Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹7.3 LAccepted-Finance JAMMU AND KASHMIR JAMMU AND KASHMIR | JAMMU | JAMMU AND KASHMIR | 181122 | L1 | Accepted-Finance L1 | |
| 2 | L2₹7.6 L+₹30,871 (4.24%)Accepted-Finance | L2 | Accepted-Finance L2 | |
| 3 | L3₹7.8 L+₹55,632 (7.64%)Accepted-Finance | L3 | Accepted-Finance L3 | |
| 4 | L4₹7.9 L+₹61,209.50 (8.41%)Accepted-Finance | L4 | Accepted-Finance L4 | |
| 5 | L5₹8.0 L+₹69,302 (9.52%)Accepted-Finance | L5 | Accepted-Finance L5 |
Tender Value
₹11.1 L
EMD Value
₹23,000
Closing Date
16 Jul 2024, 4:00 pmClosed
Executive Engineer,Elect. Division Vijaypur
Office of the Executive Engineer, Electric Division Vijaypur, JPDCL Jammu
Creation of 100 KVA Distribution Sub Station along with Laying of HT Line on turnkey basis at Shiv Mandir, Sani Mandi for PHE installation under Jal Jeevan Mission within the jurisdiction Electric Division Vijaypur, JPDCL Jammu
2024_PDD_250392_1
EDV/ 08 of 2024-2025 Dated 26-06-2024
Open Tender
Electrical Works
Turn-key
60 days
Samba District
Please refer Tender documents.
9 documents required · 9 mandatory
₹1,000
Executive Engineer, Electric Division Vijaypur
₹23,000
30 Aug 2024
26 Jun 2024
18 Jul 2024
27 Jun 2024
16 Jul 2024
27 Jun 2024
27 Jun 2024 - 16 Jul 2024
Amount
Creation, Testing & Commissioning of 100KVA Distribution Transformer Sub Station
Supply, Installation testing & commissioning of 11/0.433 KV, 100 KVA 3-Phase Distribution Transformer with Bi-metallic terminal Connectors, Energy Level: 2, "BIS Marked" (Aluminium Wound) with LV Cable Box having detachable Aluminium Gland
Supply, Transportation, Erection of 9 Mtr Long PCC Pole (WL-300 KG) including excavation of pit and back filling of soil & consolidating by ramming, watering etc.
Supply, Transportation, Fabrication & Fixing of GI Channel Iron, Cross ,GI, Angle Iron Braces, Clamps etc duly fabricated, red oxide & Aluminum paint coated including all necessary Nut & Bolts & Washers etc.
Supply, Installation, Testing & Commissioning of 11 KV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type
Supply, Installation, Testing & Commissioning of 11 KV Horn Gap Fuse Set 3 Phase 200 A .
Supply & Fixing of Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type
Providing & Fixing of 185 mm² Single-Core Cable,1.1kV Grade, PVC Insulated Stranded Conductor FRLS type
Providing & Fixing of Distribution Box for 100 kVA DTR with MCCB for incomer & SFU's for Outgoing Circuits
Providing of Earthing of substation --Excavation of earth pit of dia. 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GIStrip for neutral earthing of size 25 mm x 3 mm for connection of transformer body ,G.O Set &lightening arrestor as per IS 2629/85, GI nuts &bolts ,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
Providing of Stone Pad 300mmx300mmx75mm
Providing & Fixing of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Providing & Fixing of 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Providing & Fixing of Anti Climbing device with Clamps
Providing & Fixing of Danger Plates with Clamps
Providing & Fixing of Galvanized Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm),nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia. GI stranded wire complete
Providing and fixing of P G Clamps
LAYING OF HT LINE ON 9 MTR PCC POLES USING ACSR WEASEL CONDUCTOR (0.90 Km)
Supply, Transportation, Erection of 9 Mtr Long PCC Pole (WL-300 KG) including excavation of pit and back filling of soil & consolidating by ramming, watering etc.
Supply, Transportation, Fabrication & Fixing of GI Channel Iron, Cross arms, Angle Iron Braces, Clamps etc duly fabricated, red oxide & aluminium paint coated including all necessary Nut & Bolts & Washers etc.
Supply, Laying & Stringing of ACSR Weasel Conductor on Cross arms through insulators including proper binding & twisting with soft Aluminium Wire
Supply Installation, Testing & Commissioning of 11kV Polymeric composite Pin Insulator 12kV, 5kN,Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Supply Installation, Testing & Commissioning of 11kV Polymeric composite Disc Insulator 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Providing & Fixing of Galvanised Stay Set with 50 x 8 mm Stay Clamp, Guy Insulator (2 Nos), Anchoring Plate (200 x 200 x 6 mm), Nut & Bolts, 2 No Turn Buckle, 1.8m long, 16 mm diameter solid Stay Rod & 7/3.15 mm dia. stranded wire complete
Providing & Fixing of Danger Plates with Clamps
Providing & Fixing of Anti Climbing device with Clamps
Providing of Earthing Complete by GI Pipe 40 mm or GI Rod 20 mm, 2.5 Mtr Long through GI Strip
Providing and fixing of Aluminium Jointing sleeves
Providing and fixing of P G Clamps
Providing of Stone Pad 300mmx300mmx75mm
ERECTION OF11 KV TAP POINT ON 9 MTR PCC POLES USING ACSR WEASELCONDUCTOR (1 No)
Supply, Transportation, Erection of 9 Mtr Long PCC Pole (WL-300 KG) including excavation of pit and back filling of soil & consolidating by ramming, watering etc.
Supply, Transportation, Fabrication & Fixing of GI Channel Iron, Cross arms, Angle Iron Braces, Clamps etc duly fabricated, red oxide & aluminium paint coated including all necessary Nut & Bolts & Washers etc.
Supply ,Installation, Testing & Commissioning of 11 KV GO AB Switch ,3-Phase ,3-Pole ,400 Amp
Supply, Laying & Stringing of ACSR Weasel Conductor on Cross arms through insulators including proper binding & twisting with soft Aluminium Wire
Supply Installation, Testing & Commissioning of 11kV Polymeric composite Pin Insulator 12kV, 5kN,Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Supply Installation, Testing & Commissioning of 11kV Polymeric composite Disc Insulator 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Providing & Fixing of Galvanised Stay Set with 50 x 8 mm Stay Clamp, Guy Insulator (2 Nos), Anchoring Plate (200 x 200 x 6 mm), Nut & Bolts, 2 No Turn Buckle, 1.8m long, 16 mm diameter solid Stay Rod & 7/3.15 mm dia stranded wire complete
Providing & Fixing of Danger Plates with Clamps
Providing & Fixing of Anti Climbing device with Clamps
Providing of Earthing Complete by GI Pipe 40 mm or GI Rod 20 mm, 2.5 Mtr Long through GI Strip
Providing of Stone Pad 300 mmx300mmx75mm
Providing ,Erection, Testing & Commissioning of 11 KV CT/PT unit along with Trivector Meter (7.5/5) Complete Job.
M/S A A ENTERPRISES
ASHISH SINGH
M/S DAYAL BUILD TECH
M/s Sai Electricals
M/S HI-TECH ELECTRICAL CONSTRUCTIONS AND SUPPLIERS
VEENA CONSTRUCTION CO.
M/S K.K ELECTRICALS
M/S RATHER CONSTRUCTIONS AND TRADERS
MAHA SHAKTI ELECTRICAL WORKS
M/S BETTER CHOICE AGENCIES
vk construction
M/S A G ELECTRICALS
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .