Tender Value
₹34 L
EMD Value
₹68,000
Closing Date
19 Nov 2022, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Commander Works Engineer Bhopal
Headquarters, Commander Works Engineer, Bhopal, Military Engineer Services, SI Line, Bhopal, Pin Code - 462001 (Madhya Pradesh)
REPAIR AND RENEWAL OF E/M ITEMS AND ALLIED WORKS AT DHANA MIL STN UNDER AGE(I) DHANA
2022_MES_559599_1
83768/E8
Open Tender
Civil Works
Item Rate
180 days
Dhana
AS PER NIT CONDITION
7 documents required · 7 mandatory
₹500
Yes
AGE (I) Dhana
₹68,000
Yes
9 Jan 2023
22 Oct 2022
22 Nov 2022
22 Oct 2022
19 Nov 2022
5 Nov 2022
22 Oct 2022 - 5 Nov 2022
Amount
Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. or for cable laying or not exceeding 10 sqm on plan and not exceeding 1.5 m in depth and getting out in soft/ loose soil complete all as specified and as directed.
Excavating in trenches not exceeding 1.5 m wide and exceeding 1.5 m but not exceeding 3.0 in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. or for cable laying or not exceeding 10 sqm on plan and exceeding 1.5 m but not exceeding 3 m in depth and getting out in soft/ loose soil complete all as specified and as directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm in soft/ loose/ hard/ dense soil complete all as specified and as directed.
Removing excavated material (soils) not exceeding 50 m and depositing where directed at a level n exc. 1.5 m above the starting point
Supply & spreading in trenches dry river sand cushioning to underground cable in trenches including spreading, levelling, hand punning down complete all as specified and as directed. Note:- Depth of sand cushioning will be measured after punning down and levelling the sand properly.
Supply & laying unreinforced precast concrete cable cover class HVP type 1, with peak shape, dimension 300 mm X 180 mm X 40 mm and 65 mm peak thickness as per IS 5820: 1970 complete all as specified and as directed.
Disconnecting, taking out old unserviceable under ground cable of rated voltage 6.35 kV/ 11 kV, upto any size of nominal cross sectional area of main conductor, upto 4 core, any type from trenches including taking out concrete cable cover/ bricks etc. including removing materials to store for keeping in safe custody or for reuse or for taking credit all as specified and directed by the Engineer-in-Charge.
Supply, laying and testing cross linked polyethylene (XLPE) insulated, PVC sheathed cables for working voltages 6.35 kV/ 11 kV, three phase, earthed system, 3 core, screened, armoured power cable, 120 sqmm of nominal area of conductor, aluminium conductor, ISI marked as per IS 7098 (Part-II): 2011 laid in trenches or under floors making all connections with necessary glands lugs bushing complete all as specified and as directed.
Supply, laying and testing cross linked polyethylene (XLPE) insulated, PVC sheathed cables for working voltages 6.35 kV/ 11 kV, three phase, earthed system, 3 core, screened, armoured power cable, 95 sqmm of nominal area of conductor, aluminium conductor, ISI marked as per IS 7098 (Part-II): 2011 laid in trenches or under floors making all connections with necessary glands lugs bushing complete all as specified and as directed.
Carrying out field test for visual inspection (colour and appearance), break down voltage, water content and acidity before and submission of report all as per IS 1866: 2017 and IEC 60422: 2013 complete all as specified and as directed.
Filtration, Dehydration, reconditioning of transformer oil by using filtering equipment, vacuum dehydrator etc. to obtain minimum break down voltage of 60 kV and maximum water content of 30 mg/kg as per IS 1866: 2017 and IEC 60422: 2013 complete all as specified and as directed.
Supply and fill unused mineral insulating oils conforming to IS 335: 2018, Type II Class (Transformer oils), Uninhibited (U), pour point -10⁰C, vacuum filtered in a laboratory, Breakdown voltage of min 70 kV at 2.5 mm gap complete all as specified and as directed.
S & F 12 kV or 17.5 kV/ 250 A bushing with copper stem including both porcelain parts and metal parts with accessories as per IS 3347 Part 3 (section 1 & 2) complete all as specified and as directed.
S & F upto and including 1.1 kV/ 250 A bushing with copper stem including both porcelain parts and metal parts with accessories as per IS 3347 Part 1 (section 1 & 2) complete all as specified and as directed.
Supply only oil level indicator clean prismatic type suitable for transformer upto 250 kVA with necessary gasket etc. complete all as specified and as directed.
S & F XLPE cable end termination, cold shrinkable, outdoor type, suitable for voltage 6.35 kV/ 11 kV (Earthed), 3 core, 120 sqmm to 185 sqmm complete all as specified and as directed.
S & F XLPE cable end termination, cold shrinkable, outdoor type, suitable for voltage 6.35 kV/ 11 kV (Earthed), 3 core, 50 sqmm to 95 sqmm complete all as specified and as directed.
S & F XLPE cable end termination, cold shrinkable, indoor type, suitable for voltage 6.35 kV/ 11 kV (Earthed), 3 core, 120 sqmm to 185 sqmm complete all as specified and as directed.
S & F XLPE cable end termination, cold shrinkable, indoor type, suitable for voltage 6.35 kV/ 11 kV (Earthed), 3 core, 50 sqmm to 95 sqmm complete all as specified and as directed.
Supply and fix metal oxide surge arrester without gap for AC system as per IEC 60099-4: 2014, outdoor type, polymer housing, single column and single phase construction, distribution class, heavy duty, nominal discharge current 10 kA, repetitive charge transfer rating (Qrs) more than 0.4 C, thermal charge transfer rating (Qth) more than 1.1 C, nominal system voltage 11 kV, highest system voltage 12 kV, rated voltage of arrester 9 kV, continuous operating voltage 7.2 kV, temporary overvoltage (10.50 kV for 1 s, 9.90 kV for 10 s, 9.35 kV for 100 s), rated short circuit current 20 kA, low short circuit current 600 A, insulation withstand level (lightning impulse voltage 1.2/ 50 µs) 75 kV, lightning impulse residual voltage (8/20 µs) at nominal discharge current maximum 30 kV, high current impulse withstand capability (4/10 µs) 100 kA, minimum creepage distance 300 mm complete all as specified and as directed.
S & F in repairs silica gel breather including silica gel, indicating type, 4 to 6 mm standard size of the particle, blue colour for transformer of capacity upto and including 500 kVA complete all as specified and as directed.
M & L for spray painting of transformers (any type power or distribution)) of capacity upto and including 250 kVA (in situ) outdoor type, installed and located at different sites in scattered area under the GE complete all as specified and as directed including the following: - (a) Removal of grease, oil and other contaminants using de-greasing solvent. (b) De-rusting of surface and cleaning manually by scrubbing and wire brushing. (c) Washing thoroughly and dry properly. (d) Applying two coats of zinc phosphate primer by spray machine (e) Final painting of two coats with synthetic enamel paint by spray machine over priming coat. (f) the colours of painting shall be (i) grey for transformer body, (ii) red, yellow & blue for HT bushing, (iii) red, yellow, blue & black for LT bushing, (iv) red for drain plug, (v) white for writing SM/ MES No., location, area feeding (in short) over the body of transformer.
M & L for preparing and painting on steel tubular swaged pole 410 SP-55 (11.00 metre long) including cross arms, GI brackets, PCC coping complete all as specified and as directed comprising the following: - (a) Two coats of synthetic enamel paint in white colour over a coat of primer on PCC coping (b) Making 4 Nos of strips of 30 cm wide in alternate red and white colour using two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer (c) Providing 30 cm wide retro reflective sheet of 30 cm wide, grade 1, pressure bonding type, red colour as per IS 14221: 1995 (d) Two coats of synthetic enamel paint in red colour over a coat of primer from top of electric pole to downward upto 1 metre length including cross arms, GI brackets etc. (e) Writing pole number and voltage level encompassed by circle of suitable dia using two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer (the colour of base shall be black and the colour of font shall be white). Number and voltage level shall be handwritten, and circle shall be stencilled. (f) Painting with two coats of aluminium paint over a coat of aluminium red oxide primer on remaining exposed portions.
Dismantling danger notice plate any type and size and setting aside for re-use or removing to store or for schedule of credit
Fixing only danger notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with mild steel clamps, bolts and nuts of approved size, for HT, 250 mm X 200 mm complete all as specified and as directed.
Dismantling insulators any type, any size complete all as specified and as directed.
S & F polymer pin insulator, Type B, Nominal System voltage 11 kV, highest system voltage 12 kV, visible discharge test voltage 9 kV, wet power frequency withstand voltage 35 kV, power frequency puncture withheld voltage 105 kV, impulse withstand voltage 75 kV, minimum total creepage distance 230 mm, minimum failing load 5 kN, of suitable size with galvanised steel insulator pin, nut, washers complete all as specified and as directed.
S & F polymeric composite disc insulator, ball and socket type, Type B, Nominal System voltage 11 kV, highest system voltage 12 kV, visible discharge test voltage 9 kV, wet power frequency withstand voltage 35 kV, impulse withstand voltage 75 kV, minimum total creepage distance 230 mm, minimum failing load 70 kN, of suitable size with galvanised steel stud pin, nut, washers complete all as specified and as directed.
Dismantling air break gang operated switches vertical/horizontal mounted, drop out fuse assembly, any rating, any type including insulators and operating mechanism, carrying to MES store or taken on schedule of credit complete all as specified and as directed.
S & F gang operated air break switch as per IEC 62271-103 amended upto date, rocking/ tilting type, suitable for both horizontal and vertical mounting, three poles, outdoor type, nominal system voltage 11 kV, rated voltage 12 kV, rated frequency 50 Hz, continuous current rating 200 Amps, rated short time withstand current for three seconds 20 kA, rated peak withstand current for three seconds 50 kA, rated lightning impulse withstand voltage (i) to earth and between poles 75 kV (Peak) (ii) across the isolating distance 85 kV (Peak), power frequency withstand voltage between (i) earth & poles 28 kV (rms) (ii) across the isolating distance 32 kV (rms), minimum isolating distance in open position 310 mm, phase to phase clearance 750 mm, minimum cross sectional area of fixed contact 300 sqmm, minimum cross sectional area of moving contact 250 sqmm, copper connector having minimum cross sectional area of 250 sqm, maximum current density of 1.6 Amps/ sqmm for all current carrying parts, single number of brake per phase, medium grade galvanised iron pipe of 32 mm nominal bore and 5 to 6 metre length in single piece for operating pipe, pad-locking in both ‘on’ and ‘off’ positions with indicators, electroplated nonferrous parts, hot dip galvanised ferrous parts, 3 Nos polymer post insulator per phase as per IEC 61109 amended upto date having rated voltage 12 kV, minimum creepage distance 300 mm, impulse withstand voltage 75 kV, wet power frequency withstand voltage 35 kV, dry wet power frequency withstand voltage 35 kV complete all as specified and as directed.
Dismantling, re-erecting, restringing tensioning and repair to overhead line ACSR conductor of any size upto 5 conductors in one span as required on poles LT / HT including fixing insulators and jointing with ACSR conductor complete all as specified and as directed.
Dismantling cross-arms of mild steel channel or angle sections etc. complete and setting aside for re-use or removing to store or for schedule of credit
M & L for cross arms, bracings, supports, clamps, back plates and stay clamp fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and applying two coats of aluminium paint over a coat of red oxide primer complete all as specified and as directed.
M& L for servicing of 11 kV gang operated air break switch by cleaning the contact, pin insulator with CTs and applying petroleum jelly at the contact point and down rod links for smooth operation including replacing the rusted, corroded bolts, nuts (using galvanised iron nuts) along with replacing the burn aluminium thimbles and defective insulators, male and female contact as required at the site complete all as specified and as directed. Note: - (1) Insulator, male (moving) and female (fixed) contact shall be measured and paid separately under the relevant items. (2) The cost for replacement of aluminium thimbles, GI nuts, bolts, washers, lubricating, materials etc. shall be deemed to be included in the unit rate quoted by the contractor for the item.
Supply only male contact /moving contact blade for gang operated air break switch (Set of three)
Supply only female contact/fixed contact jaw for gang operated air break switch (Set of three)
S & F galvanised mild steel wire 3.15 mm or 4 mm dia in overhead lines complete all as specified and as directed.
Dismantling earth wire or copper conductor, service feeder or distributor span removing to store or taken on schedule of credit complete all as specified and as directed.
Dismantling ACSR or AAC conductors removing to store or taken on schedule of credit complete all as specified and as directed.
Supply, fixing and stringing ACSR (aluminium conductor galvanized steel-reinforced) of any size and type in accordance with site requirement and binding on insulator by means of 22 gauge aluminium binding wire to permissible sag complete all as specified and as directed.
M & L for loose filling with broken stone or boulder aggregates of gauge 40 to 80 mm in soakage pits, soakage wells, on open space etc. complete all as specified and as directed.
M & L for preparing and painting on cross arms of electric pole of any height with two coats of aluminium paint over a coat of aluminium red oxide primer after scrapping the metal surfaces with emery sheet complete all as specified and as directed.
Surface dressing not exceeding 15 cm deep in soft/ loose soil complete all as specified and as directed.
Dismantling steel poles/ struts, any size, transporting to store and stacking or for schedule of credit
M & L for steel tubular swaged pole 410 SP-55 (11.0 metre long) including CI base plate, finial taper plug, bolts, nuts & screws as per IS 2713 Part -I & II including painting with two coats of aluminium paint over a coat of red oxide zinc chrome primer on exposed portion and making strips of width 30 cm upto 1.5 m from the ground level in black and yellow shade in alternate layer including numbering of poles using two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer and two coats of anticorrosive paint over a coat of red oxide primer to embedded portion of pole including making good to match existing area complete all as specified and as directed.
M & L for cement concrete in foundation, filling and mass concrete in M7.5(Nominal Mix) using 40 mm nominal size graded crushed stone aggregate complete all as specified and as directed.
M & L for cement concrete in foundation, filling and mass concrete in M10(Nominal Mix) using 40 mm nominal size graded crushed stone aggregate complete all as specified and as directed.
M & L for cement concrete M15 (Nominal Mix) using 20 mm nominal size graded crushed stone aggregate in lintels upto 1.5 m clear span, cills, steps; seismic and other similar bands, plinth courses, string courses, lacing courses, parapets and railings upto 60 cm in height, copings, kneelers, apex stones, bed plates, kerbs, water troughs, slab staging for water tanks, filling of pressed steel door frame, fixing of hold fasts and the like including weathering, slightly rounded or chamfered angles and throating including necessary formworks complete all as specified and as directed.
M/S SHIVA TRADERS
M/s VIKAS TRADERS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .