Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.7 CrAccepted-AOC DONGFANG BUILDING 5TH FLOOR SUITE 607 608 PLOT AH 5 ACTION AREA 1A NEW TOWN NORTH 24 PARGANAS WEST BENGAL 700156 | 24 PARAGANAS NORTH | WEST BENGAL | 700156 | ₹2.7 Cr | L1 | Accepted-AOC ACCEPTED |
| 2 | L2₹3.1 Cr+₹40.9 L (15.3%)Rejected-Finance 4 4 FAIRLIE PLACE ROOM NO 630A HMP HOUSE KOLKATA 700001 700001 CALCUTTA CENTRAL DIVISION WEST BENGAL 700001 | KOLKATA | WEST BENGAL | 700001 | ₹3.1 Cr+₹40.9 L (15.3%) | L2 | Rejected-Finance Higher Rate |
| 3 | L3₹3.0 Cr+₹28.9 L (10.8%)Rejected-Finance 46 S P MUKHERJEE ROAD KOLKATA 700026 | KOLKATA | KOLKATA | WEST BENGAL | 700026 | ₹3.0 Cr+₹28.9 L (10.8%) | L3 | Rejected-Finance Highest Rate |
Tender Value
Refer Docs
EMD Value
₹5.7 L
Closing Date
2 Oct 2019, 2:00 pmClosed
Superintending Engineer, H.E.C., P.W.D.
KIT Annex Building, 5th FLOOR, KOLKATA 700073
SITC of Silent DG sets of different capacities with AMF panel including exhaust pipe line and necessary EI work against different important building within the premises of IPGMER,SSKM Hospital, Kol, El work Supply Delivery of 1010 KVA,750K DG set
2019_WBPWD_242213_1
WBPWD/SEHEC/SK/NIQ64/18-19/3rd
Open Tender
ELECTRICAL WORKS ORG
Item Rate
90 days
IPGMER, SSKM Hospital
Please refer Tender documents.
4 documents required · 4 mandatory
₹5.7 L
KIT Annex Building, 5th FLOOR, KOLKATA 700073
29 Jan 2021
4 Sept 2019
16 Oct 2019
5 Sept 2019
2 Oct 2019
18 Sept 2019
13 Sept 2019
Amount
Supply , delivery at site on foundation , commissioning of 1010 KVA, 415V, 50Hz, 3Ø silent new DG Set, comprising of Engine, alternator, separate AMF panel, Base frame, Fuel tank, Battery, CPCB-II approved Engine & Acoustic Enclosure having following specifications :-
Engine:-
Make : CUMMINS/Caterpillar /Parkins/MTU/Volvo Penta
Engine Type : 4 Stroke Diesel Engine
Rated Output : 1180 BHP or Higher
Duty : PRIME
Cooling : Water cooled with radiator
Cylinder : 12/16
Aspiration : Turbo Charged
Type of Governor : Electronic
Fuel Tank Capacity : Minimum capacity 990 Ltrs.
Fuel Consumption at 75% rated Load with Radiator or Fan : 165 Ltr./ Hr. or Less
Fuel Consumption at 100% rated Load with Radiator or Fan : 216 Ltr./ Hr. or Less
Overload Capacity : 10% overload for one hour for every 12 hours continuous running at full load or better
Engine instrument Panel : Consisting of starting switch with Key, Lube Oil Indicator, water temperature Indicator, RPM indicator and hour meter.
Safety Controls : Emergency Stop, Low Lube Oil Pressure warning/ Shutdown, High Engine Water Temp. warning/ Shutdown, Sensor failure Indicator, Engine over speed indicator, Battery charging and low battery indicator
Exhaust Silencer : Residential Type
Starting system : 12V./ 24 V. starting system complete with starter motor, charging alternator with rectifier and Cutout as per manufacturer standard.
Battery : Lead Acid, Low Maintenance or SMF and conforming to relevant IS Specification with Low/High Battery Voltage and Weak Battery warning
Alternator
Make : Stamford/ Leroy Somer
Rating : 415 V., 3Ph. 50 Hz., 1010 KVA, 1500 rpm
Type : Brushless, self excited and self regulated
Insulation : Class H
Protection : screen-protected drip proof with Min.IP-23 degree of protection
Voltage Regulation (max) : ±1%
Winding connection : Star with Neutral
Total Distortion factor : Less than 3%
Total Harmonic distortion in output waveform : < 5%
AMF Panel
Cubical type floor mounted AMF panel made from 14 SWG Sheet Steel, duly pretreated, powder coated painted and aesthetically finished, suitable for controlling of 1010 KVA DG set having following specification/features.
i) 415V, 1600 A , 65KA, EDO type ACB with O/L, S/C, E/F protection and microprocessor based protection release , U/V release etc. [make: ABB, Legrand, Schneider] - 2Sets
ii) In Built By-Pass switch for rated capacity
iii) On -delay timer for load change over
iv) On-delay timer for engine shut off
v) Engine On-Off switch (Push button type)
vii) Minimum five number indicating lamps to indicate 'mains ON', 'load on mains', Set running', 'load on set' and 'battery charger on'.
viii) Audio visual alarm for 'Low lubricating oil pressure', 'High water temperature, Start failure', and DG over load'.
x) Microprocessor based relay with composite meter for digital display of following.
Generator voltage/AC Mains voltage.
Generator Current in all phases
Frequency
Power Factor
Energy
Indication for alternator supply
Running time indications number of hours of operation and service intervals, service due indications
The AMF panel must be designed to ensure trouble free performance and ensure switching over Electrical Load to DG within 15 (fifteen) second from the instant of mains failure.
Acoustic Enclosure
The DG set should have integrated acoustic enclosure at the manufacturing state itself. High quality acoustic enclosure must be certified as per CPCB-II norms.
Base Frame
Common iron channel fabricated base frame containing the engine and alternator, mounted on AVM pads and having provision for lifting Hook.
Supply , delivery at site on foundation , commissioning of 750 KVA, 415V, 50Hz, 3Ø silent new DG Set, comprising of Engine, alternator, separate AMF panel, Base frame, Fuel tank, Battery, CPCB-II approved Engine & Acoustic Enclosure having following specifications :-
Engine:-
Make : CUMMINS/Caterpillar/Volvo Penta/Perkins/MTU
Engine Type : 4 Stroke Diesel Engine
Rated Output : 891 BHP or Higher
Duty : PRIME
Cooling : Water cooled with radiator
Cylinder : 6
Aspiration : Turbo Charged
Type of Governor : Electronic
Fuel Tank Capacity : Minimum capacity 990 Ltrs.
Fuel Consumption at 75% rated Load with Radiator or Fan : 132.4 Ltr./ Hr. or Less
Fuel Consumption at 100% rated Load with Radiator or Fan : 170 Ltr./ Hr. or Less
Overload Capacity : 10% overload for one hour for every 12 hours continuous running at full load or better
Engine instrument Panel : Consisting of starting switch with Key, Lube Oil Indicator, water temperature Indicator, RPM indicator and hour meter.
Safety Controls : Emergency Stop, Low Lube Oil Pressure warning/ Shutdown, High Engine Water Temp. warning/ Shutdown, Sensor failure Indicator, Engine over speed indicator, Battery charging and low battery indicator
Exhaust Silencer : Residential Type
Starting system : 12V./ 24 V. starting system complete with starter motor, charging alternator with rectifier and Cutout as per manufacturer standard.
Battery : Lead Acid, Low Maintenance or SMF and conforming to relevant IS Specification with Low/High Battery Voltage and Weak Battery warning
Alternator
Make : Stamford/ Leroy Somer
Rating : 415 V., 3Ph. 50 Hz., 750 KVA, 1500 rpm
Type : Brushless, self excited and self regulated
Insulation : Class H
Protection : screen-protected drip proof with Min.IP-23 degree of protection
Voltage Regulation (max) : ±1%
Winding connection : Star with Neutral
Total Distortion factor : Less than 3%
Total Harmonic distortion in output waveform : < 5%
AMF Panel
Cubical type floor mounted AMF panel made from 14 SWG Sheet Steel, duly pretreated, powder coated painted and aesthetically finished, suitable for controlling of 400 KVA DG set having following specification/features.
i) 415V, 1250 A, 50KA, EDO type ACB with O/L, S/C, E/F protection and microprocessor based protection release , U/V release etc. [make: ABB, Legrand, Schneider] - 2Sets
ii) In Built By-Pass switch for rated capacity
iii) On -delay timer for load change over
iv) On-delay timer for engine shut off
v) Engine On-Off switch (Push button type)
vii) Minimum five number indicating lamps to indicate 'mains ON', 'load on mains', Set running', 'load on set' and 'battery charger on'.
viii) Audio visual alarm for 'Low lubricating oil pressure', 'High water temperature, Start failure', and DG over load'.
x) Microprocessor based relay with composite meter for digital display of following.
Generator voltage/AC Mains voltage.
Generator Current in all phases
Frequency
Power Factor
Energy
Indication for alternator supply
Running time indications number of hours of operation and service intervals, service due indications
The AMF panel must be designed to ensure trouble free performance and ensure switching over Electrical Load to DG within 15 (fifteen) second from the instant of mains failure.
Acoustic Enclosure
The DG set should have integrated acoustic enclosure at the manufacturing state itself. High quality acoustic enclosure must be certified as per CPCB-II norms.
Base Frame
Common iron channel fabricated base frame containing the engine and alternator, mounted on AVM pads and having provision for lifting Hook.
Terms & Conditions
(i) Rate should be quoted inclusive of all applicable taxes and Duty etc.
(ii) All materials, equipments & accessories must conform to relevant IS specifications. The DG Set to be supplied must be from the authorized OEM of the respective Engine Manufacturer.
(iii) Necessary manufacturer's test certificate for Diesel Engine, Alternator etc. Will have to submit in triplicate copy during delivery of the equipment.
(iv) Copy of "Type Approval Certificate" and Certificate of "COP" must be produced at the time of delivery issued from competent Authority (As per CPCB-II).
(v) Circuit Diagram for AMF Panel must be submitted from the Manufacturer/OEM.
(vi) The entire set must be warranted at least 15 months from the date of Delivery/12 months/ 5000 Hrs from the date of Commissioning whichever is earlier. However Engine & Alternator should be warranted of 2 years/5000 Hrs, whichever is earlier.
Defect Liability period 1 (One) Year
(Rates should be Quoted inclusive of all taxes & duities and L.W.C. @ 1% as applicable)
Sohum Industrial Sales Corporation
C. CHOWDHURY AND CO
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .