EXECUTIVE ENGINEER
E. E. PROVINCIAL DIVISION NO. 1 PWD B AND R PATIALA
Construction of Trauma Center in Rajindra Hospital Patiala
2025_CEPW_151286_1
Bid No. 58 Dt. 30.09.2025
Open Tender
Civil Works - Buildings
Percentage
545 days
PATIALA
Please refer Tender documents.
3 documents required · 3 mandatory
₹50,000
₹1.1 Cr
Yes
10 Nov 2025
1 Oct 2025
4 Nov 2025
1 Oct 2025
4 Nov 2025
1 Oct 2025
CIVIL WORKS
Construction of Trauma Centre Building (B+6 Storey) with a provision of foundation (B+7 Storey) in RCC Frame Structure
Excavation in Soil (any type) using Hydraulic Excavator CK 90 with hydraulic excavator of 0.9 cum bucket capacity including cutting, trimming bottom and side slopes, in accordance with requirements of lines, grades and cross sections, including all lifts and combined lead upto 30m.
Earth work in excavation in foundations trenches etc. in all kinds of soil where Pick-Jumper work is not involved and not exceeding 2.0 metres depth including dressing of bottom and sides of trenches, stacking the excavated soil clear from the edge of excavation and subsequent filling around masonry in 15 cm, layers with compaction including disposal of all surplus soil as directed within lead of 30 metres.
Reinforced cement concrete M-40 mechanically batch mixed using batch type concrete mixer as per IS:1791 and vibrator but e
xcluding steel reinforcement centring and shuttering in foundation and plinth (As per CSR Preface Para 21 rate for superstructure is applicable since the foundation depth is 8'-4" (2.54mtr deep) from the Ground Level)
Reinforced cement concrete M-35 mechanically batch mixed using batch type concrete mixer as per IS:1791 and vibrated by needle vibrator but excluding steel reinforcement centring and shuttering in superstructure.
Lintels
Extra rate for First Floor
Extra rate for Second Floor
Extra rate for Third Floor
Total all Floors
Shuttering for faces of concrete foundations and foundation beam & plinth beam (vertical or battering)
First class burnt brick work laid in cement sand mortar 1:6 in foundation and plinth. (As per CSR Preface Para 21 rate for superstructure is applicable since the foundation depth is 8'-4" (2.54mtr deep) from the Ground Level)
Shelves
Total all Floor
Extra rate for First Floor
Extra rate for Second Floor
Extra rate for Third Floor
Total all Floors
Reinforced cement concrete M-40 mechanically batch mixed using batch mixed using concrete mixer and vibrated by needle vibrator but excluding steel reinforcement centring and shuttering in superstructure.
Reinforced cement concrete M-30 mechanicaly batch mixed using batch type concrete mixer as per IS:1791 and vibrated by needle vibrator but excluding steel reinforcement centring and shuttering in supersturcture.
Beams
Total all floor
Total qty for all floor
Reinforced cement concrete M-30 mechanically batch mixed using batch mixed using concrete mixer and vibrated by needle vibrator but excluding steel reinforcement centring and shuttering in superstructure.
Total all Floor
Reinforced cement concrete M-20 mechanicaly batch mixed using batch type concrete mixer as per IS:1791 and vibrated by needle vibrator but excluding steel reinforcement centring and shuttering in supersturcture.
Extra rate for Fourth Floor
Extra rate for Fifth Floor
Extra Rate for Sixth Floor
Extra rate for fifth Floor
Centring and shuttering for flat surfaces such as suspended floors, roofs, landings, chajjas, shelves etc.
Total qty for all floor
Extra rate for First Floor
Extra rate for Second Floor
Extra rate for Third Floor
Total all Floors
Shuttering for faces of concrete foundations and foundation beam & plinth beam (vertical or battering)
Extra Rate for Sixth Floor
Walls
Total qty for all floor
Extra rate for First Floor
Extra rate for Second Floor
Extra rate for Third Floor
Total all Floors
Shuttering for faces of concrete foundations and foundation beam & plinth beam (vertical or battering)
Extra Rate for Sixth Floor
Extra rate for fifth Floor
Centring and shuttering for sides and soffits of beam, beams launchings girders bressumers, lintels
Total qty for all floor
Extra rate for First Floor
Extra rate for Second Floor
Extra rate for Third Floor
Total all Floors
Shuttering for faces of concrete foundations and foundation beam & plinth beam (vertical or battering)
Extra Rate for Sixth Floor
Providing and fixing in place jali with frame with base dimension as per drawing cast in GRC (technical specification of GRC- portland cement 10 kgs, Silica sand 8.5 Kgs, AR Glass Fibre 0.55 Kg, Water 2.4-2.7 litres, Polymer 1.0-1.2 Kgs & plasticizer 11.8-23.6 ml) over an armature made in MS pipe fixed with fasteners to the existing badse of RCC/Brick surface finished to the satisfaction of architect/ECI as per design complete in all respect. Final finish /cost of paint onot included in the cost
Total qty for all floor
Extra rate for First Floor
Cement concrete 1:3:6 with stone ballast or shingle mixing by mechanical means using concrete mixer volumetric type
Total Floor:-
Extra rate for Sixth Floor
Shuttering for faces of concrete foundations and foundation beam & plinth beam (vertical or battering)
Extra rate for Sevent Floor
Total qty for all floor
Extra rate for First Floor
Cement concrete 1:3:6 with stone ballast or shingle mixing by mechanical means using concrete mixer volumetric type
Total Floor:-
Extra rate for Sixth Floor
Shuttering for faces of concrete foundations and foundation beam & plinth beam (vertical or battering)
Extra Rate for Sixth Floor
Centring and shuttering for Columns (Square or Rectangular or ply gonal in plain)
Total qty for all floor
Extra rate for First Floor
Cement concrete 1:3:6 with stone ballast or shingle mixing by mechanical means using concrete mixer volumetric type
Total Floor:-
Extra rate for Sixth Floor
Shuttering for faces of concrete foundations and foundation beam & plinth beam (vertical or battering)
Centring and shuttering for stair cases with sloping with soffits including risers and stringers.
Extra rate for Second Floor
Extra rate for Third Floor
Extra rate for Fourth Floor
Centring and shuttering for faces of walls, partitions, retaining walls and the like (vertical or bartering including attached pillasters buttersses etc
Centring and shuttering for parapet, fascias and other similar items including edges.
Extra for using computerised concrete batch mixing plant including carriage by transit mixer within 1 km lead (note: where concrete mixer is already included in the rate the same shall be deducted )
Extra for pumping charges of Batch Mix Concrete / Ready mix conrete work (RMC)
First class burnt brick work laid in cement sand mortar 1:6 in foundation and plinth. (As per CSR Preface Para 21 rate for superstructure is applicable since the foundation depth is 8'-4" (2.54mtr deep) from the Ground Level)
Extra rate for enhancement in pumping power, addition of pipe length, scaffolding for handling the pipe arrangement for pumping of concrete in subsequent storey above the below storey up to height of 4 meters or part there of up to the roof top level of that storey
Extra Rate for First Floor
Total qty for all floor
Extra rate for First Floor
Extra rate for Second Floor
Extra rate for Third Floor
Total all Floors
Shuttering for faces of concrete foundations and foundation beam & plinth beam (vertical or battering)
Extra Rate for Sixth Floor
Extra Rate for Second Floor
Extra Rate for Third Floor
Total qty for all floor
Extra rate for First Floor
Extra rate for Second Floor
Extra rate for Third Floor
Total all Floors
Extra Rate for Fourth Floor
115 mm thick brick wall with every fourth course reinforced with hoop iron laid in 1 :4 cement sand mortar in super structure.
Total Qty for all floor
Extra rate for First Floor
Extra rate for Second Floor
Extra rate for Third Floor
Total all Floors
Shuttering for faces of concrete foundations and foundation beam & plinth beam (vertical or battering)
12.5mm thick cement plaster 1:5.
Extra rate for First Floor
Extra rate for Second Floor
Extra rate for Third Floor
Total all Floors
Shuttering for faces of concrete foundations and foundation beam & plinth beam (vertical or battering)
Extra Rate for Sixth Floor
20 mm thick cement plaster 1:5 in two coats work.
Extra rate for First Floor
Extra rate for Second Floor
Extra rate for Third Floor
Total all Floors
Shuttering for faces of concrete foundations and foundation beam & plinth beam (vertical or battering)
Extra Rate for Sixth Floor
12.5 mm thick cement plaster 1:4.
Extra rate for First Floor
Extra rate for Second Floor
Extra rate for Third Floor
Total all Floors
Shuttering for faces of concrete foundations and foundation beam & plinth beam (vertical or battering)
Extra Rate for Sixth Floor
Extra Rate for Second Floor
20 mm thick cement plaster 1:4.
Extra rate for First Floor
Extra rate for Second Floor
Extra rate for Third Floor
Total all Floors
Shuttering for faces of concrete foundations and foundation beam & plinth beam (vertical or battering)
Extra Rate for Sixth Floor
Extra Rate for Second Floor
Extra Rate for Fifth Floor
Extra Rate for Sevent Floor
First class burnt brick work laid in cement sand mortar 1:6 in first storey upto 4 metres above plinth level..
Top khurra 0.6m x 0.6m for rain water pipe in 25mm thick cement concrete 1:2:4 over 50mm thick cement concrete 1:8:16.
Extra rate for Seventh Floor
Providing and fixing in position gratings 150mm x 150mm for gully trap. PVC grating
Providing and laying in super structure for first storey factory made with vibro-hydraulic compaction machine precast Hollow block of cement concrete setting in position with cement mortar 1:3 (1 cement:3 course sand ) including cost of hosting, centering and shuttering complete as per IS:2185 (Part-1): 2005.
Extra rate for Fifthh Floor
Total all Floor
Providing and fixing on wall face unplasticised Rigid PVC rain water pipes (working pressure 4 kgf / cm²) conforming to IS : 4985, including fixing with MS Clamp U-PVC pipes (working pressure 4kgf. / sqcm) pipe 110 mm dia.
Providing and fixing 110 mm dia. U.P.V.C bend for Rain water pipe as per IS:14735 including jointing complete as per specifications and to the entire satisfaction of Engineer- in- charge. UPVC 110 mm bend
Providing and fixing on wall face unplasticised Rigid PVC rain water pipes (working pressure 4 kgf / cm²) conforming to IS : 4985, including fixing with MS Clamp U-PVC pipes (working pressure 4kgf. / sqcm) pipe 110 mm dia.
Cement concrete 1:2:4 gola 10cm x 10cm concave quadrant along junction of roofs with parapet wall finished smooth, where specially specified.
Providing and fixing 110 mm dia SWR U.P.V.C Coupling/Sockete for Rain water pipe as per IS:14735 including jointing complete as per specifications and to the entire satisfaction of Engineer- in- charge.
Screed of 50mm thick cement concrete 1:8:16 with stone aggregate 40mm gaugeto be laid below the topping using mechanical mixer for mixing of material
Total qty for all floor
Extra rate for First Floor
Extra rate for Second Floor
Extra rate for Third Floor
Total all Floors
Bottom Khurra on ground 1.2m. x 0.6m. consisting of brick on-edge laid in cement mortar 1:3 over 75mm cement concrete 1:8:16 including 12.5m.m. thick cement plaster 1:3.
Providing and fixing thermal insulation of ceiling (under deck insulation) with Resin Bonded Rockloyd Rockwool (Non Combustible Grade) conforming to IS: 8183 and density 48 kg/ m3, wrapped in 200 G Virgin Polythene bags fixed to ceiling with metallic cleats (50x50x3 mm) @ 60 cm and wire mesh of 12.5mm x 24gauge wire mesh, for top most ceiling of building and all complete as per engineer in charge 50 mm thick Resin bonded Rock wool
Kota stone slab 20-25 mm thick flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) :
Providing and laying on smooth roof surface with CFC free, closed cell free Rigid Polyurethane foam slab over deck insulation conforming to IS -12436 (density of foam being 36±2 kg/m3) having thermal conductivity not more than 0.024 W/m.K, over a coat of cold adhesive like CPRX compound, laying 400 G polythene sheet over PUF slab and providing a wearing course of 40 mm thick cement screed 1: 2 : 4 (1 cement : 2 coarse sand : 4 stone aggregate 20 mm nominal size) in chequered rough finish, in panels of 2.5 m x 2.5 m and embedding with 24 G wire netting and sealing the joints with polymerized mastic, all complete as per direction of engineer-in-charge 50 mm thick Polyurethane foam (PUF) rigid insulation board
Extra Rate for Sixth Floor
Kotah stone tile 20mm thick in skirting, riser of steps, dado walls and pillars laid in 12.5mm thick cement mortar 1:3 (1 Cement and 3 Sand) and jointed with neat cement slurry mixed with pigment to match the shade of stone including rubbing and polishing
Providing and laying on smooth roof surface with CFC free, closed cell free Rigid Polyurethane foam slab over deck insulation conforming to IS -12436 (density of foam being 36±2 kg/m3) having thermal conductivity not more than 0.024 W/m.K, over a coat of cold adhesive like CPRX compound, laying 400 G polythene sheet over PUF slab and providing a wearing course of 40 mm thick cement screed 1: 2 : 4 (1 cement : 2 coarse sand : 4 stone aggregate 20 mm nominal size) in chequered rough finish, in panels of 2.5 m x 2.5 m and embedding with 24 G wire netting and sealing the joints with polymerized mastic, all complete as per direction of engineer-in-charge 50 mm thick Polyurethane foam (PUF) rigid insulation board
Extra Rate for Sixth Floor
Coloured Granite stone tiles 15mm to 20mm thick in skirting, risers of steps, dado walls and pillars laid in 12.5mm thick cement mortar 1:3 (1 cement 3 coarse sand) and jointed with neat cement slurry mixed with pigment to match the shade of stone, including rubbing and polishing including labour for fixing dowel pins and cramps..
Total qty for all floor
Extra rate for First Floor
Extra rate for Second Floor
Extra rate for Third Floor
Total all Floors
Shuttering for faces of concrete foundations and foundation beam & plinth beam (vertical or battering)
Providing of set of 4 Nos. 9.5 Litre capacity GI bucket painted in post office red colour with prior coat of red - oxide paint and written with white paint 'Fire' and mounted on MS angle iron frame with bracket of appropriate size and capacity including filling sand etc.
Total qty for all floor
Extra rate for First Floor
Extra rate for Second Floor
Extra rate for Third Floor
Total all Floors
Shuttering for faces of concrete foundations and foundation beam & plinth beam (vertical or battering)
Water proofing of roof terraces, Basements, Retaining Walls, Water tanks etc with Zydex Zycoprime / Elastobar / Equivalent solution so as to form a water-resistant cementitious bonding coat and to form on-site seamless cross-linked elastomeric membrane on the concrete surface to reduce its porosity. Creating a cementitious elastomeric polymeric membrane of Elastobar and Zycoprime/Equivalent after application of Zycosil & Zycoprime Solution in New Construction. Take equal parts of Elastobar and Cement and form a paste. Add little water to the paste to make it brushable. Apply the paste on surface with brush. Leave the surace for drying for at least 4 - 6 hours to get elastomeric membrane. After this application, make one more layer of rough cementatios membrane using mixture of 1 Part of Zycoprime + 1 Part of Cement + 1 Part of fine sand. Apply paste on the surface with a brush to make a rough texture. Now your surface is ready to bond well with tiles/screed.
Total qty for all floor
Extra rate for First Floor
Extra rate for Second Floor
Extra rate for Third Floor
Total all Floors
Shuttering for faces of concrete foundations and foundation beam & plinth beam (vertical or battering)
Providing and fixing Heat Resistant Terrace Tiles (300 mm x 300 mm x 20 mm) with SRI (solar refractive index) > 78, solar reflection > 0.70 and initial emittance > 0.75 on waterproof and sloped surface of terrace, laid on 20 mm thick cement sand mortar in the ratio of 1:4 (1 cement : 4 coarse sand) and grouting the joints with mix of white cement & marble powder in ratio of 1:1, including rubbing and polishing of the surface upto 3 cuts complete, including providing skirting upto 150 mm height along the parapet walls in the same manner
Extra Rate for First Floor
Extra Rate for Second Floor
Base course of floor consisting of 100mm thick cement concrete 1:8:16 with stone aggregate 40mm guage and 100mm fine sand filling using mechanical mixer for mixing of material
Extra rate for Fifth Floor
Extra rate for Sixth Floor
Total Qty for all Floor
Providing and laying flamed finish Granite stone 18mm thick in flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing, curing and polishing etc. all comp
Providing and laying on smooth roof surface with CFC free, closed cell free Rigid Polyurethane foam slab over deck insulation conforming to IS -12436 (density of foam being 36±2 kg/m3) having thermal conductivity not more than 0.024 W/m.K, over a coat of cold adhesive like CPRX compound, laying 400 G polythene sheet over PUF slab and providing a wearing course of 40 mm thick cement screed 1: 2 : 4 (1 cement : 2 coarse sand : 4 stone aggregate 20 mm nominal size) in chequered rough finish, in panels of 2.5 m x 2.5 m and embedding with 24 G wire netting and sealing the joints with polymerized mastic, all complete as per direction of engineer-in-charge 50 mm thick Polyurethane foam (PUF) rigid insulation board
Extra rate for First Floor
Extra rate for Second Floor
Extra rate for Third Floor
Total all Floors
Shuttering for faces of concrete foundations and foundation beam & plinth beam (vertical or battering)
Extra for pre finished nosing to treads of steps of marble stone. ( Full gola, half round gola etc.)
lete as specified and as directed by the Engineer-in-Charge : Flamed finish granite stone slab Jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent.
Providing and fixing 1st quality ceramic glazed wall tiles Matt/Semi Matt/Glosy/Highly Gloss finish/Highlighter/emboss conforming to IS : 15622 (thickness to be specified by the manufacture of approved make in all colours, shades except burgundy, bottle green, black of size 600 x 300 mm as approved by Engineer-in-Charge in skirting, risers of steps and dados over 12 mm thick bed of cement Mortar 1:4 (1 cement: 4 fine sand) and jointing with grey cement slurry @ 3.3kg per sqm including pointing in white cement mixed with pigment of matching shade complete.
Extra Rate for Third Floor
Providing and fixing Morwad Marble Strip 12mm to 15mm thick and 100 mm wide in kotah stone flooring over 12.50mm thickness base of cement mortar 1:3 jointed with cement slurry including cost of additional mortar equivalent to the kota stone thickness andcolouring pigment to match the colour rubbed and polished to granolithic finish complete in all respects.respects.
Extra Rate for Fourth Floor
Total Qty for all floor
Extra rate for First Floor
Extra rate for Second Floor
Extra rate for Third Floor
Total all Floors
Shuttering for faces of concrete foundations and foundation beam & plinth beam (vertical or battering)
Extra Rate for Fifth Floor
Providing and Laying Tactile Flooring full body vitrified , low water absorption below 5%, having excellent slip resistance , very dense, durable and abrasion resistant, solid through colour, fade proof, highly chemical and stain resistance unglazed finish porcelain tile of size 300mm x 300mm x 10mm + 5mm thick, approved profile design, Tec-button/Tec-liner laid in ordinary grey cement and on 20mm thick bed of cement mortar 1:3 filling neat cement slurry between joints with White Cement containing pigment to match the shade complete in all respect. (Tile design and pattern will be as per guidelines issued for persons with disability)
Providing & fixing Protection railing along wall made of 12mm thick kail wood seasoned fixed with fixed bymeans of PVC plug & screw finished with 1.25mm thick stainless steel sheet fixed by lapping backside of wooden strip on 1 and screwed on other end of the edge as per requirement complete in all respect as per the directions of Engineer-in-charge.
Extra rate for First Floor
Extra rate for Second Floor
Extra rate for Third Floor
Total all Floors
Shuttering for faces of concrete foundations and foundation beam & plinth beam (vertical or battering)
Providing & fixing 16 guage stainless steel pipe railing of grade 304 duly fixed on steps with the help of bolts grouted on steps with hand rail and newel post of 50mm dia Stainles steel pipe, Balusters of 40mm dia stainless steel pipe complete in all respects.
Marble work of thickness 12-15 mm for wall lining (veneer work), backing filled with a grout of average 12 mm thick in cement mortar 1:3 (1 cement : 3 coarse sand), including pointing with white cement mortar 1:2 (1 white cement : 2 marble dust) with an admixture of pigment to match the marble shade (To be secured to the backing by means of cramps, which shall be paid for separately). Udaipur Green Marble Tiles of thickness 12mm to 15mm Slabs sizes above 0.50 Sqm
Extra for marble stone flooring in treads of steps and risers using single length up to 2.00 metre.
Providing and Laying Out Door Precast Designer chequered tiles of any size & any shape 25mm thickness having top layer of white cement mixed with pigment, laid on 20mm thick bed of ordinary cement mortar 1:3(1 ordinary cement :3 fine sand), joints grouted with white cement slurry containing pigment to match the shade complete in all respect as per specifications and to the entire satisfaction of engineer- in- charge.
Door and window frame of size 113mmx60mmx with 35mm wide single rebate
Ground Floor
For fixed portion & Chaukhat
For shutters of doors, windows & ventilators including providing and fixing hinges/pivots and labour for fixing of fittings wherever required including the cost of PVC Plug / neoprene gasket required
Providing Polyster Powder coating 50 micron any coloured specrified to aluminium section of various sizes including carrriage of material from marktet to workshop .
Providing and laying vitrified floor tiles in different sizes in light colour shades made using Full Body Technology (thickness to be specified by the manufacturer) with water absorption’s less than 0.08% and conforming to IS : 15622 of approved make in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement: 4 fine sand), complete. ( Full body vitrified tiles have pigment in entire body / thickness of tile which makes chips and scratches less noticeable and make na ideal choice for high traffic zones.) Size 600x600 mm
Grouting the joints of flooring tiles having joints of 3 mm width, using epoxy grout mix of 0.70 kg of organic coated filler of desired shade (0.10 kg of hardener and 0.20 kg of resin per kg), including filling / grouting and finishing complete as per direction of Engineer-in-charge. Size 600x600 mm.
Total All Floors
Providing and fixing Mettal extendable hold fasteners on C.C. /R.C.C./Brick masonry surface backing including drilling necessary holes and the cost of bolt etc complete. Fastener with threaded dia 10 mm
Wrought iron and mild steel ladders, framed grills, grating etc. with ends of bars, riveted or welded or forged, framed window guards, barred iron doors, stair case, iron railing including cost of bolts and nuts or screws or welding rod, complete fixed in position.
Conglomerate floor 50mm thick cement concrete topping 1:2:4 (Using mechanical mixer for mixing of material).
Supplying and fixing of Japani sheet frames (Chowkat) consisting of 18 gauge (1.25mm) thick steel sheet of the specified section (standard design latest), including iron lugs (hold fasts) iron hinges conforming to PWD specifications including bolts for fixing steps, lock notch provision for receiving tower bolts and finished, fixed in position including the cost of cement concrete 1:3:6 for filling in the frame and cement concrete 1:2:4 for lugs complete to the satisfaction of Engineer-in-charge.
Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/appropriate z sections and other profile sections conforming to Is: 733 and IS : 1285 of Jindal, Hindalco, Mahavir or equivalent make approved by Engineer in Charge , fixed with rawl plugs and screws or with fixing clips, or with expansion hold fasteners including necessary filling up of gaps at junctions, at top, bottom and sides with required PVC Plug/neoprene felt etc. Aluminium sections shall be smooth, rust free, straight, mitered and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing/paneling, C.P.brass/stainless steel screws, all complete as per architectural drawings and the directions of Engineer-In-Charge. (Glazing and paneling to be paid for separately) :
Providing & fixing ACP Sheets of various thickness High Class ISI marked complete in all respect as per the directions of Engineer-in-charge. 6mm thick ACP Sheet
Providing and fixing aluminum Wire Mesh including cost of necessary fittings i.e. screws,u Type Beading etc. complete
Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with PVC Plug/ neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item)
Providing and fixing double action hydraulic floor spring of approved brand and manufacture IS : 6315 marked, for doors including cost of cutting floors as required, embedding in floors and cover plates with brass pivot and single piece MS sheet outer box with slide plate and with stainless steel cover plate etc. complete as per the direction of Engineer-in-charge.
Factory manufactured solid flush door fixed in position iron hinges, etc (excluding the cost of any fittings other than specified above but including labour for fixing the same in position (Code : IS 2202-1) (1999) Commercial with elm or gurjan facing on both \ Sides with laminated core and lipped edges:- 35mm thick
Cost of Aluminium fittings complete for doors, windows such as tower bolts, handless and screw etc. for these fittings (Excluding sliding bolt) For shutter area above 0.50 sqm
Providing & Fixing decorative high pressure laminated sheet 1mm (2 Star) thick with high density protective surface layer and reverse side of adhesive bonding quality conforming to IS : 2046 Type S, including cost of adhesive of approved quality.
Extra for providing vision panel not exceeding 0.1 sqm in all type of flush doors (including cost of glass) Rectangular or square
Providing and fixing teak wood beading to door windows chowkats with iron screws fixed in position complete as per design and shape required 40mmx12mm
Providing & fixing 8" stainless steel tower bolts ISI marked on door & window frames complete in all respect as per the directions of Engineer-in-charge.
Providing and fixing 0.50mm thick aluminum sheet including cost of necessary fittings i.e. screws, etc. complete (Kick Plate on Both sides of Door)
Cold twisted deformed (Ribbed/ Tor Steel Bar/TMT) Bars Fe 500 grade as per IS 1786-2008, for R.C.C works, where not including in the complete rate of RCC including bending and placing in position complete
Total Qty for All Floor
Extra rate for First Floor
Extra rate for Second Floor
Extra rate for Third Floor
Total all Floors
Shuttering for faces of concrete foundations and foundation beam & plinth beam (vertical or battering)
Extra Rate for Sixth Floor
Providing and fixing bright finished brass door latch with necessary screws etc. complete : 300x16x5 mm
Providing and fixing bright finished brass 100 mm mortise latch and lock with 6 levers and a pair of lever handles with necessary screws etc. complete (best make of approved quality).
Providing and fixing hydraulic door closer ISI mark with necessary screw etc. complete
I.S.I Designation No. III (size of door 851mm to 1000mm)
Providing & fixing 4" stainless steel handles ISI marked on door & window frames complete in all respect as per the directions of Engineer-in-charge.
Providing & fixing 6" stainless steel tower bolts ISI marked on door & window frames complete in all respect as per the directions of Engineer-in-charge.
Providing & fixing 4" stainless steel tower bolts ISI marked on door & window frames complete in all respect
as per the directions of Engineer-in-charge.
Providing and applying plaster of paris (ISI marked such as JK, Kohinoor, Maharaja etc.) punning 6mm thickness over plastered surface to prepare the surface even and smooth complete in all respect as per the directions of Engineer-in-charge.
Preparation of plastered or concrete surface for painting (including sand papering the surface) using ready mixed cement based wall putty by applying two or more coats to get required finish
Applying priming coat with cement primer in all shade on newly plastered or concrete exterior surface
Wall painting with plastic emulsion paint of approved brand and manufacturer to give an even shade (two or more coats)
Extra rate for using steel produced in integrated plant from original ores complete in all respect as per the directions of Engineer-in-charge.
Applying priming coat with metal primer on new steel or iron work including preparation of surface.
Providing and fixing factory made ISI marked un-insulated metal fire rated doorset assembly for all non egress application areas like shafts etc. consisting galvanized iron steel frame and single leaf shutter including necessary hardware accessories conforming to FD 120 UD classification of IS 3614 :2021 with fire rating of 120 minutes integrity. The door frame and shutter shall be made out of minimum 1.20 mm thick Gl Sheet with minimum 120 GSM Zinc coating as per IS: 277. The entire fire rated doorset assembly shall be tested in unlatched condition as per IS 17518 (Part-1): 2022 Frame: The frame shall be of minimum size 90 x 60 mm with grooved profile to take appropriate fire rated smoke seal, having mitred cut joints (self tab/screwed assembled at site) and provided with appropriate reinforcement suitable for taking hardware and flush fixing as per IS: 4351. The smoke seal material shall be of EPDM tested in accordance with ASTM E- 84 of minimum size 10×4 mm, fixed within the inbuilt groove or stuck with adhesive on the entire perimeter of the frame. The door frame shall be fixed in all four sides to masonry wall opening with CSK/Hex headed fasteners of minimum 8 mm dia size and minimum 80 mm long with 8mm dia polyamide sleeves @ 4 number at each on vertical sides (up to 2100 mm height) and 2 numbers each on top and bottom sides. Door shutter: The double skin single leaf door shutter shall be consisting of minimum 46 mm thick and having box like structure, slots cut and holes punched, for fixing of hardwares with stiffeners as per IS: 16074 including Resin bonded honey comb paper core infill material of density 5 kg/cum. The door shutter shall be mounted on the frame with SS 304 grade ball bearing butt hinges as per EN 1935: 2002 or butt hinges as per IS 12817 both, of minimum size 100x75x3 mm @ minimum 4 numbers up to 2100 mm / 2400 mm height or as per test evidence, which ever is more, fixed with M6 25 screws. All doors shall be factory prepared for receiving appropriate hardware and provided with necessary reinforcement for hardware accessories.
Finishing walls with acrylic smooth exterior paint of required shade with two or more coats applied @ 1.67 litre/10Sqm over and including base coat of water proofing Cement Paint applied @ 2.20 Kg/10 Sqm
Finishing walls with textured exterior paint of required shade with two or more coats applied @ 3.28 litre/10Sqm over and including base coat of water proofing Cement Paint applied @ 2.20 Kg/10 Sqm
Providing and Fixing of Copper Sheet 16 Gauge 350mm wide on expansion joint including covering with C. Concrete complete in all respect as per specifications.
Providing and fixing covering 200mm wide Aluminium Sheet 14 Gauge with gatties and screw on vertical expansion joints one side fixed and one side fixed with slotted holes to allow movement complete in all respect as per specifications and to the entire satisfaction of engineer- in- charge.
Preformed fillers for expansion joints in concrete pavement and structures (non-extruding and resilient type) part-3 Polymer Based (CED 13: building construction practices including painting, varnishing and allied finishing) complete as per IS 1838-3 (2011):
Single leaf un-insulated metal fire rated door and frame of FD 120 UD with 120 minutes integrity only as per IS 3614:2021- For non egress application like area shafts etc.
120 minutes integrity. The door frame and shutter shall be made out of minimum 1.20 mm thick GI Sheet with minimum 120 GSM Zinc coating as per IS: 277. The entire fire rated doorset assembly shall be tested in unlatched condition as per IS 17518 (Part- 1): 2022 Frame: The frame shall be of minimum size 90 x 60 mm with grooved profile to take appropriate fire rated smoke seal, having mitred cut joints (self tab/screwed assembled at site) and provided with appropriate reinforcement suitable for taking hardware and flush fixing as per IS: 4351. The smoke seal material shall be of EPDM tested in accordance with ASTM E- 84 of minimum size 10×4 mm, fixed within the inbuilt groove or stuck with adhesive on the entire perimeter of the frame. The door frame shall be fixed in all three sides to masonry wall opening with CSK/Hex headed fasteners of minimum 8 mm dia size and minimum 80 mm long with 8mm dia polyamide sleeves @ 5 numbers at each on vertical side and 3 numbers on top side. Door shutter: The double skin double leaf door shutter shall be consisting of minimum 46 mm thick and having box like structure, slots cut and holes punched for fixing of hardware with stiffener as per IS 16074 including Resin bonded honey comb paper core infill material of density 5 kg/cum. Each door leaf shall be provided with vision panel, having maximum area of 0.12 sqm, of 120 minute fire rated minimum 6 mm thick clear borosilicate glass pane fixed with clip-on arrangement and fire rated ceramic tape having minimum size 13x2mm to be fixed all around the glass on both the sides. Integral astragals to be provided for double leaf doors on the meeting style each on both active and inactive leaf. The door shutters shall be mounted on the frame with SS 304 grade ball bearing butt hinges as per EN 1935: 2002 or butt hinges as per IS 12817 both, of minimum size 100x75x3 mm @ 5 numbers hinges per door leaf upto 2400 mm height or as per test evidence, which ever is more, fixed with M6 25 screws. All doors shall be factory prepared for receiving appropriate hardware and provided with necessary reinforcement for hardware accessories.
Double leaf un-insulated metal fire rated doorset of FD 120 UD classification with 120 minutes integrity only as per IS 3614:2021-For egress application like utility room and service area etc.
Providing & fixing Structure frame work in approved pattern on aluminium frame work 10 guage finished with ACP sheet 4mm thick jointing with silicon complete as per architect drawing & as desired by Engineer-in-Charge.
Providing and fixing tiled false ceiling of specified materials of size 595x595 mm ( GI Metal Ceiling Lay in plain Tegular edge Global white color tiles of size 595x595 mm, and 0.5 mm thick with 8 mm drop; made of G I sheet having galvanizing of 100 gms/sqm (both sides inclusive) and electro statically polyester powder coated of thickness 60 microns(minimum), including factory painted after bending.) in true horizontal level, suspended on inter locking metal grid of hot dipped galvanized steel sections ( galvanized @ 120 grams/ sqm, both side inclusive) consisting of main "T" runner with suitably spaced joints to get required length and of size 24x38 mm made from 0.30 mm thick (minimum) sheet, spaced at 1200 mm center to center and cross "T" of size 24x25 mm made of 0.30 mm thick (minimum) sheet, 1200 mm long spaced between main "T" at 600 mm center to center to form a grid of 1200x600 mm and secondary cross "T" of length 600 mm and size 24x25 mm made of 0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600 mm panel to form grids of 600x600 mm and wall angle of size 24x24x0.3 mm and laying false ceiling tiles of approved texture in the grid including, required cutting/making, opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main "T" runners to be suspended from ceiling using GI slotted cleats of size 27 x 37 x 25 x1.6 mm fixed to ceiling with 12.5 mm dia and 50 mm long dash fasteners, 4 mm GI adjustable rods with galvanised butterfly level clips of size 85 x 30 x 0.8 mm spaced at 1200 mm center to center along main T, bottom exposed width of 24 mm of all Tsections shall be pre-painted with polyester paint, all complete for all heights as per specifications, drawings and as directed by Engineer-in-charge.
Providing and fixing mineral fibre false ceiling tiles at all heights of size 595X595mm of approved texture, design and pattern. The tiles should have Humidity Resistance (RH) of 99%, Light Reflection > 85%, Thermal Conductivity k = 0.052 - 0.057 w/m K, Fire Performance as per (BS 476 pt - 6 &7)in true horizontal level suspended on interlocking T-Grid of hot dipped all round galvanized iron section of 0.33 mm thick (galvanized @120 gsm) comprising of main T runners of 15x32 mm of length 3000 mm, cross T of size 15x32mm of length 1200 mm and secondary intermediate cross T of size 15x32 mm of length 600 mm to form grid module of size 600x600 mm suspended from ceiling using galvanized mild steel it
em (galvanised@80gsm) 50 mm long 8mm outer diameter M-6 dash fasteners, 6 mm diameter fully threaded hanger rod up to 1000 mm length and L-shape level adjuster of size 85x25x2 mm, spaced at 1200 mm centre to centre along main ‘T’. The system should rest on periphery walls /partitions with the help of GI perimeter wall angle of size24x24X3000 mm made of 0.40 mm thick sheet, to be fixed to the wall with help of plastic rawl plug at 450 mm centre to centre & 40 mm long dry wall S.S. screws. The exposed bottom portion of all T-sections used in false ceiling support system shall be pre-painted with polyester baked paint, for all heights. The work shall be carried out as per specifications, drawings and as per directions of the engineer-in-charge.
Distempering with Acrylic washable oil bound distemper (of approved manufacture) two or more coats over one priming coat to give an even shade
Painting two or more coats excluding priming coat with synthetic enamel paint in all shades on wood work, metallic or plastered, concrete surface to give an even shade.
Providing and fixing 110 mm dia SWR U.P.V.C Coupling/Sockete for Rain water pipe as per IS:14735 including jointing complete as per specifications and to the entire satisfaction of Engineer- in- charge.
Extra for marble stone flooring in treads of steps and risers using single length up to 2.00 metre.
Providing and fixing double glazed hermetically sealed glazing in aluminium windows, ventilators and partition etc. with 6 mm thick clear float glass both side, having 12 mm air gap, including providing EPDM gasket, perforated aluminium spacers, desiccants, sealant (Both primary and secondary sealant) etc. as per specifications, drawings and direction of Engineer-in-charge complete.
Design supply & installation of suspended Spider Glazing system designed to withstand the wind pressure as per IS 875 (Part-III). The Suspended System held with Spider Fittings of SS-316 Grade Steel of approved manufacturer with glass panel having 12 mm thick clear toughened glass held together with SS- 316 Grade Stainless steel Spider.& bolt assembly with laminated glass fins 21 mm thick. The Glass fins and glass panel assembly shall be connected to Slab/beams by means of SS- 316 Grade stainless steel brackets & Anchor bolts and at the bottom using SS channel of 50x25x2mm using fastener & anchor bolts, non star bushes and separators to prevent bi-metallic contacts, all complete to perform as per specification and approved drawings. The complete system to be designed to accommodate thermal expansion & seismic movements etc. The joints between glass panels (6 to 8 mm) and gaps at the perimeter & in U channel of the assembly to be filled with non staining weather sealant, so as to make the entire system fully water proof & dust proof.
Providing and fixing 12 mm thick frameless toughened glass door shutter of approved brand and manufacture, including providing and fixing top & bottom pivot & double acting hydraulic floor spring type fixing arrangement and making necessary holes etc. for fixing required door fittings, all complete as per direction of Engineer-in-charge
Providing & fixing loovers convax capsule shape made of ACP Sheets 6mm thick High Class ISI marked fixed with top & bottom aluminium profile by means of silicon & screws as per requirement complete in all respect as per the directions of Engineer-in-charge.
Design, Providing fabrication and erection of shed of high tensile roofing with PVC membrane made of mild steel tubular frame work thickness as per standard, redoxide & decospray paint, heat welding, heat sealing of membrane 730 GSM, ploting of structure, water proofing of structure, fixing of metallic ribes, S.S fitting, Aluminium fitting complete in all respect as per specifcation, drawing and to the entire satisfication of Engineer-In-Charge. (including cost of Structure designing, Cost of any kind /size of tubular structure but excluding cost of foundation)
Construction of Plinth protection complete as per drawing.
Earth work in excavation in foundations, trenches etc. in all kinds of soil where pick jumper work is not involved and not exceeding 2.0 metres depth including dressing of bottom and sides of trenches, stacking the excavated soil clear from the edge of excavation and subsequent filling around masonry in 15 cm. layers with compaction including disposal of all surplus soil as directed within a lead of 30 metres.
Cement Concrete 1:8:16 with 40mm guage stone aggregate using concrete mixing volumetric type
First class burnt brick work laid in cement sand mortar 1:5 in foundation and plinth.
12.5 mm thick cement plaster 1:5 complete in all respect as per specifcation, drawing and to the entire satisfication of Engineer-In-Charge.
Construction of Connnecting Corridor Towards CCB
Cement concrete 1:5:10 with 40 mm gauge stone ballast. using concrete mixing volumetric type
Reinforced cement concrete M-25 mechanicaly batch mixed using batch type concrete mixer as per IS:1791 and vibrated by needle vibrator but excluding steel reinforcement centring and shuttering in foundation and plinth.
Reinforced cement concrete M-25 mechanicaly batch mixed using batch type concrete mixer as per IS:1791 and vibrated by needle vibrator but excluding steel reinforcement centring and shuttering in supersturcture.
Beams
Total all floor
Cement Concrete 1:8:16 with 40mm guage stone aggregate using concrete mixing volumetric type
Cement concrete 1:5:10 with 40 mm gauge stone ballast. using concrete mixing volumetric type
Reinforced cement concrete M-25 mechanicaly batch mixed using batch type concrete mixer as per IS:1791 and vibrated by needle vibrator but excluding steel reinforcement centring and shuttering in foundation and plinth.
Reinforced cement concrete M-25 mechanicaly batch mixed using batch type concrete mixer as per IS:1791 and vibrated by needle vibrator but excluding steel reinforcement centring and shuttering in supersturcture.
Total qty for all floor
Cement concrete 1:5:10 with 40 mm gauge stone ballast. using concrete mixing volumetric type
Reinforced cement concrete M-25 mechanicaly batch mixed using batch type concrete mixer as per IS:1791 and vibrated by needle vibrator but excluding steel reinforcement centring and shuttering in foundation and plinth.
Reinforced cement concrete M-25 mechanicaly batch mixed using batch type concrete mixer as per IS:1791 and vibrated by needle vibrator but excluding steel reinforcement centring and shuttering in supersturcture.
Columns
Total all Floor
Reinforced cement concrete M-25 mechanicaly batch mixed using batch type concrete mixer as per IS:1791 and vibrated by needle vibrator but excluding steel reinforcement centring and shuttering in foundation and plinth.
Reinforced cement concrete M-25 mechanicaly batch mixed using batch type concrete mixer as per IS:1791 and vibrated by needle vibrator but excluding steel reinforcement centring and shuttering in supersturcture.
Centring and shuttering for flat surfaces such as suspended floors, roofs, landings, chajjas, shelves etc.
Total qty for all floor
Cement concrete 1:5:10 with 40 mm gauge stone ballast. using concrete mixing volumetric type
Reinforced cement concrete M-25 mechanicaly batch mixed using batch type concrete mixer as per IS:1791 and vibrated by needle vibrator but excluding steel reinforcement centring and shuttering in foundation and plinth.
All Floor Total
Walls
Total qty for all floor
Cement Concrete 1:8:16 with 40mm guage stone aggregate using concrete mixing volumetric type
First class burnt brick work laid in cement sand mortar 1:5 in foundation and plinth.
12.5 mm thick cement plaster 1:5 complete in all respect as per specifcation, drawing and to the entire satisfication of Engineer-In-Charge.
Construction of Connnecting Corridor Towards CCB
Cement concrete 1:5:10 with 40 mm gauge stone ballast. using concrete mixing volumetric type
Reinforced cement concrete M-25 mechanicaly batch mixed using batch type concrete mixer as per IS:1791 and vibrated by needle vibrator but excluding steel reinforcement centring and shuttering in foundation and plinth.
All Floor Total
Centring and shuttering for sides and soffits of beam, beams launchings girders bressumers, lintels
Total qty for all floor
Cement Concrete 1:8:16 with 40mm guage stone aggregate using concrete mixing volumetric type
Cement concrete 1:5:10 with 40 mm gauge stone ballast. using concrete mixing volumetric type
Reinforced cement concrete M-25 mechanicaly batch mixed using batch type concrete mixer as per IS:1791 and vibrated by needle vibrator but excluding steel reinforcement centring and shuttering in foundation and plinth.
All Floor Total
Centring and shuttering for Columns (Square or Rectangular or ply gonal in plain)
Total qty for all floor
Reinforced cement concrete M-25 mechanicaly batch mixed using batch type concrete mixer as per IS:1791 and vibrated by needle vibrator but excluding steel reinforcement centring and shuttering in foundation and plinth.
All Floor Total
Extra Rate for Fifth Floor
Extra Rate for Sevent Floor
First class burnt brick work laid in cement sand mortar 1:6 in first storey upto 4 metres above plinth level..
Top khurra 0.6m x 0.6m for rain water pipe in 25mm thick cement concrete 1:2:4 over 50mm thick cement concrete 1:8:16.
Extra rate for Seventh Floor
Providing and fixing in position gratings 150mm x 150mm for gully trap. PVC grating
Terracing consiting of tiles 22.86x11.43x3.83cm laid over 25 mm mud plaster 7.5 cm mud filling on another layer of 25mm mud plaster including two coats of bitumen laid hot at 1.65 Kg. /Sqm top of R.C.C. slab including grouting with cement sand mortar 1:4 and top surface to be left clean after wire brushing
Total all Floor
Extra rate for Second Floor
Cement concrete 1:2:4 gola 10cm x 10cm concave quadrant along junction of roofs with parapet wall finished smooth, where specially specified.
Screed of 50mm thick cement concrete 1:8:16 with stone aggregate 40mm gaugeto be laid below the topping using mechanical mixer for mixing of material
Total qty for all floor
Extra rate for First Floor
Extra Rate for Fourth Floor
Total qty for all floor
Extra Rate for Fifth Floor
Cold twisted deformed (Ribbed/ Tor Steel Bar/TMT) Bars Fe 500 grade as per IS 1786-2008, for R.C.C works, where not including in the complete rate of RCC including bending and placing in position complete
Total Qty for All Floor
Providing and fixing bright finished brass door latch with necessary screws etc. complete : 300x16x5 mm
Preparation of plastered or concrete surface for painting (including sand papering the surface) using ready mixed cement based wall putty by applying two or more coats to get required finish
Applying priming coat with cement primer in all shade on newly plastered or concrete exterior surface
Extra rate for using steel produced in integrated plant from original ores complete in all respect as per the directions of Engineer-in-charge.
Finishing walls with acrylic smooth exterior paint of required shade with two or more coats applied @ 1.67 litre/10Sqm over and including base coat of water proofing Cement Paint applied @ 2.20 Kg/10 Sqm
Extra rate for 4mtr to 5mtr height
Extra rate for 5mtr to 6mtr height
Extra rate for 6mtr to 7mtr height
Extra rate for 7mtr to 8mtr height
Extra rate for 8mtr to 9mtr height
Extra rate for 9mtr to 10mtr height
Extra rate for 10mtr to 14mtr height (Average rate= (315+450)/2)
Parapet
Extra rate for 10mtr to 14mtr height (Average rate= (287.00+410)/2)
Providing Various signage Outside & Inside Building incompliance to the Harmonised guidelines & standards for Universal accessibility-2021
Providing & fixing of Informatory sign board single legged double sided Size 600x600mm non glared with retro reflective high intensity Microprismatic grade sheeting type-iv as per ASTM D4956-09 fixed over 4mm thick ACP sheeting having aluminium skin thickness of 0.25 to 0.3 mm on both sided and fixing the same with suitable epoxy base adhesive on back support frame of M.S hollow section 60x40x3.4 mm supported on a square M.S hollow steel section post 60x60x3mm conforming to IS code firmly fixed to ground in foundation concrete M-20 of size 0.45 x 0.45 x 0.60 M for vertical post complete in all respects, as per specification & as desired by Engineer-in-Charge (Confirming to Harmonised guidelines & standards for Universal accessiblity in India-2021 issued by Ministry of Housing and Urban Affairs Government of India)
Providing & fixing of Informatory sign board double sided hanging from ceiling Size 1371 x 634mm non glared with retro reflective high intensity Microprismatic grade sheeting type-iv as per ASTM D4956-09 fixed over 4mm thick ACP sheeting having aluminium skin thickness of 0.25 to 0.3 mm on both sided and fixing the same with suitable epoxy base adhesive on back support frame of 40x20x3.2 Stainless Steel supported on a square M.S hollow steel section post 40x40x3mm conforming to IS code firmly hanged from ceiling/beam by fixing with expandable fastners complete in all respects, as per specification & as desired by Engineer-in-Charge (Confirming to Harmonised guidelines & standards for Universal accessiblity in India-2021 issued by Ministry of Housing and Urban Affairs Government of India)
Providing & fixing of Informatory sign board double sided hanging from ceiling Size 1371 x 952mm non glared with retro reflective high intensity Microprismatic grade sheeting type-iv as per ASTM D4956-0
9 fixed over 4mm thick ACP sheeting having aluminium skin thickness of 0.25 to 0.3 mm on both sided and fixing the same with suitable epoxy base adhesive on back support frame of 40x20x3.2 Stainless Steel supported on a square M.S hollow steel section post 40x40x3mm conforming to IS code firmly hanged from ceiling/beam by fixing with expandable fastners complete in all respects, as per specification & as desired by Engineer-in-Charge (Confirming to Harmonised guidelines & standards for Universal accessiblity in India-2021 issued by Ministry of Housing and Urban Affairs Government of India)
Providing & fixing of Single Side Signage with provision of Multilingual text integral with minimum 3.8mm thick blue/white or combine Acrylic base plate with upper case san serif words made of white acrylic non glare cut out letter of height not less than 20mm, raised above base plate by not less than 0.8mm and the equivalent workd/s written in Multilanguage i.e Regional, devnagri, English language as required with same specifications with Grade 1 Braille to be integral with the sign face and should be raised not less than 0.5mm above Acrylic base Plate complete in all respects, as per specification & as desired by Engineer-in-Charge (Confirming to Harmonised guidelines & standards for Universal accessiblity in India-2021 issued by Ministry of Housing and Urban Affairs Government of India)
Providing & fixing of Single side signage/Tactile Layout/Emergency Evacuation Layout with Provision of Multilingual text integral with minimum3.8mm thick blue/white or Combine Acrylic base plate with upper case san serif workds made of white acrylic non glare cut our letters of height not less than 0.8mm and the equivalent work/s writtenin Multilanguage i.e Regional, devnagri, English language as required with same specification with Grade 1 Braille to be integral with the sign face and should be raised not less than 0.5mm above Acrylic base Plate complete in all respects, as per specification & as desired by Engineer-in-Charge (Confirming to Harmonised guidelines & standards for Universal accessiblity in India-2021 issued by Ministry of Housing and Urban Affairs Government of India)
Extra Cost for using darker fast shade for interlocking pavers Tiles of any shape & thickness instead of grey colours.
Providing & fixing of Braille labels made of Stainless Steel (Grade-304) Size 170mm x 30mm x 4mm having Braille Dots raised 0.5mm above base plate complete in all respects, as per specification & as desired by Engineer-in-Charge (Confirming to Harmonised guidelines & standards for Universal accessiblity in India-2021 issued by Ministry of Housing and Urban Affairs Government of India)
Providing and fixing 110 mm dia SWR U.P.V.C Coupling/Sockete for Rain water pipe as per IS:14735 including jointing complete as per specifications and to the entire satisfaction of Engineer- in- charge.
Providing and fixing 1st quality ceramic glazed wall tiles Matt/Semi Matt/Glosy/Highly Gloss finish/Highlighter/emboss conforming to IS : 15622 (thickness to be specified by the manufacture of approved make in all colours, shades except burgundy, bottle green, black of size 600 x 300 mm as approved by Engineer-in-Charge in skirting, risers of steps and dados over 12 mm thick bed of cement Mortar 1:4 (1 cement: 4 fine sand) and jointing with grey cement slurry @ 3.3kg per sqm including pointing in white cement mixed with pigment of matching shade complete.
Providing & fixing of 50mm wide high intensitiy reflective, conspicuity tape colour contrast, self adhesive to be fixed on front edge of tread of stair case to help people with visual disabliity and elderly even in dim light conditions & reduce the risk of slipping Make 3M or equivalent brand complete in all respects, as per specification & as desired by Engineer-in-Charge (Confirming to Harmonised guidelines & standards for Universal accessiblity in India-2021 issued by Ministry of Housing and Urban Affairs Government of India)
Providing & fixing of 50 mm wide antiskid tape made of slip resistant material colour contrast, edge strip/tape self adhesive to be fixed on top/edge of tread of Stair to help people with visual disabliity and elderly even in dim light conditions & reduce the risk of slipping complete in all respects, as per specification & as desired by Engineer-in-Charge (Confirming to Harmonised guidelines & standards for Universal accessiblity in India-2021 issued by Ministry of Housing and Urban Affairs Government of India)
PUBLIC HEALTH SERVICES
Providing and fixing in position singel socket SWR UPVC soil waste or antisyphonage pipes as per IS 13592 of E.D.C manufacture or of any other reputed firm including cutting, jointing, wastage, but excluding cost of jointing. Single Socket Type B
Road marking with hot applied thermoplastic compound 2.5mm thick including reflectorising glass beads @ 0.25kg per sqm area as per IRC:35 1997 complete as per technical clause 803 of MORT&H specifications
Outer Infrastructure
Providing and fixing in position SWR UPVC special for soil waste vent or anti syphonage pipes as per as per IS - 14735 including cutting and wastage etc. cutting holes in walls roofs or floors etc. and making good to its original condition but excluding cost of lead joining.
Construction of Parking/pavement & Footpath
Elbow 90 Degree (All side socketed)
Vent Cowls
Coupler
Single Tee With Door
Construction of embankment with good quality earth obtained from borrow pits including compensation of earth, loading, unloading, carriage to site of work, spreading, grading to required slope and compacting to meet requirement of table 300-2 as per technical clause 305 of MORT&H specifications.
Elbow 90 degree (all side socket)
Vent Cowls
Coupler
Single Tee With Door
Floor Trap 110mm x 75mm
Providing PVC solvent cement joints to SWR Pipes and specials including cost of PVC solvent cement and tools etc of approved make (to the approval of Engineer-in-charge)
Providing & Fixing in position M.S or heavy flat iron clamps made out of M.S flat iron not less than 5 mm of the approved design for fixing C.I. soil waste, vent or antisyhonage pipes to walls complete in all respects including cutting and making good the walls and floors etc. and painting.
M.S. Holder bats clamps for 100mm i/d as per table-1
M.S. Holder bats clamps for 75mm i/d as per table-1
Core cutting in RCC slab 125mm dia or 150mm dia withe the help of core cutting machine as per requirement at site & as desired by Engineer-in-Charge.
Providing and fixing galvonised hanging clamp 100mm dia chimney type for PVC pipe, 12mm galvonised fully thread bar with nut bolt as per requirement at site & as desired by Engineer-in-Charge.
Providing and fixing in position gully traps fixed in cement concrete 1:4:8 complete with Grating 150mm x 150mm, cover and frame clear opening 300mm x 300mm and out of side size 330mm x 330mm and chamber including cost of all bricks work in cement morter 1:5 cement concrete 1:2:4 in coping around cover and frame etc. as per standard design minimum depth of water should be 150 mm with a minimum seal 50mm.
100mm internal Diametre S.W.gully trap with H.C.I. grating and cast iron cover weighing approximately 7.26 kg. and frame clear opening 300mm x 300mm and out of side size 330mm x 330mm as per table-1
Construction of brick masonry inspection chambers size as given below upto 0.60 metre average depth in 1:5 cement sand mortar, C.C.1:4:8 ( 150mm thick) in foundation, cement concrete 1:2:4 benching 12.50mm thick cement plaster 1:2 with a floating coat of 1mm thick of neat cement, R.C.C. 1:2:4 slabs 100mm thick cement concrete topping 50mm thick with 455mm x 455mm, 455mm x 610mm inside R.C.C. inspection chamber cover and frame (Weight as per I.S.I specifications) painted with 3 coats of black bitumastic paint conforming to I.S.I complete as per standard design.
450mm x 600mm inside with 455mm x 610mm cover and frame light duty double seal
Providing and laying, jointing, fixing and testing ISI Marked uPVC Pipe Lines as per ISI 4985-2000, including specials such as tees, bends, sockets, elbow etc., cutting, testing (including cost of specials) in the ground complete in all respects.
uPVC Pipe 6 Kgf/cm2 50mm i/d as per table-1
CONCEALED IN WALL: Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes as per IS 15778 (ISI marked with the prior approval of Engineer-in- Charge), having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing including jointing of pipes & fittings, with one step CPVC solvent cement and testing of pipes complete as per direction of Engineer-in-Charge.
CPVC SDR 11 Pipe & fitting 16mm o/d
SDR 11 CPVC pipes & fittings 20mm o/d
CPVC SDR 11 Pipe & fitting 25mm o/d
CPVC SDR 11 Pipe & fitting 50mm o/d
Cutting chase in brick walls in cement or in floor for embedding G.I. or C.I pipes lines and making good the same to its original condition. Size 75mm x 75mm
qty same as GI P 15mm i/d to 25 mm (Table-2)
Cutting holes upto 23cm square through B.B. in cement walls or stone masonary wall in cement for pipes, and making good the same & finishing according to existing finish where required.
Through wall 11.43 cm thick Detail as per Table-2
Through wall 22.86 cm thick Detail as per Table-2
Providing, fixing and jointing Cpvc Union Couplings with Upvc Pipes complete in all respect.
Granular Sub Base Grade I Construction of granular sub-base by providing material, spreading in uniform layers with motor grader on prepared surface, mixing by mix in place method with rotavator at OMC, and compacting with vibratory roller to achieve the desired density, complete as per MORD technical specifications
Providing, laying, spreading and compacting graded stone aggregate to wet mix macadam specification including premixing the Material with water at OMC in mechanical mix plant, carriage from mix plant to site of work, laying in uniform layers with paver in sub- base / base course on well prepared surface and compacting with vibratory roller to achieve the desired density complete as per technical clause 406 of MORT&H specifications.
Providing and laying 60 mm thick factory made cement concrete interlocking paver block of M-35 grade machine made rubber moulded smooth finish with strong vibratory process or with vibro- hydraulic compaction machine and of approved size and design / shape laid in Ordinary Grey and pattern over and including 40 mm thick compacted bed of coarse sand, filling the joints with fine sand etc, all complete as per directions of Engineer-in-Charge. IS COde : 15658 (2006)
Providing, fixing and jointing CPVC Ball valves screwed with CPVC ball & spindle & Teflon seats, on CPVC Pipe lines including all carriages complete.
25mm i/d Brass Ball valves
50mm i/d Brass Ball valves
Providing and laying factory made rubber moulded smooth finish cement concrete Kerb M-20 grade 250mm high with bottom width 165mm and top width 115mm made over strong vibratory table and fixing with cement mortar 1:2 as per MORT&H specifications
Providing and fixing in position Chinaware European type water closet P trap or S trap of approved make (to the approval of the Engineer-in-charge) consisting of 10 ltr. PVC flushing cistern ISI marked, PVC short bend 32 mm dia including cost of seat cover complete in all respect and to the entire satisfaction of Engineer-in-charge. Detail attached as per Table-3
Providing and fixing jet spray with 2'-6" long PVC pipe.With PTMT nut Detail attached as per Table-3
Providing & Fixing in position C.P. Brass Hexa Nipple 15mm of approved make (to the approval of Engineer-in-charge ) complete in all respect. Detail attached as per Table-3
Providing and fixing in position vitreous Chinaware white lIndian make large flat back or angular lipped front urinal 375 x 390 x 590 mm of approved make (to the approval of the Engineer-in-charge) consisting of C.P. brass Urinal waste Coupling dome type 32mm outer length 75 mm , C.P. brass Urinal Spreader Ocular-Regular and C.P. brass tube connection 300 mm long complete.
Applying priming coat with cement primer in all shade on newly plastered or concrete exterior sufrace
Providing and fixing in position vitreous chinaware white lavatory suites of approved make (to the approval of Engineer-in-charge) consisting of C.P. brass waste 32mm dia with one C.P. brass pillar tap including Rack Bolt Screw Pair 115mm long complete in all respect.
Size 49 cm dia (above counter round)
Size 550 mm x 400 mm x 815mm
Painting two or more coats excluding priming coat with synthetic enamel paint in all shades on wood work, metallic or plastered, concrete surface to give an even shade.
110mm o/d single socket SWR UPVC pipe lines laid complete
75mm o/d single socket SWR UPVC pipe lines laid complete
Providing and fixing vitreous chinaware standard pedestal of approved make (to the approval of Engineer-in-charge) for wash hand basin complete in all respect.
Providing & fixing in position PVC flexible tube connection of approved make (to the approval of Engineer-in-charge ) complete in all respect. PVC tube connection of size 15 mm x 375 mm with PTMT nut
For 110mm o/d pipes
For 75mm o/d pipes
Providing and fixing in position towel rails / ring of approved make (to the approval of Engineer-in-charge ) fixed in with rawl plugs embedded in walls with brass screws complete in all respect.
20mm i/d Cpvc Union
C.P brass towel ring
Providing and fixing in position C.P. brass soap dish of approved make (to the approval of Engineer-in-charge ) fixed into wall with rawl plugs and C.P brass screws complete in all respect.
Providing & Fixing in postion 15 mm i/d bib cock of approved make (to the approval of Engineer-in-charge )complete in all respect.
C.P. brass Bib cock long nose/ long body without flange
C.P Brass bib cock foam flow without flange
25mm i/d Cpvc Union
Providing & Fixing in postion stop cock / Angle valve of approved make (to the approval of Engineer-in-charge ) complete in all respect.
C.P.brass 15mm Angle valve without flange
C.P.brass 15mm Concealed stop cock with flange
Providing & Fixing in position C.P. Brass flange Dome of approved make (to the approval of Engineer-in-charge ) under various fixtures complete in all respect.
Providing & Fixing in position C.P. Brass extension piece 25mm long to 100mm long of approved make (to the approval of Engineer-incharge )with various fixtures complete in all respect. C.P. Brass extension piece, 25mm long to 50mm long
Providing & Fixing in position 5mm thick bevelled edge mirror of superior glass (of approved make) complete with 4mm thick hard board backing fixed in with rawl plugs 50mm, C.P. brass screws and washers and S/S Studs on top complete in all respect (as required by the Engineer-in- Charge) (Size 600mm x 450mm)
Providing and fixing in position premium range C.P. Brass Fittings and accessories of approved make (to the approval of Engineer-in-charge ) complete in all respect. C.P. Brass Accessories:
C.P. brass toilet roll holder with flap
Providing & Fixing in position C.P./Aluminium Khunti of approved make (to the approval of Engineer-in-charge ) fixed into wall with C.P. brass screws and rawl plugs etc. complete in all respect. C.P. Brass khunti with 3 pegs
Providing and fixing in position vitreous Chinaware white channel of approved make (to the approval of Engineer-in-charge) of size 600 mmx100mm including laying and fixing in cement concrete 1:2:4 complete in all respect.
Providing & placing in position on terrace (at all floor levels) HDPE water storage tanks of approved make (to the approval of Engineer -in-charge) with cover with suitable locking arrangement and making necessary holes for inlet, outlet and over flo pipes but without fittings and base support for tank. Tripple Layer Tanks
50mm i/d Cpvc Union
Providing and fixing in position set of EWC and WHB size 46x36 cm for Handicapped person of approved make (to the approval of the Engineer-in-charge) consisting of matching cistern, one pair mounting brackets, seat cover, one no. hinges rail 76cm and 4 no. grab rails 60cm complete in all respect and to the entire satisfaction of Engineer-in-charge. Detail attached as per Table-3
Vitreous white Chinaware Partition Large partition size 75 x 16.5 x 36.5 cm
Providing and fixing in position vitreous Chinaware white laboratory sinks of approved make (to the approval of Engineer-in-charge) consisting of a pair of brackets, C.P. brass waste 40mm complete in all respect.
Size 470mmx370mmx180mm
Construction of Plateform complete as per specification & as desired by Enginer-in-charge
For 2000 ltr Water Tank
Providing and fixing in position SS Grab Bar Grade 304 of approved make (to the approval of the Engineer-in-charge) fixed in to wall with brass screws complete in all respect.
35mm dia 900mm (36”) long
35mm dia 1200mm (48”) long
Foldable U Type 762mm long
Providing and fixing 110 mm dia SWR U.P.V.C Coupling/Sockete for Rain water pipe as per IS:14735 including jointing complete as per specifications and to the entire satisfaction of Engineer- in- charge.
Extra Rate for Third Floor
Screed of 50mm thick cement concrete 1:8:16 with stone aggregate 40mm gaugeto be laid below the topping using mechanical mixer for mixing of material
Total All Floor
Extra rate for First Floor
Extra rate for Second Floor
Extra rate for Third Floor
Total all Floors
Shuttering for faces of concrete foundations and foundation beam & plinth beam (vertical or battering)
Providing and laying Rectified Porcelin floor tiles 400x400mm or more (thickness to be specified by the manufacturer) of premium quality conforming to IS:15622 of approved make in all colours laid on 20mm thick bed of Cement Mortar 1:4 ( 1 Cement : 4 Fine sand) for new flooring complete .
Total All Floor
Extra rate for First Floor
Extra rate for Second Floor
Extra rate for Third Floor
Providing and laying water proofing treatment to vertical and horizontal surfaces of depressed portions of W.C., kitchen and the like consisting of: i) Ist course of applying cement slurry @ 4.4 Kg/ sqm mixed with water proofing compound conforming to IS : 2645 in recommended proportions including rounding off junction of vertical and horizontal surface. ii) IInd course of 20 mm cement plaster 1:3 (1 cement : 3 coarse sand) mixed with water proofing compound in recommended proportion including rounding off junction of vertical and horizontal surface. iii) IIIrd course of applying blown or residual bitumen applied hot at 1.7 kg per sqm of area. iv) IVth course of 400 micron thick PVC sheet. (Overlaps at joints of PVC sheet should be 100 mm wide and pasted to each other with bitumen @ 1.7 Kg/sqm).
Providing and fixing Heat Resistant Terrace Tiles (300 mm x 300 mm x 20 mm) with SRI (solar refractive index) > 78, solar reflection > 0.70 and initial emittance > 0.75 on waterproof and sloped surface of terrace, laid on 20 mm thick cement sand mortar in the ratio of 1:4 (1 cement : 4 coarse sand) and grouting the joints with mix of white cement & marble powder in ratio of 1:1, including rubbing and polishing of the surface upto 3 cuts complete, including providing skirting upto 150 mm height along the parapet walls in the same manner
Total All Floor
Extra Rate for First Floor
Extra Rate for Second Floor
Base course of floor consisting of 100mm thick cement concrete 1:8:16 with stone aggregate 40mm guage and 100mm fine sand filling using mechanical mixer for mixing of material
Extra rate for Fifth Floor
Extra rate for Sixth Floor
Coloured Granite stone tiles 15mm to 20mm thick in skirting, risers of steps, dado walls and pillars laid in 12.5mm thick cement mortar 1:3 (1 cement 3 coarse sand) and jointed with neat cement slurry mixed with pigment to match the shade of stone, including rubbing and polishing including labour for fixing dowel pins and cramps.
Total All Floor
Extra Rate for First Floor
Extra Rate for Second Floor
Base course of floor consisting of 100mm thick cement concrete 1:8:16 with stone aggregate 40mm guage and 100mm fine sand filling using mechanical mixer for mixing of material
Extra rate for Fifth Floor
Extra rate for Sixth Floor
Extra for pre finished nosing to treads of steps of marble stone. ( Full gola, half round gola etc.)
Providing & fixing in position Water Cooler without Stablizer of approved make (to the approval of Engineer-in-charge ) including carriage complete in all respect.
Providing and fixing in position C.P elbow action pillar tap of approved make (to the approval of Engineer-in-charge) complete in all respect. (Difference in cost of between Elbow action pillar tap and Normal Pillar tap)
Providing and fixing P.V.C Waste Pipe Collapsiable 32mm complete in all respect.
Providing and fixing in position C.P. brass bottle trap 32mm dia with 40 mm seal of approved make (to the approval of Engineer-in-charge) complete in all respect.
Providing & fixing in position UV filter having flow rate 200 ltr/hr with 3 stage purification process having 16 watt UV lamp and 35 Watt power rating of approved make (to the approval of Engineer-in-charge ) including carriage and fixing in position complete in all respect.
C.P. brass towel Rails size 15mm dia 610mm long
Providing & Fixing in postion CP Brass Spout Operated Pillar Tap with base flange (for foot operated valve) of approved make (to the approval of Engineer-in-charge) complete in all respect (instead of Pillar tap in Lavatory Suites).
Providing and fixing in position automatic Brass Ball Cock in tanks. Brass Ball Cock with rod and Plastic Ball
Brass Ball Cock with rod and Plastic Ball 50mm i/d
Providing and fixing in position G.I. Tank Nipple of approved make (to the approval of Engineer-in-charge) in PVC Water storage tanks complete in all respect.
G.I. tank nipple 25mm i/d
G.I. tank nipple 50mm i/d
Water Cooler Full Steel Body 150/150 ltr without Stablizer Detail as per Table-3
Water Cooler Semi Steel Body 80/120 ltr Capacity without Stablize
r Detail as per Table-3
Supply and erection of Single phase copper wound Automatic voltage stablizer of suitable capacity electronically controlled circuit with input voltage 140-260 volts single phase AC supply and output voltage 220 ± 5% volts single phase AC supply having main silicon core copper wound step up transformer with suitable nos. of turns on primary side and secondary side the transformer should be fully insulated inside the MS sheet box of suitable size. There should be power control relay and single pole MCB (C-curve, 10kA) of suitable capacity complete with internal copper wiring along with amp. meter and volt meter, high voltage cut off 280 volt input (240 volt output) and 90 volt maximum boost and overloading protection to be provided:- Automatic Voltage Stablizer 2 KVA
Electrical Works
Providing Internal Electrical Installations:
Wiring Computer terminal point having 3 Nos. 6Amp. 2/3 universal socket (shuttered), 1No. 16 Amp. switch with indicator and 1No. blanking plate (Modular accessories).
POINT WIRING:
Ceiling Rose (Flush Piano type)
RECESSED PVC CONDUIT PIPE WIRING SYSTEM WITH MODULAR SWITCHES: Wiring in PVC insulated copper conductor single core FR cable (ISI marked) overall 1.5sq. mm, 1100volts grade to be laid in heavy gauge PVC conduit pipe 20mm/ 25mm dia. (ISI Marked) recessed in wall etc., complete with powder coated/anodized concealed metal boxes (1.6mm thick with Brass lugs) required for suitable number of modules (Modular accessories) for having Step type electronic fan regulators (two module) 100watts, bell push, 6Amp. 2/3 universal socket (shuttered), 16/20Amp. combined/ universal Socket (shuttered), 6/10Amp. Switches, 16/20Amp. switches with indicator etc. and covered with Frame Plate etc., PVC connector (For Fan Box and Call Bell), Steel Hooks, Sheet metal fan box (1.6mm thick shape hexagonal), Circular junction Boxes (Four way PVC 1½" deep for walls and CI 3" deep for ceiling), bonding to earth with PVC insulated copper conductor single core FR cable (ISI marked) 1sq. mm, 1100volts grade (For 6Amp. wall socket & plug control point) and other petty material etc., including the cost of above material, cutting and filling up of chases (with finishing the surface):-
Wiring fan point with sheet metal fan box
Wiring light point
Wiring call-bell point
Wiring 3 pin 6 Amp. wall socket point
Wiring 3 Pin 6 Amp. Plug control comprising wall socket point
Wiring 3 pin 16/20 amp. power plug control point
Wiring light point without control switch.
Supply and erection of Wall Fan Plastic Body 400MM, 16" including flexible wire & petty material etc. for connections and testing complete in all respect as approved and desired by the Engineer in-charges at site.
Wiring light point with double control switches.
RECESSED COMPUTER SUPPLY TERMINAL POINTS (USED FOR HGW, PVC CONDUIT & HDPE PIPE WIRING SYSTEM WITH MODULAR ACCESSORIES): Wiring Computer supply terminal points recessed in wall etc., complete with powder coated/anodized concealed metal boxes required for suitable number of modules (Modular accessories) for having 6Amp. 2/3 universal socket (shuttered), 16/20Amp. combined/ universal Socket (shuttered), 6/10/16/20Amp. Switches and blanking plate etc., and covered with Frame Plate and other petty material etc. including the cost of above material, cutting and filling up of chases (with finishing the surface):-
SUPPLY AND ERECTION OF WIRING ACCESSORIES: Supply and erection of switches, sockets and other accessories (flush piano type/ modular accessories) in the existing bakelite/ modular cover frame including fixing & connections and petty material etc.:-
Call Bell 220/230 volts AC Ding Dong
LED'S FIXTURES & FANS:
Supply and erection of Slim Recessed mounted, Round downlighter 12 watt with Pressure die cast aluminium housing & polycarbonate diffuser with surge protection 10KV and efficacy of LED fixture minimum 100 lumens per watt and operating voltage between 140 to 270 volt, input AC frequency 50 Hz ± 3 %, housing & driver shall be of same brand, supported with LM 79 reports not more than 2 years old from NABL /UL accredited laboratory complete along with erection of the same with connections, testing etc. complete in all respects as approved and desired by the Engineer-in-charge at site. The certification and specifications of the LED Fitting's should be as approved by O/o Advisor (Technical), Govt of Punjab vide Letter no.AT/2021/GL/1410-1422 Dated 06/05/2021. Besides this the lighting fixtures manufactures should have in house NABL accredited laboratory.
Supply and erection of Slim Recessed mounted, Round downlighter 18 watt with Pressure die cast aluminium housing & polycarbonate diffuser with surge protection 10KV and efficacy of LED fixture minimum 100 lumens per watt and operating voltage between 140 to 270 volt, input AC frequency 50 Hz ± 3 %, housing & driver shall be of same brand, supported with LM 79 reports not more than 2 years old from NABL /UL accredited laboratory complete along with erection of the same with connections, testing etc. complete in all respects as approved and desired by the Engineer-in-charge at site. The certification and specifications of the LED Fitting's should be as approved by O/o Advisor (Technical), Govt of Punjab vide Letter no.AT/2021/GL/1410-1422 Dated 06/05/2021. Besides this the lighting fixtures manufactures should have in house NABL accredited laboratory.
Supply and erection of LED batten 20 Watt LED (including constant LED driver) with High quality extruded aluminium with efficacy of LED fixture minimunm 100 lumens per watt and operating voltage between 140 to 270 volt, THD <10% ingress protection IP20 (as per latest BIS standards) surge protection - 2.5 KV and above (as per IS/IEC standards) wattage of each low power LED less than 1 watt input AC frequency 50 Hz ± 3 % with 5 year warranty including there drivers complete along with erection of the same with connections, testing etc. complete in all respects as approved and desired by the Engineer-in-charge at site. LED Fitting as per Specifications approved by Hon. Tech. Advisor to CM Punjab vide Letter ION No: AT/2021/GL/1410-1422, Dated: 06.05.2021. Besides this the lighting fixtures manufactures should have in house NABL accredited laboratory.
Supply and erection of LED batten 40 Watt LED (including constant LED driver) with High quality extruded aluminium with efficacy of LED fixture minimunm 100 lumens per watt and operating voltage between 140 to 270 volt, THD <10% ingress protection IP20 (as per latest BIS standards) surge protection - 2.5 KV and above (as per IS/IEC standards) wattage of each low power LED less than 1 watt input AC frequency 50 Hz ± 3 % with 5 year warranty including there drivers complete along with erection of the same with connections, testing etc. complete in all respects as approved and desired by the Engineer-in-charge at site. LED Fitting as per Specifications approved by Hon. Tech. Advisor to CM Punjab vide Letter ION No: AT/2021/GL/1410-1422, Dated: 06.05.2021. Besides this the lighting fixtures manufactures should have in house NABL accredited laboratory.
Supply and erection of Recessed mounted 36watt LED panel (including LED driver) with CRCA sheet having efficacy of LED fixture minimunm 100 lumens per watt and operating voltage between 140 to 270 volt, THD <10% ingress protection IP20 (as per latest BIS standards) surge protection - 2.5 KV and above (as per IS/IEC standards) wattage of each low power LED less than 1 watt input AC frequency 50 Hz ± 3 % with 5 year warranty including there drivers complete along with erection of the same with connections, testing etc. complete in all respects as approved and desired by the Engineer-in-charge at site. LED Fitting as per Specifications approved by Hon. Tech. Advisor to CM Punjab vide Letter ION No: AT/2021/GL/1410-1422, Dated: 06.05.2021. Besides this the lighting fixtures manufactures should have in house NABL accredited laboratory.
Supply and erection of BEE 3-Star rating AC Ceiling Fan 1200mm (48") suitable for 230 V single phase with double ball bearing, copper wound, full aluminium body, 3Nos. of blades, white in colour. The mounting type is down rod mount. The product should possess a minimum air deleivery of 210 CMM (approx.). The rated speed of the the product must be minimum of 300 revolutions per minute and 5Nos. of speeds. The product should have a manufcaturer's guarantee /warranty of minimum 2 years. The product should be complete in all aspects with fan motor, bladeset, down rod, conopy
set, shackle kit, twisted wire etc., including erection & testing of ceiling fan having connection with PVC insulated PVC sheathed two single core copper conductor (FR) cable 0.75 sq. mm complete in all respects as per satisfcation of the Engineer in-charge at site.
Supply and erection of Heavy duty Exhaust Fan 300mm, 900RPM with aluminium louver shutter, double ball bearing longer life including flexible wire & petty material etc. for connections and testing complete in all respect as approved and desired by the Engineer in-charges at site.
OCCUPANCY SENSORS:
Overall size 1.5sq.mm (Un-sheathed)
Overall size 2.5sq.mm (Un-sheathed)
Supply and erection of Ceiling mounted Occupancy based PIR sensor (360° detection angle motion detector) with installation height 3mts, 8.5 Amps resistive load, Detection dia 8M, time delay - 5s to 59 mins , Light level threshold - 5 to 1275 Lux, IP - 20, Sensitivity Adjustment, Walk LED test, with additional options like walkthrough, daylight set point, vacancy complete in all respect as approved and desired by the Engineer in-charges at site.
SUSPENSION RODS FOR CEILING FANS:
HEAVY GUAGE WELDED CONDUIT PIPES: Supply & erection of Heavy guage welded conduit pipe (ISI marked) as per IS:9537:Part-II for wiring purposes including bends, junction boxes, Steel hooks, GI saddle clamps and other petty materials etc., where necessary including painting as per PWD General Specifications:-
Overall size 16sq.mm (Un-sheathed)
Supply & erection of 19/20mm dia. M.S. conduit pipe (1.6mm thick), white painted suspension rod for ceiling fan.
CONDUIT PIPE & COPPER WIRES:
PVC, HDPE PIPES & PVC FLEXIBLE PIPES: Supply & erection of PVC Conduit Pipes (ISI marked) as per IS9537:Part-III & HDPE pipes (ISI marked) as per IS:4984:1995 for wiring purposes including bends, junction boxes, Steel hooks, M.S. saddle clamps and other petty materials etc., as per PWD General Specifications:-
Heavy gauge PVC conduit pipe 20mm dia. (ISI marked) Flushed
Heavy gauge PVC conduit pipe 25mm dia. (ISI marked) Flushed
Heavy gauge PVC conduit pipe 32mm dia. (ISI marked) Flushed
Cable End Box for TPN Vertical 4/8/12Way
Heavy gauge PVC conduit pipe 40mm dia. (ISI marked) Flushed
MCB Single Pole 6-32amp. (10kA, Curve-C)
MCB Four Pole 40amp. (10kA, Curve-C)
MCB Four Pole 50, 63amp. (10kA, Curve-C)
PVC INSULATED SINGLE CORE FR COPPER CONDUCTOR CABLE: Supply and erection of PVC insulated FR single core Unsheathed copper conductor cable (ISI marked) suitable upto 1100 volts grade confirm to IS:694/1990 left bare in pipe or casing of suitable size complete in all respect as desired by the Engineer-in-charge:-
Overall size 1sq.mm (Un-sheathed)
Overall size 4sq.mm (Un-sheathed)
Overall size 6sq.mm (Un-sheathed)
Overall size 10sq.mm (Un-sheathed)
Overall size 25sq.mm (Un-sheathed)
SUB DISTRIBUTION SYSTEM:
SHEET METAL DOUBLE DOOR DISTRIBUTION BOARD FOR MCB/ RCBO/ RCCB's: Supply and erection of sheet metal Double Door Distribution Boards IP 43- IK09 metal door (dust protected) as per IS 8623-1&3, IEC 61439-1&3 suitable for flush mounting with fully insulated copper busbars, shrouded neutral bars, earth bars, cement spill protector, colorcoded interconnecting wire set, cable ties, blanking plates and circuit identifications label and of required no. of ways for mounting miniature circuit breakers/ RCBO's/ RCCB's in the distribution board (For SP&N distribution board with provision DP MCB's/ RCCB's/ RCBO's as incomer and SP MCB's as outgoings and for TP&N horizontal distribution board with provision TPN/ FP MCB's/ RCCB's/ RCBO's as incomer and SP MCB's as outgoings) as per PWD General specifications including connections with suitable size of thimbles and bonding to existing earth etc:-
TP&N Vertical Double Door Distribution Board 4 way each.
TP&N Vertical Double Door Distribution Board 8 way each.
Supply and erection of sheet metal Cable End Box (Make is same as MCB Distribution Board) mounting on the top or bottom of the MCB Distribution Board (Either Horizontal or Vertical) to keep loose wires & cables as per PWD General specifications including petty materials etc as required:-
MINIATURE CIRCUIT BREAKERS: Supply and erection of Miniature Circuit Breaker MCB's for circuit protection against overload and short circuit current fault suitable for 240/ 415 volts 50cycles AC supply with breaking capacity of 10kA, Curve-C and low watt losses as per IS/IEC 60898-1, energy limitation class-3, true contact indication, label holder facility in the existing MCB distribution board as per PWD General Specifications including connections with suitable size of thimbles/lugs:-
MAIN DISTRIBUTION SYSTEM:
MAIN VERTICAL DISTRIBUTION BOARD (EMERGENCY): TPN 4Way to feed MCB DB's (EMERGENCY LOAD) ON GROUND FLOOR
Supply and erection of sheet metal double door vertical distribution boards IP 43-IK09 metal door (dust protected) as per IS:8623-1&3, IEC 61439-1&3 suitable for flush mounting with fully insulated copper busbars for each phase, 2 Nos. shrouded neutral bars, 2Nos. earth bars, cement spill protector, color-coded interconnecting wire set, cable ties, blanking plates and circuit identifications label and of required no. of ways for mounting MCCB's as incomer and outgoings SP/TP miniature circuit breakers in the distribution board as per PWD General specifications including connections with suitable size of thimbles and bonding to existing earth etc.:-
TP&N Double Door Vertical DB's 8 way each (With provision of FP MCCB upto 125amp)
Overall size 25sq.mm (Un-sheathed)
TP&N Double Door Vertical DB's 12 way each (With provision of FP MCCB upto 125amp)
MCCB's (MOULDED CASE CIRCUIT BREAKER): Supply and erection of Moulded Case Circuit Breaker (Panel mounting Cubical type) in the existing Cubical Panel (confirm to IEC:60947-2) having Ics=100% Icu, 100% neutral with spreader links and relevant PWD general specifications complete with G.I. Bolts, Nuts & Connection on both sides of MCCB with suitable size of thimbles etc:-
MCCB Four Pole 100amp., 415volts, ≥25kA Fixed Magnetic and Adjustable Thermal Setting
RISING MAIN: (IN ELECTRICAL ROOM)
Supply and erection of PVC flexible pipe complete without compression glands, locking arrangement, check-nuts as required:-
EMERGENCY RISING MAIN:
Supply, Installing testing and commissioning of 400A, 25KA Air Insulated Type Rising Mains for use on 3 phase 4 wire 415 V, 50Hz A.C. supply with enclosure having IP-54 rating after fixing the tap off boxes and all accessories, made of 1.6mm thick steel sheet duly powder coated in convenient sections complete with 4 Nos. aluminium bus bars having current density of 130 A/ sq cm at nominal current rating, necessary joints & expansion joints, fire barrier at each floor, provision of tapping at every meter, continuous earthing with 2 Nos. aluminium strip of suitable size (one on each side) including, G.I. clamping brackets, angle iron bracket, steel fasteners, connecting to earthing system etc. as required complete in all respects as approved and desired by the Engineer-in-charge at site.
Supply, installation, testing & commisioning of 400 Amp Main End Feed Unit Box (with provision of MCCB but without MCCB )on the existing Air Insulated rising mains for use on 3 phase 4 wire 415 V, 50Hz A.C supply with Flange End, Rotary Handel, box made with 1.6mm thick G.I sheet steel enclosure (IP54) duly powder coated complete in all respects as approved and desired by the Engineer-in-charge at site.
NORMAL RISING MAIN:
Supply, Installing testing and commissioning of 250A, 25KA Air Insulated Type Rising Mains for use on 3 phase 4 wire 415 V, 50Hz A.C. supply with enclosure having IP-54 rating after fixing the tap off boxes and all accessories, made of 1.6mm thick steel sheet duly powder coated in convenient sections complete with 4 Nos. aluminium bus bars having current density of 130 A/ sq cm at nominal current rating, necessary joints & expansion joints, fire barrier at each floor, provision of tapping at every meter, continuous earthing with 2 Nos. aluminium strip of suitable size (one on each side) including, G.I. clamping brackets, angle iron bracket, steel fasteners, connecting to earthing system etc. as required complete in all respects as approved and desired by the Engineer-in-charge at site.
Supply, installation, testing & commisioning of 250 Amp Main End Feed Unit Box (with provision of MCCB but without MCCB )on the existing Air Insulated rising mains for use on 3 phase 4
wire 415 V, 50Hz A.C supply with Flange End, Rotary Handel, box made with 1.6mm thick G.I sheet steel enclosure (IP54) duly powder coated complete in all respects as approved and desired by the Engineer-in-charge at site.
Supply, installation, of Tap off box for with provision of MCCB Four Pole 40-63Amp. (Excluding MCCB Cost) complete in all respects as approved and desired by the Engineer-in-charge at site.
Supply, installation, of Tap off box for with provision of MCCB Four Pole 80-100Amp. (Excluding MCCB Cost) complete in all respects as approved and desired by the Engineer-in-charge at site.
MCCB Four Pole 63amp., 415volts, ≥25kA Fixed Magnetic and Adjustable Thermal Setting
MCCB Four Pole 80-100amp., 415volts, ≥25kA Fixed Magnetic and Adjustable Thermal Setting
MCCB Four Pole 400amp., 415volts, ≥36kA Microprocessor Based Adjustable Thermal and Magnetic Setting
Supply, installation, testing & commisioning of 250 Amp Main End Feed Unit Box (with provision of MCCB but without MCCB )on the existing Air Insulated rising mains for use on 3 phase 4
wire 415 V, 50Hz A.C supply with Flange End, Rotary Handel, box made with 1.6mm thick G.I sheet steel enclosure (IP54) duly powder coated complete in all respects as approved and desired by the Engineer-in-charge at site.
MCCB Four Pole 250amp., 415volts, ≥36kA Microprocessor Based Adjustable Thermal and Magnetic Setting
Supply, installation, of Tap off box for with provision of MCCB Four Pole 80-100Amp. (Excluding MCCB Cost) complete in all respects as approved and desired by the Engineer-in-charge at site.
PVC flexible pipe 40mm dia.
Supply, installation, testing & commisioning of 250 Amp Main End Feed Unit Box (with provision of MCCB but without MCCB )on the existing Air Insulated rising mains for use on 3 phase 4
wire 415 V, 50Hz A.C supply with Flange End, Rotary Handel, box made with 1.6mm thick G.I sheet steel enclosure (IP54) duly powder coated complete in all respects as approved and desired by the Engineer-in-charge at site.
Supply and erection of Compression glands, Locking arrangement, Checknuts for PVC flexible pipe complete with as required:-
Supply, installation, of Tap off box for with provision of MCCB Four Pole 80-100Amp. (Excluding MCCB Cost) complete in all respects as approved and desired by the Engineer-in-charge at site.
PVC compression Socket gland 40mm dia.
Supply, installation, testing & commisioning of 250 Amp Main End Feed Unit Box (with provision of MCCB but without MCCB )on the existing Air Insulated rising mains for use on 3 phase 4
wire 415 V, 50Hz A.C supply with Flange End, Rotary Handel, box made with 1.6mm thick G.I sheet steel enclosure (IP54) duly powder coated complete in all respects as approved and desired by the Engineer-in-charge at site.
INDOOR LT PANELS: FOR MAIN BUILDIING
Supply, installation, of Tap off box for with provision of MCCB Four Pole 80-100Amp. (Excluding MCCB Cost) complete in all respects as approved and desired by the Engineer-in-charge at site.
MAIN LT PANEL ( FOR MAIN BUILDING LOAD)
Designing, Supply, Erection, Testing & commissioning of indoor Type TTA LT cubical panel enclosure (dust, vermin and interchangeable modules with facilites for extensions or reduction as per the space or requirments). The Panel shall be suitable for operation at 415+6% Volts, 50HZ, 3 phase 4 wire & earth system. The assembly manufacture should be ISO approved and CPRI tested for short circuit of (minimum 50kA) as well as IP degree of protection (IP44). Fabrication: Panel shall be made from 14/16 SWG CRCA sheet, conforming to IS:8623. The fabrication should be such that all the member i.e. vertical/horizontal should be detachable type i.e. total bolted. In case of any changes required at site should be possible then and their self without any cutting or welding. The fabrication of the panel in 3B construction fully compartmentalized type i.e. bus bar channel as well as the cable chamber should be totally isolated from the feeder chamber. Where the crossing of the wire or bus link should have proper rubber gourmets or non-hygroscopic material. No live part should be in visible condition. The base channel will be made out of 75mm x 40mm x 5mm rolled channel. "The door should be double folded without edge and the gasket should be ‘S’ type puffed neutral rubber gasket for long life. The hinges of the door should be bolted type with double hole arrangement. The panel door lock should be quick openable type spring loaded. There should not be any special tool or key to open the lock. Minimum depth 400mm / wide 300 mm for busbar/ Cable ally at the front of the panel. The panel will be free standing floor mounting type having provision for cable entry from bottom/top with cable glands etc.
gainst overload & shortcircuit with setting at 50%-100%-OFF, suitability for isolation as per IEC 60947-2. The ACB should be capable for recording 10 fault history, LCD Display of current & voltage, Icu = Ics = Icw (1 Sec.) = 50kA = 1Nos. Outgoings: ■ Air Circuit Breaker Four Pole, 1000amp., 415volts (Electrical Draw-Out Type) = 1No. ■ Air Circuit Breaker Four Pole, 1250amp., 415volts (Electrical Draw-Out Type) = 1No. ■ 400amp. 415 volts breaking capacity ≥36kA, FP microprocessor based adjustable thermal and magnetic protection MCCB unit = 1No. ■ 250A 415V breaking capacity ≥36kA 4P microprocessor based adjustable thermal and magnetic protection MCCB unit = 7Nos. ■ MCB Four pole 40amp. (Breaking capacity 10kA, Curve-C) suitable for 240/ 415 volts 50cycles AC supply = 3Nos. ■ MCB Four pole 63amp. (Breaking capacity 10kA, Curve-C) suitable for 240/ 415 volts 50cycles AC supply = 3Nos.
■ All Incomers & Out going With Extendable Rotary Handle with adjustable depth complete as per schematic diagram attached & Satisfaction of the Engineer in charge at site. Enclosure: Panel Size: As per Norms
APFC FOR 1600KVA TRANSFORMERS:
MCCB Four Pole 100amp., 415volts, ≥25kA Fixed Magnetic and Adjustable Thermal Setting
Heavy gauge PVC conduit pipe 40mm dia. (ISI marked) Flushed
MCB Four Pole 50, 63amp. (10kA, Curve-C)
SYNCHRONIZATION AMF PANEL ( FOR MAIN BUILDING EMERGENCY LOAD)
SUB LT PANEL PANEL (EMERGENCY) ( FOR MAIN BUILDING EMERGENCY LOAD)
Incomer: Air Circuit Breaker Four Pole, 1250amp., 415volts (Electrical Draw
MAIN LT PANEL (BUILDING HVAC LOAD):
LT PANELS & MCCB's (MOULDED CASE CIRCUIT BREAKERS): Designing, Supply, Erection, Testing & commissioning of indoor Type LT cubical panel enclosure (dust, vermin and interchangeable modules with facilites for extensions or reduction as per the space or requirments). The Panel shall be suitable for operation at 415+6% Volts, 50HZ, 3 phase 4 wire & earth system. The assembly manufacturer should be ISO approved and CPRI tested for short circuit of (minimum 50kA) as well as IP degree of protection (IP 54/55). Fabrication: Panel shall be made from 14/16 SWG CRCA sheet, conforming to IS 8623/1977-82. The sheet metal used for the fabrication of control panel will be 2mm for load bearing member’s door and fittings plates etc. the partitions and other non load bearing members will be fabricated out of 1.6mm sheet, the sheet will be of mild steel CRCA type. The base channel will be made out of 75 x 40 x 5mm rolled channel. The door should be double folded without edge and the gasket should be ‘S’ type puffed neutral rubber gasket for long life. The hinges of the door should be bolted type with double hole arrangement. The panel door lock should be quick openable type spring loaded. There should not be any special tool or key to open the lock. Minimum depth 400mm / wide 300 mm for busbar/ Cable ally at the front of the panel. The panel will be free standing floor mounting type having provision for cable entry from bottom/top with cable glands etc. The fabrication should be such that all the member i.e. vertical/horizontal should be detachable type i.e. total bolted. In case of any changes required at site. it should be possible then and their self without any cutting or welding. The fabrication of the panel in 3B construction fully compartmentalized type i.e. bus bar chamber as well as the cable chamber should be totally isolated from the feeder chamber. Where there crossing of the wire or bus links. It s
hould have proper rubber gourmets or non-hygroscopic material. No live part should be in visible condition. Painting: The sheet metal is sprayed with corrosion resistant etch Primer. The finishing treatment shall be applicable with air drying paint (7/9 tank Powder coated process should present in company pemises) after necessary putty work .
Fixing additional Length of earthing with 8 S.W.G. (4mm dia.) copper wire in G.I. pipe with sockets, elbows, steel hooks and GI saddle clamps including painting etc.:-
LT PANEL-1 (EMERGENCY SERVICES): FOR 6NOS. LIFTS & 4NOS. MODULAR OT'S:
LT Panel enclosure having space for 1No. Incomer MCCB 400Amp. and 8Nos. outgoing MCCB's 40amp. to 160amp. according to the requirement at site (Approx. size 1750 x 1750 x 400mm) (DETAIL SEE IN PANEL INVENTORY)
LT PANEL-2 (EMERGENCY SERVICES): FOR X-RAY MACHINES & STERLIZATION UNITS:
LT PANEL-2 (EMERGENCY SERVICES): FOR X-RAY MACHINES & STERLIZATION UNITS:
LT Panel enclosure having space for 1No. Incomer MCCB 400Amp. and 4Nos. outgoing MCCB's 100amp. to 160amp. according to the requirement at site (Approx. size 2025 x 1100 x 400mm) (DETAIL SEE IN PANEL INVENTORY)
MCCB's (MOULDED CASE CIRCUIT BREAKER): Supply and erection of Moulded Case Circuit Breaker (Panel mounting Cubical type) in the existing Cubical Panel (confirm to IEC:60947-2) having Ics=100% Icu, 100% neutral with spreader terminal links, Extended rotary handle and relevant PWD general specifications complete with G.I. Bolts, Nuts & Connection on both sides of MCCB with suitable size of thimbles etc
MCCB Four Pole 40/63/80/100amp., 415volts, ≥25kA Fixed Magnetic and Adjustable Thermal Setting
MCCB's WITH MS SHEET ENCLOSURE FOR X-RAY MACHINES, STERLIZATION UNITS)
MS SHEET ENCLOSURE FOR MCCB's: Supply & Erection of indoor type MCCB enclosure of suitable size having provision for MCCB with extended rotary handle. The Enclosure shall be made from 14/16 SWG CRCA sheet, confirming to IS 8623/1977-82. The door should be double folded without edge and the gasket should be ‘S’ type puffed neutral rubber gasket for long life. The hinges of the door should be bolted type with double hole arrangement. The Enclosure door lock should be quick openable type spring loaded. There should not be any special tool or key to open the lock. The Enclosure will be wall mounting type having provision for cable entry from bottom/top with cable glands etc. The sheet metal is sprayed with corrosion resistant etch primer. The finishing treatment shall be applicable with air drying paint (7/9 tank Powder coated process should present in company pemises) after necessary putty work:-
MS Sheet Enclosure having provision for MCCB 40-160Amp.with extended rotary handle (Approx. Size 500mm x 300mm x 200mm)
MCCB's (MOULDED CASE CIRCUIT BREAKER): Supply and erection of Moulded Case Circuit Breaker (Panel mounting Cubical type) in the existing Cubical Panel (confirm to IEC:60947-2) having Ics=100% Icu, 100% neutral with spreader links and relevant PWD general specifications complete with G.I. Bolts, Nuts & Connection on both sides of MCCB with suitable size of thimbles etc:-
MCCB Four Pole 63amp., 415volts, ≥25kA Fixed Magnetic and Adjustable Thermal Setting (For 1No. X-Ray Machine & 2Nos. Sterlization Units)
MCCB Four Pole 100amp., 415volts, ≥25kA Fixed Magnetic and Adjustable Thermal Setting (For 1No. X-Ray Machine)
EARTHING SYSTEM (INDOOR):
COPPER EARTHING 8SWG :- Earthing with 8 SWG (4mm dia.) electrolytic copper wire thimbled (1No. copper thimble with suitable size steel bolt, washers & double nut) with 30cm x 60cm x 2mm thick copper plate (made cylindrical) burried below ground level in the hole of excavation having bore dia. 125mm and surrounded by salt & charcoal dust mixture (20 kg.) including fixing the copper wire run through 20mm dia. G.I. pipe (A-Class) recessed in wall and in floor etc., up to suitable Length in metre (including bore Length). G.I. pipe 20mm dia. (A-class) of suitable Length should be laid in the hole of excavation 1 feet below ground level and having GI Reducer 50mm x 20mm with PVC Cap (For pouring water) fixed on the top level of the pipe. 300mm x 300mm x 300mm deep haudi of First class bricks finished with 1:4 cement plaster and haudi covered with cast iron lid having size 300mm x 300mm (Heavy) around the hole of excavation:-
Earthing with 8 SWG (4mm dia.) copper wire thimbled with 30cm x 60cm x 2mm thick copper plate burried 10.50 metre (34.44 feet) below ground level (up to 14metre in Length) with G.I. pipe 20mm dia. (A-class), 9metre long
Additional Length copper wire 8 S.W.G. (4mm dia.) in 20mm dia. G.I. pipe (Flushed)
COPPER EARTHING :- (Upto 14 metre in Length):-Earthing with electrolytic Copper Tape rivetted (with 5Nos. copper rivets)/Steel Nut & bolts (with 4Nos. 32mm long, 8mm thick with washer and double nut) to 30cm x 120cm x 2mm thick copper plate (made cylindrical) burried 10.50 metre (34.44 feet) below ground level in the hole of excavation having bore dia. 125mm and surrounded by salt & charcoal dust mixture (20 kg.) including fixing the Copper Tape recessed in wall and in floor etc., up to 14metre in Length (including bore Length). G.I. pipe 20mm dia. (A-class), 9metre long should be laid in the hole of excavation 1 feet below ground level and having GI Reducer 50mm x 20mm with PVC Cap (For pouring water) fixed on the top level of the pipe. 300mm x 300mm x 300mm deep haudi of First class bricks finished with 1:4 cement plaster and haudi covered with cast iron lid having size 300mm x 300mm (Heavy) around the hole of excavation:-
Earthing with 20mm x 3mm Copper Tape (upto 14Metre in Length)
Earthing with 25mm x 3mm Copper Tape (upto 14Metre in Length)
Earthing with 40mm x 5mm Copper Tape
(upto 14Metre in Length)
COPPER EARTHING STRIP (As Additional Length): Fixing additional Length of earthing with Copper Tape (On Surface/Flushed) with petty material as required etc.:-
Additional Length 20mm x 3mm thick Copper Tape .
Additional Length 25mm x 3mm thick Copper Tap
Additional Length 25mm x 5mm thick Copper Tap
Additional Length 40mm x 5mm thick Copper Tape
INDOOR LT CABLES, CABLE TRAY, DWC PIPE , BRASS GLANDS & THIMBLES:
XLPE INSULATED UN-ARMOURED CABLES (LOOSE):- Supply, laying and erection of aluminium conductor XLPE insulated PVC sheathed Un-armoured and served cable 1100 volts grade as per IS 7098 (Part-1)1988 to be laid loose in the existing trench or pipe as per PWD General Specifications:-
Overall size 6sq.mm (2Core) Un-armoured (Loose)
Overall size 16sq.mm (4 Core) Un-armoured (Loose)
Overall size 150sq.mm (3½ Core) Un-armoured (Loose)
Overall size 240sq.mm (3½ Core) Un-armoured (Loose)
Overall size 300sq.mm (3½ Core) Un-armoured (Loose)
Overall size 400sq.mm (3½ Core) Un-armoured (Loose)
CABLE TRAY: Supply and erection of MS perforated cable tray (MS Sheet thickness 2mm) with DA gray paint on the existing surface with the help of MS angle iron support (to be painted with approved paint) of size 50mm x 50mm x 6mm thick to be fixed with fastners/ nut & bolts etc., complete in all respect as desired by the Engineer-in-charge and as per PWD General Specifications:-
Cable Tray Size 300mm x 50mm x 50mm (2mm thick)
Cable Tray Size 450mm x 50mm x 50mm (2mm thick)
Aluminium thimble cable Core size 120sq.mm
DOUBLE WALLED CORRUGATED (DWC) HDPE PIPES: Supply and erection of Double Walled Corrugated (DWC) HDPE pipe to be laid 1/2mtr. below ground level including excavation placing the pipe in position and back filling with excavated soil etc. of the required size:-
Double walled corrugated (DWC) HDPE pipe 63/51 mm (outer/ inner dia.)
Double Walled Corrugated HDPE Pipe 90/76mm (Outer/ Inner dia.)
Double walled corrugated (DWC) HDPE pipe120/103.50mm (outer/ inner dia.)
Double Walled Corrugated HDPE Pipe 160/ 136mm (Outer/ Inner dia.)
Double Walled Corrugated HDPE Pipe 180/152mm (Outer/ Inner dia.)
Supply and erection of heavy duty brass single compression gland for cable end termination duly complete with checknuts etc. including making necessary connections:-
Brass Gland for Aluminium cable 2/3/4 Core size 6sq.mm
Brass Gland for Aluminium cable 2/3/4 Core size 16sq.mm
Brass Gland for Aluminium cable 2/3/3½/4 Core size 150sq.mm
Brass Gland for Aluminium cable 3/3½/4 Core size 240sq.mm
Brass Gland for Aluminium cable 3/3½/4 Core size 300sq.mm
Brass Gland for Aluminium cable 3/3½/4 Core size 400sq.mm
Supply and erection of heavy duty aluminium thimbles/lugs for cable end termination duly crimped including making necessary connections completely:-
Aluminium thimble cable Core size 4 - 6sq.mm
Aluminium thimble cable Core size 10 -16sq.mm
Aluminium thimble cable Core size 70sq.mm
Aluminium thimble cable Core size 150sq.mm
Aluminium thimble cable Core size 240sq.mm
Aluminium thimble cable Core size 300sq.mm
Aluminium thimble cable Core size 400sq.mm
Supply and erection of heavy duty Copper thimbles/lugs for cable end termination duly crimped including making necessary connections etc. completely:-
Copper thimble cable Core size 4 - 6sq.mm
Supply and erection of heavy duty Copper thimbles/lugs for cable end termination duly crimped including making necessary connections etc. completely:-
Copper thimble cable Core size 10 - 16sq.mm
MCCB Four Pole 63amp., 415volts, ≥25kA Fixed Magnetic and Adjustable Thermal Setting (For 1No. X-Ray Machine & 2Nos. Sterlization Units)
SAFETY EQUIPMENTS:
Providing and fixing of 4.5 Kg. Capacity FIRE EXTINGUISHER,CO2 type as per IS:15683 complete with all accessories as per Manufactures Specification. ISI Mark complete in all respect
Providing and fixing of 6 Kg. Capacity FIRE EXTINGUISHER, ABC Powder type (stored pressure) asper IS:15683 complete with all accessories as per Manufactures Specification. ISI Mark complete in all respect
Providing Advance Lightning Protection System:
COPPER EARTHING STRIP (As Additional Length): Fixing additional Length of earthing with Copper Tape (On Surface/Flushed) with petty material as required etc.:-
Supply, erection, testing & commisioning of Early Streamer Emission (ESE) type Lightning Protection Complete with Lightning Air Terminal. The System should be corrosion resistant stainless steel chrome body capable of working in hazardous atmosphere and protecting against direct Lightning point as well conducting /diverting it to earth completely after tracing the Lightning in advance. As per NF C 17-102:2011 the air terminal should be tested for Lightning impulse current (10/350 micro sec) =100 KA and for local certification the air terminal should be tested for switching impulse current of 40 KA (8/20 micro sec) as per CPRI with 5 positive and 5 negative impulse. The ESE Terminals shall offer a protection radius of 79mtr., Level-1 High Protection and preferably to be mounted on roof top and center of the building / blocks with the highly insulated polyplastic adaptor with the Mast. (Its working principle evolves from local electrostatic field that develops naturally around the system as a thunderstorm begins to gather. In the event of descending lightning, an inbuilt triggering device generates high tension pulses at the conductor tip, causing a ‘corona effect’.) complete in all respect as approved and desired by the Engineer in-charges at site. Protection radius of 79Mtr at level 1 & 107 Mtr at level 4
hould have proper rubber gourmets or non-hygroscopic material. No live part should be in visible condition. Painting: The sheet metal is sprayed with corrosion resistant etch Primer. The finishing treatment shall be applicable with air drying paint (7/9 tank Powder coated process should present in company pemises) after necessary putty work .
Supply and fixing of GI Mast 5 mtr. height along with suitable base plate for mounting the terminal along with highly insulated adopter to mount ESE Air Terminal with the Mast.The Adapter shall have suitable Metal connector /Connecting point in such a way the top portion shall be electrically connected to the central tip of the ESE terminal and bottom portion connected to the down conducto, stray wires along with support shall be securely fixed with base plate and gauge wires where ever required complete in all respect as approved and desired by the Engineer in-charges at site.
Supply and installation of Lightning Strike Counter (6 digit display) of non-resettable (electromechanical) type which allows the automatic counting of the strikes received by the lightning protection system. This information is used to enhance lightning protection security & increase the effectiveness of inspection & maintenance procedures. It should be in IP-65 enclosure with minimum sensitivity of 1KA and maximum capacity 100KA. No external power source is required. It should be installed always 2 mtrs. above the ground level complete in all respect as approved and desired by the Engineer in-charges at site.
Supply & erection of test Link of non-corroding, weather proof, water proof polycarbonate IP 65/55 enclosure including providing of 2 Nos. of insulated supports with suitable holes prefitted nuts & bolts to fix the down conductor & earth wire. The transparent cover fitted at approximately 500-1000mm from ground level shall be provided on each down conductor complete in all respect as approved and desired by the Engineer in-charges at site.
Supply, installati
SUB LT PANEL PANEL (EMERGENCY) ( FOR MAIN BUILDING EMERGENCY LOAD)
PVC, HDPE PIPES & PVC FLEXIBLE PIPES: Supply & erection of PVC Conduit Pipes (ISI marked) as per IS9537:Part-III & HDPE pipes (ISI marked) as per IS:4984:1995 for wiring purposes including bends, junction boxes, Steel hooks, M.S. saddle clamps and other petty materials etc., as per PWD General Specifications:-
on & testing of chemical earthing (Maintenance Free Earthing) system with UL approved copper bonded rod and exothermically welded copper busbar both tested by CPRI at 50kA Fault Current. A copper bonded steel rod shall have 3000 mm length and 17.2 mm dia. with copper coating thickness of minimum 250 microns. Along with earth enhancement compound tested by ROHS complying IEC 62561-7 in a sealed bag of minimum 50 kg (25 kg Bag x 2). A copper clad steel solid ground wire of 8 mm dia. for interconnecting earth pits. Each earth pit shall be covered with heavy duty weather proof environment friendly polyplastic earth pit chamber. The grounding minerals should not be pollute the ground water. The grounding minerals shall be tested & certified for the resistivity of less than 0.12 ohm-mtr complete in all respect as approved and desired by the Engineer in-charges at site.
Heavy gauge PVC conduit pipe 32mm dia. (ISI marked) Flushed
Cost of pole foundation with earth work in excavation in foundations trenches etc. 0.25 meter below ground level, Cement Concrete 1:4:8 with stone ballast, Reinforced cement concrete M-20,Cold twisted deformed (Ribbed/tor Steel Bar) Bars Fe 500 grade as per IS 1786-2008 complete in all respect as desired by engineer in charge.
Heavy gauge PVC conduit pipe 40mm dia. (ISI marked) Flushed
MCB Single Pole 6-32amp. (10kA, Curve-C)
PVC INSULATED SINGLE CORE FR COPPER CONDUCTOR CABLE: Supply and erection of PVC insulated FR single core Unsheathed copper conductor cable (ISI marked) suitable upto 1100 volts grade confirm to IS:694/1990 left bare in pipe or casing of suitable size complete in all respect as desired by the Engineer-in-charge:-
Overall size 70sq.mm (Un-sheathed) (Conductor connected the air terminal to earthing)
Providing 6Nos. Passenger Lifts (3No. 13 Passenger, 7Stops & 3Nos. 26 Passenger, 7Stops) & 2Nos. Dumbwaitor (2Stops):
Other Features: 1. Battery operated emergency light with rechargeable battery 2. Battery operated emergency alarm with rechargeable battery 3. Adjustable Guide shoes 4. Micro movement LED based buttons 5. Door Open and Close buttons 6. Emergency Intercom provided inside the elevator 7. Emergency Intercom usable without the voice communication 8. Load weighing device with overload bypass feature and Overload function with Audio Visual Indication 9. Steel items, door frames sill angle's, fascia plates, spring buffers 10. Automatic phase reversal device and Phase Failure protection 11. Call registration 12. Audio & Video System installted in the lift indicating arrival at a floor 13. Manual break lever 14. Additional car gate lock 15. Automatic break testing infrared safety curten 16. Braille Buttons (Inside and outside) with Braille instructions for the communication system 17. Kick plate/Skirting 18. Lift anoucement system to announce floor level's in english language only and indication of door for entrance / exit is either Open or Close 19. Car Operating Panel 20. Car plateform constructed out of cold rolled grain oreinted formed sheets of steel 21. Phase two device fire man drive 22. Fire Man switch at main lobby 23. Car false ceiling in stainless steel 24. Pit ladder 25. Anti Nuisance car call protection 26. Door Nudging 27. Automated Resuce Device to bring the elevator to the nearest landing in case of power failure. 28. The use of visually and accoustically reflective wall surace should be minimized within the lift car as visual reflections can cause discomfort and affect the visual acuity of people with impairements. 29. The floor of lift car should be slip resistant and have similar frictional qualities to thye floor of lift landing to decrease the risk of stumbling. 30. The provision of mirror on the wall of the lift car opposite the lift door not extend below 900mm from the lift floor to avoid confusing people with impaired sight. 31. The emergency communication system should be coupled with an induction loop system installed all around the lift. Telephone units, where provided, should have an inbuilt inductive coupler to assist persons using hearing aids.
Supply, installation, testing and commissioning of 1 No. lift of 26/27 passengers cum Bed Lift machine room less. Type and Capacity : Approximately 1768 Kg, 26/27 Passengers Speed:1.0 Meter per second Type of drive: AC Variable Voltage Variable Frequency with 16-Bit Microprocessor. Motor: Permanent Magnet Gearless Machine to be hoisted on the top of guide rail within the elevator hoist way Travel: Approximately 16 meter________ Serving: _7 Floors _7Stops _7 Openings _7 Levels (All on the same side) Hoist way Required: 2400mm (Wide) x 3000mm (Deep) Clear dimensions Headroom Height (HR): 5000 mm beyond finished floor level of last landing Pit Depth: 1800mm below the finish floor level of first landing Car Size Area: Minimum 3.74 square meter and Maximum 3.85 square meter Car Enclosure: Constructed out of stainless steel Scratch proof Finish (Vandal Proof). Car Entrance: Center Opening Automatic Doors (Fire rated door up to 120 minutes) of Stainless steel finish panel in Scratch Resistance/ Vandal proof
Supply, installation, testing and commissioning of 1 No. Hydraulic Dumbwaiter machine room less. 1. Type of Lift : Hydraulic Dumbwaiter (No Pit & Machine Room) 2. Shaft Dimension: 1200 mm x 1200mm (Width & Depth) 3. Platform Size : 800mm X 800mm (Approx.) 4. Load : 200 Kg 5. Internal Cabin : SS Cabin with Falseceiling & LED Light 6. Speed : 0.5 Mtr/Sec or more 7. No. of Stops : 2 8. Travel Distance : 4000mm 9. Door Width & Height: Collapsible Door 700mm (Opening) & 2000mm (Height) 10. Power pack location : Ground floor Free service Two Year after the S/I/T/C work and all std. Govt. features.
Overall size 16sq.mm (4Core) Un-armoured (Loose)
XLPE INSULATED UN-ARMOURED CABLES (ON SURFACE): Supply, laying and erection of aluminium conductor XLPE insulated PVC sheathed Un-armoured and served cable 1100 volts grade as per IS 7098 (Part-1)1988 to be laid (On Surface) as per PWD General Specifications:-
Overall size 16sq.mm (4Core) Un-armoured (On-Surface)
DOUBLE WALLED CORRUGATED (DWC) HDPE PIPES: Supply and erection of Double Walled Corrugated (DWC) HDPE pipe to be laid 1mtr. below ground level including excavation placing the pipe in position and back filling with excavated soil etc. of the required size:-
COPPER EARTHING (8 SWG COPPER EARTHING): Earthing with 8 SWG (4mm dia.) electrolytic copper wire thimbled (1No. copper thimble with suitable size steel bolt, washers & double nut) with 30cm x 60cm x 2mm thick copper plate (made cylindrical) burried below ground level in the hole of excavation having bore dia. 125mm and surrounded by salt & charcoal dust mixture (20 kg.) including fixing the copper wire run through 20mm dia. G.I. pipe (A-Class) recessed in wall and in floor etc., up to suitable Length in metre (including bore Length). G.I. pipe 20mm dia. (A-class) of suitable Length should be laid in the hole of excavation 1 feet below ground level and having GI Reducer 50mm x 20mm with PVC Cap (For pouring water) fixed on the top level of the pipe. 300mm x 300mm x 300mm deep haudi of First class bricks finished with 1:4 cement plaster and haudi covered with cast iron lid having size 300mm x 300mm (Heavy) around the hole of excavation:-
Additional Length copper wire 8 S.W.G. (4mm dia.) in 20mm dia. G.I. pipe (On Surface)
MCCB's (MOULDED CASE CIRCUIT BREAKER): Supply and erection of Moulded Case Circuit Breaker (Panel mounting Cubicle type) in the existing Cubical Panel (conforms to IEC:60947-II) having Ics=100% Icu, 100% neutral with spreader links and relevant PWD General Specifications (Electrical Works) complete with G.I. Bolts, Nuts & Connection on both sides of MCCB with sutiable size of Thimbles etc.
MCCB Four Pole 40amp., 415volts, ≥25kA Fixed Magnetic and Adjustable Thermal Setting
MS SHEET ENCLOSURE FOR MCCB's: Supply & Erection of indoor type MCCB enclosure of suitable size having provision for MCCB with extended rotary handle. The Enclosure shall be made from 14/16 SWG CRCA sheet, confirming to IS 8623/1977-82. The door should be double folded without edge and the gasket should be ‘S’ type puffed neutral rubber gasket for long life. The hinges of the door should be bolted type with double hole arrangement. The Enclosure door lock should be quick openable type spring loaded. There should not be any special tool or key to open the lock. The Enclosure will be wall mounting type having provision for cable entry from bottom/top with cable glands etc. The sheet metal is sprayed with corrosion resistant etch primer. The finishing treatment shall be applicable with air drying paint (7/9 tank Powder coated process should present in company pemises) after necessary putty work:-
SP&N Double Door Distribution Board 8 way each
Cable End Box for SPN 8 Way
MCB Double Pole 6-32amp. (10kA, Curve-C)
Providing EPABX System:
Supply, installtion, testing & commisioning of the Switching system of the EPABX should be designed with IP at the core allowing fully distributed IP solutions across data networks in 19” Rack Mountable,7 universal slots in single Node and should support card Analog Extension Card , Digital Extension Card , for the respective addition / expansion. Analog & Digital
extensions can be increased in the steps of 8, 16 & 32 Ports.Analog Trunks , PRI, BRI Trunks, E1 & SIP Trunks . Single card/module should support 2 or more PRIs, It should support 100% IP or 100 % TDM or a hybrid of IP/TDM technologies. The system should support IP Communication Devices (wired and wireless) e.g. IP Phones (Hard and Soft phones), Mobile IP Phones, multimedia PCs, SIP phones, Video phones (Hard & soft), etc.1.3. The system should also support Legacy TDM communication devices (Digital and analog 2 Wire telephone instruments with or without caller-id (Both FSK and DTMF), Fax, modems, ISDN phones etc. 1.6. The proposed system should support direct SIP integration with Microsoft Lync 2013 including following. Vendor should provide proper document towards certification with Microsoft Lync 2013 integration.1.16. The system should support at least 228 analog extensions in a single node and up to 600 analog Extensions in multiples nodes,at least 400 Digital Phones in a single node and 600 digital phones in multiple node,support at least 600 SIP extensions in a single node,Support 600 DECT/SIP DECT phones.support at least 224 DECT base stations and over 4000 SIP-DECT Base stations.should support minimum 56 Analog Trunks ,56 ISDN BRI trunks,14 PRI Trunks.Fax over IP with T.38 Interface and should support minimum 140 channels.240 SIP access channels.1.26. The system should have in-built Auto Attendant and 2 Port Voice Mail, Direct Inward System Access (DISA), Direct Outward System Access (DOSA) & Music On Hold (MOH). The system should be communication server should be on Leaders of Gartner Magic Quadrant. The OEM should be present globally minimum 70-75 countries. EPABX/Server, Digital Phone, IP Phone, cloud server must be from same OEM. Contactor shall off load the work to specialized agency having direct distributorship from OEM & distributor will have minimum 15 years experience with same OEM & have already maintained services minimum 18-20 EPABX system in Punjab region. complete in all respect as per satisfaction of the Engineer in charge of the work.
Supply, installtion, testing & commisioning of card 08 PNT Line (backup Lines) complete in all respect as per satisfaction of the Engineer in charge of the work.
Supply and erection of LED batten 20 Watt LED (including constant LED driver) with High quality extruded aluminium with efficacy of LED fixture minimunm 100 lumens per watt and operating voltage between 140 to 270 volt, THD <10% ingress protection IP20 (as per latest BIS standards) surge protection - 2.5 KV and above (as per IS/IEC standards) wattage of each low power LED less than 1 watt input AC frequency 50 Hz ± 3 % with 5 year warranty including there drivers complete along with erection of the same with connections, testing etc. complete in all respects as approved and desired by the Engineer-in-charge at site. LED Fitting as per Specifications approved by Hon. Tech. Advisor to CM Punjab vide Letter ION No: AT/2021/GL/1410-1422, Dated: 06.05.2021. Besides this the lighting fixtures manufactures should have in house NABL accredited laboratory.
Supply and erection of Recessed mounted 36watt LED panel (including LED driver) with CRCA sheet having efficacy of LED fixture minimunm 100 lumens per watt and operating voltage between 140 to 270 volt, THD <10% ingress protection IP20 (as per latest BIS standards) surge protection - 2.5 KV and above (as per IS/IEC standards) wattage of each low power LED less than 1 watt input AC frequency 50 Hz ± 3 % with 5 year warranty including there drivers complete along with erection of the same with connections, testing etc. complete in all respects as approved and desired by the Engineer-in-charge at site. LED Fitting as per Specifications approved by Hon. Tech. Advisor to CM Punjab vide Letter ION No: AT/2021/GL/1410-1422, Dated: 06.05.2021. Besides this the lighting fixtures manufactures should have in house NABL accredited laboratory.
Supply, installtion, testing & commisioning of card 01 PRI Line (30 Channel) complete in all respect as per satisfaction of the Engineer in charge of the work.
Supply, installtion, testing & commisioning of card SIP Trunk license for integration complete in all respect as per satisfaction of the Engineer in charge of the work.
Supply, installtion, testing & commisioning of card 32 Analog Extensions complete in all respect as per satisfaction of the Engineer in charge of the work.
Supply Installation Testing and Commissioning of the Sip Extension with its license for IP telephones complete along with erection of the same with connections, testing etc. complete in all respects as approved and desired by the Engineer-in-charge at site.
ncluding a built-in troubleshooting sectionMass deployment via central provisioning of user configuration files – TFTP, FTP, HTTP, HTTPSTR-069 support,PoE Class 1 Level “V” energy efficiency rated power adapters available complete in all respects as approved and desired by the Engineer-in-charge at site.
Supply Installation Testing and Commissioning of Operator console with following Features 7” (800x480 pixel) Touchscreen LCD with cordless handset,DSS 4.3” 480x272 pixel color backlit LCD display with 28 programmable keys, if required then (optional) can be daisy-chained for a combined total of up to 3 modules of 28 programmable keys on each modules, All attached PKM’s powered by the phone – no separate power adapter required, there should not be any cordcoil for connection IP phone based with hand set2 x GigE ethernet ports Built in Bluetooth 4.1 support 96 (16 x 6) programmable keys 6 softkeys Mitel Hi-Q Audio Technology Hearing aid compatible (HAC) handset Codecs (not all codecs supported by MiNet and SIP firmware): G.711, G.729, G.722, G.722.1 (MiNet only ); G.726, iLBC AMR, AMR-WB (G.722.2) (SIP only) Powered USB 2.0 Host port (500mA) Sidecar expansion port PoE Class 3 with automatic PoE Class CONTEXT SENSITIVE SOFT KEYS BLUETOOTH WIRELESS INTERFACE MOBILE INTEGRATION, Mobile Call Audio via desk phone, Mobile Contact Sync, Sidecar expansion port, Dedicated 4-pin modular headset port convertible to DHSG/EHS capable, Support for Mitel Teleworker Solution, Automatic Call Distribution (ACD) agent and supervisor, hot desking and resiliency, Secure encrypted voice communication • Quality of Service support – IEEE 802.1 p/Q VLAN and priority tagiing • IEEE 802.1x authentication support USB CHARGING PORT complete in all respects as approved and desired by the Engineer-in-charge at site.
Supply Installation Testing and Commissioning of Conference room Phone with following Features, 7” 800x400 Color Touch Display Multi-programmable personal touch keys,Touch - 6 context-sensitive soft keys PoE power (802.3af), Bluetooth 4.1 enabled, MobileLink enabled, 8 beam forming microphone with 360° pickups, Powered USB 2.0 host port (500mA), USB 2.0 Device port, USB CHARGING PORT, PROGRAMMABLE KEYS 96, CONTEXT SENSITIVE SOFT KEYS complete in all respects as approved and desired by the Engineer-in-charge at site.
Supply Installation Testing and Commissioning of Analog phone with caller id and hand free facility complete in all respects as approved and desired by the Engineer-in-charge at site.
Supply Installation Testing and Commissioning of Executive SIP Desktop Phone 7” (800x480 pixel) color LCD Touch Display, Bluetooth 4.1,MobileLink mobile device integration, Mobile phone charging point, Cordless speech optimized handset, Enhanced full-duplex speaker phone ,Programmable Personal soft touch keys,for access to Lines, Speed Dials and, Telephony functions, Context sensitive touch soft keys, 11 dedicated feature keys,lus dial pad,• Dual 10/100/1000 Mbps Ethernet port,(LAN/PC), MobileLink, Mobile pairing via BT, Mobile Call Audio via desk phone, Mobile Contact Sync, Mobile Charging (USB,ort)Speech optimized cordless handset, Hearing aid compatible (HAC) handset, Full-duplex high quality speakerphone, Codecs (not all codecs supported by,MiNet and SIP firmware):,o G.711, G.729, G.722,o G.722.1 (MiNet only );,o G.726, iLBC AMR, AMR-WB (G.722.2) (SIP only), Headset connection interfaces – USB,,Accepts standards-based (IEEE 802.3af),Power over Ethernet (PoE), PoE Class 3 with automatic PoE Class,change on Expansion Module installation ,Supports local powering via 48VDC PoE injector or 48VDC wall adapter,MTBF Rate: 40 years,Canada: CS03 Part V (Hearing Aid Compatible), USA: FCC part 68 (CFR 47) (Hearing Aid,Compatible), Australia/New Zealand: PTC220, AS/CA S004, AS/ACIF, 2040 complete in all respects as approved and desired by the Engineer-in-charge at site.
Supply Installation Testing and Commissioning of SIP Desktop Phone should protected with an antimicrobial treatment shown to inhibit certain virus & bacteria growth on the phone’s surfaces by up to 99.9%* Support for up to 18 lines • 3.5" QVGA (320x240 pixel) color display high qu
ality full-duplex speakerphone Programmable personal keys and Context sensitive soft keys • Native EHS/ DHSG analog headset support, Programmable keys for access to Lines, Speed Dials and Telephony functions • Context sensitive soft keys 4-way navigation key,Hearing aid compatible (HAC) handset • Full-duplex high-quality speakerphone • Codecs (supported codecs differ based on, call manager platform)- G.711, G.729, G.722 G.722.1 (Minet Only) - G.726, iLBC AMR, G.722.2 AMR-WB (SIP Only) Headset connection interfaces – USB and Analog EHS/DHSG port Dual 10/100/1000 Mbps Ethernet ports (LAN/PC) Support for Mitel Teleworker Solution, Automatic Call Distribution (ACD) agent and supervisor, hot desking, and resiliency,Support for use with Mitel MiCollab Client, Multiple-languages support: English, French, German, Italian, Portuguese, Spanish and Dutch (downloadable anguage packs with SIP), Secure encrypted voice communication Quality of Service support – IEEE 802.1,p/Q VLAN and priority tagging, IEEE 802.1x authentication support, Powered USB 2.0 Host port (100mA), Sidecar expansion port Dedicated 4-pin modular headset port convertible to EHS/DHSG capable headset port complete in all respects as approved and desired by the Engineer-in-charge at site.
Supply Installation Testing and Commissioning of 20 Pair DB with Original Krone Module lock & key facility complete along with erection of the same with connections, testing etc. complete in all respects as approved and desired by the Engineer-in-charge at site.
Supply Installation Testing and Commissioning of 200 Pair MDF with Krone for EPBAX side with Original Krone Module lock & key facility complete along with erection of the same with connections, testing etc. complete in all respects as approved and desired by the Engineer-in-charge at site.
Supply, Installation Testing and commissioning of EPABX Rack chassis as per requirement 42U x 800W x 800D/ 1000D/ 1200D Floor Stand UL certified rack with Multi hollow extrusion Aluminium profile frame, Top and bottom cover with provision of either brush cable entry or cable entry holes with rubber grommets, Front single door with Glass/ Mesh and rear double door with mesh, Static load bearing capacity of Upto 1200KG., confirming to following standards - IEC EN 60529, IEC EN 62262, ISO 9001:2008, ISO 14001: 2015, ISO 45001: 2018, Salt spray test according to ISO 9227 (NSS test) for 250 Hours, Colour - Combination of RAL 7037 (For frame) & RAL 7035 (For other parts) with fine texture, Rack including accessories like Horizontal PDU, Metal Cable manager, Hardware packet and Monitor Shelf etc. should be from same OEM Floor Stand racks should be available in following dimensions complete in all respects as approved and desired by the Engineer-in-charge at site.
Cable End Box for SPN 8 Way
Supply, Installation, Testing & Commissioning of Online UPS 3KVA 9E IN 2000XL Tower Model With Rack, batteries & interlink cables with 60 minutes backup, with following features : 3000 VA, 2400 Watts, 0 to 40 Degree @ 100% Load @ 50 Degree with 50% Load, Storage Temperature -15°C~60°C, Relative Humidity 0-95% No condensates, Altitude <1000m, Acoustic Noise 40 dBA @ 1 Meter, Cooling Forced air cooling by the internal fans, Rated Input Voltage 208/220/230/240 Vac, Maximum working input voltage range 160 to 300 Vac @ 100% Load 100 to 300 Vac @ 50% Load, Rated kVA 3000 VA, Rated kW 2400 Watts, Load power factor range 0.5~1 lagging, Load Crest Ratio 3:1, Output wave type Pure sine wave, Online Efficiency >91%, Battery Type & Backup (in VAH) VRLA (Valve Regulated Lead Acid Battery), 12VDC,2496VAH(30 minutes ) & 4032VAH(60 minutes ), Battery Capacity and Number Back UP dependent and 8 No's, Available ECO Mode, Communication (Independent SCI), Intelligent Card slot (Independent SCI), OVCD, EPO Function, Intelligent Fans Speed control, Auto restart function, Cold start complete in all respects as approved and desired by the Engineer in-charge at site.
RECESSED TV, TELEPHONE & NETWORKING SOCKETS OUTLET POINTS (USED FOR HGW, PVC CONDUIT & HDPE PIPE WIRING SYSTEM WITH MODULAR ACCESSORIES): Supply and erection of TV socket, Telephone socket and Networking socket points in powder coated/anodized concealed metal boxes recessed in wall required for suitable number of modules (Modular accessories) for having TV sockets, Telephone sockets RJ11 & Networking socket RJ45 (one module), covered with Frame Plate and other petty material etc., including the cost of above material, cutting and filling up of chases (with finishing the surface):-
Wiring Telephone socket point RJ11 (one module)
Supply and erection of LED batten 20 Watt LED (including constant LED driver) with High quality extruded aluminium with efficacy of LED fixture minimunm 100 lumens per watt and operating voltage between 140 to 270 volt, THD <10% ingress protection IP20 (as per latest BIS standards) surge protection - 2.5 KV and above (as per IS/IEC standards) wattage of each low power LED less than 1 watt input AC frequency 50 Hz ± 3 % with 5 year warranty including there drivers complete along with erection of the same with connections, testing etc. complete in all respects as approved and desired by the Engineer-in-charge at site. LED Fitting as per Specifications approved by Hon. Tech. Advisor to CM Punjab vide Letter ION No: AT/2021/GL/1410-1422, Dated: 06.05.2021. Besides this the lighting fixtures manufactures should have in house NABL accredited laboratory.
Supply and erection of Recessed mounted 36watt LED panel (including LED driver) with CRCA sheet having efficacy of LED fixture minimunm 100 lumens per watt and operating voltage between 140 to 270 volt, THD <10% ingress protection IP20 (as per latest BIS standards) surge protection - 2.5 KV and above (as per IS/IEC standards) wattage of each low power LED less than 1 watt input AC frequency 50 Hz ± 3 % with 5 year warranty including there drivers complete along with erection of the same with connections, testing etc. complete in all respects as approved and desired by the Engineer-in-charge at site. LED Fitting as per Specifications approved by Hon. Tech. Advisor to CM Punjab vide Letter ION No: AT/2021/GL/1410-1422, Dated: 06.05.2021. Besides this the lighting fixtures manufactures should have in house NABL accredited laboratory.
Supply and erection of telephone cable with solid bare copper conductor, special grade PE insulation, paired, polyster taped, nylon rip cord, FR PVC sheathed, conforming to TEC Specification No. G/WIR-06/03 left bare in pipe or casing of suitable size complete in all respect as desired by the Engineer-in-charge:-
Telephone Cable 0.5 Sq.mm, 2 Pair
Telephone Cable 0.5 Sq.mm, 20 Pair
Telephone Cable 0.5 Sq.mm, 50 Pair
Providing Networking System along with allied accessories:
Supply, Installation and Comissioning of L3 Switch 24 x 1/10G SFP+ Fiber Ports ,4 x 1G/10G/25G SFP28 Ports ,Ethernet: Out-of-band 1G port (Back) ,Console: USB-C (Front) ,Storage: 2 x USB-A (Back) ,Quad-Core Cortex-A57 ARMv8 1.8Ghz 64-bit, 2GB RAM DDR4 ,Packet buffer memory: 32 MB ,Flash: 512MB NAND 8-bit ECC ,Max physical switches per stack, at the edge: 8 ,Switching fabric: 680 Gbps Line-Rate (non blocking fabric) ,Throughput: 505.92 Mpps ,Forwarding mode: Store-and-forward ,Address database size: 16,000 MAC addresses (48-bit MAC address) ,Number of VLANs: 4,093 (IEEE 802.1Q) simultaneously ,Number of multicast groups= 2048 IPv4 ,Number of multicast groups= 2048 IPv6 ,ARP-4K/NDP- 512 ,Number of LAGs : 128 LAGs with up to 8 ports per group ,Number of hardware queues for QoS: 8 (Standalone) ,Jumbo frame support: up to 12K packet size ,Mean time between failures (MTBF): 778,000 hours ,sFlow: samplers:Total stack po
rt count,pollers:Total stack port count, 8 receivers ,Protocol based VLAN ,GARP with GVRP/GMRP ,MVR (Multicast VLAN Registration) ,Multiple Registration Protocol (MRP) ,Multicast VLAN Registration Protocol (MVRP) ,LAG Hashing ,LAG Member Port Flaps Tracking ,UDLD support ,Per VLAN STP (PVSTP) with FastUplink and FastBackbone ,Per VLAN Rapid STP (PVRSTP) ,IGMP Proxy ,Static Routing (IPv4, IPv6) ,Port based Routing ,ECMP Static Routing ,Port Based Routing ,VLAN Routing ,RIP v1 and v2 ,OSPF v2 and v3 ,OSPF Flood Blocking ,Route Redistribution ,VRRP ,VRRP Route/Interface Tracking ,IEEE 802.1p CoS ,DiffServ QoS ,WRED (Weighted Deficit Round Robin) ,Single Rate Policing ,Strict Priority queue technology ,Auto-VoIP ,IP DSCP ,IP Precedence ,IP TOS ,Broadcast, Multicast and Unicast Network Storm Protection ,CPU rate limiting ,DoS attack protection ,ICMP throttling ,Management ACL ,Radius accounting ,TACACS+ ,L2/L3/L4 Access Control List (ACL) ,ACL over VLAN ,Dynamic ACL ,IEEE 802.1x Radius Port Access Authentication ,802.1x MAC Address Authentication Bypass (MAB) ,Port Security ,Dynamic ARP Inspection ,MAC Filtering ,Port MAC Locking ,ISDP (Industry Standard Discovery Protocol) ,Out of band Management ,802.1ab LLDP and LLDP-MED ,Command Line Interface (CLI) ,Web-based graphical user interface (GUI) ,Admin access control via Radius and TACACS+ ,Telnet ,IPv6 Management ,Dual Software (Firmware) images ,Radius accounting ,Malicious Code Detection ,Access Control Lists (ACLs) L2 / L3 / L4 ,Time-based ACLs ,ACL over VLANs ,IPv6 RA Guard Stateless Mode ,Network Authentication Successive Tiering ,Per port: Speed, link, activity ,Per device: Power, Fan, Stack Master, Stack ID ,Operating Temperature: 32° to 122°F (0° to 50°C) ,Operating Humidity: 90% maximum relative humidity, non-condensing ,Storage Temperature: – 4° to 158°F (–20° to 70°C) ,Storage Humidity: 95% maximum relative humidity, non-condensing ,CE: EN 55032, CISPR 32:2012 ,EN 55024, VCCI : VCCI-CISPR 32:2016, Class A ,IEC 60950-1, UL listed (UL 1950)/cUL IEC 950/EN 60950 ,RCM (AS/NZS) 60950.1:2015 ,BSMI: CNS 14336-1 ,FCC: 47 CFR FCC Part 15 ,EN 61000-3-2:2014 ,ISED: ICES-003:2016 ,ODM vendor should be ISO certifiedcomplete in all respect as per satisfaction of the Engineer in charge of the work.
Supply, Installation and Comissioning of L2 switch without PoE, 24 RJ-45 connectors for 10BASE-T, 100BASE-TX and 1000BASE-T (Auto Uplink on all ports) ,2 Dedicated 100/1000X Fiber SFP ports ,IEEE 802.3 Ethernet ,IEEE 802.3i 10BASE-T ,IEEE 802.3u 100BASE-T ,IEEE 802.3ab 1000BASE-T ,IEEE 802.1Q VLAN Tagging ,IEEE 802.3x Full-Duplex Flow Control ,IEEE 802.3z Gigabit Ethernet 1000BASE-SX/LX ,IEEE 802.3ad Trunking (LACP) ,IEEE 802.1AB LLDP with ANSI/TIA-1057 (LLDP-MED) ,IEEE 802.1p Class of Service ,IEEE 802.1D Spanning Tree (STP) ,IEEE 802.1s Multiple Spanning Tree (MSTP) ,IEEE 802.1w Rapid Spanning Tree (RSTP) ,IEEE 802.1X Radius network access control ,Forwarding modes: Store-and-forward ,Bandwidth: 52 Gbps ,Packet buffer: 2Mb ,Priority queues: 8 ,Priority queuing: Weighted Round Robin (WRR) ,Address database size: 16,000 media access control (MAC) addresses per system ,Addressing: 48-bit MAC address ,Multicast groups: 512 ,Number of static routes: 32 ,Number of routed VLANs: 15 ,ACL: 100 shared for MAC, IP and IPv6 ACLs ,Jumbo frame: 9K ,Mean time between failures (MTBF): 567,680 hours ,Acoustic Noise: 0 dBA ,Protocol based VLANs ,MAC based VLANs ,Voice VLAN ,Guest VLAN ,RADIUS based VLAN assignment via .1x ,MAC-based .1x ,RADIUS Accounting ,Broadcast, Unicast, Multicast Storm Protection ,DoS Attacks ,Dynamic ARP inspection ,IGMP Snooping (v1, v2 and v3) ,MLD Snooping Support (v1 and v2) ,Multicast VLAN Registration ,DHCP Client ,DHCP Snooping ,Static Routing ,VLAN Routing ,IP Source Guard ,L2 / L3 / L4 Access Control Lists (ACLs) ,IP-based ACLs (IPv4 and IPv6) ,MAC-based ACL ,TCP/UDP-based ACL ,MAC lockdown ,Dynamic VLAN Assignment ,Dynamic ARP inspection ,Access Lists ,L2 MAC, L3 IP and L4 Port ACLs ,Ingress and Egress rate limiting ,Support for IPv6 fields ,DiffServ QoS ,Dst MAC and IP ,IPv4 and v6 DSCP ,IPv4 and v6 TOS ,WRED (Weighted Deficit Round Robin) ,Strict Priority Queue Technology ,Auto-VoIP ,Port Mirroring ,Configurable Management VLAN ,Admin Access Control via Radius and TACACS+ ,Web-based Graphical User Interface (GUI) ,IPv6 Management ,Dual Software (firmware) Image ,Dual Configuration File ,SNTP Client over UDP Port 123 ,SNMP v1/v2/v3 ,RMON 1,2,3,9 ,Cable Test Utility ,SSL/HTTPS and TLS v1.0 for Web-based access ,TFTP and HTTP File Transfers (uploads, downloads) ,HTTP Download (firmware) ,Syslog (RFC 3164) ,Per Device: Power and Fan ,Per Port: Speed, Link, Activity ,Maximum Power Consumption: 17.5W ,100-240V AC/50-60 Hz universal input ,Operating temperature: 32° to 131°F (0° to 55° C) ,Storage temperature: -4° to 158°F (-20° to 70° C) ,Operating humidity: 90% maximum relative humidity, non-condensing ,Storage humidity: 95% maximum relative humidity, non-condensing ,Operating altitude: 10,000 ft (3,000 m) maximum ,Storage altitude: 10,000 ft (3,000 m) maximum ,CE mark, commercial ,FCC Part 15 Class A, VCCI Class A ,Class A EN 55022 (CISPR 22) Class A ,Class A C-Tick ,EN 50082-1 ,EN 55024 ,CCC ,CE mark, commercial ,CSA certified (CSA 22.2 #950) ,UL listed (UL 1950)/cUL IEC 950/EN 60950 complete in all respect as per satisfaction of the Engineer in charge of the work.
Supply, Installation and Comissioning of Patch Panel should be made of cold rolled steel.Should conform to TIA / EIA 568-C.2 Component Compliant.Should terminate 24 UTP CAT 6 (4 pair) Cables.Should confirm to EIA/TIA 568A wiring Pattern.Each port Should be features the spring-loaded shutter.Should be prevents incomplete mating Should be protects from dust and contaminants.Should be Front and rear port labelling as well as panel identification label.Should be Integral cable management shelf ensures bend radi
us compliance.Operating Life should be minimum 750 insertion cycles.Should be RoHS compliant.. complete in all respect as per satisfaction of the Engineer in charge of the work.
Supply, Installation and Comissioning of Patch Cord 1 Mtr Patch cord Should be 4 Pairs 24 AWG copper cables.The Outer Jacket should be Low Smoke Zero Halogen.24 AWG stranded bare copper.Operating temperature range should be -20°C to 60°C.Should minimum comply with proposed ANSI/TIA/EIA-568-C.2.Should be verified by ETL (ETL certificate to be enclosed with the Bid)UL listed (UL certificate to be provided along with the Bid)Should Have cross separator.Standard length should be available 0.5M to 10M.Should be RoHS compliant. . complete in all respect as per satisfaction of the Engineer in charge of the work.
Supply Installation Testing and Commissioning of 200 Pair MDF with Krone for EPBAX side with Original Krone Module lock & key facility complete along with erection of the same with connections, testing etc. complete in all respects as approved and desired by the Engineer-in-charge at site.
RECESSED TV, TELEPHONE & NETWORKING SOCKETS OUTLET POINTS (USED FOR HGW, PVC CONDUIT & HDPE PIPE WIRING SYSTEM WITH MODULAR ACCESSORIES): Supply and erection of TV socket, Telephone socket and Networking socket points in powder coated/anodized concealed metal boxes recessed in wall required for suitable number of modules (Modular accessories) for having TV sockets, Telephone sockets RJ11 & Networking socket RJ45 (one module), covered with Frame Plate and other petty material etc., including the cost of above material, cutting and filling up of chases (with finishing the surface):-
Wiring Telephone socket point RJ11 (one module)
Supply and erection of LED batten 20 Watt LED (including constant LED driver) with High quality extruded aluminium with efficacy of LED fixture minimunm 100 lumens per watt and operating voltage between 140 to 270 volt, THD <10% ingress protection IP20 (as per latest BIS standards) surge protection - 2.5 KV and above (as per IS/IEC standards) wattage of each low power LED less than 1 watt input AC frequency 50 Hz ± 3 % with 5 year warranty including there drivers complete along with erection of the same with connections, testing etc. complete in all respects as approved and desired by the Engineer-in-charge at site. LED Fitting as per Specifications approved by Hon. Tech. Advisor to CM Punjab vide Letter ION No: AT/2021/GL/1410-1422, Dated: 06.05.2021. Besides this the lighting fixtures manufactures should have in house NABL accredited laboratory.
Supply and erection of Recessed mounted 36watt LED panel (including LED driver) with CRCA sheet having efficacy of LED fixture minimunm 100 lumens per watt and operating voltage between 140 to 270 volt, THD <10% ingress protection IP20 (as per latest BIS standards) surge protection - 2.5 KV and above (as per IS/IEC standards) wattage of each low power LED less than 1 watt input AC frequency 50 Hz ± 3 % with 5 year warranty including there drivers complete along with erection of the same with connections, testing etc. complete in all respects as approved and desired by the Engineer-in-charge at site. LED Fitting as per Specifications approved by Hon. Tech. Advisor to CM Punjab vide Letter ION No: AT/2021/GL/1410-1422, Dated: 06.05.2021. Besides this the lighting fixtures manufactures should have in house NABL accredited laboratory.
Supply, Installation and Comissioning of Patch Cord 2 Mtr. Patch cord Should be 4 Pairs 24 AWG copper cables.The Outer Jacket should be Low Smoke Zero Halogen.24 AWG stranded bare copper.Operating temperature range should be -20°C to 60°C.Should minimum comply with proposed ANSI/TIA/EIA-568-C.2.Should be verified by ETL (ETL certificate to be enclosed with the Bid)UL listed (UL certificate to be provided along with the Bid)Should Have cross separator.Standard length should be available 0.5M to 10M.Should be RoHS compliant..complete in all respect as per satisfaction of the Engineer in charge of the work.
Supply, Installation and Comissioning of 6 core Single mode outdoor Fiber Outdoor Loose Tube Armoured 9/125μm OS2 Type Optical Cable.Fiber Cable should be containing upto 72 optical fibres in water blocked loose tubes and solid polyethylene fillers, total of 6 elements laid-up around a fibre reinforced plastic (FRP) central strength member, water blocked interstices, taped, corrugated steel tape armoured, polyethylene overall sheathed. Anti-Rodent/Termite.Central Strength Member should be FRP (Fibre Reinforced Plastic) 2.0 mm OD.Outer sheath should be of UV proof HDPE Black.Fiber cable Should be Max.Tensile Strength: 3500N Max. Crush Resistance: 6000N/10 cm.Operating Temperature range should be -40°C to +70°C.Cable should be of ROHS Compliant complete in all respect as per satisfaction of the Engineer in charge of the work.
Supply, Installation and Comissioning of 1G Base-LR Single-Mode, 10KM, SFP+ (1310 nm). All Switches, Wireless and its and Networkiing Components from Same OEM.OEM should be present as Leader in Gartner Quadrant from last 5 years,OEM Authorization should be required on letteheadcomplete in all respect as per satisfaction of the Engineer in charge of the work.
Supply, Installation and Comissioning of LC-SC Single Mode Fiber patch cord 2 mtr should be SC or LC LSOH Jacket ‐ Reduces toxic / corrosive.SC to LC duplex fiber optic patch cord single mode OS2 9/125 micron.Fiber patch cord should be 100% Factory polished and tested.Cable diameter should be 1.6 mm.Jacket color should be Industry Standard Colour ‐ OS1‐Yellow.Buffer diameter Should be 900 micron meter.Fiber patch cord should be of ROHS Compliant complete in all respect as per satisfaction of the Engineer in charge of the work.
Supply, Installation and Comissioning of SC Pigtail, Simplex - Single Mode.PIGTAIL SC SM SIMPLEX LENGTH- 1m ,Pigtails Corning G652D, G657A, G657Bsingle-mode /Insertion Loss Typical:<0.2dB, Max. 0.3dB(MTRJ: Max. 0.5dB)/Return Loss PC>45dB, UPC>50 dB,APC>60dB /ConnectorFerrule Ceramic, (MTRJ: PS- Polyphenylene Sulphide )Apex Offset <50um / Fiber Height ±100nm , End-face Radius of Curvature 7mm < R < 25mm (Excluding MTRJ)/ Repeatability <0.2dB 1,000 times mating cycles / Working Temperature – 20C ~+ 65C. complete in all respect as per satisfaction of the Engineer in charge of the work.
Supply, Installation and Comissioning of 12 Port Fully loaded single mode, Rack-mountable, SC/LC type LIU. Enclosure should be CRS (cold rolled steel).Should be fully Secured with Lockable and Secured Steel doors and Comes multiple entry points.Enclosure should be finish black powder Coat.Enclosure should be accepts SC Duplex and Quad LC Adapters.Should be loaded with SC/LC type adopter plate.Pigtail should be 100% Factory polished, tested and guaranteed performance.Should be complete with splicing tray and other standard accessories.Should be of ROHS Compliant. complete in all respect as per satisfaction of the Engineer in charge of the work.
Supply, Installation and Comissioning of 24 Port Fully loaded single mode, Rack-mountable, SC/LC type LIU. Enclosure should be CRS (cold rolled steel).Should be fully Secured with Lockable and Secured Steel doors and Comes multiple entry points.Enclosure should be finish black powder Coat.Enclosure should be accepts SC Duplex and Quad LC Adapters.Should be loaded with SC/LC type adopter plate.Pigtail should be 100% Factory polished, tested and guaranteed performance.Should be complete with splicing tray and other standard accessories.Should be of ROHS Compliant complete in all respect as per satisfaction of the Engineer in charge of the work.
Supply, Installation, Testing and Commissioning of 27U Network Enclosure Frame-600X800-STEEL with accessories like fan, pdu, cable manager etc. Supply of 27U Enclosure Frame-800X1000-STEEL, Caster Wheels Set of 4 (2 with Brakes & 2 without Brakes),Adjustable Levellers set of 4, Glass Door-800-27U, Metal Door-800-27U-Vented, Side Panels-1000-27U-Vented, Mounting Hardware-(Pack of 20), FHU with 4 FAN 360CFM, Vertical Power Distribution Unit with 12 x 5/15 sockets Round Pin, 230 Volts AC, 32 Amp with Plug, Vertical Cable Manager-27U-Loop, Horz. Cable Manager-1U-Loop, Conforms to DIN 41494 O
R equivalent ISO Standards, Adjustable 19” equipment mounting verticals provide the better mounting flexibility maximizing the usable mounting space, Depth adjustable mounting slots, Top and bottom Panel with ventilation and cable entry facility, Provision to mount the cooling fans on the top panel, Powder coated finish with pretreatment process meeting all industry standards, Grounding and Bonding Options can be provided, 100% assured compatibility with all equipment conforming to DIN 41494. General industrial standard for equipment, Conforms to DIN 41494 or equivalent standard, Welded Frame, Lockable Toughened Glass Door, Metal Vented Door Steel, DIN Standard 10mm Sq. Slots / Direct M6 Tap, 19” Mounting angles made of formed steel Powder Coated, Welded to Frame, Vented and Field Cable entry exit cut outs complete in all respect as per satisfaction of the Engineer in charge of the work.
Supply, Installation, Testing and Commissioning of Wall Mount 15U x 600 W x 600 D ,Front Glass Door (tinted,Toughened) with Lock & Key, 2 pairs of 19" Mounting Rails with U-Marking , Welded Side Walls, Min Accessories : 1U Cable Manager (1), Hardware Packet (1 Pkt), 6 Socket 5 Amp. Power Distribution Unit (1 No), Roof Mounted Fan Unit / 90 CFM /230V AC.as per DIN 41494 Standards complete in all respect as per satisfaction of the Engineer in charge of the work.
Supply, Installation, Testing & Commissioning of Online UPS 2KVA 9E IN 2000XL Tower Model With Rack, batteries & interlink cables with 60 minutes backup, with following features : 2000 VA, 1600 Watts, 0 to 40 Degree @ 100% Load @ 50 Degree with 50% Load, Storage Temperature -15°C~60°C, Relative Humidity 0-95% No condensates, Altitude <1000m, Acoustic Noise 40 dBA @ 1 Meter, Cooling Forced air cooling by the internal fans, Rated Input Voltage 208/220/230/240 Vac, Maximum working input voltage range 160 to 300 Vac @ 100% Load 100 to 300 Vac @ 50% Load, Rated kVA 2000 VA, Rated kW 1600 Watts, Load power factor range 0.5~1 lagging, Load Crest Ratio 3:1, Output wave type Pure sine wave, Online Efficiency >91%, Battery Type & Backup (in VAH) VRLA (Valve Regulated Lead Acid Battery), 12VDC,2496VAH(30 minutes ) & 4032VAH(60 minutes ), Battery Capacity and Number Back UP dependent and 8 No's, Available ECO Mode, Communication (Independent SCI), Intelligent Card slot (Independent SCI), OVCD, EPO Function, Intelligent Fans Speed control, Auto restart function, Cold start complete in all respects as approved and desired by the Engineer in-charge at site.
Wiring Networking socket point RJ45 (one module)
COPPER CONDUCTOR CABLES FOR SPECIAL ELECTRICAL SERVICES: Supply and erection of CAT 6 with 23AWG solid bare copper conductor, special grade PE insulation with star separator, 4pair Unshielded Twisted Pair (UTP) industrial cable, FR PVC sheathed, Class-E, 250 MHz of bandwidth, supporting data transfer speeds of up to 10 Gbps (10GBASE-T) for distances up to approximately 180 feet, cables are manufactured and tested to meet the ANSI/TIA 568-C.2 and ISO/IEC 11801 Class E standards left bare in pipe or casing of suitable size complete in all respect as desired by the Engineer-in-charge:-
CAT 6 LAN cable
Providing CCTV System:
Supply, erection, testing & commissioning of Camera shall utilize high sensitivity 5-Megapixel CMOS sensors with 1/2.7 Sensor”, 5MP Progressive Scan CMOS Sensor and Active Pixel count Effective Pixels 2880(H)x1620(V). Minimum Illumination 0.004Lux @(F1.6, AGC ON); 0 Lux with IR. Camera shall integrate automatic shutter, shutter time is (1/5s-1/20,000s Adjustable). Camera shall integrate 2.8-12mm Lens, F No. 1.8 (W) ~ 3.3(T), with Angle of View: Horizontal: 107-34°, Vertical: 55-19°, Diagonal: 134-38°. Camera shall have IRIS Control: Fixed/Auto. Camera shall integrate IR cut filter with auto switch (Day/Night/Auto/Image/Schedule). IR distance shall be up to 30m. Camera shall have Output PAL/NTSC adjustable. Camera shall offer WDR up to 120dB, (Off/On, WDR coefficient range). Camera shall support to adjust Image Setting Brightness, Contrast, Sharpness, Saturation, Color and 3D DNR noise reduction. Camera shall offer BLC/HLC modes of backlight compensation. Camera shall support to Automatic Gain Control, Automatic White Balance, Anti-Flicker, Mirror & Corridor mode. Camera shall have Digital Zoom feature. Smart Event. Camera shall offer intelligent analysis functions, Perimeter Intrusion Detection, Line crossing Detection, Human & Vehicle Detection, Stationary Object Detection, Cross Counting, Crowd Density detection, Queue Length, Rare Sound detection, Heat MAP, Face Detection. Camera shall support Motion Detection Support (8 level). Camera shall offer event Trigger Schedule Linkage: Capture, email, FTP upload. Audio & Video Encoding. Camera shall offer H.264 and H.265 Encoding image compression format. Camera shall offer the following resolution streams: Mainstream@30fps 5MP (2880x1620), 4MP (2560x1440), 3MP (2304x1296),1080P(1920x1080), 720P(1280x720), Substream@30fps 720P (1280x720), VGA (640x480), QVGA (320x240), Third stream@30fps VGA (640x480), QVGA (320x240). Camera shall offer CBR/VBR bit rate control, bit rate is between 256kbps-8Mbps suitable for different image quality and fluency requirements. N
etwork Function. Camera shall support the following protocols: TCP/IP, HTTP, DHCP, DNS, DDNS, RTP/RTSP, SMTP, NTP, UPnP, SNMP, HTTPS, FTP. Camera shall conform to the ONVIF Profile S, G, T. Camera shall have IRIS Control: Fixed/Auto. Camera approved makes bosch, mountxross, axis, pelco shall offer Up to 4 area privacy mask. Camera shall support setting Character Overlay (OSD) Title, time and date overlay. Camera shall support setting Unicast and Multicast Streaming. Camera shall support General Function like User Authentication, IP address filtering, Complicated password. Camera shall offer Built In web server with an interactive Graphical User Interface. Camera shall support UPnP, ONVIF Discovery Interface. Interface. Camera shall integrate 1*RJ45 10M/100M Ethernet Port. Camera shall support Audio port: 1 input (RCA), 1 output (RCA) & Alarm port: 1 input, 1 output. Camera shall support standard 256G Micro SD card storage. General. Camera shall have Power Supply PoE(802.3af)/DC 12V±10% with Power Consumption <<5.5W (IR ON), <<3W (IR OFF). Camera shall offer IP67 Weather resistant Protection Complaint with Metal Body. Operating Conditions shall be -35°C ~ 60°C Humidity 95% or less (non-condensing). Camera shall integrate 1 reset button .complete in all respect as per satisfaction of the Engineer in charge of the work. All CCTV Cameras should be STQC Compliance
Supply, erection, testing & commissioning of AI Network 60fps outdoor Camera shall utilize high sensitivity 2-Megapixel CMOS sensors with 1/2.8”, optical format, progressive scan and Active Pixel Count: 1920x1080 pixel array. Minimum Illumination Color 0.002lux @ F1.6(AGC ON) ; B/W 0 lux @ IR ON . Camera shall integrate automatic shutter, shutter time is 1/5 ~ 1/20000s Adjustable. Camera shall integrate 2.8mm - 12mm lens, Max. Aperture Ratio 1.8 (W) ~ 3.3(T), Lens Type Motorized(Ø14), Angle of View: 101 ~ 33°, Vertical:52 ~ 18°, Diagonal: 124 ~ 37°. Camera shall integrate IRIS Control: Fixed/Auto. Camera shall integrate IR filter that can automatically switch. (Day/Night/Auto/Image/Schedule). IR distance shall be up to 50m. Camera shall offer 120dB, which support three levels of Auto/Low/High. Camera shall support to adjust image saturation, brightness, contrast, sharpness, and 3D DNR noise reduction. Camera shall offer BLC, AGC, and WDR modes of backlight compensation. Camera shall integrate Anti-Flicker: Outdoor, 50Hz, 60Hz . Camera shall offer corridor mode, including rotation, suitable for corridor scenes, convenient for construction and installation. Camera shall offer 16x digital zoom. Smart Event . Camera shall offer intelligent analysis functions, including Face Detection, Human & Vehicle Detection, Perimeter Intrusion Detection, Line Crossing Detection, Cross Counting, Stationary Object Detection, Heat Map, Crowd Density Detection, Queue Length Detection, License Plate Detection, and Rare Sound Detection. Audio & Video Encoding . Camera shall offer Video Encode H.265/H.264 compression format. Camera shall offer the following resolution streams : . Main stream @60fps - 1080P (1920x1080), 960P (1280x960), 720P (1280x720) . Sub stream @30fps - 720P (1280x720), VGA(640x480), QVGA(320x240). Third stream@30fps - VGA(640x480), QVGA(320x240) . Camera shall offer CBR/VBR bit rate control; bit rate is between 256 Kbps to 8 Mbps, suitable for different image quality and fluency requirements. Camera shall capable of Audio record with Built-in-mic. Network Function . Camera shall support the following protocols: TCP/IP, HTTP, DHCP, DNS, DDNS, RTP/RTSP, SMTP, NTP, UPnP, SNMP, HTTPS, FTP . Camera shall integrate IR filter that can automatically switch. (Day/Night/Auto/Image/Schedule. approved camera makes bosch, mountxross, axis, pelco shall support setting a custom password to improve the security when logging in for the first time; User Access 2 (admin+user). Camera shall offer Up to Off/On (4 Zone, Rectangle) privacy masking. Camera shall support setting OSD, Self-adaptive with video background, date and time with different formatting. Camera shall offer Streaming Method : Unicas
t and Multicast . Camera shall offer IP address filtering. Camera shall have interactive Graphical User Interface, Web Server: Built In web server. Shall compatible with web browsers IE10/11, Safari V12.1 above, Firefox V.52 above, Google chrome V.57 above, Edge V.79 above . Camera shall support Discovery Interface UPnP, ONVIF . Interface . Camera shall integrate 1*RJ45 10M/100M Ethernet Port. Camera shall support standard 256G Micro SD card storage. General . Power over Ethernet (PoE): PoE IEEE802.3af / 12V DC Optional. The power consumption shall be 3W-4W max without IR on, and 5W - 7W max with IR on . Camera shall offer IP67-rated for Weather-resistant Performance. Camera shall offer Metal Housing . Operating Conditions shall be -35 °C ~ 60 °C Humidity 95% or less (non-condensing). Certifications & Standards. Camera shall have the following Certifications: CE, FCC, BIS complete in all respect as per satisfaction of the Engineer in charge of the work. All CCTV Cameras should be STQC Compliance
Supply, erection, testing & commissioning of PoE Spliliter 12 volt, 1 Amp, IP66 For High Voltage Protection complete in all respect as per satisfaction of the Engineer in charge of the work.
Supply, erection, testing & commissioning of NVR shall have 64-channel video input. NVR shall be Embedded Linux. NVR shall support following bandwidth - 1280Mbps, Incoming 640Mbps & Outgoing 640Mbps. NVR shall support Video Output: 3 (1024*768, 1280*720, 1280*1024, 1440*900, 1920*1080, 1600*1200, 1920*1200, 3840*2160/7680*4320) HDMI; 1 (1024*768, 1280*720, 1280*1024, 1440*900, 1920*1080). Async out. NVR shall offer the following recording resolution streams Video Resolution: 12MP, 8MP, 5MP, 3MP, 2MP (1080P), 1.3MP (960P), 1.0MP (720P). NVR shall support Preview Capability: multiple matrix mode, Supported frame rate: 4K:240fps, 4MP:480fps, 2MP:960fps. NVR shall support schedule base snapshot, manual snapshot, event-based snapshot. NVR shall support Motion Detection. NVR shall support 4 zones Privacy Mask. NVR shall offer intelligent analysis functions powered including Human & Vehicle Detection, Perimeter Intrusion Detection, Line Crossing Detection, Stationary Object Detection, Crossing Counting, Heat Map, Crowd Density Detection, Rare Sound detection (gunshot/baby crying/dog barking), Face Detection. AUDIO. NVR shall support G.711A/G.711U Audio compression. NVR shall integrate Audio input 1 CH RCA port. NVR shall integrate Audio output 1 CH RCA port, HDMI audio. Video Recording and Playback. NVR shall support 1-30fps Video Frame Rate. NVR shall have Record Mode: schedule, event based- motion, I/O, PIR. NVR shall offer 16 CH max sync playback. NVR shall be able to playback according to different types, including Playback Mode Instant playback, Local video, local image. NVR shall support Record Search Time, calendar, channel search, and event search, (ANR, regular video, motion detection video, alarm video, intelligent detection video). NVR shall support following Video Playback: Start, stop, normal play, back play, frame by frame forward, full screen, Fast forward/backward (2x, 4x, 8x, 16x), Slow forward (1/2x, 1/4x, 1/8x, 1/16x), Add custom/ Default Tag, digital zoom, video clip, sub-stream/main-stream, playback video bar, scale of 30 mins to 24 hrs. NVR shall support 8 SATA, 1 x eSATA, HDD Capacity Single max. 18TB (enterprise class) & up to 12TB Surveillance HDD. NVR shall support RAID0, RAID1, RAID5, RAID6, RAID10. NVR Should have S.M.A.R.T info feature to check health of HDD, temperature and status. NVR shall offer Local, Network HDD NFS, SMB/CIFS. NVR shall offer USB mobile hard disk, U disk, network backup Method. NVR Should support FTP for uploading alarm video. NVR shall ANR Support Smart IPC (with SD card) ANR. Function. NVR shall support the following protocol: IPv4, IPv6, TCP/IP, HTTP, HTTPS, DDNS, RTMP, SMTP(SSL), SNMP, DHCP, PPPoE, UPnP, NTP, P2P, FTP, IP filter. NVR shall support ONVIF Profile S Support. NVR shall support ONVIF/RTSP/HTTP/HTTPS/RTMP port customized. NVR shall support Mobile Surveillance Support Apple, Android & Internet Explorer Support IE, Chrome, Firefox, Safari. NVR shall Digital Zoom support. NVR shall have IPC ti
ming Manual/auto/timing/reconnect timing. NVR shall support the following Event Actions: pre and post recording, Send email, show message, send email, FTP upload video or screenshot, Cloud upload video or screenshot, full screen, voice prompts, Alarm output trigger, PTZ linkage. NVR Should support combination of different events for effective alarm trigger and response. NVR Shall have exception alarms on event type of no space on disk, disk error, video loss. NVR makes bosch, mountxross, axis, pelco Shall be able to configure covert on camera by which recording is happening, but live view is restricted. Network Detection monitoring, Utilization of total and used bandwidth, IP filter with blacklist and whitelist. NVR Shall support video cover privacy mask both on live and recording up to 4 areas. NVR shall have User Management User add, delete, modify, permission management, support. NVR Shall be able to trigger PTZ presets on any camera AI event. NVR shall support Security Mode Authorized username and password, HTTPS with password, RTSP Validation. NVR should Manage IPC Support IPC centralized management, including IPC parameter configuration, information export and import, real-time information acquisition and upgrade. NVR shall have Statistics of events for face recognition, vehicle & human, cross count and heat map. Network Interface. NVR shall integrate 2 X RJ45 10M/100M/1000M adaptive Ethernet port. Alarm Input 16 CH alarm input & Alarm Output 4 CH alarm output. NVR shall integrate 1* RS485 , 1* RS232 & USB2.0*1(front), USB3.0*2(rear). General. The power consumption shall be AC 100-240 V, 250W & Power Consumption ≤8W (Without HDD). Operation Temp./ Humidity -10°C ~ 55°C/10%-90% complete in all respects as approved and desired by the Engineer-in-charge at site.
Supply, erection, testing & commissioning of L3 Switch 16-1G/10G Base-X Fiber SFP+ Ports ,Ethernet: Out-of-band 1G port ,Console: RJ45 RS232 ,Console: USB-C ,Storage: USB-A ,LED Ext: USB-C ,PSU with On/Off switch ,1U Rackmount ,ARM A9 1.25Ghz 32-Bit ,2GB RAM ,Packet buffer memory: 16 MB ,Flash: 256 MB ,Switching fabric: 320 Gbps Line-Rate (non blocking fabric) ,Throughput : Min. 238.08 Mpps ,Latency <1.30μs 1G & <0.86μs 10G Ports ,IP Multicast Routing Entries : 512 IPv4 & 128 IPv6. ,Address database size: 16,000 MAC addresses (48-bit MAC address) ,Number of VLANs: 4,093 (IEEE 802.1Q) simultaneously ,Jumbo Frames Up to 12K ,Multicast IGMP Group membership : 2K IPv4 & 2K IPv6 ,DHCP Server: IPv4: 256 pools IPv6: 16 pools ,4K ARP/NDP ,sFlow: 16 samplers, 16 pollers, 8 receivers ,Software-controlled fan adjustments ,Pre-configured for audio and video over IP out of the box with zero touch configuration ,For audio, profiles for Dante, Q-SYS and AES67 AVB lincese should be available. ,Auto-Trunk and Auto-LAG, ,static, RIP and PIM-SM, DM and SSM multicast routing, DHCP Server and Pv2 Transparent Clock ,Voice VLAN with SIP, H323 and SCCP protocols detection ,authentication tiering with successive DOT1X, MAB and Captive Portal methods for streamlined BYOD ,Mean Time Between Failures (MTBF): 844,633 hours (96.4 years) ,Power Consumption (All ports used, line-rate traffic, maximum): 47.84W - 163.33 BTU/hr ,Power Consumption (Standby, no connection on any port): 19.27W - 65.78BTU/hr ,Industry standard SNMP, RMON, MIB, LLDP, AAA, sFlow, RSPAN and PTPv2 ,Voice VLAN with SIP, H323 and SCCP protocols detection and LLDP-MED ,Advanced IPv4/IPv6 security implementation including malicious code detection, DHCP Snooping, IP Source Guard protection and DoS attacks mitigation ,8 LAGs with up to 8 ports per group ,Number of IP interfaces 128 ,Multicast VLAN Registration Protocol (MVRP) ,RIPv1/RIPv2 ,Policy Based Routing (PBR) ,Malicious Code Detection ,802.1x MAC Address Authentication Bypass (MAB) ,IEEE 1588 PTPv2 ,IEEE 802.1BA-2011 Audio Video Bridging (AVB) ,Radius Users ,IGMPv3 MLDv2 Snooping, Proxy ASM & SSM ,Control Packet Flooding ,802.1AS, 802.1Qav, 802.1Qat MSRP, 802.1ak MMRP, 802.1ak MVRP ,Per VLAN Rapid STP (PVRSTP), BPDU/STRG Root Guard ,VLAN routing, DHCP Relay, Stateful DHCPv6 Se
rver ,IEEE 802.1p CoS ,DiffServ QoS ,WRED (Weighted Deficit Round Robin) ,Single Rate Policing ,Strict Priority queue technology ,MAC ACL Support ,Auto-VoIP ,IP DSCP ,IP Precedence ,IP TOS ,L3 IPv6 Flow Label ,Interface Traffic Shaping ,PHB Support ,Minimum Bandwidth per-interface ,Broadcast, Multicast and Unicast Network Storm Protection ,CPU Protection ,DoS attack protection ,ICMP throttling ,Management ACL ,Radius accounting ,TACACS+ ,L2/L3/L4 Access Control List (ACL): MAC, IPv4, IPv6, TCP, UDP ACL ,Protocol based ACL ,ACL over VLAN ,Dynamic ACL ,IEEE 802.1x Radius Port Access Authentication ,Port Security ,Dynamic ARP Inspection ,MAC Filtering ,Port MAC Locking ,Private Edge VLAN ,IEEE 802.3ae 10-Gigabit Ethernet ,IEEE 802.3ad Trunking (LACP) ,IEEE 802.1AB LLDP with ANSI/TIA-1057 (LLDP-MED) ,IEEE 802.1D Spanning Tree (STP) ,IEEE 802.1s Multiple Spanning Tree (MSTP) ,IEEE 802.1w Rapid Spanning Tree (RSTP) ,IEEE 802.1p Quality of Service ,IEEE 802.1Q Virtual LANs / port-based VLANs ,IEEE 802.3ac — VLAN tagging ,IEEE 802.1v protocol-based VLAN ,IEEE 802.1X Radius Network Access Control ,IEEE 802.3x flow control ,GMRP — Dynamic L2 multicast registration ,GVRP — Dynamic VLAN registration ,GARP -Generic Attribute Registration Protocol ,ISDP (Industry Standard Discovery Protocol) ,Out of band Management ,SNMP v1, v2 and v3 ,RMON 1, 2, 3, 9 ,sFlow ,Command Line Interface (CLI) ,Web-based graphical user interface (GUI) ,Admin access control via Radius and TACACS+ ,Telnet ,IPv6 Management ,Dual Software (Firmware) images ,Dual Configuartion file ,Radius accounting ,SNTP ,XMODEM ,Port Mirroring ,Cable Test Utility ,SSH v1/v2 ,SSL v3 and TLS v1.2 for HTTPS web-based access ,File Transfer (uploads, downloads) through TFTP/HTTP ,SCP/ SFTP/ HTTPS ,Syslog ,Non disruptive Config Management ,Remote Port Mirroring (RSPAN) ,Persistent log supported ,Per port: Speed, link, activity ,Per device: Power, Fan ,Operating Temperature: 32° to 122°F (0° to 50°C) ,Operating Humidity: 90% maximum relative humidity, non-condensing ,Storage Temperature: – 4° to 158°F (–20° to 70°C) ,Storage Humidity: 95% maximum relative humidity, non-condensing ,CE: EN 55032:2012+AC:2013/CISPR 32:2012, EN 61000-3-2:2014, EN 60950-1, EN 62368-1 ,Class A, EN 61000-3-3:2013, EN 55024:2010 ,FCC Part 15 Class A ,VCCI-CISPR 32:2016, Class A ,RCM: AS/NZS CISPR 32:2013 Class A ,ISED: ICES-003:2016 Issue 6, Class A, ANSI C63.4:2014 ,BSMI: CNS 13438 Class A ,CB report / certificate IEC 62368-1 ,UL listed (UL 1950)/cUL IEC 950/EN 60950 complete in all respects as approved and desired by the Engineer-in-charge at site.
Supply, erection, testing & commissioning of 20 Port Gigabit Intelligent Standard PoE Switch, Ethernet 16*Gigabit PoE Ports 2*Uplink ports 2*Gigabit SFP Ports, Chipset EN8850DH,RTL8238B, Performance Bandwidth 40Gbps, Packet Forward Rate 29.76Mpps, Package Cache 3Mbit, MAC Address 8K, Forwarding Mode Store and forward, Network Protocol IEEE802.3 (Ethernet), IEEE802.3u (Fast Ethernet), IEEE802.3ab (Gigabit Ethernet), IEEE802.3x (Flow Control), IEEE 802.3z (Gigabit Ethernet Fiber Standard), PoE protocol IEEE802.3af (15.4W), IEEE802.3at (30W), POE port output voltage: DC 44-57V, POE power supply core: 1/2+; 3/6-, Industry Standard EMS: EN61000-4-2 (ESD), IEN61000-4-5 (Surge), Network medium: 10Base-T: Cat 3, 4, 5 Class or above UTP/STP (≤ 100m), 100Base-TX: Cat 5 Class or above UTP/STP (≤ 100m), 1000Base-TX: Cat 5 Class or above UTP/STP (≤ 100m), Optical Medium Multimode optical fiber: 50/125, 62.5/125, 100/140um, Single-mode optical fiber: 8/125, 8.7/125, 9/125, 10/125um, Safety Certificate CE/FCC/ROHS, Working Environment Working temperature: -10~50°C, Storage temperature: -40~70°C, Working humidity: 10%~90%, non-condensing, Storage humidity: 5%~95%, non-condensing, Structure Size: Product Dimensions: 320*207*44mm, Package Dimensions: 370*290*85mm, Product N.W: 1.87KG, Product G.W: 2.43KG, Packing Info Carton Dimensions: 445*310*390mm Packing Quantity:5 PCS, Packing Weight: 13.15KG, Power Voltage Input Voltage: AC 100-240 V 50-60Hz, approved makes cisco netgear hrui hp should
Supply, erection, testing & commissioning of HDD Formatted capacity 6 TB, Data transfer rate (max) Buffer to host Host to/from drive (sustained) 6 Gb/s 171 MB/s, Cache (MB) 64, Rotational speed (RPM) IntelliPower, Load/unload cycles4 300,000, Non-recoverable read errors per bits read <1 in 1014,Operating (2 ms, read/write) 30,Operating (2 ms, read) 65, Non-operating (2 ms) 250,Average power requirements (W) Read/Write 5.90, Idle 4.90, Standby and Sleep 0.40 complete in all respects as approved and desired by the Engineer in-charge at site.
Supply, erection, testing & commissioning of Display : 50 inch, 4K (3,840 x 2,160), Direct LED, Professional Display with 4K Processor, Native Contrast ratio 5,000:1 or higher, Response time 12 ms or lower, Brightness 400 cd/m² or higher, 24/7, Portrait/Tilt functionality, HDMI Auto wake up, HTML5 platform, 16GB On Board Storage, HDMI*4 with HDCP 2.3 / RS232 / USB / RJ45 / Wi-Fi Direct / 20W Speakers / Android OS or similar, Viewing angle 178 degree, Apple AirPlay & Chromecast.complete in all respects as approved and desired by the Engineer-in-charge at site.
Supply, Installation, Testing & Commissioning of 6 Mtr HDMI Cable for NVR, UL Listed complete in all respects as approved and desired by the Engineer in-charge at site.
Overall size 1.5sq.mm (48/0.20mm), 2Core
Supply, Installation, Testing & Commissioning of 1 KVA UPS with Input power factor - 0.99, Output power factor - 0.8, OVCD inbuilt , DC V 36v, Efficiency : Above 90% complete in all respects as approved and desired by the Engineer in-charge at site.
Providing Fire Detection/ Emergency Evacuation & PA System:
FIRE PANELS & ANNUNCIATORS:
Supply, installation, testing & Commissioning of Microprocessor based Multi-loop, True Peer-to-Peer Networkable Addressable Fire Alarm Control Panel with minimum 600 characters LCD display, 4000 event , 1000 alarm log history events, Qwerty/ Touch Screen keypad for operation. The panel should be equipped with sufficient numbers of loops considering 20% spare capacity in each loop. Each loop shall have a capacity of minimum 250 analog addressable devices (Devices and detectors). The panel shall work in degrade mode in case of CPU failure, Products not having this feature will offer Redundant CPU. Four access levels, flash EPROM, Panel Shall include 240 volts AC power supply, automatic battery charger, 24 volts sealed lead acid batteries sufficient for 24 hours normal working and 30 mins in alarm condition. The panel shall support with Integrated 8 channel Digital Voice Evacuation System Controller capable of broadcasting Evacuation Messages on same peer-to-peer Network and 2 ways Communication Fire Fighters System capable of supervising all the speaker circuits with adequate zone control and accessories. Failure of Fire Panel CPU shall not result in failure of DVC operation. The Fire Fighters Telephone System shall be capable of having minimum 5 Telephones in conference in multiple FFT Risers. The panel shall be expandable upto Min. 10 loop, UL & FM approved. Panel shall have provsion for Modbus/ Bacnet over IP protocol for future integration with BMS. However, for present arrangement FA system will be standalone with 24x7 monitoring. The panel shall be capable for remote accessibility on a mobile app through cloud platform/solution. Designed to meet UL864, 10th. complete in all respects as approved and desired by the Engineer in-charge at site.
Supply and erection of LED batten 20 Watt LED (including constant LED driver) with High quality extruded aluminium with efficacy of LED fixture minimunm 100 lumens per watt and operating voltage between 140 to 270 volt, THD <10% ingress protection IP20 (as per latest BIS standards) surge protection - 2.5 KV and above (as per IS/IEC standards) wattage of each low power LED less than 1 watt input AC frequency 50 Hz ± 3 % with 5 year warranty including there drivers complete along with erection of the same with connections, testing etc. complete in all respects as approved and desired by the Engineer-in-charge at site. LED Fitting as per Specifications approved by Hon. Tech. Advisor to CM Punjab vide Letter ION No: AT/2021/GL/1410-1422, Dated: 06.05.2021. Besides this the lighting fixtures manufactures should have in house NABL accredited laboratory.
Supply and erection of Recessed mounted 36watt LED panel (including LED driver) with CRCA sheet having efficacy of LED fixture minimunm 100 lumens per watt and operating voltage between 140 to 270 volt, THD <10% ingress protection IP20 (as per latest BIS standards) surge protection - 2.5 KV and above (as per IS/IEC standards) wattage of each low power LED less than 1 watt input AC frequency 50 Hz ± 3 % with 5 year warranty including there drivers complete along with erection of the same with connections, testing etc. complete in all respects as approved and desired by the Engineer-in-charge at site. LED Fitting as per Specifications approved by Hon. Tech. Advisor to CM Punjab vide Letter ION No: AT/2021/GL/1410-1422, Dated: 06.05.2021. Besides this the lighting fixtures manufactures should have in house NABL accredited laboratory.
Supply, installation, testing & Commissioning of Loop Cards Class A Wiring with min. supporting cable length Up to 1.2 Km UL & FM Approved .complete in all respects as approved and desired by the Engineer in-charge at site.
Supply, installation, testing & Commissioning of Paging Microphone compatible with Emergency evacuation Control Panel UL Listed complete in all respects as approved and desired by the Engineer in-charge at site.
Supply, installation, testing & Commissioning of Addressable photo-Thermal multi criteria Detector and base with sensitivity range as per NFPA 72. The intelligent detection device shall include the ability to combine the signal of the thermal sensor with the signal of the photoelectric signal in an effort to react hastily in the event of a fire situation. It shall also include the inherent ability to distinguish between a fire condition and a false alarm condition by examining the characteristics of the thermal and smoke sensing chambers and comparing them to a database of actual fire and deceptive phenomena. The detector shall have bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary/ Electronic decimal switches. Designed to meet UL & FM Approved . The solution should be from single OEM. complete in all respects as approved and desired by the Engineer in-charge at site.
Supply, install
ation, testing & Commissioning of Reponse Indicator for up side of ceiling complete in all respects as approved and desired by the Engineer in-charge at site.
Supply, installation, testing & Commissioning of Addressable Smoke photo-Thermal Detector and base with sensitivity range as per NFPA 72. The intelligent detection device shall include the ability to combine the signal of the thermal sensor with the signal of the photoelectric signal in an effort to react hastily in the event of a fire situation. It shall also include the inherent ability to distinguish between a fire condition and a false alarm condition by examining the characteristics of the thermal and smoke sensing chambers and comparing them to a database of actual fire and deceptive phenomena. The detector shall have bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary/ Electronic decimal switches. Designed to meet UL & FM Approved . The solution should be from single OEM. complete in all respects as approved and desired by the Engineer in-charge at site.
Supply, installation, testing & Commissioning of Addressable Rate of Rise Heat Detector rated at 8.3 deg C/min.NFPA 72. The detector shall have bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary/ Electronic decimal switches.UL & FM Approved The solution should be from single OEM.complete in all respects as approved and desired by the Engineer in-charge at site.
Supply, installation, testing & Commissioning of Addressable High Sensitivity Photo Detector with sensitivity level of 0.02% to 2% Obs/Feet. Mandatory for critical room like Server room,Computer room ,UPS Room,Record Rooms , Mal-Khana and almed room. The detector shall have the optic block to amplify signals from smoke, but diminish stray internal reflections that can cause false alarms. The detector should have on board drfit compensation, transient rejecion algoritms with superiro EMI protection. The detector shall have twin bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary decimal switches. Designed to meet UL268, 7th Edition. UL & FM Approved complete in all respects as approved and desired by the Engineer in-charge at site.
Supply and erection of LED batten 20 Watt LED (including constant LED driver) with High quality extruded aluminium with efficacy of LED fixture minimunm 100 lumens per watt and operating voltage between 140 to 270 volt, THD <10% ingress protection IP20 (as per latest BIS standards) surge protection - 2.5 KV and above (as per IS/IEC standards) wattage of each low power LED less than 1 watt input AC frequency 50 Hz ± 3 % with 5 year warranty including there drivers complete along with erection of the same with connections, testing etc. complete in all respects as approved and desired by the Engineer-in-charge at site. LED Fitting as per Specifications approved by Hon. Tech. Advisor to CM Punjab vide Letter ION No: AT/2021/GL/1410-1422, Dated: 06.05.2021. Besides this the lighting fixtures manufactures should have in house NABL accredited laboratory.
Supply and erection of Recessed mounted 36watt LED panel (including LED driver) with CRCA sheet having efficacy of LED fixture minimunm 100 lumens per watt and operating voltage between 140 to 270 volt, THD <10% ingress protection IP20 (as per latest BIS standards) surge protection - 2.5 KV and above (as per IS/IEC standards) wattage of each low power LED less than 1 watt input AC frequency 50 Hz ± 3 % with 5 year warranty including there drivers complete along with erection of the same with connections, testing etc. complete in all respects as approved and desired by the Engineer-in-charge at site. LED Fitting as per Specifications approved by Hon. Tech. Advisor to CM Punjab vide Letter ION No: AT/2021/GL/1410-1422, Dated: 06.05.2021. Besides this the lighting fixtures manufactures should have in house NABL accredited laboratory.
Supply, installation, testing & Commissioning of Addressable Manual Call Point (Pull down / Break Glass Type). The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device complete in all respects as approved and desired by the Engineer in-charge at site.UL & FM Approved complete in all respects as approved and desired by the Engineer in-charge at site.
Supply, installation, testing & Commissioning of Sounder cum Strobe rated at 80 dBA @ 3m for Audible annunciation and Min.110 cd flashintg at 1 Hz for visual indication. UL & FM Approved complete in all respects as approved and desired by the Engineer in-charge at site.
Supply, installation, testing & Commissioning of Strobe rated at 80 dBA @ 3m for Audible annunciation and 115cd flashintg at 1 Hz for visual indication. UL Listed. complete in all respects as approved and desired by the Engineer in-charge at site.
Supply, installation, testing & Commissioning of Addressable Control Module for Sounders / Strobes / Sounder cum Strobes/ Telephone Jack. The control module shall provide supervised NAC output rated at 24v DC, 2A. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Addressing shall be with user friendly rotary / Electronic decimal switches UL & FM Approved complete in all respects as approved and desired by the Engineer in-charge at site.
Supply, installation, testing & Commissioning of Monitor Module for Sprinklers, Panic Bars & other Third Party Inputs. The monitor module shall monitor potential free contacts. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Addressing shall be with user friendly rotary/ Electronic decimal switches UL & FM Approved complete in all respects as approved and desired by the Engineer in-charge at site.
Supply, installation, testing & Commissioning of Isolator Module for Isolating short / dewired / loose circuits with automatic resetting arrangement. Isolator Base can also be proposed, however in that case needs to be considered with each detector & module. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device.UL & FM Approved Module shall be supplied with mounting plate from OEM for ease of installation & maintenance.The solution should be from single OEM.complete in all respects as approved and desired by the Engineer in-charge at site.
Supply, installation, testing & Commissioning of Monitor Module for Sprinklers, Panic Bars & other Third Party Inputs. The monitor module shall monitor potential free contacts. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Addressing shall be with user friendly rotary/ Electronic decimal switches UL & FM Approved complete in all respects as approved and desired by the Engineer in-charge at site.
Supply, installation, testing & Commissioning of Addressable Relay Module for AHU, Access Control, Lifts, Staircase Pressurization, Fire Suppression & other Third Party Outputs. The relay module shall provide contact rated at 24v DC, 2A. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Addressing shall be with user friendly rotary/ Electronic decimal switches UL & FM Approved complete in all respects as approved and desired by the Engineer in-charge at site.
Supply, installation, testing & Commissioning of Monitor Module for Sprinklers, Panic Bars & other Third Party Inputs. The monitor module shall monitor potential free contacts. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Addressing shall be with user friendly rotary/ Electronic decimal switches UL & FM Approved complete in all respects as approved and desired by the Engineer in-charge at site.
Supply,installation, testing & Commissioning of Digital Audio Amplifier with cabinet & Amp power supply. Amplifier shall be capable of N:N/N:1 configuration and shall be dual channel capable of processing Two of 8 audio channels and a total of Min 95 W ( It may be 1 unit or Combination of Multiple units to achieve the Requirement) at 70.7 VRMS output along with necessary enclosures with local FFT Raiser. The Digital Audio Amplifier shall be fully monitored for fault and alarm reporting. The proposed Digital Audio Amplifiers shall (be Wall/Panel Mounted) Failure of Fire Panel CPU shall not result in failure of Amplifier operation. Amplifiers shall be distributed across the building/floor to manage the sound attenuation problem & for the best sound intelligibility. All amplifiers shall provide back up of minimum 5 hours using secondary power source(battery power/UPS power) complete in all respects as approved and desired by the Engineer in-charge at site.
Supply, installation, testing & Commissioning of 2W Multi-Tap (0.25W; 0.5W; 1W; 2W), Ceiling/Wall Mount Speakers. The speakers shall be of the same make as that of the Control Panel & Amplifiers. They shall be compatible with supplied Amplifiers and shall work on 70.7Vrms UL Listed complete in all respects as approved and desired by the Engineer in-charge at site.
Supply, installation, testing & Commissioning of Back Box for 2W Multi-Tap (0.25W; 0.5W; 1W; 2W), Ceiling/Wall Mount Speakers as per site requirement complete in all respects as approved and desired by the Engineer in-charge at site.
Supply, installation, testing & Commissioning of Digital Voice Command Keyboard/ Touch Screen for local annunciation and controls; status LEDs and 24 user-programmable buttons.Display All Call, Page Active Evac Areas, Page Active Alert Areas, Page Inactive Areas UL Listed . The solution should be from single OEM.
Supply, installation, te
sting & Commissioning of Fire Fighter's Telephone Handset for two way communication between Remote Fire Fighter & Fire Command Center UL Listed complete in all respects as approved and desired by the Engineer in-charge at site.
Providing Advance Lightning Protection System:
COPPER EARTHING STRIP (As Additional Length): Fixing additional Length of earthing with Copper Tape (On Surface/Flushed) with petty material as required etc.:-
Additional Length 25mm x 5mm thick Copper Tap
Additional Length 40mm x 5mm thick Copper Tape
Supply, installation, testing & Commissioning of Addressable Fire Fighter's Telephone Jack for two way communication between Remote Fire Fighter & Fire Command Center UL Listed complete in all respects as approved and desired by the Engineer in-charge at site.
Supply, installation, testing & Commissioning of Exi LED M ST LED based exit sign with dimming function, Reading distance, exit sign Two-sided 25m, Voltage 220-240VAC / 50-60Hz, Power consumption 3.3W / 3.5VA, Battery 3.6V/1.2Ah NiMH, Battery protection Over charge protection /deep discharge protection, Charging Time 16 hours, Battery back-up time 1 hour / 3 hours / 8 hours (from dip switch), Light source 15 LED, Approvals EN 60598-1, EN 60598-2-22, EN 55015, EN 61547, EN 61000-3-2, EN 61000-3-3, Ambient temperature 5 to 40 °C, Humidity Up to 95%, IK rating IK09, IP rating IP40, Dimensions 265 x 53 x 222 mm, Weight 540 / 742 gr , Colour Anodized aluminum / black plastic, Materials Aluminum, Acrylic Plate, Mounting method Ceiling, wall bracket, suspended, pendulum, flag mount, Delivered as self-contained/auto test luminaire Choice of 1, 3 or 8 hour autonomy via DIP switch IP 40 – dustproof luminaire Reading distance upto 25 meters.High lumen output – 1h = 180lm / 3h = 110lm /8h = 40lm Technical lifetime of LED > 100 000 hours , 4 Pictograms (left, right, down, up) are included in the luminaire ordering part code complete in all respects as approved and desired by the Engineer in-charge at site.
Supply, installation, testing & Commissioning of Emergency LED NM LED IP42 230V 2X6W 1h/3h/8h. The luminiare comes in plastic housing. Mounting bracket is not required for this luminaire, IP42/NA 0 Non -Maintained Self Testing 12V / 7Ah Pb, LED based for anti-panic area, surface assembly Delivered as self-contained/auto test luminaire Choice of 1, 3 or 8 hour autonomy via DIP switch High lumen output – 1h = 360lm / 3h = 170lm / 8h = 70lm Simple and quick assembly and maintenance Technical lifetime of LED > 100 000 hours • IP42 – dust and waterproof luminaire, Voltage 220-240VAC / 50-60Hz Power consumption 11.4W / 11.8VA Battery 12V / 7Ah Pb Battery protection Over charge protection /deep discharge protection Charging Time 23 hours, Battery back-up time 1 hour / 3 hours / 8 hours (from dip switch), Light source LED 2x6, Technical lifetime (light source) >100 000 hours, Lumen output, emergency (1h / 3h / 8h) 3200 / 1600 / 800 lm, Approvals EN 60598-1, EN 60598-2-22, EN 55015, EN 61547, EN 61000-3-2, EN 61000-3-3, Ambient temperature 5 to 40 °C, Humidity Up to 95%, IP rating IP42, Dimensions 302 x 94 x 210 mm, Weight 4200 / 4420 gr, Materials PC/ABS, PC, Aluminium, Mounting method Wall mounting complete in all respects as approved and desired by the Engineer in-charge at site.
Supply, installation, testing & Commissioning of Online UPS 1 kva 800 Watts Tower UPS with 1 hour battery backup. Operating Temperature Range 0 to 40 Degree @ 100% Load @ 50 Degree with 50% Load,Storage Temperature -15°C~60°C, Relative Humidity 0-95% No condensates, Acoustic Noise 40 dBA @ 1 Meter, Cooling Forced air cooling by the internal fans, Input Socket IEC C13, Output Socket IEC C14, No of output sockets 3 No's, Rated Input Voltage 208/220/230/240 Vac, Maximum working input voltage range 160 to 300 Vac @ 100% Load, 100 to 300 Vac @ 50% Load, Input Power Factor 0.99, Input THDi% 5%, Generator Set Yes 1.5 x UPS Capacity, Rated kVA 1000 VA, Rated kW 800 Watts, Load type Resistive load/ lagging load/ non-linear load/ transformer load/ lighting load, Load power factor range 0.5~1 lagging, Load Crest Ratio 3:1, Online Efficiency 88%, Rated Battery Voltage 36 Vdc, Battery Type VRLA (Valve Regulated Lead Acid Battery), 12VDC, Battery backup Back UP : 936VAH, Maximum charging current 10 Amps, ECO Mode Available, Communication (Independent SCI) Available, Intelligent Card slot (Independent SCI) Available, OVCD Available, EPO Function Available, Intelligent Fans Speed control Available, Auto restart function Available, Cold start Available complete in all respects as approved and desired by the Engineer in-charge at site.
PVC INSULATED PVC SHEATHED FR ROUND FLEXIBLE COPPER CONDUCTOR CABLE: Supply and erection of PVC insulated PVC sheathed FR (2Core) round flexible wire with copper conductor cable (ISI marked) confirm to IS:694/1990 left bare in pipe or on surface with cleats of suitable size complete in all respect as desired by the Engineer-in-charge:-
PVC INSULATED PVC SHEATHED FR ROUND FLEXIBLE COPPER CONDUCTOR CABLE: Supply and erection of PVC insulated PVC sheathed FR (2Core) round flexible wire with copper conductor cable (ISI marked) confirm to IS:694/1990 left bare in pipe or on surface with cleats of suitable size complete in all respect as desired by the Engineer-in-charge:-
Supply and erection of fire survival cable for fire alarm & PA system with annealed stranded copper conductor, fire resistant mica tape wrapped (at 950°C for 180 minutes), XLPE insulated, LSHZ (low smoke & zero halogen) bedding, LSZH (low smoke & zero halogen) red outer sheath, galvanized steel wire armour, 600/1000 volts grade, Fire resistant to IEC 331 & BS7846 F2/BS6387 & CWZ, Acid gas emission to BS EN 50267 (IEC60754), smoke emission to BS EN 50268 (IEC61034) and flame propagation to BS EN 50265, BS EN 50266 (IEC 60332-3) left bare in pipe or casing or on surface with cleats of suitable size complete in all respect as desired by the Engineer-in-charge:-
Fire Survival cable 2Coe x 1.5 sq.mm
HEAVY GUAGE WELDED CONDUIT PIPES: Supply & erection of Heavy guage welded conduit pipe (ISI marked) as per IS:9537:Part-II for wiring purposes including bends, junction boxes, Steel hooks, GI saddle clamps and other petty materials etc., where necessary including painting as per PWD Gen
eral Specifications:-
Heavy gauge welded conduit pipe 25mm dia. (ISI marked 1.60mm thick) Flushed
Providing Nurse Call System :
Supply, erection, testing & commissioning of VDE0834 approved Patient Handset without speech *One patient call button, red. With locating light and reassurance light.With DIN VDE call panel monitoring. *Antimicrobial membrane keypad: The patient call button has a tangible,raised edge, enabling very simple keying. Furthermore, the entire surface of the patient call button can be pressed. *15-pin Sub-D plug, can be withdrawn in any direction. complete in all respects as approved and desired by the Engineer-in-charge at site.
Supply, erection, testing & commissioning of VDE0834 approved Call & reset panel with socket: *Patient call button, red. With locating light and reassurance light. *Cancel button, grey. *15-pin Sub-D socket for connection of: – Adapter for medical device, with Sub-D plug – Radio receiver *Line monitoring/Plug removed call. *Functions may be modified subsequently. *Connection of room and bed light,control with patient handset with light buttons. *Mounted in round mounting box R1.. complete in all respects as approved and desired by the Engineer-in-charge at site.
Supply, erection, testing & commissioning of VDE0834 approved Pull cord panel with 3 m pull cord: *Pull cord for pull cord panel (red), for patient call. With reassurance light (LED, yellow). *Mounted in round mounting box R1. complete in all respects as approved and desired by the Engineer-in-charge at site.
Supply, erection, testing & commissioning of VDE0834 approved Reset panel for cancelling calls: *Cancel button, grey. *Functions may be modified subsequently. *Mounted in round mounting box R1. complete in all respects as approved and desired by the Engineer-in-charge at site.
Supply, erection, testing & commissioning of VDE0834 approved Room electronics: *Addressable LON node with control electronics for all room components. *With 8 freely programmable monitored inputs and outputs for connecting room components in accordance with DIN VDE 0834: – Call and presence panel – Sockets at the bed *For each input there is an output for a reassurance light for unambiguous identification of the call line in the room.. complete in all respects as approved and desired by the Engineer-in-charge at site.
Supply, erection, testing & commissioning of VDE0834 approved Repeater without galvanic separation: – For expanding system bus sections with more than 31 nodes – To refresh the data signal over distances of more than 1000 m – To branch the system bus into spurs *2-channel data line amplifier *Data flow control with LED *Isolation of the channels with jumpers to simplify troubleshooting in the call system. complete in all respects as approved and desired by the Engineer-in-charge at site.
Supply, erection, testing & commissioning of Software for logging events (calls, messages,faults, presences, voice contacts,announcements, tag information, shift changes)complete in all respects as approved and desired by the Engineer-in-charge at site.
Providing UPS System 2Nos. 30KVA with isolation transformer (30 Min. Back-up):
Supply, Erection, Testing & commissioning of 30 KVA IGBT based Online UPS 30000 VA / 24000 watt 3 phase input 3 phase out put with inbuilt isolation transformer, approx 30 min backup (Special Features:-Advanced Microprocessor Control, LCD Display on front Panel, 0.9 Power Factor (30000 VA / 24000 watt), Can be mounted in a Server Rack, Can be Mounted in Parrallel Mode, Heavy Duty Charger upto 13amp, Dual Input Supply available, Extra Wide Input Voltage Range, Input Power Factor Correction, Sine-Wave Output, EMI/RFI Filters & Surge Protection, Self Diagnostic & Battery Tests, Intelligent Battery Management, User-friendly Panel with Load & Battery Bar-Graphs, Power Chute Software for UPS Power Management & Diagnostics compatible to, Windows, Novell & Unix (Automatic PC Shut down Software), 32/34 nos.100ah Battery, Rack for Battery, Battery interconnecting cables, cables between UPS and Battery and Battery circuit breaker as approved & desired by the Engineer in charge at site. complete in all respects as approved and desired by the Engineer-in-charge at site.
Providing Silent Diesel Generating Sets: For Main Building: 1No. 320kVA, 250kVA & 160kVA DG Set with Manual Control Panel:
Supply, Erection, Testing and Commissioning of Silent (Sound Proof) Diesel Generator Set 320KVA /256KW with AMF Panel .It should be air cooled/water cooled naturally aspirated/ turbo charged/ turbo charged after cool (As per manufacturer standard). ENGINE: The Diesel engine developing 400 BHP (Approx.) for giving a power rating as per ISO 8528- Part-1 ( With CPCB-IV Norms as amended upto date) in KVA at the load terminals of alternator at 1500 rpm at actual site conditions. The engine shall confirm to IS 10000/ ISO 3046/ BS: 649/ BS 5514 amended up to date have dynamically balanced Fly wheel, air cleaner (dry/ oil bath type) as per manufacturer standard. A mechanical/ electronic governor of TYPE A1 AND A2 to maintain engine speed at all conditions of load, daily fuel service tank of minimum 8 hours running capacity as per manufacturer standard, Dry exhaust manifold with suitable exhaust residential grade silencer to reduce
the noise level.suitable self-starter for 12 V/ 24 V DC ,battery charging alternator unit and voltage regulator, Lubrication oil cooler,Lubrication oil filters with replaceable elements. ENGINE CONTROL PANEL: Engine control panel fitted and having digital display i.e Start/stop key switch/push button, Battery charging indication,Engine Hours indications, Over speed indication, High water temperature indication, Lubricant oil pressure indication,) RPM indication and MCCB (Fixed Thermal and Adjustable Thermal protection) of suitable rating for outgoing supply. ALTERNATOR: The alternator should be designed as per (IS4722 and IEC:34 ) standard. Rated Power Factor : 0.8 (lag), Rated voltage : 230/415 volt, SPDP (Screen Protected Drip Proof), Degree of protection: IP-23, Ventilation : Self ventilated air cooled Alternator should have 40 degree maximum class H insulation, Automatic voltage regulator unit should be provided as per standard practice of manufacturer. Its voltage dip shall not exceed more than 20% of the rated voltage at any step load or transient load as per ISO 8528 (Part-1). Its efficiency at full load 0.8 power factor, 10% overload one hour in every 12 hrs of continuous use.
ACOUSTIC ENCLOSURE: The enclosure shall be fabricated out the CRCA sheet of thickness not less than 1.6 mm on the outside cover with inside cover having not less than 0.6 mm thick perforated powder coated CRCA sheet. It should be IP54 Suitable for outdoor installation exposed to weather conditions, noise level up to 75 dB (A). All sheet metal parts should be processed through 7-tank pre treatment process and batteries accommodated in the battery rack .The acoustic lining should be made up of high quality insulation material i.e. Rockwool / glass/ mineral wool / PU foam of appropriate thickness & density for sound absorption.The inside of enclosure should be provided with at least one no. 28 W-T5 fluorescent tube light/ LED 10Watt luminaries controlled by a 5A switch for adequate lighting during servicing etc.with 2 year warranty from the date of installation. complete in all respect as desired by engineer at site:-The Generator set should be instaaled at site on the suitable size existing plinth of RCC as per specifacation DG set as per satisfacation of the Engineer- in-Charge at site. The model of engine will be decided by the Engineer in Charge. MANUAL CONTROL PANEL: Manual control panel shall be fabricated out of 1.6 mm sheet steel, totally enclosed, dust, damp and vermin proof wall mounted/ free standing floor mounted type with IP-53 degree of protection & front operated, composite meter for digital display, HRC fuses of suitable rating. MCCB (Fixed Thermal and Adjustable Thermal protection)/ ACB (Over cuurent/ overload, shorcircuit, instantenous, earth fault protection) should be used. Battery charger complete with voltage regulator, Voltmeter and Ammeter for charging the battery from external mains. This will be in addition to the battery charging alternator or dynamo fitted on the engine.All the components in the control panel shall be properly mounted, duly wired and labeled. Suitable terminals are to be provided for panel incoming and outgoing connections. System opeartion facility provided shall afford the following operational requirements. Necessary instruments and accessories such as voltmeter, power factor meter, KW meter, KWH meter, Ammeter, Frequency meter,battery charger complete in all respect as desired by engineer at site:-
sting & Commissioning of Fire Fighter's Telephone Handset for two way communication between Remote Fire Fighter & Fire Command Center UL Listed complete in all respects as approved and desired by the Engineer in-charge at site.
Supply,installation, testing & Commissioning of Digital Audio Amplifier with cabinet & Amp power supply. Amplifier shall be capable of N:N/N:1 configuration and shall be dual channel capable of processing Two of 8 audio channels and a total of Min 95 W ( It may be 1 unit or Combination of Multiple units to achieve the Requirement) at 70.7 VRMS output along with necessary enclosures with local FFT Raiser. The Digital Audio Amplifier shall be fully monitored for fault and alarm reporting. The proposed Digital Audio Amplifiers shall (be Wall/Panel Mounted) Failure of Fire Panel CPU shall not result in failure of Amplifier operation. Amplifiers shall be distributed across the building/floor to manage the sound attenuation problem & for the best sound intelligibility. All amplifiers shall provide back up of minimum 5 hours using secondary power source(battery power/UPS power) complete in all respects as approved and desired by the Engineer in-charge at site.
MCCB Four Pole 63amp., 415volts, ≥25kA Fixed Magnetic and Adjustable Thermal Setting (For 1No. X-Ray Machine & 2Nos. Sterlization Units)
Supply, Erection, Testing and Commissioning of Silent (Sound Proof) Diesel Generator Set 250 KVA /200KW with AMF Control Panel .It should be air cooled/water cooled naturally aspirated/ turbo charged/ turbo charged after cool (As per manufacturer standard). ENGINE: The Diesel engine developing 310 BHP (Approx.) for giving a power rating as per ISO 8528- Part-1 ( With CPCB-IV Norms as amended upto date) in KVA at the load terminals of alternator at 1500 rpm at actual site conditions. The engine shall confirm to IS 10000/ ISO 3046/ BS: 649/ BS 5514 amended up to date have dynamically balanced Fly wheel, air cleaner (dry/ oil bath type) as per manufacturer standard. A mechanical/ electronic governor of TYPE A1 AND A2 to maintain engine speed at all conditions of load, daily fuel service tank of minimum 8 hours running capacity as per manufacturer standard, Dry exhaust manifold with suitable exhaust residential grade silencer to reduce the noise level.suitable self-starter for 12 V/ 24 V DC ,battery charging alternator unit and voltage regulator, Lubrication oil cooler,Lubrication oil filters with replaceable elements. ENGINE CONTROL PANEL: Engine control panel fitted and having digital display i.e Start/stop key switch/push button, Battery charging indication,Engine Hours indications, Over speed indication, High water temperature indication, Lubricant oil pressure indication,) RPM indication and MCCB (Fixed Thermal and Adjustable Thermal protection) of suitable rating for outgoing supply. ALTERNATOR: The alternator should be designed as per (IS4722 and IEC:34 ) standard. Rated Power Factor : 0.8 (lag), Rated voltage : 230/415 volt, SPDP (Screen Protected Drip Proof), Degree of protection: IP-23, Ventilation : Self ventilated air cooled Alternator should have 40 degree maximum class H insulation, Automatic voltage regulator unit should be provided as per standard practice of manufacturer. Its voltage dip shall not exceed more than 20% of the rated voltage at any step load or transient load as per ISO 8528 (Part-1). Its efficiency at full load 0.8 power factor, 10% overload one hour in every 12 hrs of continuous use.
Supply, Erection, Testing and Commissioning of Silent (Sound Proof) Diesel Generator Set 160 KVA /128KW .It should be air cooled/water cooled naturally aspirated/ turbo charged/ turbo charged after cool (As per manufacturer standard). ENGINE: The Diesel engine developing 199 BHP (Approx.) for giving a power rating as per ISO 8528- Part-1 ( With CPCB-II Norms) in KVA at the load terminals of alternator at 1500 rpm at actual site conditions. The engine shall confirm to IS 10000/ ISO 3046/ BS: 649/ BS 5514 amended up to date have dynamically balanced Fly wheel, air cleaner (dry/ oil bath type) as per manufacturer standard. A mechanical/ electronic governor of TYPE A1 AND A2 to maintain engine speed at all conditions of load, daily fuel service tank of minimum 8 hours running capacity as per manufacturer standard, Dry exhaust manifold with suitable exhaust residential grade silencer to reduce the noise level.suitable self-starter for 12 V/ 24 V DC ,battery charging alternator unit and voltage regulator, Lubrication oil cooler,Lubrication oil filters with replaceable elements. ENGINE CONTROL PANEL: Engine control panel fitted and having digital display i.e Start/stop key switch/push button, Battery charging indication,Engine Hours indications, Over speed indication, High water temperature indication, Lubricant oil pressure indication,) RPM indication and MCCB (Fixed Thermal and Adjustable Thermal protection) of suitable rating for outgoing supply. ALTERNATOR: The alternator should be designed as per (IS4722 and IEC:34 ) standard. Rated Power Factor : 0.8 (lag), Rated voltage : 230/415 volt, SPDP (Screen Protected Drip Proof), Degree of protection: IP-23, Ventilation : Self ventilated air cooled Alternator should have 40 degree maximum class H insulation, Automatic voltage regulator unit should be provided as per standard practice of manufacturer. Its voltage dip shall not exceed more than 20% of the rated voltage at any step load or transient load as per ISO 8528 (Part-1). Its efficiency at full load 0.8 power factor, 10% overload one hour in every 12 hrs of continuous use.
Providing Advance Lightning Protection System:
COPPER EARTHING STRIP (As Additional Length): Fixing additional Length of earthing with Copper Tape (On Surface/Flushed) with petty material as required etc.:-
Additional Length 20mm x 3mm thick Copper Tape .
Additional Length 25mm x 3mm thick Copper Tap
Additional Length 25mm x 5mm thick Copper Tap
Additional Length 40mm x 5mm thick Copper Tape
INDOOR LT CABLES, CABLE TRAY & DWC PIPE:
XLPE INSULATED UN-ARMOURED CABLES (LOOSE):- Supply, laying and erection of aluminium conductor XLPE insulated PVC sheathed Un-armoured and served cable 1100 volts grade as per IS 7098 (Part-1)1988 to be laid loose in the existing trench or pipe as per PWD General Specifications:-
INDOOR LT CABLES, CABLE TRAY, DWC PIPE , BRASS GLANDS & THIMBLES:
Overall size 6sq.mm (2Core) Un-armoured (Loose)
Overall size 240sq.mm (3½ Core) Un-armoured (Loose) 2Runs from DG Set 320KVA to Synch. AMF Panel
Overall size 150sq.mm (3½ Core) Un-armoured (Loose)
Overall size 400sq.mm (3½ Core) Un-armoured (Loose)
Cable Tray Size 300mm x 50mm x 50mm (2mm thick)
Aluminium thimble cable Core size 120sq.mm
Double walled corrugated (DWC) HDPE pipe 63/51 mm (outer/ inner dia.)
Supply, installation, testing & Commissioning of Addressable Fire Fighter's Telephone Jack for two way communication between Remote Fire Fighter & Fire Command Center UL Listed complete in all respects as approved and desired by the Engineer in-charge at site.
LT PANEL-2 (EMERGENCY SERVICES): FOR X-RAY MACHINES & STERLIZATION UNITS:
erall size 400sq.mm (3½ Core) Un-armoured (Loose) 1Run from DG Set 250KVA to Synch. AMF Panel
Overall size 185sq.mm (3½ Core) Un-armoured (Loose) 1Run from DG Set 160KVA to Synch. AMF Panel
MCCB's (MOULDED CASE CIRCUIT BREAKER): Supply and erection of Moulded Case Circuit Breaker (Panel mounting Cubical type) in the existing Cubical Panel (confirm to IEC:60947-2) having Ics=100% Icu, 100% neutral with spreader terminal links, Extended rotary handle and relevant PWD general specifications complete with G.I. Bolts, Nuts & Connection on both sides of MCCB with suitable size of thimbles etc
PVC INSULATED PVC SHEATHED FR ROUND FLEXIBLE COPPER CONDUCTOR CABLE: Supply and erection of PVC insulated PVC sheathed FR (2Core) round flexible wire with copper conductor cable (ISI marked) confirm to IS:694/1990 left bare in pipe or on surface with cleats of suitable size complete in all respect as desired by the Engineer-in-charge:-
MS Sheet Enclosure having provision for MCCB 40-160Amp.with extended rotary handle (Approx. Size 500mm x 300mm x 200mm)
PVC INSULATED SINGLE CORE FR COPPER CONDUCTOR CABLE: Supply and erection of XLPE/ PVC insulated PVC sheathed (10 core) unarmoured copper conductor cable (ISI marked) confirm to IS:7098 (PART-I), 1988 loose in the existing trench or pipe with suitable size of copper thimbles/ lugs complete in all respect as desired by the Engineer-in-charge:- (From DG Sets to Synch. AMF Panel)
Overall size 2.5sq.mm (10 Core)
COPPER EARTHING
COPPER EARTHING (Upto 14 metre in Length):- iii- Earthing with electrolytic Copper Tape rivetted (with 5Nos. copper rivets)/Steel Nut & bolts (with 4Nos. 32mm long, 8mm thick with washer and double nut) to 30cm x 120cm x 2mm thick copper plate (made cylindrical) burried 10.50 metre (34.44 feet) below ground level in the hole of excavation having bore dia. 125mm and surrounded by salt & charcoal dust mixture (20 kg.) including fixing the Copper Tape recessed in wall and in floor etc., up to 14metre in Length (including bore Length). G.I. pipe 20mm dia. (A-class), 9metre long should be laid in the hole of excavation 1 feet below ground level and having GI Reducer 50mm x 20mm with PVC Cap (For pouring water) fixed on the top level of the pipe. 300mm x 300mm x 300mm deep haudi of First class bricks finished with 1:4 cement plaster and haudi covered with cast iron lid having size 300mm x 300mm (Heavy) around the hole of excavation:- (Body earthing & Neutral Earthing)
Earthing with 25mm x 3mm Copper Tape (upto 14Metre in Length) (Body earthing & Neutral Earthing: 8Nos. for DG Set 160KVA & 250KVA)
Earthing with 25mm x 5mm Copper Tape (upto 14Metre in Length) (Body earthing & Neutral Earthing: 4Nos. for DG Set 320KVA)
Additional Length 25mm x 3mm thick Copper Tape
Providing 11 KV Sub Station: For Main Building: 1No. 1600KVA Transformer For HVAC Load of the Building: 1No. 1600KVA Transformer
VACUUM CIRCUIT BREAKER: IN SUBSTATION FOR 2NOS. TRANSFORMERS 1600KVA
Brass Gland for Aluminium cable 2/3/4 Core size 16sq.mm
Brass Gland for Aluminium cable 2/3/3½/4 Core size 150sq.mm
Supply, Erection, Testing and Commisioning of 11kV, 3Phase, 50Hz, Indoor metal clad, floor mounted, ‘Horizontal draw out’ type VCB (Vacuum Circuit Breaker) switch board unit 630 Amp. which includes 630/800 Amp. Vacuum Circuit Breaker for Incoming/ Out going feeder with Electrolytic Copper bus bars of suitable rating, Horizontal Isolation type as per IEC 62271-100-200. The Switchgear panels shall be sheet steel construction with sheet steel not less than 2.5mm thickness for load bearing sections and not less than 2mm thickness for non-load bearing, dust, moisture and vermin proof to provide a degree of protection IP-4X in accordance with IS:13947. VCBs are type tested according to International Standards IEC-62271 at renowned laboratories. They are compact, safe and reliable. The Panels shall be tested for IAC level of 25kA/1 Sec. No. of operations of Vacuum interrupter bottles for better performance (i) At rated current: 10,000 operation (ii) No. of short circuit dead operation at rated short circuit current: 50 opeartion
VCB parameters are as below: (a). Rated Voltage: 12kV (b). Rated short circuit breaking current withstand : Min. 25kA for 3sec. (c). Rated insulation voltage lightning (Impulse withstand) : At 75kV Peak (d). Rated insulation voltage( Power frequency withstand) : Min. 28kV (e). Rated operating sequence : O-0.3 sec - CO - 3 min-CO (f). Spring charging mechanism : Manually as well as motor operated (230V, AC, 50Hz) (g). Operation type: Manually and electrically open (Electrical-230V, AC,50Hz) (h). Earthing Switch : Mechanically interlocked device to prevent personnel from getting electric shock during breaker maintenance. VCB incorporating mechanical as well as electrical ON/OFF indiaction "OFF" push button, test/ serviceposition limit switches, with minimum 6NO+6NC breaker auxiliary contacts in service position, Manual charging of breaker should be done without opening the front door.
Overall size 1.5sq.mm (Un-sheathed)
Outgoing shall consist of: (a). Cast Resin CT's 11kV : 600-300/1-1A, Core1: Class1, 10VA for 3phase, Core2: 5P10, 10VA (b). Protections : Numerical instantaneous IDMTL mimic dispaly relay : E/F, O/C, S/C & TCS with RS485 Modbus protocol for communication & drawout type for line feeder protection (c). Master Trip/ Anti pumping relay (d). Transformer Protection : 3 elements auxiliary relay (230V, AC,
11kV, 3Phase, 50Hz, Indoor metal clad, floor mounted, ‘Horizontal draw out’ type VCB (Vacuum Circuit Breaker) Switch board unit 630 Amp. which includes 1 No. 630 /800Amp. Vacuum Circuit Breaker as Incomer, 2Nos. Vacuum Circuit Breaker as Out going feeder with in built power packs interconnected with Electrolytic Copper bus bars of suitable rating
TRANSFORMERS 1600KVA: (1No. for Building Electrical Load & 1No. for Building HVAC & PH Services Load)
Supply, installation, testing and commissioning of 11KV/433V, 1600KVA, Indoor/Outdoor type floor mounted Distribution Transformer, Three Phase 50 Hz, Oil Immersed, Naturally Cooled ONAN, Core type Double wound with copper conductor conforming to IS:1180 (As amended upto date) Level-2 & IS: 2026 with first filling of Oil as per IS:335 compltete with connections on both sides (HT/LT side) as per satisfaction of Engineer Incharge at site. (a). Output Rating : KVA (b). No Load Voltage ratio at rated voltage & frequency: 11KV/ 0.433kV (c). On Load Circuit Tap changer: +5% to -10% off circuit tapping in steps of 2.5% with RTCC (d). Vector group : Dyn11 (e). Ambient temperature: 50°C (f). Oil/ Winding temperature rise: As per IS:1180 (g). Magnetic Core: Prime grade of M4 or better (h). System Highest Voltage :- 12kV at the HV side (i). Terminations: Cable Box on HV & LV Side (j). Insulation Level: ● H.V. Power Frequency (KV rms) : 28 kV ● H.V. Impulse withstand voltage (KV peak): 75 kVp The Tranformers shall fitted with accesories like Rating and Diagram anodized aluminium plate, 2 Nos. Earthing terminals, 4 Nos. Lifting Lugs, Air Release hole with plug, Dehydrating Silica Gel Breather, Oil Level guage with minimum level marking, Conservator with Oil filling hole with cap & drain plug, Thermometer Pocket, Jacking Lugs, Bottom Drain cum filter valve, Top Filter Valve, 4Nos. Uni-directional rollers, Explosion vent with diaphragm, Marshmalling Box (Protection Class IP55), OTI with alarm & trip, WTI with alarm & trip, Double float Buchholz relay with alarm & trip, 2Nos. Shunt off valves for Buchholz relay & Fixed/ Detachable Radiator. Note: Manufacturer shell ensure that there is no mixing of scond grade core. Transformer designed for 110% continuous overfluxing withstand capability as per IS:6600. Noise Level for Transformer shall be as per NEMA TR1-2013. All Routine Test shall be carried out as per IS: 2026:-
Supply and erection of SMC Junction Box (Glass Fibre reinforced polyester sheet moulding compound) confirm to IS:14772 (Recessed/ On surface), robustly constructed, safe & shock proof, rust & tamper proof of suitable inner & outer dimensions with ± 10% tolerance in size & hinged water tight cover with locking arrangement having 1No. terminal strip with 4Nos. terminals & 1No. Single pole MCB of required capacity fixed on din bar (Din Bar Provision for 2Nos. MCB's) complete in all respect as approved and desired by the Engineer In-Charge at site:-
HT CABLE, END TERMINATION KITS & CONTROL CABLE FOR TRANSFOMER:
XLPE INSULATED HT ARMOURED CABLES (UNDERGROUND): Supply & laying of Circular Aluminium Conductor screened with extruded semiconducting compound, XLPE insulated, insulation screened with extruded semiconducting combination in combination with copper tape (0.3KA for 1sec.) cores laid up, FR PVC inner sheathed, galvanized steel strip armoured and overall FR PVC sheathed cable confirming to IS:7098 (Part-2), 2011 working voltage 11KV(E) grade to be laid 1.50 meter below ground level including excavation, sand cushioning, covering with sand & First class bricks and back filling the trench etc., of the required size:-
HT Cable Overall size 400sq.mm (3Core) (From Existing Substation to New VCB )
XLPE INSULATED HT ARMOURED CABLES (LOOSE): Supply & laying of Circular Aluminium Conductor screened with extruded semiconducting compound, XLPE insulated, insulation screened with extruded semiconducting combination in combination with copper tape (0.3KA for 1sec.) cores laid up, FR PVC inner sheathed, galvanized steel strip armoured and overall FR PVC sheathed cable confirming to IS:7098 (Part-2), 2011 working voltage 11KV(E) grade to be loose in existing tranch or pipe:- (From Metering Room to VCB & VCB to 2Nos. Transformers in Substation Room)
INDOOR LT CABLES, CABLE TRAY, DWC PIPE , BRASS GLANDS & THIMBLES:
HT Cable Overall size 185sq.mm (3Core) (From Substation Room VCB to 2Nos. 1600KVA Transformers)
Overall size 400sq.mm (3½ Core) Un-armoured (Loose)
Cable Tray Size 300mm x 50mm x 50mm (2mm thick)
S/E of Heat shrinkable cable end termination/ Straight through joint kit for 11 KVA /6.6 KV (E) XLPE Cables as approved & desired by Enginer in charge:-
Heat Shrinkable End Termination for cable size 120-185 sq. mm, 3Core (Indoor Type)
Heat Shrinkable End Termination for cable size 120-185 sq. mm, 3Core (Outdoor Type)
SUB LT PANEL PANEL (EMERGENCY) ( FOR MAIN BUILDING EMERGENCY LOAD)
Heat Shrinkable End Termination for cable size 240-400 sq. mm, 3Core (Indoor Type)
TP&N Double Door Vertical DB's 12 way each (With provision of FP MCCB upto 125amp)
Heat Shrinkable End Termination for cable size 240-400 sq. mm, 3
Core (Outdoor Type)
PVC INSULATED SINGLE CORE FR COPPER CONDUCTOR CABLE: Supply and erection of XLPE/ PVC insulated PVC sheathed (10 core) unarmoured copper conductor cable (ISI marked) confirm to IS:7098 (PART-I), 1988 loose in the existing trench or pipe with suitable size of copper thimbles/ lugs complete in all respect as desired by the Engineer-in-charge:- (From Substation VCB to 2Nos. Transformers 400KVA)
Overall size 16sq.mm (4Core) Un-armoured (Loose)
Providing and fixing H.T. danger notice plate of 250 mm x 200mm, made of mild steel at least 2mm thick and vitreous enamelled white on both sides and with inscription in single red colour on front side as required.
stage.html
html • 0.02 MB
cancelled_1.pdf
pdf • 0.45 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.12 MB
dnit.pdf
Tender Documents • 15.49 MB
BOQ_306393.xls
BOQ • 1.65 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .