| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹22.7 LAccepted-AOC | 1 | Accepted-AOC Being lowest and reasonable rates | |
| 2 | 2₹23.9 L+₹1.2 L (5.39%)Rejected-Finance RZ 212F D BLOCK RAJ NAGAR PART II PALAM COLONY NEW DELHI 110077 | SOUTH WEST | DELHI | 110077 | 2 | Rejected-Finance Not being lowest tenderer | |
| 3 | 3₹26.5 L+₹3.8 L (16.7%)Rejected-Finance | 3 | Rejected-Finance Not being lowest tenderer | |
| 4 | 4₹29.3 L+₹6.6 L (29.1%)Rejected-Finance WZ 1000 NANGAL RAYA PANKHA ROAD SOUTH WEST DELHI DELHI 110046 | DELHI | SOUTH WEST DELHI | DELHI | 110046 | 4 | Rejected-Finance Not being lowest tenderer | |
| 5 | 5₹29.6 L+₹7.0 L (30.7%)Rejected-Finance NO 9 BYRAVESHWARA INDUSTRIAL ESTATE ANDRAHALLI MAIN ROAD NEAR PEENYA 2ND STAGE BENGALURU 560 091 | BENGALURU URBAN | KARNATAKA | 560091 | 5 | Rejected-Finance Not being lowest tenderer |
Tender Value
₹48.4 L
EMD Value
₹96,800
Closing Date
12 Nov 2021, 6:00 pmClosed
CWE U
HQ CWE U Delhi Cantt 110010
REPAIR REPLACEMENT OF 33 YARD SWITCHGEAR AND OF CONNECTED ACCESSORIES OF 11 KV DISTRIBUTION NETWORK OF SHANKAR VIHAR SHEKHAWATI CGDA NIDEM HQ SFC AND NSB II AREA OF AGE U ES NO III UNDER GE U ELECT SUPPLY DELHI CANTT 10
2021_MES_481191_1
89036/CWE(U)/D-19/2021-22/E8
Open Tender
Electrical and Maintenance Works
Item Rate
120 days
Delhi Cantt
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
Yes
GE U Electric Supply
₹96,800
Yes
2 Dec 2021
12 Oct 2021
15 Nov 2021
12 Oct 2021
12 Nov 2021
27 Oct 2021
Amount
Excavation in trenches not exc. 1.5 m wide and not exc 1.5 m deep in soft/loose soil) for laying of cables or GI pipe and getting out including levelling of bottom suface to required level complete all as specified and directed.
Material and labour for river washed and screened, dry sand for filling in trenches below and around underground cables for cushioning of cables etc, complete all as specified.
Supplying and laying un-reinforced precast concrete cable cover, class HV, type 1, flat size 300mmx 180mm x 40mm.
Returning filling in, including spreading, levelling, watering and well ramming soil in layers not exceeding 25 cm thick all as specified and directed.
Removing excavated material (ie soil) from site to a distance n. exc 50 m away and depositing where directed at a level n. exc. 1.5 m above the starting point complete all as specified and directed
Supplying, laying, testing and connecting in replacement / rerouting XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with multistranded aluminum conductors, 11 KV grade, IS 7098 marked, suitable for HT 11 KV(E) system, laid in trenches / ducts / encased in GI pipe / fixed to pole, including jointing & testing complete all as specified and directed of size 185 sqmm 3 core for re routeing the existing cable of 180 ORs qtr at Mahipalpur
Supplying, laying, testing and connecting in replacement / rerouting XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with multistranded aluminum conductors, 11 KV grade, IS 7098 marked, suitable for HT 11 KV(E) system, laid in trenches / ducts / encased in GI pipe / fixed to pole, including jointing & testing complete all as specified and directed of size 300 sqmm 3 core for re routeing the existing cable at NSB-II/ SFC area
Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 200 mm dia suitable for 0.6 mpa working pressure
Material and labour for route tracing the 11 KV HT cable complete all as specified and directed.
Supply and fix Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 185 sqmm 3 core.
Earthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick, burieddirectly in ground (earth pit not less than 2.25 metres deep below groundlevel) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to galvanised earth strip of size 32x6mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion Kg/Sqm with frame funnel and GI watering pipe of 20 mm dia medium grade, 40 mm dia bore light grade protection pipe to test point including testing etc all complete all as specified and directed.
M & L for cutting and removing grass, vegetation bushes etc from surrounding 4 pole/6 pole HT structure/ 33 KV yard and etc , outside area of HT installation and removing all rubbish to a distance not exceeding 50 m as directed at site.
Material and labour for sprading of stone aggregate of nominal size not more than 25mm under 4/6 pole HT structure /surounding area of outdoor RMU manually without damaging any equipments, cable or parts , spreading & levelling of finished gravel uniformaly in layers n. ecc. 15 cm thick watered and rammed to true surface all as specified and directed
Suplying only in replacement in sub station fixing 3.3 to 11 KV electrical insulation mat of size 5 mtr x 1 mtr x 2.5 mm thick specification as per IS 15652 2006
S&F in replacement for Danger Notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled white , with letters, figures and conventional skull and bobes in signal red colour and fixed with MS clamps, bolts and nuts of approved size, for HT, 25x20 cm size including taking down old one complete all as specified and directed.
S&F in replacement Lightening arrestors expulsion type with all fittings, transmission class, discharge capacity 65 kilo Amps suitable for 11000 volts complete as specified and directed.
Labour and T&P for Demolition of path /concrete in ground floors and pavings n exc 15 cm thickness (below or above ground level) complete all as specified and as directed.
M&L for painting with two coats of superior aluminium paint including necessary preparation of old existing surfaces of wire mesh / matte steel fencing by brushing/cleaning complete steel structure/frame/ gate for 11 KV / 0.433 kv TFR up to 30 Sqmm area complete all as specified and directed.
Supply only rubber hand cloves ISI Marked suitable for working on HT 15 KV complete all as specified and directed.
Supply only safety long gumboot ISI marked with steel toe complete all as specified and directed.
Material and labour for servicing of HT control panel including outdoor CT, PT and relays in control panel of outdoor SF6 breaker of capacity 1250 Amps and rating 36 KV complete as details mentioned as under:- Details of servicing of HT Panel (breaker) :- (i) Checking of Closing/Tripping coil assembly (ii) Adjustment of mechanism if required. (iii) Clean the circuit breaker to remove dust and dirt. The envelope of the vacuum interrupter and insulating materials shall be wiped with a clean cloth. (iv) Checking the contact for wear. Replace if the contact piece has worn out. (v) Apply a small amount of oil to rotary sections, sliding surfaces, pins, coupling section, etc.use grease for the operating shaft and bearings, and machine oil for other parts. (vi) Check for rust and wear. (vii) Checking of spring charge mechanism (viii) Check for loosened bolts and nuts, broken spring washers and snap pins etc. (ix) Check for loosened connections, rust, damaged lead wires. (x) Checking of control circuit & tighten the connections if any.
Material & labour for opening of the VCB/OCB , 11 KV 400 to 2000 Amps of any make by removing of the Breaker from the existing position after disconnecting all the connections from the system, servicing, Overhauling of the same, checking of the same for proper operation, spring charge, charged control cables are fastened tightly to the terminals, any abnormality, VCB, cleaning the surface of the insulators, fasten the bolts, checking and correcting interrupting units, mechanism, linkages etc, fasten the hardwares of control wiring, check that the split pins, Circlips, dowell pins etc. have not come out and are intact, lubricate the mechanism, moving parts by castrol, all purpose grease or equivalent, check that the vaccum pots/chambers is within limit including opening of the shutters properly, replacing of the trip catch, roller, holding catch, stopper, close push button, closing cum reassembling, control limit switches reconnecting of the breaker for smooth functioning complete all as specified and directed.
Material & labour for Decarbonizing/cleaning complete HT 11KV, 3 phase independent main bus bar, section bus bar chamber of HT panel electrification connection complete, consisting of set of 3 to 5 HT VCB switch gear arrangement incoming and outgoing installed in sub-stations after removing the complete bus bar spout, circuit spout from the bus bar chamber/cleaning with CTC and ensure proper decarburizing, re-fixing the same after applying backtol (Red) solution to the spout, checking all the connections, tightening the nuts, bolts thimbles for incoming and outgoing system complete, replacement of damaged space heater along with thermostats, as specified and directed, rate quoted is inclusive of bactol red, CTC & cotton waste provided by contractor complete all as specified and directed.
Material & labour for Decarbonizing/cleaning complete HT 11KV, 3 phase independent main bus bar, section bus bar chamber of HT panel electrification connection complete, consisting set of 6 to 10 HT VCB switch gear arrangement incoming and outgoing installed in sub-stations after removing the complete bus bar spout, circuit spout from the bus bar chamber/cleaning with CTC and ensure proper decarburizing, re-fixing the same after applying backtol (Red) solution to the spout, checking all the connections, tightening the nuts, bolts thimbles for incoming and outgoing system complete, replacement of damaged space heater along with thermostats, as specified and directed, rate quoted is inclusive of bactol red, CTC & cotton waste provided by contractor complete all as specified and directed.
Material & labour for Decarbonizing/cleaning complete HT cable ougoing/Incoming circuit of CTs & PTs, 3 phase, cleaning with CTC and ensure proper decarburizing, re-fixing the same after applying backtol (Red) solution to the spout, checking all the connections, tightening the nuts, bolts thimbles for incoming and outgoing system complete, as specified and directed, rate quoted is inclusive of bactol red, CTC & cotton waste provided by contractor complete all as specified and directed.
Material and labour for testing and calibration of HT Panel Complete as mentioned under - (i) Primary Injection Test of CT / PT (ii) Closing & Opening Timing Test for all three poles. (iii) IR Test with megger in open and closed condition. (iv) Contact resistance test for all three poles (v) Closing coil resistance (vi) Tripping coil resistance. Testing of following relays of control panel with Secondary Injection Kit ,checking and programming of relay :- (i) Over current and earth fault relay (ii) DC Supply supervision relay. (iii) Master trip relay Note:- (I) DC Supply for relay testing shall arranged by the contractor.
M&L for ON load / ON line Centrifuging and dehydration including filteration and cleaning of transformer oil by dehydration machine of 33 KV transformer at site and topping up deficient transformer oil including testing of samples before and after dehydration and filteration complete all as specified and directed. Note :- Deficient quantity of Transformer oil required for top up shall be measured and paid separately under item No 29 here-in -after as supply only.
Supply & filling transformer oil of approved quality as per IS having dielectric strength of 45-60 KV in 2.5mm gap for filling in OLTC & for topping up in transformer as required and directed.
Supply & fixing in replacement of closing coil assembly 50 volts DC of existing make for SF 6 breaker of capacity 1250 amps of rating 36 KV complete all as directed by Engr -in-Charge.
Supply & fixing in replacement of tripping coil assembly 50 volts DC of existing make for SF 6 breaker of capacity 1250 amps of rating 36 KV complete all as directed by Engr -in-Charge.
Supply & fixing in replacement of closing coil assembly 50 volts DC of existing make for VCB of capacity 1250 amps of rating 36 KV complete all as directed by Engr -in-Charge.
Supply & fixing in replacement of tripping coil assembly 50 volts DC of existing make for VCB of capacity 1250 amps of rating 36 KV complete all as directed by Engr -in-Charge.
Material & labour for repair /overhauling of OLTC ( On load tap changer ) of 33KV/11KV Power transformer of capacities 8/10 MVA at site by carried out following work of Schinder/ABB make :- (a) Opening of top plate of OLTC. (b) Draining out of transformers oil from the OLTC. (c) Stoping of leakage of oil from main shaft of OLTC including replacement of oil seal and all gasket of OLTC. (d) Checking /servicing of moving and fixed contact of OLTC and resistence test of contact. (e) Flushing of OLTC assembly with hot new oil and removing of sludge. (f) Filling of new transformer oil in OLTC . (g) Tightening of all tapping leads and connections. (h) Refixing of top plate of OLTC in original position after overhauling. (i) Electrical testing of manual/auto operation of OLTC. Note :- Transformer oil as required shall be measured and paid separately under respective item here-in -before as supply only.
M&L for Servicing & Repairs to Air-break switch (isolator) off load, rotating type, 33 KV, 800 Amps to 1250 Amps capacity, with proper alignment of isolator rotating blades, with fixed contact jaws, arcing horns, applying petrolium jelly to moving mechanism, cleaning and lubricating to isolator gear box assembly, tightening all nuts, bolts and clamps of jumpers etc, repairing to isolator gear box assembly and making in proper serviceable condition for smooth functioning, testing and commissioning on load complete all as specified and directed.
Supply & fixing in replacements, male/moving contact/ rotating blade of HDE copper silver plated of Air Brake, off load isolator switch, rotating type, 33 KV, 1250/800 Amps capacity with all fixing nuts, bolts etc complete all as specified and directed.
Supply & fixing in replacements, Fixed Contacts, made of HDE copper, silver plated, of Air Brake, off load isolator switch, rotating type, 33 KV, 1250/800 Amps capacity with all fixing nuts, bolts etc. complete all as specified and directed.
Supply, installation, testing and commissioning in replacement of lightening arrestor SMX type at door complete with all fittings transmission class 36 KV 10 KA 50 Hz suitable for system voltage 33/36 KV complete all as specified and directed.
Supplying ,fixing , testing of master trip relay in replacements , 50/24 Volt DC in control panel including wiring complete as directed at site.
Supplying ,fixing , testing of master trip relay in replacements ,110V Volt DC in control panel including wiring complete as directed at site.
Supplying ,fixing , testing of master trip relay in replacements ,50 Volt DC in control panel including wiring complete as directed at site.
Supplying ,fixing , testing of Trip circuit supervision relay in replacements, 50/24 Volt DC in control panel including wiring complete as directed at site.
Supplying ,fixing , testing of DC supervision relay in replacements, 50/24 Volt DC in control panel including wiring complete as directed at site.
Supplying and fixing PT fuse for 11 KV/110 V PT complete as directed at site.
Supply, installation and testing in replacement of over current & earth fault feeder protection relays comprising of the following protection auxillary working voltage at 110 V to 24 V DC supply, with 4 count inputs CT / 15 / 1 A, 5 discrete & 9 discrete outputs DNP3, modbus RTC, IEC 60870-5-103 communication flush mounted (a) over current ANSI code 50/51 (b) Re-closer ANSI code: 79 (c) cold pickup (d) Earth fault code 50G/51G (e) Phase under current ANSI code: 37 (f) Restricted earth fault ANSI code : 64 REF (g) Negative sequence overcurrents ANSI code : 46 (h) Fault recording (i) Event recording (j) Disturbance Recording (k) Trip circuit supervision ANSI code : TCS Make:- schnieder P123 or equivalent in siemens/ABB/C&S
S&F in replacement of main Bus spout for Areva/Alstom/CG make, complete suitable for 11 KV HT VCB of capacity 400 Amps with female contact, epoxy insulated body, locking/ connect nuts along with fixing accessories complete all as specified and directed.
S&F in replacement of main Bus spout for Areva/Alstom/CG make, complete suitable for 11 KV HT VCB of capacity 630 Amps with female contact, epoxy insulated body, locking/ connect nuts along with fixing accessories complete all as specified and directed.
S&F in replacement of circuit male with female contact spout for Areva/Alstom/ CG complete suitable for 11 KV HT VCB of capacity 400/630/800 Amps complete all as specified and directed.
Supply and fix in replacement triping coil assembly 24/50/110 Volt DC for 11 KV HT VCB of capacity 400/630/800 Amps capacity all as specified and directed.
Supply and fix in replacement closing coil assembly 24/50/110 volts DC for 11 KV HT VCB of capacity 400/630/800 Amps capacity all as specified and directed.
Supply and fix in replacement auxillary switch (7 No + 7NC) for HT V.C.B 12KV 400/630/800 Amps capacity complete all as specified and directed.
Supply and fix in replacement spring charging motor with spun/worm gear assembly type 220 Volt AC motorised mechanism of 11 KV VCB including testing & puting on load complete all as specified & directed and suitable for VCB of the following make : CG/Seimens/Aeva/ABB/Crompton/L&T.
Supply and fix in replacement of LED indication lamp for breaker ON/OFF/TRIP/Breaker Spring Charged/R-Y-B etc in HT 11 KV VCB panel including associated wiring, if reqd, complete all as specified and directed.
Supply only Bus supporting epoxy insulators with fixing nuts & bolts with washer on both ends.
Supply and fix in replacement Digital Ampere meter 0-300 Amps in HT 11 KV VCB panel working on auxilary supply of 110V DC/ 220V AC including associated wiring, if reqd, complete all as specified and directed.
Supply and fix in replacement Digital volt meter 0-15 KV in HT 11 KV VCB panel working on auxilary supply of 110V including associated wiring, if reqd, complete all as specified and directed.
Supply and fix in replacement T&C Switch for Breaker ON/OFF purpose in HT 11 KV VCB panel including associated wiring, if reqd, for proper functioning of switch complete all as specified and directed.
Supply and fix in replacement vacuum interrupter (3 inch/4 inch dia) WL type suitable for 11 KV VCB 630 Amps including testing & puting on load complete all as specified & directed for the VCB of make Crompton/ABB/Siemens/L&T.
Material & labour for complete replacement of the epoxy body of the Areva/Alstom/ CG 11 kv VCB 400/630 A along with new epoxy body of similar rating & model , epoxy insulators supporting insulator & circuit / Bus connections.
Supply and fix in replacements PT unit three phase three limb upto 11 KV draw out type single ratio having primary 11 KV & secondary 110 volts, 200 VA class I, including necessary bus bar connection & wiring for metering after disconnecting of HT supply from HT VCB of any capacity for repair works, taking out unserviceable PT unit complete all as specified and directed .
Supply and fix in replacement of HT 11 KV current transformer double wound cast resin type of ratio 200/100/5+5 Amps suitable for metering and protection, 26.3 KA/1 Sec, accuracy class 0.5, 5P10 including associated wiring complete all as specified and directed.
Supply and fix in replacement of HT 11 KV current transformer double wound cast resin type of ratio 100/50/5+5 Amps suitable for metering and protection, 26.3 KA/1 Sec, accuracy class 0.5, 5P10 including associated wiring complete all as specified and directed.
Supply and fix in replacements Digital Multifunction Meter with Multi Display for all basic parameters, power, energy, pf, max demand, etc and RS-485 port for ModBus communication in existing HT 11 KV VCB panel including associated wiring complete all as specified and directed.
M&L for Laminated paper sticker of letter size 250 mm x 8 mm in Red/Black/ white colour and printing of SM/MES No/feeder name/CT ratio etc as provided by AGE (U) E/S No-III in black colour and pasting the same on HT/LT panels complete all as specified and directed. Note:- Each sticker shall have different printing matter.
S&F in replacements of earth continuity conductor or main earthing lead fixed on wall or recess or chases or buried in ground or drawn in conduit/pipe or fixed on poles or any other situation for loop earthing etc as required of size 32 x 6 mm galvanized iron strip incl necessary cutting chases, excavation, nut bolts etc incl dismantling old strip complete all as directed.
Supply & fixing in replacement of Air circuit breaker 4 pole 800 Amps 50 KA with microprocesser based fixed type , manual operated including dismantling & taking out old unserviceable ACB from panels & fabrication works to BUS bar for proper fitting .
Supply & fixing in replacement of Air circuit breaker 4 pole 1000 Amps 50 KA with microprocesser based draw out type , electrical operated along with cardel bus bars modification including dismantling & taking out old unserviceable ACB from panels & fabrication works
Supply and installation in replacement Anti-condensation space-heater withThermostatic control in cable and circuit breaker compartments of HT switchgears complete all as specified and directed.
Taking out of heavy duty colling fan ,3 phase, 50 Hz of size 18" to 24" form power transformer 33/11 KV of capacity 8/10 MVA ,servicing of the fan by opening including cleaning, greasing , replacement of defective spares parts such as bearing/ bushing, capacitor, canopy, clamp, blade, etc with new one and painting of fan body with synthetic enamel paint and re-assembling in same position after repairs and testing complete all as directed by Engr-in-Charge. Note :- (a) The cost of spare parts deemed to be included in quoted rates . (b) Rewinding of the fan will be measured and paid separately under respective item of schedule here-in-after.
M&L in replacements for Rewinding of heavy duty colling fan, 3 phase, 50 Hz of size 18" to 24" of power transformer 33/11 KV capacity with super enamelled copper wire as per existing gauge including heating, varnishing, etc complete as required and directed.
S & F in replacement of hooter complete complete with switch etc suitable for warming HT 11 KV VCBs internal chambers
S & F battery 12V, DC, 100 AH maintnance free dry battery complete all as specified and as directed as per make : Exide/Luminous/Sukam
S & F Exhaust fan 450 mm sweep heavy duty with heavy duty bearings , balanced blades lovers single phase supply complete with acessories all As specified and as directed.
M&L for re-painting of HT 11 KV VCB panel consisting not less than 08 Nos VCB/Bus Coupler of approx size 4 to 6 Sqm with 2 coats of super enamal paint over a coat of red-oxide with sparygun including writing of Inoming/outgoing/Bus cupller Name/numbers in appropriate size of letters as directed and as specified.
M&L for re-painting of HT 11 KV VCB panel consisting not less than 6 Nos VCB/Bus Coupler of approx size 4 to 6 Sqm with 2 coats of super enamal paint over a coat of red-oxide with sparygun including writing of Inoming/outgoing/Bus cupller Name/numbers in appropriate size of letters as directed and as specified.
Supply, fixing and testing of the 33 KV current Transformer shall be paper impregnate oil immersed type,single phase 50 HZ confirming to IS:2705/1992 ( Part I,II,III & IV) with latest amendment in all respect except where ever modified in this specification. (a)Normal system voltage (KV rms) 33 KV (b) Highest system voltage (KV rms) 36 kv (c) Frequency 50 Hz (d) Transformation ratio (CT Ratio) 400-200/1-1-1-1A e) Rated output (VA burden) core 1-15 VA, Core 2-30 VA (f) Accuracy class -core1-1.0, core2-5P10 (g) Short time current 31.5KA RMS for 3 sec (h) Rated continuous thermal current 120% of rated current (j) Insulation Level- 36/70 KV.170 KVP (k) Max. temp. rise over max. ambient temp. of 50 deg. C at rated continuous thermal current at rated frequency and with rated burden.
S&F in replacement of PG clamps aluminium cast alloy suitable for ACSR conductor suitable for (weasel / panther ) for straight connections/ cross / t connections of type( as per conductor) 33 kv yard with GI nuts, bolts etc complete all as specified and directed.
Material and labour for Preparation of old painted surfaces of 33 KV yard including all steel structures/ frame/gate of bus bay at Grid at an height of 10 mtrs to 15 mtr from GL consisting for 5 nos isolator per bay CT and PT and VCB supporting structure by brushing/cleaning stains, greasy spots with thinner, applying two coats of spray painting of existing colour (synthetic enamel paint) with spraying machine in the yard complete all as specified and directed. Note:- Including all safety measures.
M&L for replacement of aluminium jumper made of ACSR conductor of type weasel / Panther / of size not less than 1 mtr of length conductor of 33 KV yard.
Material and labour for Preparation of old painted surfaces of fencing of 33 KV yard shankar vihar grid by brushing/cleaning stains, greasy spots with thinner, applying two coats of painting of existing colour (synthetic enamel paint) in the yard complete all as specified and directed.
Supply , fixing & testing of 3 Phase, 4 Wire, 11KV/110 V, 100/5A, Class 0.5S, 50 Hz, basic current 5A, CT/PT operated fully Static and AMR compatible Tri-Vector Energy Meters fitted with existing 11KV HT Panel for measurement of different electrical parameters as Active Energy (KWH), Reactive Energy (KVARH), Apparent Energy (KVAH) etc. IEC 62053-22 Electricity metering: Data exchange for meter reading and tariff complete all as directed by Engr- in- charge at site.
S&F of Switch Disconnector Fuse units of 630Amp TPN in existing main LT Panels along with bus bars modification including dismantling & taking out old unserviceable one from panels & fabrication works complete all as specified and directed.
Supply, installing, testing and commissioning in replacement outdoor type stainless steel (SS 316) cubical enclosure compartmentalized exterior and interior mirror type brushed suitable for highly corrosive environment, high creep resistance, better mechanical properties like ductility, yield strength, hardness etc.The enclosure shall be made of 2 mm thick SS 316 sheet. The fixing of double doors shall be on SS hinges with anti-theft provision (the door can’t be removed from enclosure without cutting enclosure). All fabrication/welding shall be done with TIG/MIG or as approved by Engineer in charge suitable for SS 316. Sliding handle and locking arrangement front and rear both side . Enclosure shall be suitable for AC supply system 415 volts, 3 phase, 4 wire, 50 Hz. IP-55 class protection and mounted on channel 75 mm welded with panel of SS 316. The enclosure shall have provision of cable alley . Cable entry from bottom side including internal wiring with PVC insulated solid, copper conductor FRLS cable, IS-694 marked, 1100 volts grade of appropriate size (but not less than 2.5 sqmm). Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45 cm above the nearest road level.
Incomer of the panel having ACB 4 pole , 1000 Amp , 50 kA , 415 Volt AC Horizontal draw out type motorized (EDO) , front operated with Microprocessor based LCD protection release for adjustable over current, short circuit and earth fault protection-01 No, Digital Multifunction Meter (Accuracy class 0.5) with LCD display for measuring of current, voltage, power, power-factor, energy parameters etc and Aluminium bus bar of rating 1500 Amp, 4 pole , mounted on SMC insulator- set of four. Outgoing of the panel having MCCB 4 pole , 320 Amps,50 Hz,415 Volts, 35 KA with microprocessor release - 01 Nos . MCCB 4 pole , 250 Amps,50 Hz,415 Volts, 35 KA with microprocessor release - 02 Nos, MCCB 4 pole , 200 Amps,50 Hz,415 Volts, 25 KA with microprocessor release - 02 Nos, MCCB 4 pole , 125 Amps,50 Hz,415 Volts, 25 KA with microprocessor release - 01 Nos, MCCB 4 pole , 100 Amps,50 Hz,415 Volts, 25 KA with microprocessor release - 01 Nos. All outgoing busbar shall be of current carrying capacity not less than 1.5 times the rated current of MCCBs. All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947-II/IS 13947-II (Latest Version). The MCCB should have Ics=100%Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacturer. All out going feeder shall be connected by cable through suitable size gland plate / glands
Supply and fixing Steel work in tubular trusses including special shaped washer etc,complete using ERW or induction butt welded tubes ,including one coat of zinck chromate primer paint including prepration of surface at contractor's workshopbefore fabrication complete allas specified and directed.
Material and labour for galvanised sheet 0.50 mm thick power pre coated in roof fixed with 'L' type or 'J' type or cranked hooked bolt complete all as specified and directed
Material & laboure for PCC (1:4:8) type D-2 using 40 mm graded stone aggregate as in foundation filling and mass concrete complete all as specified and directed.
Supply and fix Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 300 sqmm 3 core
Shifting and transportation of Transformer upto 630KVA at new site care fully by using 8 Ton crane (Hydra) at new location including installation on foundation or store in store yard complete all as specified and directed by Eng in charge
Material and labour for taking complete shutdown of LT panel, decarbonisation of all cable joints and bus bar joints,cleaning of epoxy insulation, replacement of corroded nuts and bolts complete as directed by Eng in charge
MV Engineers And Contractors
Rajindera Enterprises
mayur enterprises
Vijay Electricals
Buddham Builders
M P TYAGI ENGINEERS AND CONTRACTORS
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .