Tender ID
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Tender Value
₹14.0 L
EMD Value
₹28,100
Closing Date
2 Dec 2026, 11:00 am6d left
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
EEE/Central North Zone
EEE/Central North Zone
Provision of lighting arrangements with SHML along with fitting at MPL Parks in Saraswati Vihar, Paschim Vihar and Rani Baghs various locations in AC-15 under KPZ.
2026_MCD_298884_1
TC/ENGG./EEE/KPZ/2026-27/38.1
Open Tender
Electrical Works
Percentage
90 days
EEE/Central North Zone
Please refer Tender documents.
3 documents required · 3 mandatory
₹0
₹28,100
24 Nov 2026
24 Nov 2026
2 Dec 2026
24 Nov 2026
2 Dec 2026
24 Nov 2026
120 days
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1ABC | |||||
| 1.01 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc.(but without charcoal/ coke and salt ) as required. | 6 | Set | 5,958 | ₹35,748 |
| 1.02 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. | 12 | PM | 287 | ₹3,444 |
| 1.03 | Laying of one number PVC insulated and PVC sheathed/ XLPE power cable of 1.1 KV grade of following size in the existingRCC/HUME/METAL pipe as required. Up to 35 sqmm | 428 | PM | 47 | ₹20,116 |
| 1.04 | Laying of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. Up to 35 sqmm | 47 | PM | 36 | ₹1,692 |
| 1.05 | S/L of following size DWC HDPE Pipe ISI marked along with all accessories like socket ,bend ,couplers etc.conforming to IS 14930 ,part II complete with fitting and cutting ,jointing etc .direct in ground (75 cm below ground level )including excavation and refilling the trench but excluding sand cushioning and protective covering etc, complete as required (a)63mm dia (OD-63mm ID -51mm nominal ). | 320 | PM | 289 | ₹92,480 |
| 1.06 | Supplying and fixing of light class GI pipe of 50 mm dia (nominal) 3 meters length along the pole for protection of under ground cable as required. | 6 | Each | 2,783 | ₹16,698 |
| 1.07 | Providing and fixing H.T. danger notice plate of 250 mm X 200 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required. | 6 | Each | 340 | ₹2,040 |
| 1.08 | Supplying, installation, Testing & Commissioning of Flood Light,
powder coated pressure die cast aluminum body with built in or separate
driver as per the requirement with Driver efficiency >85%, Input voltage:
Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC
61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P.
F.≥0.95, IP-66,IK-10, CRI >80 , under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg120deg as per the application and the project requirement deg., suitable tilt able fitting, life time (LED,Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) , SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). 100 Watt | 36 | Each | 2,567 | ₹92,412 |
| 1.09 | Providing and laying of HDPE PIPE OF 40mm outer dia with PN 4 rating by hand Moling/Mannual method Confirming to IS 4984 592 | 78 | PM | 592 | ₹46,176 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.47 MB
DNIT_TenderCondition1.pdf
Tender Documents • 8.40 MB
MCD_GCC_Latest_Circulars.pdf
Tender Documents • 13.92 MB
BOQ_348084.xls
BOQ • 0.38 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .