Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹37.3 LAccepted-AOC | L-1 | Accepted-AOC L-1 | |
| 2 | L-2₹41.1 L+₹2.7 L (6.99%)Rejected-AOC | L-2 | Rejected-AOC L-2 | |
| 3 | Rejected-Technical | - | Rejected-Technical Not enlisted in Cat a(i) | |
| 4 | Rejected-Technical H NO 206 RAJAPUR DUJANIA MOHALLA DASNA DEHAT VILLAGE TOWN INDERGARHI CITY GHAZIABAD GHAZIABAD UTTAR PRADESH 201002 INDIA | GHAZIABAD | UTTAR PRADESH | 201002 | - | Rejected-Technical Not enlisted in Cat a(i) |
Tender Value
Refer Docs
EMD Value
₹54,000
Closing Date
8 Feb 2022, 6:00 pmClosed
GE I RND Delhi
MILITARY ENGINEER SERVICES, GARRISON ENGINEER I RND, LUCKNOW ROAD, TIMARPUR, DELHI-110054
REPLACEMENT OF OLD RUSTED UNSERVICEABLE SECURITY LAMP POLE AND HPSV LIGHT FITTINGS ALONGWITH CONNECTED WORK AT JCB BUILDING METCALFE HOUSE ANNEXE UNDER GE (I) RND DELHI
2021_MES_494444_1
GE/RnD-84/DLI/2021-2022
Open Tender
Civil Works
Item Rate
180 days
Delhi
Class D, Cat b(i)
2 documents required · 2 mandatory
₹500
GE I RND Delhi
₹54,000
Yes
28 Feb 2022
13 Dec 2021
10 Feb 2022
13 Dec 2021
8 Feb 2022
27 Jan 2022
Amount
Dismantling of steel tubular poles /struts, any size and deep aside for schedule of credit not exceeding 50 Mtr complete all as specified and directed.
Supply and erection of Steel tubular swaged poles with cast iron base plate, finial taper plug, bolts nuts & screws as specified type 410 SP-31 09 Mtr long. Poles shall be coated with two coats of black bituminous paint throughout internally, and externally up to the planting depth. The remaining portion of the exterior shall be painted with one coat of red oxide primer and two coat of epoxy coated aluminium paint complete all as specified and directed. Note:- Excavation, earth work, PCC in foundation & coping shall be measured and paid seperately under respective items.
Supply and erection of Steel tubular swaged poles double swan necked complete with cast iron base plate, finial taper plug, bolts nuts & screws as specified type 410 SP-31 09 Mtr long. Poles shall be coated with two coats of black bituminous paint throughout internally, and externally up to the planting depth. The remaining portion of the exterior shall be painted with one coat of red oxide primer and two coat of epoxy coated aluminium paint complete all as specified and directed. Note:- Excavation, earth work, PCC in foundation & coping shall be measured and paid seperately under respective items.
S&F LED street light 90 watt made up of pressure die cast housing with toughned glass and individual high power LEDs with secondary optics, IP66 protection and impact resistance of IK07 with all accessories complete all as specified & directed.
Supply, laying and testing cable XLPE insulated, screened PVC bedded, galvanised steel strip or wire armoured electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50 Sqmm 3.5 Core complete all as specified and directed.
Supply, laying and testing cable XLPE insulated, screened PVC bedded, galvanised steel strip or wire armoured electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 Sqmm 4 Core complete all as specified and directed.
Supply, laying and testing cable XLPE insulated, screened PVC bedded, galvanised steel strip or wire armoured electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 Sqmm 4 Core complete all as specified and directed.
Material and Labour for earthing complete with Steel earth plate electrode 600mmx600mmx6mm thick burried in ground vertically to a depth not less than 2.25meters below ground level with top edge of the earth plate at a depth not less than 1.5 meter below the ground level, earth plate surrounded 15cm thick layers of common salt and charcoal dust starting from ground below 15 cm of earth plate and up to 15 cm above the same. GI plate connected with galvanised iron strip of 25x4 mm by means of Copper nuts, bolts and washers. Strip shall be laid in 40mm dia light grade GI pipe as protection from top of the plate up to test point (cost of protection pipe up to 7.5 meters from earth electrode will be included in the rates quoted by the contractor) with following complete all as specified and shown in electrical plate No 3 of SSR Part-I & testing on completion :- (a) GI strip of size 25mm x 4mm. (b) Watering pipe GI light grade 20mm dia from top of the earth electrode up to MS funnel with wire mesh embeded in floor of PCC earth pit. (GI Funnel should properly be tightened on GI watering pipe and embeded in PCC earth pit with open top suitable for watering of earth pits) (c) Excavation & earthwork in any type of soil PCC earth pit 30x30x30cm constructed in PCC 1:2:4 type B1 exposed surfaces smoothly finished with 15mm thick cement mortar 1:6 including RCC pit cover 50mm thick 1:2:4 type B1 reinforced with 8mm dia mild steel TMT bar 75mm centre to centre with 2 Nos MS handles of 12mm dia mild steel TMT bars suitable for carrying of pit cover.
Material and Labour for earthing complete with Steel earth plate electrode 600mmx600mmx6mm thick burried in ground vertically to a depth not less than 2.25meters below ground level with top edge of the earth plate at a depth not less than 1.5 meter below the ground level, earth plate surrounded 15cm thick layers of common salt and charcoal dust starting from ground below 15 cm of earth plate and up to 15 cm above the same. GI plate connected with galvanised iron earth wire 4.00 mm dia by means of Copper nuts, bolts and washers. GI wire shall be laid in 20 mm dia light grade GI pipe as protection from top of the plate up to test point (cost of protection pipe up to 7.5 meters from earth electrode will be included in the rates quoted by the contractor) with following complete all as specified and shown in electrical plate No 3 of SSR Part-I & testing on completion :- (a) GI wire of 4 mm dia. (b) Watering pipe GI light grade 20mm dia from top of the earth electrode up to MS funnel with wire mesh embeded in floor of PCC earth pit. (GI Funnel should properly tightned on GI watering pipe and embeded in PCC floor of earth pit with open top suitable for watering of earth pits) (c) Excavation & earthwork in any type of soil PCC earth pit 30x30x30cm constructed in PCC 1:2:4 type B1 exposed surfaces smoothly finished with 15mm thick cement mortar 1:6 plaster including RCC pit cover 50mm thick 1:2:4 type B1 reinforced with 8mm dia mild steel TMT bar 75mm centre to centre with 2 Nos MS handles of 12mm dia mild steel TMT bars suitable for carrying of pit cover.
M&L for Earth continuity conductor or main earthing lead fixed to wall on batten/recess/chases/buried in ground/drawn in conduit/pipe or any other indicated situation for loop earthing etc as required 25x4 mm galvanised iron strip complete all as specified and directed.
M&L for Earth continuity conductor or main earthing lead fixed to wall on batten/recess/chases/buried in ground/drawn in conduit/pipe or any other indicated situation for loop earthing etc as required 4.0mm dia galvanised iron wire complete all as specified and directed.
S&F Cable Junction outdoor type "SMC KIOSK box IP 66/67 "weather proof, of size 300x450x170 mm incl fixing of 05 Nos terminal connection 100Amp 4 Pole, and MCB 6-32Amps suitable for in and out connection of 4 core XLPE cable 16 -50 Sqmm fixed on pole including all accesories like GI clamps, 25x25mm, nut bolts, washer etc complete all as specified and directed
M&L for Glossy number plate of size 300x300 mm of acrylic sheet for street light with fixing accessories like clamp 25x25mm, nut bolts complete all as specified and directed.
M&L in replacement of GI bracket made of 40 mm dia medium grade GI pipe bend to shape approx 1.8 mtr length including mild steel flat iron clamp etc for fixing of street light complete all as specified and directed.
Excavation in trenches not exc. 1.5 mtr wide and not exc 1.5 m depth and getting out in hard/dense soil complete all as specified and directed.
All as per Srl item No. 16.00 but depth exc 1.5 m and not exc 3.00 m.
Excavation in trenches not exc. 1.5 mtr wide and not exc 1.5 m depth and getting out in soft/loose soil complete all as specified and directed.
All as per Srl item No. 18.00 but depth exc 1.5 m and not exc 3.00 m.
Returning, filling in inclduing spreading, leveling, watering and well ramming in layers not exc 25 cm in any type of soil complete all as specified and directed.
Removing surplus excavated materials to a distance not exc 50 m and depositing where directed at a level not exc 1.5 m above the starting point complete all as specified and directed.
Supply & laying dry fine sand for cushioning of underground cable laid in trenches/duct complete all as specified and directed. Note :- Punned thickness shall be measured.
M&L for sub class '' B" burnt brick flat across the cable, for protection of cable laid in trenches complete all as specified and directed.
M&L for PCC 1:2:4 type B1 (20mm graded stone aggregate) in lintels upto 1.5m clear span, cills, steps, seismic and other similar bands, plinth courses, string courses, lacing courses, parapets and railings upto 60cm in height, copings, kneelers, apex stone, bed plates, including weathering, slightly rounded or chamfered angles and throating complete all as specified & directed.
M&L for PCC 1:4:8 type D-2 using (40 mm graded stone aggregate) as in foundation, filling and mass concrete complete all as specified and as directed.
M&L for PCC 1:3:6 type C-1 using 20 mm graded stone aggregate for foundation of pole, around pole, Road Cutting and Hard surface redressing etc complete all as specified and as directed.
Supply and laying in replacement of GI pipe light grade of 40 mm dia fixed from ground to junction box fixed on pole for protection of UG cable complete all as specified and directed.
Supply and laying in replacement of GI pipe light grade 50 mm dia laid in trenches for protection of UG cable complete all as specified and directed.
Supply and laying in replacement of GI pipe light grade 100 mm dia laid in trenches for protection of UG cable complete all as specified and directed.
S&F PVC sheathed multi stranded copper conductor cable 2.5 Sqmm 3 core for connection of street light fittings inserting from top in side the pole and connecting in junction box including making Hole in Pole as per site requirement complete all as specified and directed.
M&L for point wiring for one light/fan point controlled by one switch concealed type with PVC insulated unsheathed copper conductor cable FRLSH 1.5 sqmm multi stranded two single copper conductor including suitable size PVC conduit pipe 20 mm dia medium grade with all accessories and with 1.5 sqmm PVC insulated copper conductor cable FRLSH continous earth wire, recessed mounting pressed steel GI sheet box 2 mm thick suitable for modular switch/socket of adequate size including inner and outer white cover plate of modular complete all as specified and directed for followings :-
All as per item No 31 above but for one 3 pin 6 Amps socket outlet on same board
All as per item No 31 above but 2.5 sqmm for one 3 pin 6 Amps socket outlet on independent board
M&L for power point wiring concealed type with PVC insulated unsheathed copper conductor cable FRLSH 4 sqmm multi stranded two single copper conductor including PVC conduit pipe 20 mm dia medium grade with all accessories and with 4.0 sqmm PVC insulated copper conductor cable FRLSH continuous earth wire, recessed mounting pressed steel GI sheet box 2.0 mm thick suitable for modular switch/sockets including inner and outer cover plate of adequate size complete all as specified and directed .
M&L for modular switch single pole one way 6 Amps 1 module complete all as specified and directed
M&L for modular switch single pole one way 16 Amps 1 module complete all as specified and directed
M&L for modular socket 6 A/16 amp -3/5 pin combined 2 module complete all as specified and directed.
M&L for modular socket 6 A-2/3 pin combined 2 module complete all as specified and directed.
S&F for ceiling rose, surface bakelite 65x50mm three terminals complete all as specified and directed
S&F for fan step regulator, 120W, 2 Module complete all as specified and directed
S&F for 42W LED recess mounted bakalite panel 2 x 2 luminaire suitable for surface/grid ceiling for low ceiling applications complete with tube, driver and connecting cable including making electric connection to ceiling rose or connector complete all as specified and directed.
S&F for Surface and wall mounted LED batten, extruded aluminium housing provided for efficient heat dissipation with polycarbonate diffuser & integrated electronic driver.trica batten 230 volt, 50 Hz, 22 watt and twin core 1.5 sqmm flexible copper cable for connecting to ceiling rose complete all as specified and directed.
S&F MCB distribution board double door vertical type made out of CRCA mild steel sheet surface with insulated material like polyester or with epoxy powder coating, TPN 8 way. 415 volts with bus bar rating 200 Amps, dust and vermin proof and IP 43 - IK 09 protection suitable for incorporation of MCCB, including grouting in the wall, cutting & chasing etc complete all as specified and directed.
S&F sheet metal enclosure, SPN type with two pin & earth plug and socket Industrial type DB with and including one MCB SP, C Curve type of capacity 25 Amp, 10 KA complete all as specified and directed.
S&F amp rating 240V, 10KA 'C' curve miniature circuit breaker (MCB) of 6 - 32 Amps SP and current carrying capacity in the MCB DB with connection testing and commissioning complete all as specified and directed
S&F MCCB 3 Pole, 415 V, fixed type, 25 to 100 Amps with breaking capacity 16 KA complete all as specified and directed
M&L for sub main wiring with four run of single core PVC insulated FRLSH multistranded copper conductor cable of size 16 Sq mm and two run of 16 Sq mm PVC insulated FRLSH copper conductor cable as earth continuity conductor drawn in and including rigid PVC conduit concealed medium grade 40 mm dia of conduct complete all as specified and directed. Note:- 6 run of 16 sqmm cable and one run of PVC conduit shall be measured as one unit
M&L for sub main wiring with two run of single core PVC insulated FRLSH multistranded copper conductor cable of size 4 Sq mm and one run of 4 Sq mm PVC insulated FRLSH copper conductor cable as earth continuity conductor drawn in and including PVC rigid conduit concealed medium grade 25mm dia of condut complete all as specified and directed. Note:- 3 run of 4 sqmm cable and one run of PVC conduit shall be measured as one unit.
S&F PVC trunking of size 50 x 105 with body and cover 01 - compartment complete all as specified and directed
S&F telephone socket RJ-11 01 Module with shutter complete all as specified and directed
S&F Information socket category 5e-UTP 01 Module with shutter complete all as specified and directed.
S&F detectors Complying with and type certified to EN - 45 Addressable type multisensor detector with heat and smoke combination complete all as specified and directed
Supply and laying of twisted 2 core 1.5 Sqmm shielded PVC insulated FPLP cable for fire alarms control cable ISI Marked unsheathed multistranded cable copper conductor including make connection with existing Fire Alarm panel complete all as specified and directed
S&F of 20mm dia MS conduit concealed/Surface in wall/Ceiling/above false ceiling and all fixing accessories/ materials including taking down old MS conduit complete all as specified and directed
S&F Remote response indicators complete all as specified and directed
S&F Response indicator unit complete complete all as specified and directed
Taking down/dismantling of split type AC 2.0 TR (Indoor and out door unit) from existing location and keep in safe custody at site and refixing and install and testing the same including additional Gas charging and copper tubeing (5/8" and 1/4") upto 7.0 Mtr complete all as specified and directed
S&F ceiling fan in replacement complete with blades, down rods, electronic regulator and accessories, 230 V, 1400 mm sweep. Min air delivery 210 CFM with service value 6.00 BEE. Five star rated with brushless direct current motor (BLDC) complete all as specified and directed
Excavation over area, n exc 1.50 mtr deep and getting out in soft/loose soil complete all as specified and directed
M&L for brickwork with subclass 'B' bricks, straight or curved on plan exc. 6m mean radius built in CM 1:4 complete all as specified and directed.
M&L rendering 15mm thick in cement mortar 1:4 with using water proofing compound on brick or concrete surfaces finished even and smooth without using extra cement complete all as specified and directed. Note:- Waterproofing compound shall be measured & paid seperately.
S&F mild steel Framed work such as grills, gratings, etc., with ends of bars shouldered and/or riveted, or forged into spikes; framed guard bars; barred iron doors; ladders; framed balusters; walk ways; railings; framework of water tanks and similar work conforming to Fe 410-0 or Fe 310-0 complete all as specified and directed
M&L for providing and fixing factory made precast RCC perforated drain covers, having concrete of strength not less than M-25, of size 1100 x 450x50 mm, reinforced with 8 mm dia four nos longitudinal & 9 nos cross sectional TMT bars, including providing 50 mm dia perforations @ 100 to 125 mm c/c, including providing edge binding with M.S. flats of size 50 mm x 1.6 mm complete all as specified and directed
Dismantling interlocking tiles (of any thickness) and shape and including 40 mm thick compacted sand cushioning complete all as specified and directed.
M&L for precast concrete coloured designer interlocking paver block any shape and size confirming to IS-15658 - 2006 of 60mm thickness M-40 grade with grey cement and pigment laid over 40 mm thick sand cushioning complete all as specified and directed.
Demolition of cement concrete of any description and in any position not otherwise specifically provided including removing the demolished material out side MoD land in low lying area complete all as specified and directed.
S&F factory made kerb stone of M-25 grade cement concrete in position to the required line, level and curvature, jointed with cement mortar 1:3 (1 cement: 3 coarse sand), including making joints with or without grooves (thickness of joints except at sharp curve shall not to more than 5mm), including making drainage opening wherever required complete etc. as per direction of Engineer-in-charge (length of finished kerb edging shall be measured for payment). Note:- kerb stone shall be approved by Engineer-in-charge before procurement in bulk.
M&L for applying two coat of synthetic enamel paint over new plastered/concrete surfaces including preparation of new surface of any description over 10cm width or girth over a coat of priming paint complete all as specified and directed.
S&F PVC(SWR) 110mm dia soil waste and rainwater drainage pipes single socketed in any length with rubber ring joint fixed to wall complete all as specified and directed.
M&L for sand filling under floors or in foundations including watering & compaction complete all as specified and directed.
Supply only integral water proofing compound complete all as specified and directed.
M&L for preparation of new or previously untreated steel surface and applying two coats of synthetic enamel paint over a coat of red oxide/zinc chrome primer complete all as specified and directed.
Surjit and Sons
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .