Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹35.8 LAccepted-AOC 70 SUBHASH ROAD HARJINDER NAGAR KANPUR 208007 | KANPUR | KANPUR | UTTAR PRADESH | 208007 | L1 | Accepted-AOC LOWEST | |
| 2 | L2₹36.8 L+₹52,260.80 (1.44%)Rejected-Finance 441 G F LIG FLATS PH 2 SEC 14 PKT 3 DWARKA NEW DELHI SECTOR 14 DWARKA DWARKA SOUTH WEST DELHI DELHI 110078 | SOUTH WEST DELHI | DELHI | 110078 | L2 | Rejected-Finance OTHER THAN LOWEST | |
| 3 | L3₹36.9 L+₹64,006.20 (1.77%)Rejected-Finance 41 SAKOORPUR ROAD NEAR PRIMARY SCHOOL NEW JANKIPURAM NEELMATHA LUCKNOW CANTONMENT PO DILKUSHA LUCKNOW UP PIN 226002 | LUCKNOW | LUCKNOW | UTTAR PRADESH | 226002 | L3 | Rejected-Finance OTHER THAN LOWEST | |
| 4 | L4₹37.8 L+₹1.6 L (4.41%)Rejected-Finance | L4 | Rejected-Finance OTHER THAN LOWEST | |
| 5 | L5₹38.9 L+₹2.7 L (7.34%)Rejected-Finance MD 1 236 SECTOR D1 LDA COLONY KANPUR ROAD LUCKNOW U P PIN 226012 | LUCKNOW | UTTAR PRADESH | 226012 | L5 | Rejected-Finance OTHER THAN LOWEST |
| Sl No | Description | Qty | Unit | M/S Reliance Construction L10 | OMVIN ENTERPRISES LLP L2 | M/S BHAGIRATHI ENTERPRISES L3 | VIDYA TRADERS L4 | M I & CO. L12 | R K CONTRACTOR AND SUPPLIERS L5 | OM NAMAH SHIVAY ENTERPRISES L11 | Joy Dey Enterprises L7 | suniltraders L8 | m/s raghubar dayal L9 | M/S Husna Electrical Works L6 | M/S SHIVA CONSTRUCTION L1 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Supply & fix IN replacement of sheet metal enclosure indoor type of size 1.2 x 1.5 x 0.25 mtr suitable to fix on wall/floor made out of 2mm thick CRCA sheet having independent compartments suitable for single phase energy meters (compatible with smart meter size space) and MCB provided with front hinged shutters with lockable arrangements and clear glass to visualize the meter reading without opening the compartment with sufficient working space in compartment pre wired with single core PVC insulated and sheathed FRLS stranded copper conductor wire of suitable size from bus bar to meter compartment 07 Nos duly crimped with copper thimbles, duly powder coated complete incl taking down old meter panel all as specified and directed by Engr-in-charge and consisting with the following :-
(a) Aluminium Bus bar for 3 phase 4 wire system of 4 x 200 Amps rated insulated Al strip mounted on resin cast insulators in independent compartment having front openable shutter - One set.
(b) incoming MCCB, four pole, 415 volts, 100-125 Amps, 25 KA with adjustable Overload setting Ir = (0.8 to 1.0)xIn - One No.
(c) outgoing MCB SPN, 40 Amp,10 KA C-Curve - 07 Nos.
(d) Multifuction meter(0-500) Volts with inbuilt selector - One set.
(e) Indicator Lamps LED in Red in Red/ Yellow/ Blue colour - One Set of Three.
Note:- (I) Before manufacuring of eletric meter panel drawing should be passed through Engineer-in- Charge(II) charges for old meter taking down carefully from old panel refixing done in new panel is included in qouated rate | 15 | Each | 50,000 ₹7,50,000 | 57,000 ₹8,55,000 | 24,500 ₹3,67,500 Lowest | 25,000 ₹3,75,000 | 56,000 ₹8,40,000 | 70,000 ₹10,50,000 | 63,000 ₹9,45,000 | 44,000 ₹6,60,000 | 38,000 ₹5,70,000 | 50,000 ₹7,50,000 | 60,000 ₹9,00,000 | 28,900 ₹4,33,500 |
| 2.00 | Supply & fix in replacement of sheet metal enclosure indoor type of size 1 x 1 x 0.25 mtr suitable to fix on wall/floor made out of 2mm thick CRCA sheet having independent compartments suitable for single phase energy meters (compatible with smart meter size space ) and MCB provided with front hinged shutters with lockable arrangements and clear glass to visualize the meter reading without opening the compartment with sufficient working space in compartment pre wired with single core PVC insulated and sheathed FRLS stranded copper conductor wire of suitable size from bus bar to meter compartment 05 Nos duly crimped with copper thimbles, duly powder coated complete incl taking down old meter panel all as specified and directed by Engr-in-charge and consisting with the following :-
(a) Aluminium Bus bar for 3 phase 4 wire system of 4 x 200 Amps rated insulated Al strip mounted on resin cast insulators in independent compartment having front openable shutter - One set.
(b) incoming MCCB, four pole, 415 volts, 63-100 Amps, 25 KA with adjustable Overload setting Ir = (0.8 to 1.0)xIn - One No.
(c) outgoing MCB SPN, 40 Amp,10 KA C-Curve - 05 Nos.
(d) Multifuction meter(0-500) Volts with inbuilt selector - One set.
(e) Indicator Lamps LED in Red in Red/ Yellow/ Blue colour - One Set of Three.
Note:- (I) Before manufacuring of eletric meter panel drawing should be passed through Engineer-in- Charge(II) charges for old meter taking down carefully from old panel and refixing done in new panel is included in qouated rate | 10 | Each | 35,000 ₹3,50,000 | 45,000 ₹4,50,000 | 22,500 ₹2,25,000 | 20,000 ₹2,00,000 Lowest | 55,000 ₹5,50,000 | 50,000 ₹5,00,000 | 41,178 ₹4,11,780 | 41,500 ₹4,15,000 | 34,000 ₹3,40,000 | 38,000 ₹3,80,000 | 45,000 ₹4,50,000 | 24,300 ₹2,43,000 |
| 3.00 | Supply & fix in replacement of sheet metal enclosure indoor type of size 1.5 x 1.1 x 0.25 mtr suitable to fix on wall/floor made out of 2mm thick CRCA sheet having independent compartments suitable for three phase smart energy meters (compatible with smart meter) and MCB provided with front hinged shutters with lockable arrangements and clear glass to visualize the meter reading without opening the compartment with sufficient working space in compartment pre wired with single core PVC insulated and sheathed FRLS stranded copper conductor wire of suitable size from bus bar to meter compartment 05 Nos duly crimped with copper thimbles, duly powder coated complete incl taking down old meter panel all as specified and directed by Engr-in-charge and consisting with the following :-
(a) aluminium Bus bar for 3 phase 4 wire system of 4 x 200 Amps rated insulated copper strip mounted on resin cast insulators in independent compartment having front openable shutter - One set.
(b) incoming MCCB, four pole, 415 volts, 125 Amps, 25 KA with adjustable Overload setting Ir = (0.8 to 1.0)xIn - One No.
(c) outgoing MCB TPN, 63 Amp,10 KA C-Curve - 05 Nos.
(d) Multifuction meter(0-500) Volts with inbuilt selector - One set.
(e) Indicator Lamps LED in Red in Red/ Yellow/ Blue colour - One Set of Three.
Note:- Before manufacuring of eletric meter panel drawing should be passed through Engineer-in- Charge | 6 | Each | 40,000 ₹2,40,000 | 56,000 ₹3,36,000 | 23,500 ₹1,41,000 Lowest | 33,500 ₹2,01,000 | 64,000 ₹3,84,000 | 70,000 ₹4,20,000 | 64,100 ₹3,84,600 | 42,000 ₹2,52,000 | 30,000 ₹1,80,000 | 48,000 ₹2,88,000 | 45,000 ₹2,70,000 | 28,000 ₹1,68,000 |
| 4.00 | Taking down carefully sub-main wiring any type including dismantling of accessories and making good disturbed surfaces to match the existing complete all as specified and directed | 3,800 | RM | 10 ₹38,000 | 2 ₹7,600 | 5 ₹19,000 | 10 ₹38,000 | 10 ₹38,000 | 5 ₹19,000 | 1 ₹3,800 Lowest | 5 ₹19,000 | 10 ₹38,000 | 10 ₹38,000 | 19 ₹72,200 | 2 ₹7,600 |
| 5.00 | M&L for sub-main wiring along with earth continuity conductor, using PVC insulated FRLS, multi-stranded copper conductor cables, colour-coded, drawn into and including concealed rigid non-metallic PVC conduit, medium grade, ISI marked, ivory colour, complete with all conduit accessories such as bends, tees, junction boxes, inspection boxes, saddles/clamps etc including cutting chases, making good disturbed surfaces to match existing finish complete in all respects of the following nominal sizes:–
(a) 2x4 sqmm + 1x4 sqmm earth wire in 20 mm dia conduit. | 550 | RM | 150 ₹82,500 | 120 ₹66,000 | 230 ₹1,26,500 | 185 ₹1,01,750 | 90 ₹49,500 Lowest | 135 ₹74,250 | 199 ₹1,09,450 | 250 ₹1,37,500 | 140 ₹77,000 | 100 ₹55,000 | 300 ₹1,65,000 | 220 ₹1,21,000 |
| 6.00 | All as item No 05 but size 2x6 sqmm + 1x6 sqmm earth wire in 25 mm dia conduit complete all as specified and directed | 2,150 | RM | 200 ₹4,30,000 | 165 ₹3,54,750 | 320 ₹6,88,000 | 240 ₹5,16,000 | 100 ₹2,15,000 Lowest | 130 ₹2,79,500 | 280 ₹6,02,000 | 350 ₹7,52,500 | 180 ₹3,87,000 | 130 ₹2,79,500 | 300 ₹6,45,000 | 320 ₹6,88,000 |
| 7.00 | All as item No 05 but size 2x10 sqmm + 1x10 sqmm earth wire in 25 mm dia conduit complete all as specified and directed | 450 | RM | 300 ₹1,35,000 | 300 ₹1,35,000 | 480 ₹2,16,000 | 340 ₹1,53,000 | 120 ₹54,000 | 300 ₹1,35,000 | 425 ₹1,91,250 | 55 ₹24,750 Lowest | 380 ₹1,71,000 | 240 ₹1,08,000 | 500 ₹2,25,000 | 425 ₹1,91,250 |
| 8.00 | S&F sub main wiring with two single core PVC FRLS insulated multistranded copper conductor of size 4 sqmm nominal cross sectional area and one run of 4.0 sqmm nominal cross sectional area PVC FRLS insulated multistranded copper conductor green colour as continuous earth wire drawn in and including not less than 20mm dia 'medium grade' PVC existing conduits (ISI marked) and fittings complete all as specified and directed.
NOTE:- One unit length shall measured as two run of main wire and one run of conduit & earth wire. | 650 | RM | 125 ₹81,250 | 120 ₹78,000 Lowest | 200 ₹1,30,000 | 120 ₹78,000 Lowest | 700 ₹4,55,000 | 200 ₹1,30,000 | 175 ₹1,13,750 | 250 ₹1,62,500 | 140 ₹91,000 | 120 ₹78,000 Lowest | 200 ₹1,30,000 | 195 ₹1,26,750 |
| 9.00 | Supply and fixing in replacement for 1.5 sqmm single core copper,multistandard PVC insulated (FRLS) unsheathed, cable 1100 volts grade complete all as specified and directed | 650 | RM | 30 ₹19,500 | 18 ₹11,700 | 35 ₹22,750 | 35 ₹22,750 | 50 ₹32,500 | 30 ₹19,500 | 17 ₹11,050 Lowest | 26 ₹16,900 | 165 ₹1,07,250 | 45 ₹29,250 | 70 ₹45,500 | 40 ₹26,000 |
| 10.00 | Supply and fixing in replacement for 2.5 sqmm single core copper,multistandard PVC insulated (FRLS) unsheathed, cable 1100 volts grade complete all as specified and directed | 550 | RM | 40 ₹22,000 | 25 ₹13,750 | 40 ₹22,000 | 38 ₹20,900 | 60 ₹33,000 | 60 ₹33,000 | 23 ₹12,650 Lowest | 45 ₹24,750 | 28 ₹15,400 | 65 ₹35,750 | 90 ₹49,500 | 60 ₹33,000 |
Tender Value
₹49 L
EMD Value
₹98,000
Closing Date
30 Jun 2026, 6:00 pmClosed
GE (WEST) LUCKNOW
GE (WEST) LUCKNOW PIN 226002 C/O 56 APO
REPAIR/ MAINT TO ELECT METER PANEL BOARD VTPN DBs MCCB EARTHING INCLUDING ALLIED WORKS IN ZONE A B AND C AREA UNDER GE (WEST) LUCKNOW
2026_MES_770944_1
GE/W/LKO/T-40 OF 2026-27
Open Tender
Electrical and Maintenance Works
Item Rate
240 days
LUCKNOW
AS PER NIT AND TENDER DOCUMENTS
7 documents required · 7 mandatory
₹500
GE (WEST) LUCKNOW
₹98,000
Yes
19 Aug 2026
9 Jun 2026
2 Jul 2026
9 Jun 2026
30 Jun 2026
23 Jun 2026
9 Jun 2026 - 16 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply & fix IN replacement of sheet metal enclosure indoor type of size 1.2 x 1.5 x 0.25 mtr suitable to fix on wall/floor made out of 2mm thick CRCA sheet having independent compartments suitable for single phase energy meters (compatible with smart meter size space) and MCB provided with front hinged shutters with lockable arrangements and clear glass to visualize the meter reading without opening the compartment with sufficient working space in compartment pre wired with single core PVC insulated and sheathed FRLS stranded copper conductor wire of suitable size from bus bar to meter compartment 07 Nos duly crimped with copper thimbles, duly powder coated complete incl taking down old meter panel all as specified and directed by Engr-in-charge and consisting with the following :-
(a) Aluminium Bus bar for 3 phase 4 wire system of 4 x 200 Amps rated insulated Al strip mounted on resin cast insulators in independent compartment having front openable shutter - One set.
(b) incoming MCCB, four pole, 415 volts, 100-125 Amps, 25 KA with adjustable Overload setting Ir = (0.8 to 1.0)xIn - One No.
(c) outgoing MCB SPN, 40 Amp,10 KA C-Curve - 07 Nos.
(d) Multifuction meter(0-500) Volts with inbuilt selector - One set.
(e) Indicator Lamps LED in Red in Red/ Yellow/ Blue colour - One Set of Three.
Note:- (I) Before manufacuring of eletric meter panel drawing should be passed through Engineer-in- Charge(II) charges for old meter taking down carefully from old panel refixing done in new panel is included in qouated rate | 15 | Each | - | - |
| 2 | Supply & fix in replacement of sheet metal enclosure indoor type of size 1 x 1 x 0.25 mtr suitable to fix on wall/floor made out of 2mm thick CRCA sheet having independent compartments suitable for single phase energy meters (compatible with smart meter size space ) and MCB provided with front hinged shutters with lockable arrangements and clear glass to visualize the meter reading without opening the compartment with sufficient working space in compartment pre wired with single core PVC insulated and sheathed FRLS stranded copper conductor wire of suitable size from bus bar to meter compartment 05 Nos duly crimped with copper thimbles, duly powder coated complete incl taking down old meter panel all as specified and directed by Engr-in-charge and consisting with the following :-
(a) Aluminium Bus bar for 3 phase 4 wire system of 4 x 200 Amps rated insulated Al strip mounted on resin cast insulators in independent compartment having front openable shutter - One set.
(b) incoming MCCB, four pole, 415 volts, 63-100 Amps, 25 KA with adjustable Overload setting Ir = (0.8 to 1.0)xIn - One No.
(c) outgoing MCB SPN, 40 Amp,10 KA C-Curve - 05 Nos.
(d) Multifuction meter(0-500) Volts with inbuilt selector - One set.
(e) Indicator Lamps LED in Red in Red/ Yellow/ Blue colour - One Set of Three.
Note:- (I) Before manufacuring of eletric meter panel drawing should be passed through Engineer-in- Charge(II) charges for old meter taking down carefully from old panel and refixing done in new panel is included in qouated rate | 10 | Each | - | - |
| 3 | Supply & fix in replacement of sheet metal enclosure indoor type of size 1.5 x 1.1 x 0.25 mtr suitable to fix on wall/floor made out of 2mm thick CRCA sheet having independent compartments suitable for three phase smart energy meters (compatible with smart meter) and MCB provided with front hinged shutters with lockable arrangements and clear glass to visualize the meter reading without opening the compartment with sufficient working space in compartment pre wired with single core PVC insulated and sheathed FRLS stranded copper conductor wire of suitable size from bus bar to meter compartment 05 Nos duly crimped with copper thimbles, duly powder coated complete incl taking down old meter panel all as specified and directed by Engr-in-charge and consisting with the following :-
(a) aluminium Bus bar for 3 phase 4 wire system of 4 x 200 Amps rated insulated copper strip mounted on resin cast insulators in independent compartment having front openable shutter - One set.
(b) incoming MCCB, four pole, 415 volts, 125 Amps, 25 KA with adjustable Overload setting Ir = (0.8 to 1.0)xIn - One No.
(c) outgoing MCB TPN, 63 Amp,10 KA C-Curve - 05 Nos.
(d) Multifuction meter(0-500) Volts with inbuilt selector - One set.
(e) Indicator Lamps LED in Red in Red/ Yellow/ Blue colour - One Set of Three.
Note:- Before manufacuring of eletric meter panel drawing should be passed through Engineer-in- Charge | 6 | Each | - | - |
| 4 | Taking down carefully sub-main wiring any type including dismantling of accessories and making good disturbed surfaces to match the existing complete all as specified and directed | 3,800 | RM | - | - |
| 5 | M&L for sub-main wiring along with earth continuity conductor, using PVC insulated FRLS, multi-stranded copper conductor cables, colour-coded, drawn into and including concealed rigid non-metallic PVC conduit, medium grade, ISI marked, ivory colour, complete with all conduit accessories such as bends, tees, junction boxes, inspection boxes, saddles/clamps etc including cutting chases, making good disturbed surfaces to match existing finish complete in all respects of the following nominal sizes:–
(a) 2x4 sqmm + 1x4 sqmm earth wire in 20 mm dia conduit. | 550 | RM | - | - |
| 6 | All as item No 05 but size 2x6 sqmm + 1x6 sqmm earth wire in 25 mm dia conduit complete all as specified and directed | 2,150 | RM | - | - |
| 7 | All as item No 05 but size 2x10 sqmm + 1x10 sqmm earth wire in 25 mm dia conduit complete all as specified and directed | 450 | RM | - | - |
| 8 | S&F sub main wiring with two single core PVC FRLS insulated multistranded copper conductor of size 4 sqmm nominal cross sectional area and one run of 4.0 sqmm nominal cross sectional area PVC FRLS insulated multistranded copper conductor green colour as continuous earth wire drawn in and including not less than 20mm dia 'medium grade' PVC existing conduits (ISI marked) and fittings complete all as specified and directed.
NOTE:- One unit length shall measured as two run of main wire and one run of conduit & earth wire. | 650 | RM | - | - |
| 9 | Supply and fixing in replacement for 1.5 sqmm single core copper,multistandard PVC insulated (FRLS) unsheathed, cable 1100 volts grade complete all as specified and directed | 650 | RM | - | - |
| 10 | Supply and fixing in replacement for 2.5 sqmm single core copper,multistandard PVC insulated (FRLS) unsheathed, cable 1100 volts grade complete all as specified and directed | 550 | RM | - | - |
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.39 MB
BOQ_863329.xls
BOQ • 0.36 MB
TENDER.pdf
Tender Documents • 1.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .