Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
Tender Value
₹1.3 L
EMD Value
₹2,631
Closing Date
4 Aug 2021, 3:30 pmClosed
EE Electrical
IWD IIT Kanpur
Replacement of defective and old wiring switch socket distribution board etc in House No 604 at IIT Kanpur
2021_IITK_640076_1
40/IWD/ED/233
Limited
Electrical Works
Item Rate
30 days
IIT Kanpur
As per tender
3 documents required · 3 mandatory
₹0
₹2,631
Yes
10 Aug 2021
23 Jul 2021
5 Aug 2021
23 Jul 2021
4 Aug 2021
23 Jul 2021
23 Jul 2021 - 30 Jul 2021
Amount
Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required.
Group B
Supplying and drawing following sizes of FR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit/ PVC truncking as required.
1 x 1.5 sq. mm
3 x 1.5 sq. mm
3 x 4 sq. mm
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
5/6 amp switch
2 way 5/6 amp switch
3 pin 5/6 amp socket outlet
15/16 amp switch
6 pin 15/16 amp socket outlet
Telephone socket outlet/ jack outlet
Bell push
Supply, Installation, testing & commissioning of AC ceiling fan of following sweep 220 volts without regulator I/c wiring the down rods of standard length up to 30 cm with 1.5 sq.mm. PVC insulated copper conductor single core cable etc as reqd.
Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
Supplying and fixing following size/ modules, GI/PVC box alongwith modular base & cover plate for modular switches in recess etc as required.
1 or 2 Module (75mmX75mm)
3 Module (100mmX75mm)
6 Module (200mmX75mm)
8 Module (125mmX125mm)
12 Module (200mmX150mm)
Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required.
Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required.
Supplying and fixing brass batten/ angle holder including connection etc. as required.
Supplying and fixing call bell/ buzzer suitable for single phase, 230 V, complete as required.
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
16 way, Double door
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Single pole
Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 300 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Providing and fixing following sizes of PVC casing and capping on surface as reqd.
Providing and fixing casing and capping in place of defective and dameged wood batten including dismentling of betten and wire & relaying of wires as required complet.
Supplying and fixing wooden board of following sizes on surface/recessed with suitable size of phenolic laminated sheet cover etc. complete as required.
100 mm X 100 mm
Supplying and fixing 3 mm thick phenolic laminated sheet on existing board with brass screw and cup washer etc. complete as required.
Supplying, fixing, connecting, commissioning and testing of the following luminaries light fixtures complete with all accessories and without lamp as required complete.
Drum light fitting suitable for 60W GLS lamp
Wall bracket fitting suitable for 60W GLS lamp
Bulk head fitting suitable for 60W GLS lamp
Dismantling, disconnecting old damaged unserviceable fl fitting/ exhaust fan/ ceiling fan/ bulkhead fitting with bracket etc. as reqd. and depositing in sectional store.
Dismantling of switch / socket /regulator etc. with wooden board and depositing in sectional store.as reqd.
Supplying and drawing telephone cable of 2 pair 0.5 mm dia FRLS PVC insulated annealed copper conductor, unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required.
Laying UTP cable enhanced cat 5/cat 6 cable in existing steel conduit pipe/GI pipe/ raceway / RCC pipe as reqd. the cost shall also include numbering of networking wire from room to rack as reqd. (wire will be supplied by dept)
Dismantling damaged DB/TPN Switches/ loose wire boxes along with all accessories and depositing the same in the store as req
Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required..
Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required.
V.S ENTERPRISES
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .