Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.9 LAccepted-AOC BHATI ABHOYNAGAR WEST VIVEKANANDA CLUB ROAD NEAR HOUSE OF DOCTOR GOURISHANKAR CHAKRABORTY P O AGARTALA TRIPURA WEST PIN 799001 | AGARTALA | WEST TRIPURA | TRIPURA | 799001 | ₹8.9 L Quoted ₹9.1 L | L1 | Accepted-AOC SUCCESSFUL BIDDER |
| 2 | L2₹9.2 LRejected-Finance | ₹9.2 L | L2 | Rejected-Finance REJECTED NOT BEING L1 BIDDER |
| 3 | L3₹9.3 LRejected-Finance | ₹9.3 L | L3 | Rejected-Finance REJECTED NOT BEING L1 BIDDER |
| 4 | L4₹9.5 LRejected-Finance | ₹9.5 L | L4 | Rejected-Finance REJECTED NOT BEING L1 BIDDER |
| Sl No | Description | Qty | Unit | SHRI RAJESH DEY L3 | M/S Ajoy Acharjee L2 | M/S UTTAM GANGULY ENTERPRISE L4 | SUMAN DEB L1 |
|---|---|---|---|---|---|---|---|
| 1.00 | Materials and labour for earthing complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6 mm thick, burried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 m below ground level connected with GI lead wire 4.0mm dia by means of nuts, bolts, check nuts and washers , earthing lead to be protected by galvanised iron pipe of 20mm bore (medium grade) and other end connected to earthing test point or lightening arrestor or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (medium grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessary earth work in excavation, returning filling and removal of surplus earth upto a distance not exceeding 50 m etc all as shown on electrical plate No. 3 of MES Schedule Part-I(2009) complete including testing on completion including taking down old unserviciable earthing set all as specified and as directed.
Notes:-
(i) Main earthing strip from earth plate electrode to rest point upto length of 7.5 meters length shall deemed to be included in the unit rate quoted against this item.
(ii) On testing after completion if the desired resistenance is not obtained the contractor shall redo the earthing without any extra cost to the department. | 30 | Each set | 9,050 ₹2.7 L | 9,000 ₹2.7 L | 10,000 ₹3 L | 8,850 ₹2.7 L |
| 2.00 | Materials and labour for earthing complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6 mm thick, burried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 m below ground level connected with GI strip of size 25x4mm by means of nuts, bolts, check nuts and washers made of galvanised iron or steel earthing lead to be protected by galvanised iron pipe of 40mm bore (medium grade) and other end connected to earthing test point or lightening arrestor or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (medium grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessary earth work in excavation, returning filling and removal of surplus earth upto a distance not exceeding 50 m etc all as shown on electrical plate No. 3 of MES Schedule Part-I(2009) complete including testing on completion including taking down old unserviciable earthing set all as specified and as directed.
Notes:-
(i) Main earthing strip from earth plate electrode to rest point upto length of 7.5 meters length shall deemed to be included in the unit rate quoted against this item.
(ii) On testing after completion if the desired resistenance is not obtained the contractor shall redo the earthing without any extra cost to the department. | 13 | Each set | 9,800 ₹1.3 L | 9,600 ₹1.2 L | 9,500 ₹1.2 L | 9,400 ₹1.2 L |
| 3.00 | Materials and labour for earthing complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6 mm thick, burried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 m below ground level connected with GI strip of size 32x6mm by means of nuts, bolts, check nuts and washers made of galvanised iron or steel earthing lead to be protected by galvanised iron pipe of 40mm bore (medium grade) and other end connected to earthing test point or lightening arrestor or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (medium grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessary earth work in excavation, returning filling and removal of surplus earth upto a distance not exceeding 50 m etc all as shown on electrical plate No. 3 of MES Schedule Part-I(2009) complete including testing on completion including taking down old unserviciable earthing set all as specified and as directed.
Notes:-
(i) Main earthing strip from earth plate electrode to rest point upto length of 7.5 meters length shall deemed to be included in the unit rate quoted against this item.
(ii) On testing after completion if the desired resistenance is not obtained the contractor shall redo the earthing without any extra cost to the department. | 12 | Each set | 10,200 ₹1.2 L | 10,000 ₹1.2 L | 10,000 ₹1.2 L | 9,950 ₹1.2 L |
| 4.00 | Materials and labour for earthing complete with copper earth plate electrode 600 mm x 600 mm x 3.15 mm thick, burried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 m below ground level connected with copper strip of size 20x3mm by means of nuts, bolts, check nuts and washers made of copper or copper earthing lead to be protected by galvanised iron pipe of 40mm bore (medium grade) and other end connected to earthing test point or lightening arrestor or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (medium grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessary earth work in excavation, returning filling and removal of surplus earth upto a distance not exceeding 50 m etc all as shown on electrical plate No. 3 of MES Schedule Part-I(2009) complete including testing on completion including taking down old unserviciable earthing set all as specified and as directed.
Notes:-
(i) Main earthing strip from earth plate electrode to rest point upto length of 7.5 meters length shall deemed to be included in the unit rate quoted against this item.
(ii) On testing after completion if the desired resistenance is not obtained the contractor shall redo the earthing without any extra cost to the department. | 15 | Each set | 21,500 ₹3.2 L | 21,090 ₹3.2 L | 21,500 ₹3.2 L | 21,000 ₹3.1 L |
| 5.00 | Material and labour for Earth continuity conductor or main earthing lead of 4mm dia galvanised iron or steel wire fixed to wall on batten or recessed or chases or buried in ground or drawn in conduit/ pipe or fixed to poles or any other indicated situation for loop earthing etc, complete all as specified and directed. | 60 | RM | 75 ₹4,500 | 100 ₹6,000 | 80 ₹4,800 | 78 ₹4,680 |
| 6.00 | Material and labour for Earth continuity conductor or main earthing strip of 25x4mm galvanised iron fixed to wall on batten or recessed or chases or buried in ground or drawn in conduit/ pipe or fixed to poles or any other indicated situation for loop earthing etc, complete all as specified and directed. | 15 | RM | 230 ₹3,450 | 240 ₹3,600 | 200 ₹3,000 | 250 ₹3,750 |
| 7.00 | Material and labour for Earth continuity conductor or main earthing strip of 32x6mm galvanised iron fixed to wall on batten or recessed or chases or buried in ground or drawn in conduit/ pipe or fixed to poles or any other indicated situation for loop earthing etc, complete all as specified and directed. | 20 | RM | 305 ₹6,100 | 350 ₹7,000 | 300 ₹6,000 | 310 ₹6,200 |
| 8.00 | Material and labour for Earth continuity conductor or main earthing strip of 20x3mm copper fixed to wall on batten or recessed or chases or buried in ground or drawn in conduit/ pipe or fixed to poles or any other indicated situation for loop earthing etc, complete all as specified and directed. | 40 | RM | 590 ₹23,600 | 600 ₹24,000 | 550 ₹22,000 | 570 ₹22,800 |
| 9.00 | Repair and Replacement of air termination single pointed copper rod 12mm dia and 300mm long fixed on copper strip all as specified and directed. | 20 | Each | 590 ₹11,800 | 600 ₹12,000 | 600 ₹12,000 | 590 ₹11,800 |
| 10.00 | Repair and Replacement of air termination single pointed Aluminium rod 12mm dia and 300mm long fixed on copper strip all as specified and directed. | 10 | Each | 350 ₹3,500 | 380 ₹3,800 | 350 ₹3,500 | 370 ₹3,700 |
Updated dates
Tender Value
₹9 L
EMD Value
₹18,000
Closing Date
10 Apr 2026, 6:00 pmClosed
AGE (I) Agartala
AGE (I) AGARTALA PIN-901184 C/O 99 APO
REPAIR REPLACEMENT OF EARTH CHAMBER, EARTH TESTING POINT, LIGHTING PROTECTION, MEASUREMENT OF EARTH TEST RESULTS IN ZONE A TO D AT MIL STN AGARTALA
2026_MES_756185_1
8809/E8
Open Tender
Electrical and Maintenance Works
180 days
AGARTALA
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
AGE (I) Agartala
₹18,000
Yes
8 May 2026
13 Mar 2026
13 Apr 2026
13 Mar 2026
10 Apr 2026
27 Mar 2026
Materials and labour for earthing complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6 mm thick, burried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 m below ground level connected with GI lead wire 4.0mm dia by means of nuts, bolts, check nuts and washers , earthing lead to be protected by galvanised iron pipe of 20mm bore (medium grade) and other end connected to earthing test point or lightening arrestor or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (medium grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessary earth work in excavation, returning filling and removal of surplus earth upto a distance not exceeding 50 m etc all as shown on electrical plate No. 3 of MES Schedule Part-I(2009) complete including testing on completion including taking down old unserviciable earthing set all as specified and as directed. Notes:- (i) Main earthing strip from earth plate electrode to rest point upto length of 7.5 meters length shall deemed to be included in the unit rate quoted against this item. (ii) On testing after completion if the desired resistenance is not obtained the contractor shall redo the earthing without any extra cost to the department.
Materials and labour for earthing complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6 mm thick, burried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 m below ground level connected with GI strip of size 25x4mm by means of nuts, bolts, check nuts and washers made of galvanised iron or steel earthing lead to be protected by galvanised iron pipe of 40mm bore (medium grade) and other end connected to earthing test point or lightening arrestor or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (medium grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessary earth work in excavation, returning filling and removal of surplus earth upto a distance not exceeding 50 m etc all as shown on electrical plate No. 3 of MES Schedule Part-I(2009) complete including testing on completion including taking down old unserviciable earthing set all as specified and as directed. Notes:- (i) Main earthing strip from earth plate electrode to rest point upto length of 7.5 meters length shall deemed to be included in the unit rate quoted against this item. (ii) On testing after completion if the desired resistenance is not obtained the contractor shall redo the earthing without any extra cost to the department.
Materials and labour for earthing complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6 mm thick, burried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 m below ground level connected with GI strip of size 32x6mm by means of nuts, bolts, check nuts and washers made of galvanised iron or steel earthing lead to be protected by galvanised iron pipe of 40mm bore (medium grade) and other end connected to earthing test point or lightening arrestor or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (medium grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessary earth work in excavation, returning filling and removal of surplus earth upto a distance not exceeding 50 m etc all as shown on electrical plate No. 3 of MES Schedule Part-I(2009) complete including testing on completion including taking down old unserviciable earthing set all as specified and as directed. Notes:- (i) Main earthing strip from earth plate electrode to rest point upto length of 7.5 meters length shall deemed to be included in the unit rate quoted against this item. (ii) On testing after completion if the desired resistenance is not obtained the contractor shall redo the earthing without any extra cost to the department.
Materials and labour for earthing complete with copper earth plate electrode 600 mm x 600 mm x 3.15 mm thick, burried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 m below ground level connected with copper strip of size 20x3mm by means of nuts, bolts, check nuts and washers made of copper or copper earthing lead to be protected by galvanised iron pipe of 40mm bore (medium grade) and other end connected to earthing test point or lightening arrestor or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (medium grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessary earth work in excavation, returning filling and removal of surplus earth upto a distance not exceeding 50 m etc all as shown on electrical plate No. 3 of MES Schedule Part-I(2009) complete including testing on completion including taking down old unserviciable earthing set all as specified and as directed. Notes:- (i) Main earthing strip from earth plate electrode to rest point upto length of 7.5 meters length shall deemed to be included in the unit rate quoted against this item. (ii) On testing after completion if the desired resistenance is not obtained the contractor shall redo the earthing without any extra cost to the department.
Material and labour for Earth continuity conductor or main earthing lead of 4mm dia galvanised iron or steel wire fixed to wall on batten or recessed or chases or buried in ground or drawn in conduit/ pipe or fixed to poles or any other indicated situation for loop earthing etc, complete all as specified and directed.
Material and labour for Earth continuity conductor or main earthing strip of 25x4mm galvanised iron fixed to wall on batten or recessed or chases or buried in ground or drawn in conduit/ pipe or fixed to poles or any other indicated situation for loop earthing etc, complete all as specified and directed.
Material and labour for Earth continuity conductor or main earthing strip of 32x6mm galvanised iron fixed to wall on batten or recessed or chases or buried in ground or drawn in conduit/ pipe or fixed to poles or any other indicated situation for loop earthing etc, complete all as specified and directed.
Material and labour for Earth continuity conductor or main earthing strip of 20x3mm copper fixed to wall on batten or recessed or chases or buried in ground or drawn in conduit/ pipe or fixed to poles or any other indicated situation for loop earthing etc, complete all as specified and directed.
Repair and Replacement of air termination single pointed copper rod 12mm dia and 300mm long fixed on copper strip all as specified and directed.
Repair and Replacement of air termination single pointed Aluminium rod 12mm dia and 300mm long fixed on copper strip all as specified and directed.
Material and labour for Aluminium strip 25 x 3.15mm with saddles and fixing screws etc. for roof conductors and down conductors all as specified and directed.
Repair and Replacement of test point terminal block made of gun metal or phosphorus bronze size 75 x 75 x 25mm, drilled and screwed including 3 Nos 8mm dia to 25mm long hex head screw all as specified and directed.
Taking out earth chamber cover, cleaning inside earth pit including copper salt & salt mixed with water pouring to earth pits and removing the old rusted nuts and bolts and refixing with new nuts and bolts, Testing of earth value complete all as specified and directed
NOTES :- 1. The amount of schedule of credit shall be deducted from the total of this BOQ for arriving at contract sum. 2. Unless otherwise specified the rates for PCC shall deemed to include the cost of formwork shuttering etc, required for complete and proper execution of the work. Refer Schedule 'A' notes for details.
Please Enable Macros to View BoQ information
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.15 MB
TENDERDOCUS8809.pdf
Tender Documents • 1.47 MB
BOQ_847020.xls
BOQ • 0.26 MB