Executive Engineer (E)
EEE PWD DHC and ND/Central G.F. MSO Bldg. ND
1) Replacement of existing Sub- Station equipments 2) Replacement of LT Panels 3) SITC of Retro Fit Emission Control Device for Diesel Generators and necessary electrical work at IGDTUW, Govt of NCT of Delhi.
2026_PWD_293004_1
19/SE/C,ND/PWD/2026-27
Open Tender
Electrical Works
150 days
New Delhi
Please refer Tender documents.
16 documents required · 16 mandatory
₹0
₹4.3 L
8 Jun 2026
8 Jun 2026
15 Jun 2026
8 Jun 2026
15 Jun 2026
8 Jun 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount | Item Code |
|---|---|---|---|---|---|---|
| 1SH: I (11 KV H.T. VCB THREE BREAKER PANEL BOARD (INDOOR TYPE) (1 INCOMMING + 2 OUTGOING) Supplying, Installation, Testing & Commissioning of indoor type panels shall be constructed from CRCA or Aluminium Zinc coated steel sheet of minimum 2 mm thickness, floor mounted metal enclosed, 11 KV VCB panel, totally enclosed and fully interlocked, horizontal draw out, horizontal isolation type breaker as per IS 13118, as amended up to date and additional specifications, having capacities as mentioned below, single break, trip free mechanism, manually charged and manually closing breaker suitable for use on 11 KV, 3 phase, 50 Hz A.C. supply with short circuit fault level of minimum 26.3 kA , Panel shall be full internal arc tested i.e. in all three chambers at minimum 26.3kA for 1 sec for safety purpose (AFLR).Make of Vacuum interrupter, circuit breaker, numerical relay & Panel shall be same. . Each pole of VCB including VI should be completely epoxy insulated (partial encapsulation on accepted) for safety from vermin, dust etc Offered Panel compete with self contained, fully interlocked, rack in and rack out mechanism, air insulated copper bus bars of 800 amps capacity, Busbar should be covered with HT full voltage sleeve (Heat shrinkable PVC sleeve not accepted). Breaker featured with mechanical ON/ OFF indicator with hand trip coil, integral spring charging handle and auxiliary switch of 4 NO+4NC and equipped with following switchgears and accessories. i/c connections suitable for 3 x 300sq. mm XLPE 11 KV cable (Cable entry from bottom) end termination with heat shrinkable jointing material etc as required and as per direction of Engineer-in-Charge. INCOMING PANEL - 1 NO & OUTGOING 2 NO 11 kV, 800A, HT THREE Vacuum circuit breaker Switchboard (1I/C+2O/G ) with Aluminium Busbar - Indoor Type Incomer-1 Nos.11 kV HT Vacuum Circuit Breaker - 800 A, 3 pole = 1 No. ON/ OFF/TRIP/SPRING CHARGE/TRIP CIRCUIT HEALTHY indicating lamps. = 5 Nos. | ||||||
| 1.01 | Emergency Stop Push Button = 1 No.
Phase indicating lamps = 3 Nos.
Digital Voltmeter with selector switch. = 1 No.
MFM (Multifunction Meter) with RS 485 port = 1 No.
Control MCB SP/DP = 1 No.
Inbuilt DC Power Pack = 1 No.
Aux. relays for Anti Pumping & indication. = 1 No.
Master trip relay. = 1 No.
Over current and Earth fault based relay = 1 No.
Cast resin CTs of dual ratio 200/100/5/ 5 Amps 5VA burden, CL:1.0 for Metering & 5P 10 for protection. = 3 Nos.
Cast resin fixed type PTs 11 kV/ √3/ 110 √3, class 1, 100 VA. = 3 Nos.
TNC Switch = 1 No.
Anti- Condensation space heaters = 1 No.
Outgoing 2 Nos. 11 kV HT
Vacuum Circuit Breaker - 800 A, 3 pole = 2 Nos.
ON/ OFF/TRIP/SPRING CHARGE/TRIP CIRCUIT HEALTHY indicating lamps. = 10 Nos.
Emergency Stop Push Button = 2 Nos.
Digital Ammeter with selector switch. = 2 Nos.
Control MCB SP/DP = 2 Nos.
Inbuilt DC Power Pack = 2 Nos.
Aux. relays for Anti Pumping & indication. = 2 Nos.
Master trip relay. = 2 Nos.
Over current and Earth fault based relay = 2 Nos.
Aux relay 3c/o 24DC for TRF. fault. = 4 Nos.
Cast resin CTs of dual ratio 100/50/5/ 5 Amps 5VA burden, CL:1.0 for Metering & 5P10 for protection. = 2 Nos.
Cast resin fixed type PTs 11 kV/ √3/ 110 √3, class 1, 100 VA. = 2 Nos.
8 window annunciator with Common hooter = 2 Nos.
TNC Switch = 2 Nos.
Anti- Condensation space heaters = 2 Nos.
BUS Bar Aluminium. | 1 | Nos | 15,05,812 | ₹15,05,812 | BI01010001010000000000000515BI0100001114 |
| 2 | TRANSFORMER
Supply, installation, testing and commissioning of following capacity (continuous loading) 11/0.433 KV Delta/Star,step down, 3 Phase, 50 Hz, Dyn 11 vector group, Cast Resin / VPI (vacuum pressure impregnated) Dry Type, copper wound transformer (Electrolytic grade 99.9% pure copper, Core made of first grade Cold Rolled Grain Oriented (CRGO) Core grade MOH or better) AN (air natural) cooled
transformer suitable for indoor applications with Offload Tap Changer/ On Load Tap Changer (OLTC) ( upto 500 KVA offload and above 500 KVA On Load Tap Changer) on HV side having AVR relay and Remote Tap Changer Control (RTCC) for automatic sensing of incoming voltage, automatic operation of OLTC and facility for remote and manual operation of OLTC HV side in range of +5% to -15% in steps of 2.5%, insulation class F (minimum), suitable for environment conditions class E4, suitable for fire behaviour class F1,climate class-C1, having cable end boxes on HV side suitable for 3x300 sqmm XLPE cable of 11 KV grade with necessary hardware, clamps, lugs etc. for termination on HV/MV etc. for all transformers, bus trunking arrangement on LV side complete with all accessories and safety provisions as per relevant IS Code ,The transformer shall be provided with standard fittings/accessories as per relevant IS and mentioned below,
protection alarm/trip protection, 3 nos. of Polymeric Zinc Oxide surge Arrestors on HV Side. Winding Temperature scanner (Digital) with alarm/Trip contacts with RTD Sensors per LV winding and space for mounting differential protection CT's in LV chamber with neutral brought out separately including supplying and laying of copper conductor multicore control cable from transformer to HT breaker/HT Panel for safety tripping, complete as confirming to IS-2026 Part-11, i/c supplying and grouting of suitable M.S. Channel with all accessories ,complete in all respects as required at site as per CPWD specifications . Design ambient condition : a) air temperature 50 0C, b) Relative Humidity 90 % Max, c) Seismic Zone as per location of site, d) Altitude as per location/site. The transformer should have QR code which should contain drawing, test report OEM manual,Geo- Tag of manufacturing location, rating plate as per relevant IS Code etc. All testing shall as per relevant IS Code. Noise level Shall not exceed limits as per NEMA TR-1 with all accessories running measured as per IEC 551/ NEMA Standard. Fitting and Accessories : The following fittings shall be provided:- a) Two earthing terminals with the earthing symbol b) Rating and terminal marking plates; c) Thermometer pocket with cap; d) Lifting lugs for the complete transformer as well as for core and winding assembly; e) Bi-directional flat rollers (for transformers above 200 kVA); f) HV side neutral grounding strip (where one of the HV bushing terminal is connected to earth); g) Arcing horns or suitable rating lightning arrestors for HT side – 3 Nos. for transformers up to 200 kVA; h) Bird guard; i) Jacking pads (for transformer above 1 600 kVA); j) Name Rating & Diagram Plate. k) Monogram Plate.i) Additional neutral separately brought out on bushing for earthing. Level 3
1250 KVA (losses at 50% loading < 3600watt, losses at 100% loading < 10750watt) | 1 | Nos | 29,06,287 | ₹29,06,287 | BI01010001010000000000000515BI0100001115 |
| 3MAIN LT PANEL Supplying, installation, testing & commissioning of cubical modular type LT panel suitable for 415 V, 3 Phase, 4 Wire 50 Hz AC supply system fabricated in compartmentalized design having bus bar chamber duly fabricated from CRCA sheet steel of 2 mm thick for frame, back, sides, partition & doors and 3mm thick for glad plate duly powder coated in approved shade including cleaning & finishing complete with 7 tank process complete with 2500 Amp capacity extensible type four strip aluminium alloy bus bars of hight conductivity, DMC/ SMC bus bar supports having short circuit withstand capacity of 31 MVA for '1' Sec., bottom base channel of MS section not less than 100 mm x 50 mm x 5 mm thick, entire panel shall have a common earth bar of size 25 mm x 5 mm at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of Al. bus bars, control wiring with 2.5 sq. mm. PVC insulated copper conductor single core cable, cooling / ventilation fans including construction of suitable CC foundation, in & out connections and providing & Fixing following switch gears therein etc. complete as required as per direction of Engineer-in-Charge. Incoming (from Transformer) (i) 2 Nos- 2000 Ampers four pole horizontal drawout type electrically operated air circuit breaker of fault breaking capacity 50 kA breaking capacity (Ics = Icu = Icw=100%) for 1 second suitable upto 690V, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/test/isolated position indicators and frame earthing contact, auxiliary contacts, shunt trip, interlocking features etc. complete with self powered Microprocessor based release for adjustable setting for over current, earth fault & short circuit protection with LCD display with current power & harmonic metering& pre overload and over temperature protection indication along with USB Port for communication & all other standard features conforming to IS 1397-2 : 1993 as amended up-to-date (ii) 2 Sets- RYB Phase indication LED lamps with 6A, 10KA, "C" Curve back up MCB, breaker ON/OFF/TRIP indicating light with 6A, 10KA, "C" Curve backup MCB (iii) 2 Nos.- 3 phase Intelligent multifunction digital meter to read V, A, KVA, KWH, PF Hz etc. with 3 Nos. resin cast CTs of 2000/5 A class 1.0 accuracy and 15 VA burden and with 3 Nos 6A, 10KA, "C" Curve back up MCB. | ||||||
| 3.01 | Bus Coupler
(i) 1 Nos - 2000 Ampers four pole horizontal drawout type electrically operated air circuit breaker of fault breaking capacity 50 kA breaking capacity (Ics = Icu = Icw=100%) for 1 second suitable upto 690V with LSIG release, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/test/isolated position indicators and frame earthing contact, auxilary contacts, shunt trip, interlocking features etc.
(ii) 1 Sets- RYB Phase indication LED lamps with 6A, 10KA, "C" Curve back up MCB, breaker ON/OFF/TRIP indicating light with 6A, 10KA, "C" Curve backup MCB
BUS BARS:
FP aluminium bus bars of minimum of 2500 A capacity with heat shrinkable colored sleeves and i/c DMC/SMC bus bars supports at required intervals complete, for cross section, size supports & their spacing etc. for withstanding fault level of 31 MVA for 1 Sec.
Interlocking
(i) INTERLOCKING
Electrical Interlocking through advance contacts in ACBs (Incomers) and mechanical (Castel key) Interlocking should be provided to ensure that only one supply is available at a time on each section of BUS and to eliminate any possible of accidently approaching two supplies at one BUS section with FRLS flexible copper wire. = 1 Job | - | - | - | - | BI01010001010000000000000515BI0100001117 |
| 3.02 | Outgoing
(i) 4 Nos.-800 Ampers four pole horizontal drawout type electrically operated air circuit breaker of fault breaking capacity 50 kA breaking capacity (Ics = Icu = Icw=100%) for 1 second suitable upto 690V, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/test/isolated position indicators and frame earthing contact, auxiliary contacts, shunt trip, interlocking features etc. complete with self powered Microprocessor based release for adjustable setting for over current, earth fault & short circuit protection with LCD display with current power & harmonic metering& pre overload and over temperature protection indication along with USB port for communication & all other standard features conforming to IS 1397-2 : 1993 as amended up-to-date
(ii) 4 Sets- RYB Phase indication LED lamps with 6A, 10KA, "C" Curve back up MCB, breaker ON/OFF/TRIP indicating light with 6A, 10KA, "C" Curve backup MCB
(iii) 4 Nos.- 3 phase Intelligent multifunction digital meter to read V, A, KVA, KWH, PF Hz etc. with 3 Nos. resin cast CTs of 800/5 A class 1.0 accuracy and 15 VA burden and with 3 Nos 6A, 10KA, "C" Curve back up MCB.
(ii) 4 Set- 630A, FP, 36KA MCCB (Ics=Icu =100%) with Microprocessor based release with adjustable setting having O/L & S/C protection with Rotary handle and spreader terminal.
(iii)16 Set- 400A, FP, 36KA MCCB (Ics=Icu =100%) with Microprocessor based release with adjustable setting having O/L & S/C protection with Rotary handle and spreader terminal.
(iv) 8 Set- 250A, FP, 36KA MCCB (Ics=Icu =100%) with Microprocessor based release with adjustable setting having O/L & S/C protection with Rotary handle and spreader terminal.
(v) 6 Set- 125A, FP, 36KA MCCB (Ics=Icu =100%) with Thermal based release with adjustable setting having O/L & S/C protection with Rotary handle and spreader terminal.
(vi) 34 sets- 3 phase Intelligent multifunction digital meter to read V, A, KVA, KWH, PF Hz etc. with 3 Nos. resin cast CTs along with ON/OFF indicating light with 6A, 10KA, "C" Curve backup MCB, auxiliary contacts with MCCB | 1 | Nos | 31,84,861 | ₹31,84,861 | BI01010001010000000000000515BI0100001118 |
| 4 | PHASE SEQUENCE CORRECTION PANEL
Supply, installation, testing and commissioning of Microprocessor Based Automatic Phase Sequence Corrector Panel for non stop smooth functioning of 3 phase critical equipments with built in protection like short circuit, over load, high/low voltage cut off of load from source in cubical type compartmentalized and fabricated from minimum 2 mm thick CRCA sheet having necessary cable alleys, powder coated including connection and interconnection as required as per specifications complete with 2000 Amp capacity, features and specifications:-
Suitable for correcting the RYB phase sequence, whenever the sequence is changed or reversed
Avoid damages during phase sequence changed or reversed
It should be:-
1) Fully automatic.
2) No manual intervention.
3) Single phase prevention.
4) Voltage imbalance protection between phases.
output in the right sequence (R,Y,B)
ON delay and OFF delay selectable and adjustable.
Protects against phase unbalancing/phase loss/under and over voltages.
Indications of R Y B Phase.
2000 Amp 4 pole EDO type ACB- 2 Nos. | 2 | Nos | 4,19,324 | ₹8,38,648 | BI01010001010000000000000515BI0100001119 |
| 5 | BUS TRUNKING
Supplying, installing on wall, testing and commissioning of following capacity Air Insulated Compact Type Bus Trunking for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply with metal clad enclosure made of 1.6mm thick steel sheet duly powder coated in convenient sections complete with 4 Nos aluminium bus bars, necessary joints, elbow joints & expansion joints, fire barrier at each floor, provision of tapping at every metre, continuous earthing with 2 Nos aluminium strip of suitable size (one on each side) including, G.I. clamping brackets, angle iron bracket, steel fasteners, connecting to earthing system etc. as required
2500 A Isc = 50kA for 1 second | 20 | Meters | 17,658 | ₹3,53,160 | BI01010001010000000000000515BI0100001120 |
| 6APFC PANEL HYBRID Power Factor Correction System Supply, Installation, testing and commissioning ofHYBRID APFC Panel, 3 phase 4 wire, 415 V, 50 Hz AC System for Ambient temperature -5°C to +40°C of following capacity with passive solution of 60% capacity and active solution of 40% capacity, 3Phase 4 wire Hybrid Power Factor Correction Solution (with arrangement for neutral current balance) to achieve>0.99 lag and TDDI/THDV values within IEEE recommended limits.APFC should be designed as per IS 16636 Or IEC 61921. The active section and passive section shall work in sync to give optimized output. The degree of protection of passive section should be IP 42, and of active section should be minimum IP 21.The switching device for APFC passive section should be through capacitor duty contactor and for the active compensation system shall be IGBT based with 3 level topology having 12 IGBT in inverter circuit. The active compensation system should filter harmonics from 2nd to 50th individual harmonic order and shall be selectable for the entire range. The active compensation system should have feature to improve PF correction and harmonic filtration having response time < 100 Micro second. The hybrid panel shall be indoor type floor mounted free standing totally enclosed, extensible, fabricated in compartmentalised designed made of CRCA sheet steel of 2.0mm thick for framework & covers, 3 mm thick for gland plate i/c cleaning & finishing complete with 9 tank process for powder coated of approved shade ( RAL 7032-Siemens gray or as approved by Engineer-in-Charge), having front section (switch gear and control accessories) and rear section (capacitor and reactor), front and rear access, having suitable current carrying capacity, extensible TPN Aluminium alloy bus bar of high conductivity, DMC/SMC bus bar supports, bottom base channel of MS Section, fabrication shall be done in transportable section, entire panel shall have common copper earth bar of minimum size of 25mm x 5mm with 2 nos. earth studs, the earth terminals provided on the body of capacitor bank shall also be bonded to the main capacitor panel earth bus with 2 nos. 8 SWG or 6 SWG GI earth wires/ equivalent size of copper conductor cable, forced ventilation for maintaining temperature rise not more than 5°C from ambient, interconnections, connections with 14% detuned reactor and heavy duty 525 V ISI marked Impregnated MPP(Metalized Polypropylene) Capacitor (IS 13340 Part -1 & 2) APFC Panel shall be in compliance with IS :16636 & CPWD Specifications etc. as per below details.(A) IncomersSuitable capacity MCCB/ACB (Upto 300 KVAR, MCCB and above 300 KVAR, ACB ) Microprocessor base with O/C, S/C, E/L release of TPN 50KA breaking capacity (Ics=Icu), ON, OFF, Trip, R, Y, B - LED Indicating Lamp set alongwith required Instruments and accessories with extended rotary handel and door interlocking arrangement. Current rating of the Incomer in ampere shall be APFC Panel rating in KVAR x 1.4 x 1.5 or Nearest higher standards rating. (B) Instruments & Indications a)For Passive Section :i) 3-Phase current sensing APFC microprocessor relay/controller, advance 12/16 stages (12 stages for over all capacity of panel (active + passive) below 500 KVAR and 16 stages 500 KVAR & above) and having display of Phase wise V, A, PF, Cos-Phi, KW, KVA, KVAR, THD-V , THD-I, harmonics up to 31 level. | ||||||
| 6.01 | ii) Auto Manual Selector switch, auxiliary contactors with timer for delay in manual mode.
iii) Digital Multi function meter with LED Display for V, A, PF, KW, KVA, KVAR, THD-V & I, Frequency.
iv) Suitable rating control transformer shall be provided for control and indication circuit.
v) All components like control transformer, meter, relay and indicating lamp shall be protected by using suitable rating individual MCB's.
vi) Wiring of the control circuit shall be done by using 2.5 sq mm, FRLS/HFFR 1100 V grade, PVC insulated multi stranded copper control wire.
vii) Communication Ethernet/RS485/SNMP port open protocol for BMS integration as per approved by Engineering in charge.
b) For Active Section: Dedicated HMI (Human Machine Interface) (Minimum 7 inch display) for controlling and communication and having display of Phase wise V, A, PF, Cos-Phi, KW, KVA, KVAR, THDV , THD-I, harmonics up to 50th level. CommunicationEthernet/RS485/SNMP port open protocol for BMS integration as per approved by Engineering in charge. (a) 400 KVAR | 2 | Nos | 21,83,152 | ₹43,66,304 | BI01010001010000000000000515BI0100001122 |