Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹11.7 LAccepted-AOC | L1 | Accepted-AOC Being lowest tender | |
| 2 | L2₹14.0 L+₹1.6 L (12.5%)Rejected-Finance SAI LEELA MAHAVIR COLONY BIRLA HOUSE GOLA KA MANDIR MORAR GWALIOR 474005 | GWALIOR | GWALIOR | MADHYA PRADESH | 474005 | L2 | Rejected-Finance Not being lowest tender | |
| 3 | L3₹14.7 L+₹2.2 L (18.0%)Rejected-Finance | L3 | Rejected-Finance Not being lowest tender | |
| 4 | L4₹16.0 L+₹3.6 L (28.6%)Rejected-Finance | L4 | Rejected-Finance Not being lowest tender | |
| 5 | L5₹24.4 L+₹11.9 L (95.8%)Rejected-Finance | L5 | Rejected-Finance Not being lowest tender |
Tender Value
₹25 L
EMD Value
₹50,000
Closing Date
20 Jul 2024, 6:00 pmClosed
GE (AF) ADM AREA
GE (AF) ADM AREA GWALIOR-474020
REPAIR/REPLACEMENT AND MAINT OVERHAULING OF DG SET, BATTERY CHARGER INCLUDING REPLACEMENT OF WORN OUT PARTS AND CONNECTED CONTROLLING ACCESSORIES AT AF STN GWALIOR
2024_MES_661513_1
8422/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE (AF) ADM AREA GWALIOR
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE (AF) ADM AREA
₹50,000
Yes
16 Oct 2024
22 Jun 2024
27 Jul 2024
22 Jun 2024
20 Jul 2024
6 Jul 2024
Amount
M&L for Maintenance and servicing of standby DG Set complete including draining out of diesel from tank, cleaning the tank thoroughly and refilling the drained out diesel, draining out engine oil from the sump, cleaning the sump thoroughly and refilling the sump with new engine oil to it’s required level, replacing the fuel filter, lubricating oil filter , checking & cleaning air cleaner, changing air cleaner elements, checking coolant level & make up the same, drain the fuel filter & water separator, filling the starting batteries with electrolyte/distilled water to maintain the required specific gravity, replacing the unserviceable brass connectors for batteries, cleaning of battery terminals & applying petroleum jelly to battery terminal posts & brass connectors, including M & L for V Belts, checking of exhaust leakage, governor, breathers etc, adjust/set the same for proper functioning of DG Set, checking of fuel, oil and water coolant level etc, adjusting and keeping the fan belts to the desired tension, tightening all the bolts and nuts to the required torque etc, cleaning the DG Set with accessories as prescribed by the manufacturer and test for satisfactory running of DG set for two hour at connected load and record shall be made in respect of RPM, oil pressure , oil temperature , coolant temperature, voltage , frequency , load current , battery charging , fuel consumption etc complete all as specified and directed for 10/18/20/25 KVA D G set of Make as per existing and/or available at site in any position complete all as specified and directed.
Note :- (i) Engine oil for refilling shall be measured and paid Separately (ii) Coolant for make up shall be measured & paid separately (iii) Testing will be carried out in presence of Engineer - in - charge and DHPP consumption shall be entered in PRRB. (iv) The Make of Fuel filter , Oil Filter , V belt & component will be as per manufactures recommendations ( rate of fuel filter, oil filter, air filter and V belt shall be included in quoted rate.) (v) Servicing of DG sets shall be carried out through representative of authorised agency.
Description all as per item No.1.00 here-in-before but for 30 KVA DG Set
Description all as per item No.1.00 here-in-before but for 40 KVA DG Set
Description all as per item No.1.00 here-in-before but for 50 KVA DG Set
Description all as per item No.1.00 here-in-before but for 62.5/63 KVA DG Set
Description all as per item No.1.00 here-in-before but for 100/110 KVA DG Set
Description all as per item No.1.00 here-in-before but for 125 KVA DG Set
Description all as per item No.1.00 here-in-before but for 160/180/200 KVA DG Set
Supply only multi-grade 15W40 lubricating oil for DG Sets as per manufacturer’s instructions complete all as specified and directed. Make- IOC, Castrol, Hindustan Petroleum
Supply only coolant for radiator as per manufacturer’s instructions complete all as specified and directed. Make- Castrol, Servo, Cumins
Supply & fix Hose pipe set & Clips of water / coolant cooled radiator system for following D G set:-
(a) 10/18/20/25 KVA DG set
(b) 30 KVA DG Set
(c) 40 KVA DG set
(d) 50 KVA DG set
(e) 62.5/63 KVA DG set
(g) 100/110 KVA DG set
(h) 125 KVA DG set
(j) 160/180/200 KVA DG set
Repairs & Overhauling of radiator assembly by dismantling from engine transporting to the workshop and removing the sediments and scales, corrosion etc by means of acid, cleaning and high pressure water washing and air cleaning, gas welding / soldering with good quality material for stopping the leakage etc, re-assembling the same with new gaskets and transporting to the site, fixing to the engine with hoses, clips complete to the entire satisfaction of engineer - in - charge as required for following DG Sets.
(a) 10/18/20/25 KVA DG set
(b) 30 KVA DG Set
(c) 40 KVA DG set
(d) 50 KVA DG set
(e) 62.5/63 KVA DG set
(g) 100/110 KVA DG set
(h) 125 KVA DG set
(j) 160/180/200 KVA DG set
Dismantling the water pump of the DG Set taking out the worn out parts, refixing the water pump after replacing with new water pump repair kit set for following DG set:-
(a) 10/18/20/25 KVA DG set
(b) 30 KVA DG Set
(c) 40 KVA DG set
(d) 50 KVA DG set
(e) 62.5/63 KVA DG set
(g) 100/110 KVA DG set
(h) 125 KVA DG set
(j) 160/180/200 KVA DG set
Dismantling & strip opening of self starter for 12 volt/24 volt inspecting /checking the complete parts & taking out worn/unserviceable parts and making the self starter functional after replacing the new parts complete all as specified and directed. Note: New parts replaced shall be measured and paid separatelyas supply only under Sch ‘A’/BOQ item No 8.00/9.00 below. Fixing charge of new parts is deemed to be included in quoted rate.
Supply only the following items to self starter of existing make :-
(a) Armature assembly 12 volt suitable for 180 AH
(b) Solenoid switch 12 volts
(c) Field coil 12 volts
(d) Bendex penion 12 volts complete
(e) Carbon brush
Supply only the following items to self starter of existing make :-
(a) Armature assembly 24 volt suitable for 180 AH
(b) Solenoid switch 24 volts
(c) Field coil 24 volts
(d) Bendex penion 24 volts complete
(e) Carbon brush
Supply & fix in repair Fly wheel ring by removing alternator from engine for 50 KVA to 63 KVA DG set complete all as specified and directed.
Supply & fix in repair Fly wheel ring by removing alternator from engine for 100 KVA to 125 KVA DG set complete all as specified and directed.
Supply & fix in repair Fly wheel ring by removing alternator from engine for 180/200 KVA DG set complete all as specified and directed.
Material and labour for servicing battery charging alternators assembly of DG Set by disconnecting from engine and dismantling the battery charging alternator assembly for following DG set cleaning all accessories replacing worn out parts like carbon brush, bush/bearing , jumping leads etc and varnishing complete all all as specified and directed.
(a) 10/18/20/25 KVA DG set
(b) 30 KVA DG Set
(c) 40 KVA DG set
(d) 50 KVA DG set
(e) 62.5/63 KVA DG set
(g) 100/110 KVA DG set
(h) 125 KVA DG set
(j) 160/180/200 KVA DG set
Disconnecting and dismantling the fuel injector pump assembly from its original position, overhauling & servicing by cleaning / oiling, servicing of fuel injector pump assembly, removing and replacement with and including fuel injector pump repair kit & fuel pipe including calibration and refixing the same complete all as specified and directed.
(a) 10/18/20/25 KVA DG set
(b) 30 KVA DG Set
(c) 40 KVA DG set
(d) 50 KVA DG set
(e) 62.5/63 KVA DG set
(g) 100/110 KVA DG set
(h) 125 KVA DG set
(j) 160/180/200 KVA DG set
S&F in repair RPM meter of DG set complete all as specified and directed.
S&F in repair oil pressure Gauge on DG set complete all as specified and directed.
S&F in repair oil temperature Gauge on DG set complete all as specified and directed.
S&F in repair water temperature Gauge on DG set complete all as specified and directed.
Supply & fix in repair fuel filter and Oil Filter of existing make and description for following D G sets:-
(a) 10/18/20/25 KVA DG set
(b) 30 KVA DG Set
(c) 40 KVA DG set
(d) 50 KVA DG set
(e) 62.5/63 KVA DG set
(g) 100/110 KVA DG set
(h) 125 KVA DG set
(j) 160/180/200 KVA DG set
Supply & fix in repair Air filter of existing make and description for following D G sets:-
(a) 10/18/20/25 KVA DG set
(b) 30 KVA DG Set
(c) 40 KVA DG set
(d) 50 KVA DG set
(e) 62.5/63 KVA DG set
(g) 100/110 KVA DG set
(h) 125 KVA DG set
(j) 160/180/200 KVA DG set
Supply & fix V Belt for following D G sets:-
(a) 10/18/20/25 KVA DG set
(b) 30 KVA DG Set
(c) 40 KVA DG set
(d) 50 KVA DG set
(e) 62.5/63 KVA DG set
(g) 100/110 KVA DG set
(h) 125 KVA DG set
(j) 160/180/200 KVA DG set
S&F in repairs PVC insulated stranded copper conductor cable 25 sqmm single core, of 2 Mtr length, soldered with 2 Nos gunmetal battery terminals suitable for 60-180 Ah 12 V DC battery complete all as specified and directed.
Dismantling asbestos rope from silencer of DG set and supply & fix asbestos rope (8/10mm thick) around silencers complete all as specified and directed.
M&L for preparation of old painted surface of DG Set complete (10/18/20/25 KVA DG set) with fuel tank by scrapping / removing old paint / dust etc and painting with two coats of synthetic enamel paint (colour & tint as approved) over a coat of primer including caliberatation of capacity and marking/writing as follows:- (a) Tank capacity (b) Tank cleaned on (c) Due date.
Description all as per item No.24.01 here-in-before but for 30 KVA DG Set
Description all as per item No.24.01 here-in-before but for 40 KVA DG Set
Description all as per item No.24.01 here-in-before but for 50 KVA DG Set
Description all as per item No.24.01 here-in-before but for 62.5/63 KVA DG Set
Description all as per item No.24.01 here-in-before but for 100/110 KVA DG Set
Description all as per item No.24.01 here-in-before but for 125 KVA DG Set
Description all as per item No.24.01 here-in-before but for 160/180/200 KVA DG Set
Disconnecting and taking out carefully unserviceable alternator, transformer and old pattern AVR of any make and any capacity of DG Sets , dismantling and strip opening of alternator for servicing, taking out and removing old burnt out winding and rewinding of alternator with existing gauge super enameled copper wire (Make: Finolex/Atlas / Devi Dayal) as approved by the Engineer-in-Charge with insulating material such as lumineous paper, latherized paper, cotton tape, glass sleeves insulating Varnish etc , reassembling and fixing the same in position and testing alternator assembly all as specified and directed.
Supply and fixing new parts of existing make and descripton including testing complete all as specified and directed :-
(a) AVR unit complete for 30/40 KVA DG Set
(b) AVR unit complete for 62.5/63 KVA DG Set
(c) AVR unit complete for 110 KVA DG Set
(d) AVR unit complete for 200 KVA DG Set
(e) Terminal plate
(f) Silicon Rectifier assembly with metallic plate as existing covered with thin layer of selnium and insulted nut bolt , control wiring soldering complete suitable for 10 KVA to 200 KVA DG Set
(g) Field excitation unit three phase 415 V complete suitable for 10 KVA to 200 KVA DG Set
(h) Flexible rubber coupling star type capacity alternator complete suitable for 10 KVA to 200 KVA DG Set
(j) Carbon brushes set of four complete suitable for 10 KVA to 200 KVA DG Set
(k) Slip rings for complete suitable for 10 KVA to 200 KVA DG Set (Four rings)
M&L for repair to self starter by taking out defective parts and supplying and fixing new parts such as armature, field coils, carbon bush, pinion, shocker arm, bearing including testing suitable for 50/62.5/63/100/110/125/160/ 180/200 KVA DG set complete all as specified and directed by Engineer-in-Charge
S&F in repair flexible fuel pipe of 5 Mtr length including end banjo nut, bolts etc complete all as specified and directed.
S&F in repair ignition switch push button of all type as specified and directed
Material and labour for reconditioning 12 V 180 AH, 25 plates Batteries including replacingt with new parts such as –ve & +ve plates, PVC separators, terminal post, Acid and distilled water etc making in serviceable conditions complete all as specified and directed.
Description all as per Item No. 20.00 here-in-before but 12 Volts 150/100 AH, 17 Plate battery.
S & F in repalcement brass terminal for batteries complete all as specified and directed.
Maintrenance & Servicing of AMF panel of any description and in any position, of 30 KVA to 63 KVA capacity DG set by opening of AMF Panel, checking AC/DC circuits, Tightning of all Power / control wiring connection and replacement of unserviceable control wiring with 1.5 Sqmm, single core, copper conductor, flexible, PVC insulated, unsheathed cable suitable upto 1100 volts confirming to IS-694, taking out, removing and replacement of unserviceable parts / spares / items, reassembling the panel & fixing the same in position and testing the AMF panel on full load after completion of repairs complete all as specified and directed. Note : (i) The quoted rate deemed to include for fixing the serviceable parts in position and replacement of unserviceable parts with new parts. The new replaced parts shall be measured and paid for separately under appropriate item of Sch `A’ as `supply only ‘ but quoted rates are inclusive of replacement of small/minor parts such as nuts, bolts, washers/lugs/gaskets etc.
(a) Description all as per item No. 33.01 here-in-before but AMF panel of 100 KVA to 125 KVA capacity
(b) Description all as per item No. 33.01 here-in-before but AMF panel of 200 KVA capacity
Supply only the following spare parts components of AMF Panels repaired under sch 'A'/BOQ item No 33.01, 33.02, 33.03 here-in-before Note :- Fixing and testing element of the following items is deemed to be included in the quoted rate by the contractor for respective schedule 'A/BOQ' item No 33.01, 33.02, 33.03 here-in-before
(a) Power Contactor, three pole, AC3 rating of 400 Amps , 415 Volts
(b) Power Contactor, three pole AC3 rating of 210 Amps , 415Volts
(c) Power Contactor, three pole AC3 rating of 110 Amps , 415 Volts
(d) Power Contactor, three pole AC3 rating of 75 Amps , 415 Volts
(e) PLA relay 12/24 Volts DC, 11pin, 2 change over, cat part No. 2C/O – MPC -24D
(f) PLA relay 12 Volts DC, 9 pin, 2 change over, cat part No. 2C/O – MPC -12D
(j) Voltmeter 0-30 Volts, 96 mm X 96mm, digital type for measuring DC supply.
(m) Under voltage relay suitable for 3 phase 415 volts, AC supply
(n) Engine starting relay with sequence timer & Master timer suitable for 12 / 24 Volts DC supply.
(o) Electronic timer, type ET-100, suitable of 240 Volts, 50 Hz, AC supply, for 0 -10 seconds .
(p) Electronic DC timer suitable for 12/24 Volts DC supply, for 0-60 seconds. (on delay).
(q) Electronic timer, suitable of 240 / 415 Volts, 50 Hz, AC supply, for 0-60 seconds (OFF delay).
(r) Rectifier 4 plates single phase having charging rate 15–20 Amp per minute for 12 Volts DC battery charge.
(t) Indicating lamps neon type with holder for 12 / 24 volts DC supply (Make : L&T/BCH or equivalent make as approved by the GE )
(u) Battery Charging transformer 0 – 10 Amperes, 12 Volts DC tapping 0-12-18-24 Volts.
(v) MCB Tripel pole 240 volts 10 KA, rating 6 to 32 Amps ‘C’ series.
S&F in replacement of aluminum bus bar including drilling holes as required, including new GI nut, bolts and washers of shape, size & section as per site requirement to be fixed in feeder pillar box / panel board and insulation of bus bar with PVC tape and making connection with existing system using new lugs complete all as specified and directed.
Dismantling existing unserviceable MCCBs of any capacity and make from LT panels/ AMF Panel after disconnecting all the electrical connections all as specified and directed
Supplying, fixing and testing MCCB, 4 pole, 415 Volt AC supply, 63 Amps having breaking capacity Icu = 16 KA with fixed thermal & magnetic setting complete all as specified and directed.
Supplying, fixing and testing MCCB, 4 pole, 415 Volt AC supply, 100 Amps having breaking capacity Icu = 16 KA with fixed thermal & magnetic setting complete all as specified and directed.
Supplying, fixing and testing MCCB 4 pole, current rating of 125 Amps & ultimate breaking capacity Icu = 36 KA with fixed thermal & magnetic setting for 415 volts, 3 Phase, AC supply complete all as specified and directed.
Supplying, fixing and testing MCCB, 4 pole, 415 Volt AC supply, 160 Amps having breaking capacity Icu = 36 KA with fixed thermal & magnetic setting complete all as specified and directed.
Supplying, fixing and testing MCCB, 4 pole, 415 Volt AC supply, 200 Amps having breaking capacity Icu = 35/36 KA with fixed thermal & magnetic setting complete all as specified and directed.
Supplying, fixing and testing MCCB, 4 pole, 415 Volt AC supply, 400 Amps having breaking capacity Icu = 35/36 KA with fixed thermal & magnetic setting complete all as specified and directed.
Disconnecting and dismantling old unserviceable change over switch of any capacity and make from any position all as specified and directed.
Supplying, Fixing, jointing and testing ON LOAD change over switch (open execution), 3 pole, 415 volts of current rating 400 Amps complete all as specified and directed.
Description all as per item No. 44.01 here-in-before but of current rating 250 Amps
Description all as per item No. 44.01 here-in-before but of current rating 200 Amps
Description all as per item No. 44.01 here-in-before but of current rating 100 Amps
S&F Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 32x6mm galvanised iron or steel wire including taking down existing earthing lead complete all as specified and directed.
Excavation in trenches in soft & loose soil not exceeding 1.5 metre deep and not exceeding 1.5 m width and getting out soil including forming bottom surface to required slope/gradient for laying cables/pipes etc. all as specified and directed including removing cable protection PCC covers/ bricks & stacking serviceable covers / bricks for reuse and disposal of unserviceable covers within 50 m all as specified and directed.Note : Excavation shall be made carefully in order to avoid damage of existing cables and protection covers
Returning, filling in including spreading, leveling, watering and well ramming in layers of 25 cm thick after the cables etc. are laid, jointed & tested complete all as specified and directed.
Removal of surplus excavated spoil not exceeding 50 Mtr distance and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed.
Supplying & Laying Sub Class `B’ bricks old size with axis of the bricks perpendicular to the axis of the cable as in cable protection all as specified and directed.
Material & labour for sand filling with clean dry find sand unwashed including gently punning around cables in trenches for cable protection complete all as specified and directed NOTE:- For measurement purpose punned thickness shall be considered as per clause 19.75 of SSR Part-I
M&l forpreparation of the old decorated existing external and internal steel surfaces of feeder pillar boxes/panels/ boards of any description and in any position including removal of disintegrated & deteriorated paint either by hand scrapping or by blow lamps, applying necessary filler coat and stopping as required and applying two coats of synthetic enameled paint (grey in color) over a coat of red oxide primer with using spray machine on old prepared surfaces complete all as specified and directed. Note : Rates quoted by the contractor are deemed to include for writing the MES /SM No and other relevant details with paint in the pattern and style as approved by the Engineer-in-Charge
Disconnecting ,taking out and removing from trenches/ducts/sleeve/on pole/wall etc existing LT UG XLPE insulated, armoured cable of any description, any size/core and in any position complete all as specified and directed for the following sizes of cable :- Note: Earth work shall be measured & paid separately under respective item.
(a) 95 sqmm 4 Core
(b) 70 sqmm 3.5 Core
(c) 50 Sqmm 3.5 Core
(d) 35 Sqmm 3.5 Core
(e) 25 Sqmm 3.5 Core
Supplying, laying, jointing & testing XLPE insulated & PVC sheathed armoured LT cable, 1100 volts grade heavy duty with aluminium conductor of the following sizes laid in trenches/pipe/fixed on the wall etc complete all as specified and directed:-
(a) 95 sqmm 4 Core
(b) 70 sqmm 3.5 Core
(c) 50 Sqmm 3.5 Core
(d) 35 Sqmm 3.5 Core
(e) 25 Sqmm 3.5 Core
Supply, laying & fixing in replacement GI light grade pipes of size 80 mm dia for cable protection laid in trenches/floor/roof and on the walls, with all accessories, complete all as specified and directed.
Description all as per item No 54.00 here-in-before but pipe size 50mm dia.
Disconnection and taking out the turbo charger assembly from the Engine of any make of 40 KVA to 63 KVA DG Set capacity, strip opening of turbo charger and repair of turbo charger Kit , assembling the complete part of the turbo charger and fixing back to the engine the testing and commissioning for satisfactory working complete all as specified and directed.
Disconnection and taking out the turbo charger assembly from the Engine of any make of 100 KVA to160 KVA DG Set , strip opening of turbo charger and repair of turbo charger Kit , assembling the complete part of the turbo charger and fixing back to the engine the testing and commissioning for satisfactory working complete all as specified and directed.
Disconnection and taking out the turbo charger assembly from the Engine of any make of 180 KVA to 200 KVA DG Set, strip opening of turbo charger and repair of turbo charger Kit , assembling the complete part of the turbo charger and fixing back to the engine the testing and commissioning for satisfactory working complete all as specified and directed.
S & F in repair electronic type battery charger having capacity input voltage 220V and output voltage 12V complete all as specified and directed.
S & F in repeir electronic type battery charger having capacity input voltage 220V and output voltage 24V complete all as specified and directed.
S&F in repair lead acid battery DC 12 Volts, 150 AH complete all as specified and directed.
S&F in repair lead acid battery DC 12 Volts, 180 AH complete all as specified and directed.
S&F in repair maintenance free battery 12 Volt 180 AH suitable for DG Set complete all as specified and directed.
S&F in repair maintenance free battery 12 Volt 150 AH suitable for DG Set complete all as specified and directed.
S&F in repair maintenance free battery battery 12 Volt 120 AH suitable for DG Set complete all as specified and directed.
S & F in repair governor control unit for electronic governor suitable for DG Sets of capacity upto 125 KVA complete all as specified and directed
S & F in repair governor control unit for electronic governor suitable for DG Sets of capacity 160 to 200 KVA complete all as specified and directed
M&L for repairing of canopy of DG set by carrying out repairing of door with replacement of broken hinges including nuts, bolts/welding etc as per requirement, cleaning of base of foundation and painting MS channel with black paintl with two coats including touching of paint at cannopy where required complete all as specified and directed
Taking down and repair to Trolly mounted DG SET wheeled by taking out defective/puncher/blast and replacement of Trolly mounted DG SET wheeled including nut, bolts/towing system and side stands/brake locking system etc with in 5 Hours complete all as specified and directed.
M/s Gulshan and Brothers (BID ID -3067958)
m/s anil traders (BID ID -3056159)
BABA DEVELOPERS (BID ID -3068192)
M/S Amit Traders (BID ID -3068996)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .