| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹33.8 LAccepted-AOC | L1 | Accepted-AOC Lowest Bidder for the Work. | |
| 2 | L2₹39.0 L+₹3.4 L (9.68%)Rejected-Finance 0 NEAR SHIV MANDIR KALYANIPURA KRIPAL NAGAR AJMER RAJASTHAN 305001 UDYAM RJ 01 0091182 | AJMER | RAJASTHAN | 305001 | L2 | Rejected-Finance Other than lowest bidder. | |
| 3 | L3₹45.5 L+₹10.0 L (28.1%)Rejected-Finance | L3 | Rejected-Finance Other than lowest bidder. |
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
17 Mar 2022, 6:00 pmClosed
Commander Works Engineer Bhopal
Headquarters, Commander Works Engineer, Bhopal, Military Engineer Services, SI Line, Bhopal, Pin Code - 462001 (Madhya Pradesh)
REPAIR, REPLACEMENT OF HT CABLE, TRANSFORMERS, GANG OPERATED DEVICES, VCBS OF AJMER AND NASIRABAD UNDER GE NASIRABAD
2021_MES_498666_2
83712/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
NASIRABAD
AS PER NIT CONDITION
7 documents required · 7 mandatory
₹500
GE Nasirabad
₹80,000
Yes
9 May 2022
25 Feb 2022
19 Mar 2022
25 Feb 2022
17 Mar 2022
5 Mar 2022
25 Feb 2022 - 5 Mar 2022
Amount
Dismantling ACSR or AAC conductors removing to store or taken on schedule of credit complete all as specified and as directed.
Dismantling insulators any type, any size complete all as specified and as directed.
Dismantling cross-arms of mild steel channel or angle sections etc. complete and setting aside for re-use or removing to store or for schedule of credit
Dismantling stay assembly complete (Note: Demolition of concrete, etc. and excavation measured shall be measured and paid separately separately.)
Disconnecting, taking out old unserviceable under ground cable of rated voltage 11 kV, nominal cross sectional area of main conductor 120 sqmm, upto 4 core, any type from trenches including taking out concrete cable cover/ bricks etc. including removing materials to store for keeping in safe custody or for reuse or for taking credit all as specified and directed by the Engineer-in-Charge.
Dismantling earth wire or copper conductor, service feeder or distributor span removing to store or taken on schedule of credit complete all as specified and as directed.
Dismantling air break gang operated switches vertical/horizontal mounted including insulators and operating mechanism for repair/ replacement of broken/worn out components and insulators etc. or carrying to MES store (spare/components for replacement to be provided free by department)
Taking up or down old unserviceable GI pipe of any size fixed/ laid in any position, keeping serviceable materials separately for reuse at site or removing to store or taken on schedule of credit complete all as specified and as directed.
Dismantling concrete poles/ struts, any size, transporting to store and stacking or for schedule of credit
M & L for prestressed concrete pole, 11.0 metres long, 152 mm X 152 mm at top and 152 mm X 260 mm at bottom designed for wind load at the site including preparing and painting on prestressed concrete pole with two coats of cement base paint on exposed portion and including making strips of width 30 cm upto 1.5 m from the ground level in black and white shade in alternate layer including numbering of poles using two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer complete all as specified and as directed.
Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. or for cable laying or not exceeding 10 sqm on plan and not exceeding 1.5 m in depth and getting out in soft/ loose soil complete all as specified and as directed.
Excavating in trenches not exceeding 1.5 m wide and exceeding 1.5 m but not exceeding 3.0 in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. or for cable laying or not exceeding 10 sqm on plan and exceeding 1.5 m but not exceeding 3 m in depth and getting out in soft/ loose soil complete all as specified and as directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm in soft/ loose/ hard/ dense soil complete all as specified and as directed.
Removing excavated material (soils) not exceeding 50 m and depositing where directed at a level n exc. 1.5 m above the starting point
Supply & spreading in trenches dry river sand cushioning to underground cable in trenches including spreading, levelling hand punning down complete all as specified and as directed Note:- Depth of sand cushioning will be measured after punning down and levelling the sand properly.
M & L for laying of bricks locally available sub class 'B' bricks, non-modular sizes as per IS 1077: 1992 for cable protection cover laid flat and dry in trenches over the cable perpendicular to the direction of cable all as directed.
M & L for cement concrete in foundation, filling and mass concrete in M7.5(Nominal Mix) using 40 mm nominal size graded crushed stone aggregate complete all as specified and as directed.
M & L for cement concrete in foundation, filling and mass concrete in M10(Nominal Mix) using 40 mm nominal size graded crushed stone aggregate complete all as specified and as directed.
M & L for cement concrete M15 (Nominal Mix) using 20 mm nominal size coarse aggregate in roof kerbs or mud stops, rounded or chamfered on edges complete all as specified and as directed.
M & L for auguring under road, pavement, hard standing, railway lines by trenchless technology using latest boring technique and necessary machine for insertion of GI pipe of 65 mm to 100 mm nominal bore complete all as specified and as directed.
Supplying & laying in trenches, in road cutting and along pole 80 mm nominal bore, light grade, galvanised coated steel tube conforming to IS 1239 (Part-1): 2004 including all fittings conforming to IS 1239 (Part-2): 2011 complete all as specified and as directed.
Supplying & laying in trenches, in road cutting and along pole 100 mm nominal bore, light grade, galvanised coated steel tube conforming to IS 1239 (Part-1): 2004 including all fittings conforming to IS 1239 (Part-2): 2011 complete all as specified and as directed.
Supply, fixing and stringing ACSR (aluminium conductor galvanized steel-reinforced) of any size and type in accordance with site requirement and binding on insulator by means of 22 gauge aluminium binding wire to permissible sag complete all as specified and as directed.
M & L for cross arms, bracings, supports, clamps, back plates and stay clamp fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and applying two coats of aluminium paint over a coat of red oxide primer complete all as specified and as directed.
S & F gang operated air break switch, three poles, outdoor type, nominal system voltage 11 kV, rated voltage 12 kV, rated normal current 200 Amps, rated frequency 50 Hz, rated one minute power frequency withstand voltage between (i) earth & poles 28 kV (rms) (ii) across the isolating distance 32 kV (rms), rated lightning impulse withstand voltage (i) to earth and between poles 75 kV (Peak) (ii) across the isolating distance 85 kV (Peak), Rated short-time withstand current 25 kA for 3 seconds, rated peak withstand current 63 kA for climatic conditions at the site, mechanically operated mounted on insulator and steel frame with operating mechanism worked from ground level for current complete all as specified and as directed.
S & F drop out fuse unit expulsion type for outdoor air brake gang operated switches single pole mounted and including insulator for 11 kV working pressure fixed to and including MS channel with nuts, bolts, washers etc. synthetic bounded fuse carrying tube complete with line taps and suitable for current carryout capacity 15 Amps.
M & L for stay assembly of stay rod of diameter 20 mm complete with accessories as shown in electrical plate No. 1 (loop type insulator, stay clamps, excavation and concrete measured separately) complete all as specified and as directed.
M & L for hot dip galvanized stay strands of grade I, 7 Nos wires construction, wire diameter 4 mm, nominal strand diameter 12 mm, heavy zinc coating complete all as specified and as directed.
S & F galvanised mild steel wire 3.15 mm or 4 mm dia in overhead lines complete all as specified and as directed.
S & F XLPE cable end termination, heat shrinkable, indoor type complete with jointing material and accessories suitable for voltage 6.35 kV/ 11 kV (Earthed), 3 core, 50 sqmm to 95 sqmm complete all as specified and as directed.
S & F XLPE cable end termination, heat shrinkable, outdoor type complete with jointing material and accessories suitable for voltage 6.35 kV/ 11 kV (Earthed), 3 core, 50 sqmm to 95 sqmm complete all as specified and as directed.
S & F XLPE cable end termination, heat shrinkable, indoor type complete with jointing material and accessories suitable for voltage 6.35 kV/ 11 kV (Earthed), 3 core, 120 sqmm to 185 sqmm complete all as specified and as directed.
S & F XLPE cable end termination, heat shrinkable, outdoor type complete with jointing material and accessories suitable for voltage 6.35 kV/ 11 kV (Earthed), 3 core, 120 sqmm to 185 sqmm complete all as specified and as directed.
Supply, laying and testing cross linked polyethylene (XLPE) insulated, PVC sheathed cables for working voltages 6.35 kV/ 11 kV, three phase, earthed system, 3 core, screened, armoured power cable, 95 sqmm of nominal area of conductor, aluminium conductor, ISI marked as per IS 7098 (Part-II): 2011 laid in trenches or under floors making all connections with necessary glands lugs bushing complete all as specified and as directed.
Supply, laying and testing cross linked polyethylene (XLPE) insulated, PVC sheathed cables for working voltages 6.35 kV/ 11 kV, three phase, earthed system, 3 core, screened, armoured power cable, 120 sqmm of nominal area of conductor, aluminium conductor, ISI marked as per IS 7098 (Part-II): 2011 laid in trenches or under floors making all connections with necessary glands lugs bushing complete all as specified and as directed.
S & F porcelain pin insulator, Type B, Nominal System voltage 11 kV, highest system voltage 12 kV, visible discharge test voltage 9 kV, wet power frequency withstand voltage 35 kV, power frequency puncture withheld voltage 105 kV, impulse withstand voltage 75 kV, minimum total creepage distance 230 mm, minimum failing load 5 kN, of suitable size with galvanised steel insulator pin, nut, washers complete all as specified and as directed.
S & F polymer pin insulator, Type B, Nominal System voltage 11 kV, highest system voltage 12 kV, visible discharge test voltage 9 kV, wet power frequency withstand voltage 35 kV, power frequency puncture withheld voltage 105 kV, impulse withstand voltage 75 kV, minimum total creepage distance 230 mm, minimum failing load 5 kN, of suitable size with galvanised steel insulator pin, nut, washers complete all as specified and as directed.
S & F porcelain disc insulator, ball and socket type, Type B, Nominal System voltage 11 kV, highest system voltage 12 kV, visible discharge test voltage 9 kV, wet power frequency withstand voltage 35 kV, impulse withstand voltage 75 kV, minimum total creepage distance 230 mm, minimum failing load 70 kN, of suitable size with galvanised steel stud pin, nut, washers complete all as specified and as directed.
S & F polymeric composite disc insulator, ball and socket type, Type B, Nominal System voltage 11 kV, highest system voltage 12 kV, visible discharge test voltage 9 kV, wet power frequency withstand voltage 35 kV, impulse withstand voltage 75 kV, minimum total creepage distance 230 mm, minimum failing load 70 kN, of suitable size with galvanised steel stud pin, nut, washers complete all as specified and as directed.
Supply and erection in repairs of three piece metal oxide lightning arrestor suitable for 11 kV continuous operating voltage (3 phase) with rated voltage 12 kV (rms) with nominal discharge current rating of 2.5 kA and complete with galvanised clamping arrangements, GI bolts, nuts, washers etc. complete as specified and as directed.
Supply & connect in replacement of battery 180 AH, 25 plate with initial Charger Specific gravity 12.60 of 12 volts complete all as directed by Engineer-in-Charge. (Make:- EXIDE/Amron or equivalent)
M & L for cleaning and up keeping of MES installations / campus by surface dressing or trimming of natural ground to remove small inequalities not exceeding 15 cm deep ( including removing vegetation / shrubs / brush wood / under-growth ), cleaning of drains ( drain size 0.50 m x 0.40 m for 60 m length) & carrying away the rubbish to a distance of not exceeding 50 m away complete within fencing perimeter approximately 30 m x 50 m. complete all as directed. Note : Each job will be measured for a completed month.
M & L for preparing and painting on steel tubular swaged pole 410 SP-55 (11.00 metre long) including cross arms, GI brackets with two coats of aluminium paint over a coat of aluminium red oxide primer on exposed portion and including making strips of width 30 cm upto 1.5 m from the ground level in black and yellow shade in alternate layer including numbering of poles using two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer complete all as specified and as directed.
M & L for preparing and painting on prestressed concrete pole, 11.00 metres long, 152 mm X 152 mm at top and 152 mm X 260 mm at bottom, with two coats of cement base paint on exposed portion including painting on cross arms, street light brackets with two coats of aluminium paint over a coat of aluminium red oxide primer and including making strips of width 30 cm upto 1.5 m from the ground level in black and yellow shade in alternate layer including numbering of poles using two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer complete all as specified and as directed.
S & F in repairs ACSR (aluminium conductor galvanized steel-reinforced) of any size and type in accordance with site requirement in jumper including PVC sleeve (in Red/Yellow/Black colour) and binding on insulator by means of 22 gauge aluminium binding wire complete all as specified and as directed.
Dismantling, re-erecting, restringing tensioning and repair to overhead line ACSR conductor of any size upto 5 conductors in one span as required on poles LT / HT including fixing insulators and jointing with ACSR conductor complete all as specified and as directed.
Disconnecting all existing connection with transfomer and taking down and shifting transformer from any substation under the GE to new location and including installation at new location including connecting all connections, earthings, conductors, cables, nuts, bolts, washers etc. complete all as specified and as directed.
M & L for danger notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with mild steel clamps, bolts and nuts of approved size, for HT, 250 mm X 200 mm complete all as specified and as directed.
Preparation of newly or previously untreated steel surface of any description over 10 cm width or girth and applying two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer complete all as specified and as directed by Engineer-in-Charge
M & L for earthing complete with galvanised steel plate earth electrode 600 mm X 600 mm X 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to earthing lead of 32 mm X 6 mm galvanised mild steel strip by means of bolts, nuts, check nuts and washers of galvanised iron from earth plate to test point upto 7.5 metre including all as shown in electrical plate No. 3 of SSR Part I (2009) including necessary concrete chamber in cement concrete M15 (Nominal Mix) using 20 mm nominal size coarse aggregate, precast RCC cover slab in cement concrete M15 (Nominal mix) using 20 mm nominal size coarse aggregate of size 40 cm X 40 cm X 5 cm reinforced with 8 mm dia TMT bars @ 150 mm c/c both ways with one handle for lifting made out of 8 mm dia bar, GI funnel, GI wire mesh filter, 20 mm dia GI pipe medium grade for watering, 40 mm dia GI pipe medium grade for protection of earthing lead, charcoal or coke and salt in alternate layers including necessary excavation and earth work in any type of soil/ strata and testing complete all as specified and as directed by the Engineer-in-charge.
Preparation of newly plastered surfaces on walls and applying two coats of white wash complete all as specified and as directed.
M & L for preparation of old steel surfaces of panel board and applying one coat of aluminium paint including numbering of panel board using two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer complete all as specified and as directed.
Demolition of lime concrete of any description and in any position not otherwise specifically provided for
M & L for cement concrete M15 (Nominal Mix) using 20 mm nominal size graded crushed stone aggregate in lintels upto 1.5 m clear span, cills, steps; seismic and other similar bands, plinth courses, string courses, lacing courses, parapets and railings upto 60 cm in height, copings, kneelers, apex stones, bed plates, kerbs, water troughs, slab staging for water tanks, filling of pressed steel door frame, fixing of hold fasts and the like including weathering, slightly rounded or chamfered angles and throating including necessary formworks complete all as specified and as directed by Engineer- in-charge.
M & L for trimming of branches of trees touching HT/LT Electric over head line and making clear about 3 m in radius and carrying and disposal where directed not exceeding 50 m complete all as directed. Note :- Vehicle will be provided by department at spare time.
Supply only IDMT CGI-14N,CGI14N relay 11kv capacity Make :CG
Supply only 11KV VCB Mechanism or Spring charging Mechanism Make:-CG
Supply only 220V Spring Charging Motor Make:- Stelmec/CGL/Jyoti VCB
Supply only Tripping coil/closing coil Make:-ABB/CG
Supply only 11 KV VCB Charging key
Supply only 11 KV VCB Vacuum Bottle Interrupter Make:-CG
Supply only 11 KV VCB Crompton Insulator
Supply only 11 KV VCB Trolly Insulator
Supply only 11 KV VCB Crompton CT Set
Supply only 11 KV VCB PT Spout Crompton
Dehydration and filtration of existing transformer oil of transformer at different location with filtration machine and heating system to get the minimum di-electric strength of oil 40 kV minimum without disturbing the power supply system and refilling/ topping up /replacement of unserviceable transformer oil complete all as specified and as directed.( Note: Transformer oil required extra for filling/topping up shall be measured and paid separately under the relevant items of this schedule).
Supply, filling and topping up new transformer oil of dielectric strength not be less than 60 kV and conforming to IS 335: 1993 complete all as specified and as directed.
Disconnecting, taking down distribution transformer outdoor type 11 kV /415 volts having capacity upto and including 75 kVA, transportation to the workshop for repairs including opening of transformers cover, draining of oil, de-tanking of core and coil assembly, cleaning, washing of dust and dirt from all parts including core, tank and cooling tubes radiators etc., joint inspection for estimate, replacement of defective parts, assembly, stage inspection, re-tanking, oil filtration/ dehydration, fill dehydrated oil and fresh oil and testing the repaired transformers for all the routine tests as per IS 2026 (Part 1): 2011 with latest amendments. Note: - (a) Transformer oil shall be drained out by the contractor in suitable capacity mild steel drums to be arranged by the contractor. The said drained out transformer oil shall be refilled in the transformer duly dehydrated after repair and the cost thereof shall be included in unit rate quoted against the respective item of this schedule. (b) Rewinding of both HT & LT coil shall be measured and paid for separately under respective item of this schedule. (c) Transportation charges for transportation of transformer from site to workshop and after repair, workshop to site shall be borne by the contractor and cost thereof shall be deemed to be included in the unit rate quoted for this item. (d) The spare parts excluding nuts, bolts, washer, gasket etc., gasket etc. shall be measured and paid for separately (e) The said transformer shall be repaired in reputed workshop as decided by the GE. (f) Testing of transformer after repair shall be carried out as per IS 2026 (Part 1): 2011 and the cost of testing shall be deemed to be included in unit rate quoted against this item. (g) The IR value of the dried winding before inserting the core in the shell shall be measured and recorded.
Disconnecting, taking down distribution transformer outdoor type 11 kV /415 volts having capacity 100 kVA, 150 kVA, 200 kVA, 250kVA and 315 kVA, transportation to the workshop for repairs including opening of transformers cover, draining of oil, de-tanking of core and coil assembly, cleaning, washing of dust and dirt from all parts including core, tank and cooling tubes radiators etc., joint inspection for estimate, replacement of defective parts, assembly, stage inspection, re-tanking, oil filtration/ dehydration, fill dehydrated oil and fresh oil and testing the repaired transformers for all the routine tests as per IS 2026 (Part 1): 2011 with latest amendments. Note: - (a) Transformer oil shall be drained out by the contractor in suitable capacity mild steel drums to be arranged by the contractor. The said drained out transformer oil shall be refilled in the transformer duly dehydrated after repair and the cost thereof shall be included in unit rate quoted against the respective item of this schedule. (b) Rewinding of both HT & LT coil shall be measured and paid for separately under respective item of this schedule. (c) Transportation charges for transportation of transformer from site to workshop and after repair, workshop to site shall be borne by the contractor and cost thereof shall be deemed to be included in the unit rate quoted for this item. (d) The spare parts excluding nuts, bolts, washer, gasket etc. shall be measured and paid for separately (e) The said transformer shall be repaired in reputed workshop as decided by the GE. (f) Testing of transformer after repair shall be carried out as per IS 2026 (Part 1): 2011 and the cost of testing shall be deemed to be included in unit rate quoted against this item. (g) The IR value of the dried winding before inserting the core in the shell shall be measured and recorded.
Disconnecting, taking down distribution transformer outdoor type 11 kV /415 volts having capacity 400 kVA, 500 kVA and 630 kVA, transportation to the workshop for repairs including opening of transformers cover, draining of oil, de-tanking of core and coil assembly, cleaning, washing of dust and dirt from all parts including core, tank and cooling tubes radiators etc., joint inspection for estimate, replacement of defective parts, assembly, stage inspection, re-tanking, oil filtration/ dehydration, fill dehydrated oil and fresh oil and testing the repaired transformers for all the routine tests as per IS 2026 (Part 1): 2011 with latest amendments. Note: - (a) Transformer oil shall be drained out by the contractor in suitable capacity mild steel drums to be arranged by the contractor. The said drained out transformer oil shall be refilled in the transformer duly dehydrated after repair and the cost thereof shall be included in unit rate quoted against the respective item of this schedule. (b) Rewinding of both HT & LT coil shall be measured and paid for separately under respective item of this schedule. (c) Transportation charges for transportation of transformer from site to workshop and after repair, workshop to site shall be borne by the contractor and cost thereof shall be deemed to be included in the unit rate quoted for this item. (d) The spare parts excluding nuts, bolts, washer, gasket etc. shall be measured and paid for separately (e) The said transformer shall be repaired in reputed workshop as decided by the GE. (f) Testing of transformer after repair shall be carried out as per IS 2026 (Part 1): 2011 and the cost of testing shall be deemed to be included in unit rate quoted against this item. (g) The IR value of the dried winding before inserting the core in the shell shall be measured and recorded.
M & L for rewinding of coils on primary side of transformer of any capacity using proper size, double paper covering, ordinary copper winding wires conforming to IS 7404 (Part-1): 1991 as per existing size, turns and insulation class including connecting minor insulation materials suitable for 11 kV/ 415 V transformer complete all as specified and as directed. (Note: - Weight of only winding wire shall measured for payment purpose.)
M & L for rewinding of coils on secondary side of transformer of any capacity using proper size, double paper covering, ordinary copper winding wires conforming to IS 7404 (Part-1): 1991 as per existing size, turns and insulation class including connecting minor insulation materials suitable for 11 kV/ 415 V transformer complete all as specified and as directed. (Note: - Weight of only winding wire shall measured for payment purpose.)
M & L for rewinding of coils on primary side of transformer of any capacity using proper size, double paper covered aluminium winding wires conforming to IS 6162 (Part-II): 1971 as per existing size, turns and insulation class including connecting minor insulation materials suitable for 11 kV/ 415 V transformer complete all as specified and as directed. (Note: - Weight of only winding wire shall measured for payment purpose.)
M & L for rewinding of coils on secondary side of transformer of any capacity using proper size, double paper covered aluminium winding wires conforming to IS 6162 (Part-II): 1971 as per existing size, turns and insulation class including connecting minor insulation materials suitable for 33 kV/ 11 kV transformer complete all as specified and as directed. (Note: - Weight of only winding wire shall measured for payment purpose.)
Taking out old unserviceable burn out core lamination from transformer and S & F new core lamination made of cold rolled grain oriented (CRGO) steel or amorphous steel as per the existing grade, type etc. conforming to Indian standards complete all as specified and as directed.
S & F in repairs 12 kV or 17.5 kV/ 250 A bushing with copper stem including both porcelain parts and metal parts with accessories as per IS 3347 Part 3 (section 1 & 2) complete all as specified and as directed.
S & F 12 kV or 17.5 kV/ 250 A bushing with copper stem including both porcelain parts and metal parts with accessories as per IS 3347 Part 3 (section 1 & 2) complete all as specified and as directed.
Taking out old unserviceable off load tap changer from 11 kV / 433 V Transformer & Supply and fix new off load tap changer suitable for 11 kV/ 433 V Transformer and as per the existing one complete all as specified and as directed.
M & L for cable route indicator made out of CI plate 150 dia, 8 mm thick, embossed with lettering "MES HT Cable", welded or bolted onto 35 mm X 35 mm X 6 mm angle iron, 600 mm long duly painted with anti-corrosive paint in brown colour & including necessary earthwork and excavation, embedded in PCC M15(Nominal Mix) using 20 nominal size graded crushed stone aggregate of size 400 mm X 400 mm X 300 mm complete all as specified and as directed.
M & L for cable route indicator made out of CI plate 100 dia, 8 mm thick, embossed with lettering "MES LT Cable", welded or bolted onto 35 mm X 35 mm X 6 mm angle iron, 500 mm long duly painted with anti-corrosive paint in brown colour & including necessary earthwork and excavation, embedded in PCC M15(Nominal Mix) using 20 nominal size graded crushed stone aggregate of size 400 mm X 400 mm X 300 mm complete all as specified and as directed.
M/S JAGDAMBA ENTERPRISES
M/s SUNIL ENTERPRISES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .