Havells.
Routine/periodical cleaning the inside area of pump areaincluding cutting/removal of uprouting of unwanted grass,bushes and small trees near all around sub station and pump house complex complete including surface dressing and levelling by surfave excavation complete all as directed.
Routine and periodical work required for trimming / cutting of tree branches of any girth, touching /obstructing the over head lines of HT/LT poles of three phase distribution system at places not more than 40 mtr span distance so as to keep minimum 2.0 mtr clearance all around the lines and poles with due care after taking proper electric shoutdown from concern MES competent staff complete disposal thereof ( trimmed branches) to a distance not exceeding 100 metre complete all as specified and directed.
Supply, fixing, connecting and testing in replacement of worn out battery by sealed lead acid battery, 12 Volt DC, 140 AH duly charged including replacement of copper connection lead of suitable size with terminal clamps complete all as specified and directed. Make - Exide/Amco/Amron as approved by GE(I)
S & F in replacement Automatic battery Charger AC input 230 + 10% Voltage output DC suitable for 2x12 Volt( 24 Volt) 180 Ah battery charging sine wave complete all as specified and directed. Make Elak Pvt Ltd model AC 04 or equivalent as approved by GE.
S & F in replacement battery bank cosisting of 15 battery of 2 volt, 100 AH DC complete with battery charging set and connected cables of suitable size for HT 11 KV panel board all as specified and directed. Make Elak Pvt Ltd model AC 04 or equivalent as approved by GE.
M&L Design, Manufacture, Supply, install and commission in replacement of old wrusted unserviceble LED display board of following sizes having compact design vandalism resistant features and maintinance friendly, Thhe base of board made of ACP (Aluminium composit panel) 3mmthick and back side of board covered with GL sheet 24SWG, the letters and boarders made of acrylic sheet 3mm thick of colour as aprooved by GE(I). LED strip should as per requirment of letter space, the display language may be English/Hindi (Alpha numeric), its visibility should be shuitable for day and night(Out door application) and should be visible upto 25 Mtrs. (Minimum), the text effect should be static, the LED mean time between failure arrangement should not beless than 40000 hrs, suitable for poer supply 230 volts/50 Hz AC, with timer to switch ON and OFF the power supply to the display board. The board shall be suitably braced on backside with iron 40 mm X 40 X 6 mm and conneted to the mounting arrangement with sheet metal enclosure in CRCA Zinc coated sheet IP 54 grade, silver colour powder coated of minimum thickness of 40 microns alongwith aditional layer of transparent insulation film properly mounted/secured on wall/columns through stainless steel SS 304 or other applicable class mounting brackets and making good of disturbed surfaces as per original complete all as specified and directed by GE(I). (a) Recugalar board having max 60 letters of characters in English language letter or character size, height not exceeding 255 mm and back depth Max 45 mm of suitable width & one logo of dia not exceeding 450 mm and back depth 80 mm as per sample.
Material and labour for repair of LED glow sign board any size including replacement of acarlic/PVC sheet , letters any type and paisting with glue, including adapter if required at site complete testing and fixed at exixting location all as required and directed at site
Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre deep in soft/loose soil and getting out for cable complete all as specified and directed.
Returning filling of excavated soil after laying the cable with spreading leveling watering and well ramming in layers not exceeding 25cm thick in loose/soft soil complete all as specified and directed.
Removal of surplus soil/excavated material obtained from ground level to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.5 metre above from the starting point complete all as specified and directed.
Supply & spreading local sand obtained from ganga river in trenches for cable cushioning complete all as specified and directed.
Supply & laying /paving of dry well burnt bricks of sub class ‘B’ laid flat of whole brick over the cable after spreading the sand for cable protection complete all as specified and directed.
Cutting & Chasing required on concrete block /path/tile /floor/ wall not exceeding 20 cm girth to concealed the cable/GI wire and making good to disturbed surface with cement mortar 1:3 including facing / finishing where as required to match with existing surfaces complete all as specified and directed.
Supply & fix in replacement of GI tubing light grade 40 mm dia with all fitting and fixed complete to wall laid in trenches floor, road crossing and fixing arrangement complete for under ground cable protection including such as MS flats iron clamp nut & bolts washers all as directed and specified.
Supply & fix in replacement of GI tubing light grade 50 mm dia with all fitting and fixed complete to wall laid in trenches floor, road crossing and fixing arrangement complete for under ground cable protection including such as MS flats iron clamp nut & bolts washers all as directed and specified.
Takingout unserviceable cable any type from trenches,pole, road,duct etc including necessary joints(U/S)fittings and pipes etc complete all as specified and directed
Supply and laying in replacement in trenches /laid in floor/duct/drawn through conduit XLPE insulated PVC bedded armored heavy duty electric cable 1100V grade with aluminum conductor of cross sectional are 10 Sq mm 2 core .complete all as specified and directed
Supply and laying in replacement in trenches /laid in floor/duct/drawn through conduit XLPE insulated PVC bedded armored heavy duty electric cable 1100V grade with aluminum conductor of cross sectional are 16 Sq mm 2 core .complete all as specified and directed
Supply and laying in replacement in trenches /laid in floor/duct/drawn through conduit XLPE insulated PVC bedded armored heavy duty electric cable 1100V grade with aluminum conductor of cross sectional are 25Sq mm3.5core .complete all as specified and directed
Earthing complete with galvanised steel earth plate electrode 600x600x6mm thick burried directly in ground (Earth pit not less than 2.25 metre below ground level) with top edge of the plate not less than 1.5 metre below normal ground level connected to galvanised earth strip 32 x 6.00 mm by means of bolts nuts check nuts and protection with 40 mm dia GI Medium grade pipe and washers of galvanised iron or steel, GI strip 7.5 mtr long and plate surrounded with salt charcoal dust etc and 20 mm bore GI light grade pipe for watering, excavation and earth wire including PCC pit in cement concrete 1:3:6 type CI and 40mm thick pit cover of RCC 1:2:4 type 30 reinforced width 8mm dia MS bar @ 150 C/C both ways, furnel wiremesh and testing after completion complete all as specified and directed.
Supply, fixing and testing in replacement of Old unserviceable/ worn out flood light fitting by Turbo LED flood light 170 watt 240 volt with secondary optics made in pressure die cast housing a LED flood light high efficiency in built integrated electronic LED driver complete all as specified and directed including all accessories complete . make :Bajaj Cat No GLEAM F 198L WH SYPC SDV2 or equivalant in havells /crompton as approved by GE (I).
Supply, fixing and testing in replacement of Old unserviceable/ worn out flood light fitting by LED flood light 120 Watt, 240 volt with secondary optics made in pressure die cast housing and heat sink in aluminium extursion with IP 66 protection high efficiency in built integrated electronic LED driver complete all as specified and directed including all accessories complete . make : Bajaj Cat No GLEAM F 165L WH SYPC SDV2 or equivalant in havells /crompton as approved by GE (I). .
19. Supply, fixing and testing in replacement of Old unserviceable/ worn out flood light fitting by LED flood light 100 Watt, 240 volt with secondary optics made in pressure die cast housing and heat sink in aluminium extursion with IP 66 protection high efficiency in built integrated electronic LED driver complete all as specified and directed including all accessories complete . make : Bajaj Cat No GLEAM F 88L WH SYPC SDV2 or equivalant in havells /crompton as approved by GE (I). .
Supply and Fix MCCB optimum 2.1 (Electronic/Microprocessor range with continuously adjustableThermal and Adjustable Magnetic Release, Four Pole, 415 VAC, Current rating- 400 Amps, Breaking capacity ( Ics ) - 50 KA,including suitable size aluminium bus bar for connection complete with extension bus bar of suitable size all as specified and directed by GE (I). Make cat part No 830541of Indo Asian or equivalent of Havells/Legrand / Seimens/Schneider/Hager as approved by GE (I).
Supply and Fix MCCB with continuously adjustableThermal and Adjustable Magnetic Release, Four Pole, 415 VAC, Current rating- 200 Amps, Breaking capacity ( Ics ) - 36 KA,including suitable size aluminium bus bar for connection complete all as specified and directed by GE (I). Make cat part No 830355 of Indo Asianor equivalent of Havells/Legrand / Seimens/Schneider/Hager as approved by GE (I).
Supply of FR PVC insulated, PVC sheathed flat twin core, solid aluminium conductor cable of size 6 sq mm for voltage grade upto 1100 volt confirming to IS- 694/1990 with latest amendments and ISI marked including removing old connection and making service connections to street light feeder of Make Polycab or its equivalent of EON (Indo Aian) / Havells/ Paragon Electron/ Plaza/Rallison as approved by GE(I).
Supply of Supplying and fixing 1100 volts grade heavy duty cable PVC insulated aluminium conductor of 10 sqmm , served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including4mm suspension wire, one twin core cable flat or circular ® to street light feeder of Make Polycab or its equivalent of EON (Indo Aian) / Havells/ Paragon Electron/Plaza/Rallison as approved by GE(I).
M&L for in replacement of pre- fabricated street light junction /distribution box of size 200mm x250 mm with hinged cover system made of MS Sheet/ CRCA sheet duly painted with two coats of synthetic enamelled paint over a coat of red oxide primer suitable for mounting on pole including fixing on pole with clamp 50x6 and nut, bolts and suitable size Aluminium bus bar 02 Nos (Phase,N) connecting incoming and out going connection with proper lugging as latest practice acting as control circuit for street light including MCB SP 'C' 6 Amps for control of s/light complete all as specified and directed.
Supply & fixing bldg/poles light bracket made out 32 mm dia bore G.I pipe, light grade of length not less than 1.5 Mtr, bend to required shape for holding the fitting including Clamps 50x6 mm Flate Iron ,Nut & Bolts for supporting the brackets and taking down the old bracket from existing pole/building.
M&L for electric Welding of LT panel door hinges outdoor/indoor type panel, or any broken part including granding and making good and painting as exising colour all as specified and directed at site
M&L for preparing scraping the old painted surfaces and applying two coat of enamelled paint on LT outdoor/indoor panel any size as existing colour complete and all as specified and directed.
Supply and fixing C P hose of 30 mtr long complete all as specified and directed by Engr-in-charge.
YS CONSTRUCTION
santosh electronics
S B ENTERPRISES
VEE KAY ENTERPRISES
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .